36C24418B0580-003.pdf
PDF 20 MB Posted
- Attached to
- SPS Storage Room Climate Control, Project 542-17-102 Federal contract opportunity
- Solicitation number
- 36C24418B0580
About this file
36C24418B0580 03-Drawing-Mechanical SPS.pdf
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C24418C0218-000.docx | DOCX document | |
| 36C24418B0580-0002002.pdf | ||
| 36C24418B0580-0002001.pdf | ||
| 36C24418B0580-0002000.docx | DOCX document | |
| 36C24418B0580-0001000.docx | DOCX document | |
| 36C24418B0580-005.pdf | ||
| 36C24418B0580-006.pdf | ||
| 36C24418B0580-002.pdf | ||
| 36C24418B0580-007.pdf | ||
| 36C24418B0580-001.docx | DOCX document | |
| 36C24418B0580-004.pdf | ||
| 36C24418B0580-000.docx | DOCX document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. CONFORM TO ALL LOCAL, STATE, AND NATIONAL CODES ALONG WITH VA STANDARDS AND FEDERAL REQUIREMENTS.
EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS.
2. OBTAIN AND PAY FOR PERMITS, FEES, AND INSPECTIONS REQUIRED FOR WORK.
3. MATERIALS, EQUIPMENT AND PRODUCTS INCORPORATED IN THE WORK UNDER THE CONTRACT SHALL BE NEW, OF A SUITABLE GRADE FOR THE PURPOSES INTENDED, AND TO THE EXTENT POSSIBLE, STANDARD PRODUCTS OF THE VARIOUS MANUFACTURERS EXCEPT WHERE SPECIAL CONSTRUCTION OR PERFORMANCE FEATURES ARE CALLED FOR.
4. EQUIPMENT OR MATERIAL DEVIATIONS FROM THAT SPECIFIED OR DETAILED ON SHALL BE SUBJECT TO THE APPROVAL OF THE COR. PROPOSED EQUIPMENT DEVIATIONS SUBMITTED SHALL BE SIMILAR BOTH IN QUALITY AND CAPACITY TO
THE EQUIPMENT SPECIFIED.
5. EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITERS LABORATORIES (U.L.).
6. INSTALL EQUIPMENT AS SHOWN ON THE DRAWINGS ALLOWING FOR SUFFICIENT ACCESS AND CLEARANCE SPACE FOR EQUIPMENT MAINTENANCE, REPAIRS AND REPLACEMENT. PROVIDE PROPER CLEARANCES FOR REQUIRED PIPING AND ELECTRICAL SERVICES AND CONNECTIONS. INSTALL EQUIPMENT WITH REQUIRED ACCESS AND CLEARANCES IN ACCORDANCE WITH MANUFACTURER'S WRITTEN RECOMMENDATIONS AND WITH APPLICABLE CODES AND STANDARDS.
7. COORDINATE THE INSTALLATION AND ROUTING OF DUCTWORK, PIPING AND EQUIPMENT WITHIN THE BUILDING
STRUCTURE.
8. PROVIDE SUPPORT FOR MECHANICAL EQUIPMENT. LOCATIONS SHALL BE COORDINATED WITH OTHER TRADES PRIOR TO
INSTALLATION.
9. POWER CONNECTIONS TO THE EQUIPMENT PROVIDED UNDER THIS CONTRACT ARE PROVIDED AS WORK OF DIVISION 26.
10. PROVIDE CONTROL WIRING FOR MECHANICAL EQUIPMENT AS WORK OF DIVISION 23.
11. DUCTWORK AND PIPING LAYOUTS AND LOCATIONS ARE SCHEMATIC. DO NOT SCALE THESE DRAWINGS. EXACT ROUTING OF DUCTWORK AND PIPING MUST BE DETERMINED IN THE FIELD. DIMENSIONS SHALL BE FIELD VERIFIED BY THE CONTRACTOR BY ACTUAL MEASUREMENT AND OBSERVATION BEFORE ORDERING OR FABRICATING ANY DUCTWORK, PIPING OR EQUIPMENT. DISCREPANCIES BETWEEN THE REQUIREMENTS OF THE CONTRACT DOCUMENTS AND THE EXISTING CONDITIONS OR DIMENSIONS SHALL BE REPORTED TO THE COR BEFORE THE PERFORMANCE OF WORK.
FAILURE TO VERIFY AND REPORT SHALL CONSTITUTE THE CONTRACTOR'S ACCEPTANCE OF THE EXISTING CONDITIONS
AS FIT FOR THE PROPER EXECUTION OF WORK.
12. DUCTWORK AND PIPING SHALL BE KEPT AS CLOSE AND HIGH AS POSSIBLE TO THE BUILDING WALLS, FLOOR ABOVE AND ROOF STRUCTURE IN ORDER THAT THE MAXIMUM AMOUNT OF SPACE IS AVAILABLE. INSTALL FREE OF SAGS AND BENDS. INSTALL TO ALLOW APPLICATION OF INSULATION. ADDITIONAL OFFSETS, FITTINGS, ETC. NOT SHOWN BUT
REQUIRED TO MAINTAIN MAXIMUM CLEARANCE SHALL BE PROVIDED AT NO ADDITIONAL COST.
13. PATCH, PAINT, AND CLEAN AREAS ASSOCIATED WITH MECHANICAL WORK UNLESS NOTED OTHERWISE.
14. PROVIDE A COMPLETE 1-YEAR WARRANTY ON LABOR AND MATERIALS.
15. SUBMIT A BOUND SET OF OPERATING AND MAINTENANCE INSTRUCTIONS FOR EQUIPMENT UPON COMPLETION OF
PROJECT.
16. MAKE A COMPLETE REVIEW OF THE MECHANICAL PLANS, INCLUDING THE SCHEDULES AND DETAILS PRIOR TO
INSTALLATION OF MECHANICAL SYSTEMS AND RESOLVE ANY CONFLICTS WITH THE COR.
17. TAKE POSSESSION OF AND DISPOSE OF EXISTING MATERIALS AND EQUIPMENT BEING DEMOLISHED OR REMOVED.
ITEMS SHALL BE DISPOSED OF IN FULL COMPLIANCE WITH APPLICABLE LAWS, RULES, AND REGULATIONS.
CONTRACTOR IS RESPONSIBLE FOR COSTS ASSOCIATED WITH THE DISPOSAL OF EQUIPMENT. UNUSED MATERIAL OR
EQUIPMENT SHALL BE LEFT ONSITE AT THE END OF THE PROJECT.
18. INSTALL SHUTOFF-DUTY VALVES AT EACH BRANCH CONNECTION TO SUPPLY AND RETURN MAINS, AND AT SUPPLY AND
RETURN CONNECTIONS TO EACH PIECE OF EQUIPMENT.
19. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF THE PROJECT WORK. INSTALL SYSTEMS INDICATED TO BE EXPOSED AND SYSTEMS IN EQUIPMENT ROOMS AND SERVICE AREAS AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE. THE DRAWINGS REPRESENT THE INTENT OF THE PROJECT WORK. ALL FIELD CONDITIONS ARE NOT
REPRESENTED.
20. MEDIUM PRESSURE DUCTWORK SHALL BE CONSTRUCTED TO THE SMACNA STATIC PRESSURE CLASSIFICATION OF 6" W.G. AND SEAL CLASS "A". ALL DUCTWORK BETWEEN THE AIR HANDLING UNIT (AHU 45) AND THE TERMINAL UNITS
(AC1-TU-1-XX SHALL BE MEDIUM PRESSURE DUCTWORK.
21. LOW PRESSURE DUCTWORK SHALL BE CONSTRUCTED TO THE SMACNA STATIC PRESSURE CLASSIFICATION OF 2" W.G.
AND SEAL CLASS "A". ALL DUCTWORK NOT CLASSIFIED AS MEDIUM PRESSURE DUCTWORK BY NOTE 20 SHALL BE LOW
PRESSURE DUCTWORK UNLESS NOTED OTHERWISE.
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
APD AIRSIDE PRESSURE DROP
BLDG BUILDING
CFM CUBIC FEET PER MINUTE
CH CHILLED WATER SUPPLY AND
RETURN
CV CONSTANT VOLUME
CW DOMESTIC COLD WATER
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
D CONDENSATE DRAIN
DCW DOMESTIC COLD WATER
DN DOWN
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EG EXHAUST GRILLE
ETR EXISTING TO REMAIN
EWT ENTERING WATER TEMPERATURE
EX. EXISTING
FCU FAN COIL UNIT
GC GENERAL CONTRACTOR
FPM FEET PER MINUTE
GPM GALLONS PER MINUTE
HP HORSEPOWER
HW HEATING HOT WATER SUPPLY AND
RETURN
HWH HEATING HOT WATER SUPPLY
HWHR HEATING HOT WATER RETURN
HX HEAT EXCHANGER
IND INDUCTION UNIT
LAT LEAVING AIR TEMPERATURE
LPC LOW PRESSURE CONDENSATE
RETURN
LWT LEAVING WATER TEMPERATURE
MC MECHANICAL CONTRACTOR
MPR MEDIUM PRESSURE CONDENSATE
RETURN
MPS MEDIUM PRESSURE STEAM
SUPPLY
N/A NOT AVAILABLE
NTS NOT TO SCALE
OA OUTSIDE AIR
PCR PUMPED CONDENSATE RETURN
RA RETURN AIR
RG RETURN GRILLE
S FIRE/SMOKE BARRIER
SA SUPPLY AIR
SD SUPPLY DIFFUSER
TG TRANSFER GRILLE
TU TERMINAL UNIT
WPD WATERSIDE PRESSURE DROP
KEYED NOTE
DRAWING NUMBER
WHERE SHOWN
PIPING DOWN
PIPING UP
TEE UP
TEE DOWN
HEATING HOT WATER RETURN
EXISTING PIPING TO REMAIN
PIPING TO BE DEMOLISHED
DEMOLISH TO THIS POINT
POINT OF CONNECTION TO EXISTING
SUPPLY DIFFUSER
RETURN OR EXHAUST GRILLE
DIFFUSER TAG
DIFFUSER CFM
BALANCING DAMPER
C 275
SUPPLY DUCT (UP & DOWN)
EXHAUST OR RETURN DUCT (UP & DOWN)
ROUND DUCTWORK
DN
DNUP
UP
8"Ø
RECTANGULAR DUCTWORK10x10
TERMINAL UNIT
ASBESTOS/LEAD PAINT DISCLOSURE STATEMENT
COPIES OF PREVIOUS HAZARDOUS MATERIAL SURVEYS ARE AVAILABLE FROM THE COR FOR CONTRACTOR REVIEW.
ANY SUSPECT LEAD PAINT AND/OR ASBESTOS CONTAINING MATERIALS FOUND SHALL BE IMMEDIATELY BROUGHT TO THE COR'S ATTENTION AND WORK DISTURBING THE SUSPECT MATERIAL SHALL BE HALTED. THE CONTRACTOR SHALL WORK WITH THE COR FOR TESTING AND REMOVAL PRIOR TO ANY WORK BEING PERFORMED ON SUSPECT
MATERIALS.
EXPANSION JOINT
SMOKE DAMPER
FIRE DAMPER
MOTORIZED DAMPER
T THERMOSTAT / TEMPERATURE SENSOR
H HUMIDISTAT / HUMIDITY SENSOR
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
FAN COIL UNIT
FAN COIL UNIT MAINTENANCE AREA
EQUIPMENT TAG
FCU-001-1 EQUIPMENT NUMBER
BUILDING NUMBER
EQUIPMENT TYPE
HEATING HOT WATER SUPPLY
CHLLED WATER RETURN
CHILLED WATER SUPPLY
DPS
SPS
SP-1
PSH
SP-1
DIFFERENTIAL PRESSURE SENSOR
STATIC PRESSURE SENSOR
PRESSURE SWITCH
DEDUCT NO.1: All work associated with Building 4, Room B05A.
DEDUCT NO. 2: All work associated with Building 4, Room B07H.
DEDUCT NO. 3: All work associated with Building 58, Room 105F.
DEDUCT NO. 4: All work associated with Building 58, Room 105G.
DEDUCT NO. 5: All work associated with Building 38.
ETR 3/4" CH, 3/4" HW UP
ETR 3/4" CH,
3/4" HW DN
FCU-002-1
8"Ø
HUM-002-1
ETR 4" SAN
ETR DCW
ETR 8X6
6X4
ETR 1" CH, 1" HW UP
8"Ø
HUM-002-2
FCU-002-2
ETR 4" SAN ETR DCW
FCU-001-1
HUM-001-1
8"Ø
6"x6"
ETR 4" SAN
ETR DCW
FCU-001-2
HUM-001-2
8"Ø
ETR 2" SAN
ETR DCW
FCU-001-3
HUM-001-3
ETR 2" SAN
ETR DCW
HUM-001-4
FCU-001-4
8"Ø
ETR 2" SAN
ETR DCW
FCU-001-6
8"Ø
HUM-001-6
ETR 2" SAN
ETR DCW
FCU-001-5
HUM-001-5
ETR 1" SAN
ETR DCW
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
PROVIDE 3/4" CHILLED WATER SUPPLY, 3/4" CHILLED WATER RETURN, 3/4"
HEATING HOT WATER SUPPLY, 3/4" HEATING HOT WATER RETURN, AND 3/4",
CONDENSATE PIPING TO FCU. PROVIDE WITH INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
BALANCE EXISTING TO REMAIN OA DIFFUSER TO CFM INDICATED.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-200 FOR
BUILDING 1 ROOMS AND MH-201 FOR BUILDING 2 ROOMS.
REMOVE STEAM RADIATOR, CUT AND CAP STEAM LINES AT RISER.
PROVIDE 4-PIPE FAN COIL UNIT, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS.
REMOVE EXISTING FCU AND PREPARE EXISTING PIPING FOR CONNECTION TO
NEW FCU. DEMOLISH DUCTWORK CONNECTED TO THE FCU TO THE SUPPLY /
RETURN DIFFUSER.
DEMOLISH RETURN GRILLE / REGISTER AND CAP.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
CEILING HEIGHT TO CHANGE. DEMOLISH EXISTING SPRINKLER HEAD AND
PROVIDE NEW SPRINKLER HEAD AT NEW CEILING HEIGHT. CAREFULLY REMOVE
AND STORE ANY EXISTING TO REMAIN DIFFUSERS AND GRILLES AND REINSTALL
AT NEW CEILING HEIGHT.
EXISTING CONCEALED PIPING TO REMAIN. ABATE AND DEMOLISH ASBESTOS
INSULATION FOR EXTENT EXPOSED. PROVIDE NEW PIPING INSULATION FOR
EXTENT EXPOSED. PIPE SIZE AS NOTED. FIELD VERIFY PIPE SIZE.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" DCW PIPING, ROUTE TO P-TRAP ON
HUMIDIFIER DRAIN PIPING.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
ROOM 111F
ROOM 227A
NORTH
ROOM B01CROOM 149
ROOM 161ROOM 218B
ROOM 227
ROOM 316
VAV-003-1
6"Ø
HUM-003-1
2" ETR DCW
ETR 4"
SAN
ETR 2" HW
VAV-003-2
6"Ø
HUM-003-2
1/2" ETR DCW
ETR 3" SAN
ETR 3/4" HW
HUM-003-3
6"Ø
VAV-003-3
ETR 2" DCW
ETR 2" SAN
ETR 1" HW
VAV-003-4
HUM-003-4
6"Ø
ETR 1-1/2" DCW
ETR 2" SAN
ETR 3" HW
HUM-003-5
ETR 1-1/2" DCW ETR 2" SAN
ETR 3" HW
210 CFM
100 CFM
190 CFM
230 CFM
400 CFM
400 CFM
400 CFM
230 CFM
230 CFM
170 CFM
150 CFM
130 CFM
190 CFM 400 CFM
4100 CFM
240 CFM
60 CFM
3-TU-42 3-TU-43
3-TU-46
3-TU-48
1150 - 2060 CFM 510 CFM
300 CFM
430 CFM
655 - 780 CFM
3-TU-44
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
DEMOLISH DUCTWORK, HANGERS, AND SUPPORTS COMPLETE BETWEEN
EXISTING TO REMAIN DIFFUSER AND LIMIT OF DEMOLITION INDICATED. CAP OPEN
DUCTWORK.
PROVIDE 3/4" HWH PIPING AND 3/4" HWHR PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE. ROUTE TO TO NEW VAV BOX.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-202.
BALANCE EXISTING TO REMAIN DIFFUSER TO CFM INDICATED.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
PROVIDE SUPPLY DUCTWORK, INSULATION, HANGERS, AND SUPPORTS
COMPLETE.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE VAV BOX, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
PROVIDE HOT WATER RE-HEAT COIL. INSTALL PER MANUFACTURERS
RECOMMENDATIONS.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
CEILING HEIGHT TO CHANGE. DEMOLISH EXISTING SPRINKLER HEAD AND
PROVIDE NEW SPRINKLER HEAD AT NEW CEILING HEIGHT. CAREFULLY REMOVE
AND STORE ANY EXISTING TO REMAIN DIFFUSERS AND GRILLES AND REINSTALL
AT NEW CEILING HEIGHT.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" DCW PIPING, ROUTE TO P-TRAP ON
HUMIDIFIER DRAIN PIPING.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
BALANCE THE EXISTING TO REMAIN VAV BOX TO THE INDICATED CFMS.
BALANCE THE EXISTING TO REMAIN EXHAUST GRILLE / SUPPLY GRILLE / SUPPLY
DIFFUSER TO THE INDICATED CFM.
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
ROOM 160
ROOM B10
ROOM 141
ROOM 178
ROOM B52
ROOM 125
HUM-004-2
FCU-004-1 8"Ø
VAV-004-1
HUM-004-3
8"Ø
HUM-004-4
FCU-004-2
8"Ø
VAV-004-2
8"Ø
HUM-004-1
ETR 3" SAN
ETR 3" SAN
ETR 3" SAN
ETR 4" SAN
ETR 3/4" DCW
ETR 2" DCW
ETR 3/4" DCW
ETR 1-1/2" DCW
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
ROOM B07H
ROOM B07F
ROOM B05A
ROOM B10
PROVIDE 3/4" CHILLED WATER SUPPLY, 3/4" CHILLED WATER RETURN, 3/4"
HEATING HOT WATER SUPPLY, 3/4" HEATING HOT WATER RETURN, AND 3/4",
CONDENSATE PIPING TO FCU. PROVIDE WITH INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
BALANCE EXISTING TO REMAIN OA DIFFUSER TO CFM INDICATED.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-203.
PROVIDE VAV BOX, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
PROVIDE 4-PIPE FAN COIL UNIT, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS.
REMOVE EXISTING FCU AND PREPARE EXISTING PIPING FOR CONNECTION TO
NEW FCU. DEMOLISH DUCTWORK CONNECTED TO THE FCU TO THE SUPPLY /
RETURN DIFFUSER.
DEMOLISH RETURN GRILLE / REGISTER AND CAP.
PROVIDE 3/4" HWH PIPING AND 3/4" HWHR PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE. ROUTE TO TO NEW VAV BOX.
REMOVE EXISTING VAV BOX AND PREPARE EXISTING PIPING FOR CONNECTION
TO NEW VAV BOX. DEMOLISH DUCTWORK CONNECTED TO THE VAV BOX TO THE
EXISTING TO REMAIN DIFFUSER.
ROUTE DUCTWORK TO SUPPLY MAIN.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
CEILING HEIGHT TO CHANGE. DEMOLISH EXISTING SPRINKLER HEAD AND
PROVIDE NEW SPRINKLER HEAD AT NEW CEILING HEIGHT. CAREFULLY REMOVE
AND STORE ANY EXISTING TO REMAIN DIFFUSERS AND GRILLES AND REINSTALL
AT NEW CEILING HEIGHT.
EXISTING CONCEALED PIPING TO REMAIN. ABATE AND DEMOLISH ASBESTOS
INSULATION FOR EXTENT EXPOSED. PROVIDE NEW PIPING INSULATION FOR
EXTENT EXPOSED. PIPE SIZE AS NOTED. FIELD VERIFY PIPE SIZE.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" DCW PIPING, ROUTE TO P-TRAP ON
HUMIDIFIER DRAIN PIPING.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
BID DEDUCT NO.1: ALL WORK ASSOCIATED WITH BUILDING 4, ROOM B05A.
BID DEDUCT NO.2: ALL WORK ASSOCIATED WITH BUILDING 4, ROOM B07H.
BID DEDUCT NOTE
HUM-006-1
HUM-006-2
HUM-006-3
ETR 6" SAN
ETR 6" SAN
ETR 5" SAN
ETR 3/4" DCW
ETR 3/4" DCW
ETR 3/4" DCW
HUM-007-1
FCU-007-1ETR 2" SAN
ETR 2" DCW
HUM-007-2
8"Ø
FCU-007-2
ETR 4" SAN
ETR 2" DCW
HUM-007-3
FCU-007-3
8"ØETR 4" SAN
ETR 2" DCW
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
NORTH
ROOM B17
ROOM 234B
ROOM 154
ROOM 221A
PROVIDE 3/4" CHILLED WATER SUPPLY, 3/4" CHILLED WATER RETURN, 3/4"
HEATING HOT WATER SUPPLY, 3/4" HEATING HOT WATER RETURN, AND 3/4",
CONDENSATE PIPING TO FCU. PROVIDE WITH INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
BALANCE EXISTING TO REMAIN DIFFUSER / GRILLE / REGISTER TO CFM INDICATED.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-205.
PROVIDE 4-PIPE FAN COIL UNIT, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS.
DEMOLISH RETURN GRILLE / REGISTER AND CAP.
INTEGRATE FCU CONTROLS INTO DDC.
PROVIDE 3/8" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-204.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
CEILING HEIGHT TO CHANGE. DEMOLISH EXISTING SPRINKLER HEAD AND
PROVIDE NEW SPRINKLER HEAD AT NEW CEILING HEIGHT. CAREFULLY REMOVE
AND STORE ANY EXISTING TO REMAIN DIFFUSERS AND GRILLES AND REINSTALL
AT NEW CEILING HEIGHT.
EXISTING CONCEALED PIPING TO REMAIN. ABATE AND DEMOLISH ASBESTOS
INSULATION FOR EXTENT EXPOSED. PROVIDE NEW PIPING INSULATION FOR
EXTENT EXPOSED. PIPE SIZE AS NOTED. FIELD VERIFY PIPE SIZE.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" DCW PIPING, ROUTE TO P-TRAP ON
HUMIDIFIER DRAIN PIPING.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
ETR 1¼"CH
1"HW
CAPPED
8"Ø
HUM-008-1
FCU-008-1
ETR 4" SAN
ETR 2" DCW
8"Ø
FCU-008-2
HUM-008-2
ETR 4" SAN
ETR 2" DCW
FCU-038-1
HUM-038-1
6"Ø
ETR 2" SAN
ETR 1/2" DCW
ETR 1¼"CH
1"HW
HUM-039-1
FCU-039-1
ETR 1/2" DCW
ETR 4" SAN
ETR 1"CH
3/4"HW
HUM-039-2
8"Ø
FCU-039-2
4"Ø
ETR 1/2" DCW
ETR 4" SAN FCU-057-1
HUM-057-1ETR 1/2" DCW
ETR 2" SAN
FCU-057-2
HUM-057-2
ETR 1-1/2" DCW
ETR 2" SAN
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
ROOM 105
ROOM 205
NORTH
ROOM 216
NORTH
ROOM 222A
ROOM 123
NORTH
ROOM 202
ROOM 107
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
PROVIDE 3/4" CHILLED WATER SUPPLY, 3/4" CHILLED WATER RETURN, 3/4"
HEATING HOT WATER SUPPLY, 3/4" HEATING HOT WATER RETURN, AND 3/4",
CONDENSATE PIPING TO FCU. PROVIDE WITH INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
BALANCE EXISTING TO REMAIN OA DIFFUSER TO CFM INDICATED.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-206 FOR
BUILDING 8, MH-207 FOR BUILDING 38, MH-208 FOR BUILDING 39, AND MH-209 FOR
BUILDING 57.
PROVIDE 4-PIPE FAN COIL UNIT, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS.
DEMOLISH RETURN GRILLE / REGISTER AND CAP.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
EXISTING CONCEALED PIPING TO REMAIN. ABATE AND DEMOLISH ASBESTOS
INSULATION FOR EXTENT EXPOSED. PROVIDE NEW PIPING INSULATION FOR
EXTENT EXPOSED. PIPE SIZE AS NOTED. FIELD VERIFY PIPE SIZE.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" DCW PIPING, ROUTE TO P-TRAP ON
HUMIDIFIER DRAIN PIPING.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
BID DEDUCT NO.5: ALL WORK ASSOCIATED WITH BUILDING 38.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
PROVIDE COMMISSIONING BY FACTORY REPRESENTATIVE ON EXISTING AAON
AHU PICTURED IN 1/MH106. MODEL NUMBER:
(RQ-006-8-H-EB09-000 : FEBCDOBQKDAHAEDEOOBE000000000AB).
PROVIDE COMMISSIONING BY FACTORY REPRESENTATIVE ON EXISTING NORTEC
HUMIDIFIER PICTURED IN 3/MH106.
HUM-058-1
HUM-058-2
ETR 4" SAN
ETR 3/4" DCW
HUM-058-3
FCU-058-1
ETR 1/2" DCW
ETR 2" SAN
HUM-059-1
ETR 3/4" DCW
ETR 3" SAN
HUM-059-2ETR 1/2" DCW
ETR 2" SAN
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
ROOM 105G
ROOM 105F
ROOM 117
NORTH
ROOM 151B
ROOM 243
PROVIDE 3/4" CHILLED WATER SUPPLY, 3/4" CHILLED WATER RETURN, 3/4"
HEATING HOT WATER SUPPLY, 3/4" HEATING HOT WATER RETURN, AND 3/4",
CONDENSATE PIPING TO FCU. PROVIDE WITH INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
BALANCE EXISTING TO REMAIN OA DIFFUSER TO CFM INDICATED.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-210 FOR
BUILDING 58 AND MH-211 FOR BUILDING 59.
PROVIDE 4-PIPE FAN COIL UNIT, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS.
INTEGRATE FCU CONTROLS INTO DDC.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" PIPE, ROUTE TO P-TRAP ON HUMIDIFIER DRAIN
PIPING.
CEILING HEIGHT TO CHANGE. DEMOLISH EXISTING SPRINKLER HEAD AND
PROVIDE NEW SPRINKLER HEAD AT NEW CEILING HEIGHT. CAREFULLY REMOVE
AND STORE ANY EXISTING TO REMAIN DIFFUSERS AND GRILLES AND REINSTALL
AT NEW CEILING HEIGHT.
EXISTING CONCEALED PIPING TO REMAIN. ABATE AND DEMOLISH ASBESTOS
INSULATION FOR EXTENT EXPOSED. PROVIDE NEW PIPING INSULATION FOR
EXTENT EXPOSED. PIPE SIZE AS NOTED. FIELD VERIFY PIPE SIZE.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
BID DEDUCT NO.3: ALL WORK ASSOCIATED WITH BUILDING 58, ROOM 105F.
BID DEDUCT NO.4: ALL WORK ASSOCIATED WITH BUILDING 58, ROOM 105G.
8x6
12x10
8x8
8x6
HUM-069-1
6"Ø
6"Ø
FCU-069-1
ETR 3/4" DCW
ETR 2" SAN
VAV-138-1
HUM-138-1
6"Ø
ETR 3" SAN
ETR 2" DCW
HUM-138-2
VAV-138-2 6"Ø
ETR 2" SAN
ETR 1/2" DCW
VAV-138-3
6"Ø
HUM-138-3
ETR 2" SAN
ETR 3/4" DCW
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
NORTH
NORTH
NORTH
ROOM 158B
ROOM 237
ROOM 125A
ROOM 115
DEMOLISH DUCTWORK, HANGERS, AND SUPPORTS COMPLETE BETWEEN
EXISTING TO REMAIN DIFFUSER AND LIMIT OF DEMOLITION INDICATED. CAP OPEN
DUCTWORK.
PROVIDE 3/4" HWH PIPING AND 3/4" HWHR PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE. ROUTE TO TO NEW VAV BOX.
PROVIDE 1/2" DOMESTIC WATER PIPING. ROUTE PIPING AS SHOWN ON MH-212 FOR
BUILDING 69 AND MH-213 FOR BUILDING 138 EAST AND BUILDING 138 WEST.
BALANCE EXISTING TO REMAIN DIFFUSER TO CFM INDICATED.
PROVIDE WALL MOUNTED HUMIDITY SENSOR. MOUNT CENTERLINE WITH LIGHT
SWITCHES.
PROVIDE WALL MOUNTED TEMPERATURE SENSOR. MOUNT CENTERLINE WITH
LIGHT SWITCHES.
PROVIDE DUCTWORK, INSULATION, HANGERS, AND SUPPORTS COMPLETE.
PROVIDE ROOM HUMIDIFIER, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS. CLEARANCE SHOWN IS 6' FROM THE
WALL AND 6" ON EACH SIDE OF THE HUMIDIFIER.
PROVIDE VAV BOX, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
ROUTE DUCTWORK TO SUPPLY MAIN.
PROVIDE 3/4" CHILLED WATER SUPPLY, 3/4" CHILLED WATER RETURN, 3/4"
HEATING HOT WATER SUPPLY, 3/4" HEATING HOT WATER RETURN, AND 3/4",
CONDENSATE PIPING TO FCU. PROVIDE WITH INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE 4-PIPE FAN COIL UNIT, MOUNTINGS, AND SUPPORTS COMPLETE. INSTALL
PER MANUFACTURERS RECOMMENDATIONS.
DEMOLISH ELBOW AND TRANSFER GRILLE. EXTEND DUCTWORK TO EXISTING TO
REMAIN EXHAUST MAIN. INSTALL BALANCING DAMPER AND BALANCE TO CFM
INDICATED.
PROVIDE 1 1/4" DRAIN PIPING. ROUTE TO EXISTING SANITARY PIPE. REFER TO
MH501/11 FOR DETAILS ON CONNECTING TO HUMIDIFIER.
PROVIDE TRAP PRIMER IN ACCESSIBLE LOCATION PER MANUFACTURER
RECOMMENDATIONS. PROVIDE 1/4" DCW PIPING, ROUTE TO P-TRAP ON
HUMIDIFIER DRAIN PIPING.
PROVIDE OCCUPANCY SENSOR TO DISABLE HUMIDIFICATION UNITS WHEN ROOM
IS OCCUPIED.
1. SCHEDULE SERVICE OUTAGES WITH THE VA COR.
1/2" DCW UP
AND DOWN.
ETR 1-1/2" C.W
1" HW
1/2" HWR
1/2" C.W UP
REFER TO ENLARGED
ROOM 316 PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
1/2" C.W
REFER TO ENLARGED
ROOM 218B PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 227 PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
1/2" DCW UP
AND DOWN.
1/2" C.W
1/2" C.W
REFER TO ENLARGED
ROOM 149 PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 161 PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
1/2" DCW UP
AND DOWN.
1/2" C.W
1/2" C.W
REFER TO ENLARGED
ROOM B01C PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
1/2" DCW UP
1/2" C.W
1/2" DCW UP
1/2" DCW DN
M
OA LOUVER
M
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
1-AC-2
1-AC-1
PROVIDE UNISTRUT
AND 3/4" PLYWOOD
FRAME
MAINTENANCE
CLEARANCE
1/2"C.W DOWN
1/2" DCW DOWN.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM B01CROOM 149
ROOM 161
ROOM 218B
ROOM 227
ROOM 316
M
ACCESS
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
2-AC-2 2-AC-1
1/2" DCW UP
AND DOWN.
REFER TO ENLARGED
ROOM 227A PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
ETR 2" C.W
1/2" C.W UP
1/2" C.W
REFER TO ENLARGED
ROOM 111F PLAN
DRAWING MH101 FOR
WORK IN THIS AREA.
1/2" DCW UP
1/2"C.W DOWN
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 111F
ROOM 227A
REFER TO ENLARGED
ROOM B10 PLAN
DRAWING MH102 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM B10 PLAN
DRAWING MH102 FOR
WORK IN THIS AREA.
1/2" DCW
1/2" DCW UP
1/2" DCW
3-AH-2
3-AH-1
7 6
6 6
66 5
27 27
27 27
REFER TO ENLARGED
ROOM 178 PLAN
DRAWING MH102 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 160 PLAN
DRAWING MH102 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 141 PLAN
DRAWING MH102 FOR
WORK IN THIS AREA.
1/2" DCW UP 1/2" DCW1/2" DCW
1/2" DCW
1/2" DCW DN
ETR-3/4" DCW
MAINTENANCE
CLEARANCE
1/2" DCW DN
REFER TO MH401 FOR WORK IN THE INDICATED REGION.
3-AH-4
3-AH-5
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 160
ROOM B10
ROOM 141
ROOM 178
ROOM B52
ROOM 125
1/2"C.W DOWN
MAINTENANCE
CLEARANCE
1/2"C.W DOWN
1/2" CW UP.
REFER TO ENLARGED
ROOM B07F PLAN
DRAWING MH103 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM B07H PLAN
DRAWING MH103 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM B075A PLAN
DRAWING MH103 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM B10 PLAN
DRAWING MH103 FOR
WORK IN THIS AREA.
4-SPS-1
1/2" CW
(TYP)
1/2" DCW
UP AND
DOWN.
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
4-AC-2
ETR -
4-AC-1
ETR 1" C.W
1" HW
1/2" HWR
1/2" DCW
UP AND
DOWN.
1/2" C.W UP
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
BID DEDUCT NO.1: ALL WORK ASSOCIATED WITH BUILDING 4, ROOM B05A.
BID DEDUCT NO.2: ALL WORK ASSOCIATED WITH BUILDING 4, ROOM B07H.
BID DEDUCT NOTE
NORTH
ROOM B07H
ROOM B07F
ROOM B05A
ROOM B10
3/8" DCW
UP
REFER TO ENLARGED
ROOM B17 PLAN
DRAWING MH104 FOR
WORK IN THIS AREA.
1/2" DCW
UP AND
DOWN.
ETR 2" C.W
1" HW
1/2" HWR
1/2" DCW
UP AND
DOWN.
1/2" C.W UP
M
ACCESS
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
6-AC-2 ETR -
6-AC-1
1/2"C.W DOWN
3/8" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM B17
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
7-AC-2 7-AC-1
REFER TO ENLARGED
ROOM 154 PLAN
DRAWING MH104 FOR
WORK IN THIS AREA.
1/2" DCW UP
1/2" DCW UP
AND DOWN.
REFER TO ENLARGED
ROOM 221A PLAN
DRAWING MH104 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 234B PLAN
DRAWING MH104 FOR
WORK IN THIS AREA.
ETR 2" C.W
1" HW
1/2" HWR
1/2" C.W UP
1/2" DCW
1/2" C.W
1/2"C.W DOWN
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 234B
ROOM 154
ROOM 221A
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
8-AC-2 ETR -
8-AC-1
REFER TO ENLARGED
ROOM 105 PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
3/8" DCW UP
1/2" DCW UP
AND DOWN.
ETR 2" C.W
1" HW
1/2" HWR
1/2" DCW UP
1/2" DCW
REFER TO ENLARGED
ROOM 205 PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
1/2" DCW DOWN
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 105
ROOM 205
ETR 2" C.W
1" HW
1/2" HWR
1/2" DCW
UP
1/2" DCW UP
REFER TO ENLARGED
ROOM 216A PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
M
ACCESS
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
38-AC-2
ETR -
38-AC-1
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
BID DEDUCT NO.5: ALL WORK ASSOCIATED WITH BUILDING 38.
BID DEDUCT NOTE
ROOM 216
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
ETR - 39-AC-2 39-AC-1
REFER TO ENLARGED
ROOM 123 PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
1/2" DCW UP
GENERAL LOCATION OF
THE ECC "TLS" MAIN
FRAME FOR DDC
INTERFACE.
1/2" DCW UP
AND DOWN.
ETR 1" C.W
1" HW
1/2" HWR
1/2" DCW UP
1/2" DCW
REFER TO ENLARGED
ROOM 222A PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 222A
ROOM 123
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
57-AC-2 ETR -
57-AC-1
REFER TO ENLARGED
ROOM 107 PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
1/2" DCW UP
1/2" DCW UP
AND DOWN.
ETR 3/4" C.W
3/4" HW
1/2" DCW UP
1/2" DCW
REFER TO ENLARGED
ROOM 202 PLAN
DRAWING MH105 FOR
WORK IN THIS AREA.
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 202
ROOM 107
DOOR
(TYP)
OA LOUVER
M
ACCESS
DOOR
(TYP)
OA LOUVER
REFER TO ENLARGED
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
58-AC-2
ETR -
58-AC-1
REFER TO ENLARGED
ROOM 105G PLAN
DRAWING MH107 FOR
WORK IN THIS AREA.
1/2" DCW UP
REFER TO ENLARGED
ROOM 105F PLAN
DRAWING MH107 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 117 PLAN
DRAWING MH107 FOR
WORK IN THIS AREA.
1/2" DCW
1/2" DCW
1/2" DCW
1/2" DCW UP
AND DOWN.
ETR 2" C.W
1/2" C.W UP
3/8" DCW DOWN.
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
BID DEDUCT NO.3: ALL WORK ASSOCIATED WITH BUILDING 58, ROOM 105F.
BID DEDUCT NO.4: ALL WORK ASSOCIATED WITH BUILDING 58, ROOM 105G.
BID DEDUCT NOTE
NORTH
ROOM 105G
ROOM 105F
ROOM 117
59 HR-AH-1
ATTIC PLAN THIS
DRAWING FOR WORK
IN THIS AREA.
REFER TO ENLARGED
ROOM 151B PLAN
DRAWING MH107 FOR
WORK IN THIS AREA.
3/8" DCW UP
1/2" DCW UP
AND DOWN.
1/2" DCW
REFER TO ENLARGED
ROOM 243 PLAN
DRAWING MH107 FOR
WORK IN THIS AREA.
1/2" C.W DOWN
1/2" DCW DOWN
MAINTENANCE
CLEARANCE
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
ROOM 151B
ROOM 243
PLAN THIS DRAWING
FOR WORK IN THIS
AREA.
69 HR-AH-1
REFER TO ENLARGED
ROOM 138 PLAN
DRAWING MH108 FOR
ADDITIONAL WORK IN
THIS AREA.
ETR 1" C.W 1/2" C.W
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
ROOM 158B
1/2" DCW UP
AND DOWN.
REFER TO ENLARGED
ROOM 237 PLAN
DRAWING MH108 FOR
WORK IN THIS AREA.
ETR 1/2" C.W
1/2" C.W UP
1/2" DCW
1/2" DCW UP
1/2" DCW
1/2" DCW1/2" DCW
REFER TO ENLARGED
ROOM 125A PLAN
DRAWING MH108 FOR
WORK IN THIS AREA.
REFER TO ENLARGED
ROOM 115 PLAN
DRAWING MH108 FOR
WORK IN THIS AREA.
AHU-2/ACCU-2
ON ROOF
1/2" DCW DOWN.
MAINTENANCE
CLEARANCE
ETR - SUPPLY DUCT
138-AC-2
138-AC-2 HUMIDIFIER
ETR - 138-AC-3
138-AC-2 HUMIDIFIER
DISPERSION TUBE
CHILLED WATER COIL
STM COIL
ETR - SUPPLY DUCT
138-AC-1 HUMIDIFIER
DISPERSION TUBE
CHILLED WATER COIL
STM COIL
138-AC-1
138-AC-1 HUMIDIFIER
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
PROVIDE DOMESTIC COLD WATER PIPING, INSULATION, HANGERS, AND
SUPPORTS COMPLETE.
PROVIDE RO WATER FILTER.
CORE DRILL FLOOR/WALL, PATCH AND FIRE STOP.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
NORTH
ROOM 237
ROOM 125A
ROOM 115
FILTERS
STEAM COIL AND HUMIDIFIER
CHILLED WATER COIL
SUPPLY FAN
ETR 3-AC-1
FILTERS
STEAM COIL AND HUMIDIFIER
CHILLED WATER COIL
SUPPLY FAN
3-AC-1
PRS-003-1
1. NONE.
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
DEMOLISH STEAM PIPING AND CAP. PREPARE FOR INSTALLATION OF PRESSURE
REDUCING STATION.
PROVIDE PRESSURE REDUCING STATION. ENSURE MAINTENANCE CLEARANCE
AND ACCESS TO MAINTENANCE CLEARANCE.
COMMISSION AND TAB AIR HANDLING UNIT FOR PROPER OPERATION. REPORT
DEFICIENCIES TO THE COR.
NORTH
3RD FLOOR MECHANICAL ROOM
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
1-1/2" POCKET SLIP
DUCT
1-1/2" MIN. TO 3" MAX.
INSTALLED. 6" NOMINAL WITH
MATERIAL TAUT
1" FLANGE & HEM
BOLT ON 4" CENTER
ALTERNATE
POSITION OF BOLT
1" x 1/8" BAND IRON
WASHER
FLANGED CONNECTION
ON FAN SIDE
FLEXIBLE MATERIAL
AS SPECIFIED
5/16" FLANGE
BOLT ON 4" CENTERS
1" x 1/8" BAND IRON
WASHER
FALNGED CONNECTION
ON FAN SIDE
1" x 1/8" DRAW BAND
FLEXIBLE
MATERIAL AS
SPECIFIED
SHEET METAL
SCREWS ON
12" CENTERS
RIVET ON 4" CENTERS
DUCT
1-1/2" MIN. TO 3" MAX.
INSTALLED. 6" NOMINAL WITH
MATERIAL TAUT
RECTANGULAR FLEXIBLE CONNECTION
ROUND FLEXIBLE CONNECTION
1-1/2"1/2" 1/2"
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
NOTES:
1. DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
2. DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR
FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.
SECTIONSIDE ELEVATION
1/2" ROUND ROD PIN
1/8" CLEARANCE
ALL AROUND
INSIDE END
BEARING
INSULATION
STAND-OFF
DAMPER BLADE
HANDLE WITH
LOCKING
QUADRANT
STIFFEN BLADE
AS REQUIRED
INSULATION SEE
SPECIFICATION
DUCT
OUTSIDE END BEARING
NOM. SIZE (IN.)
PIPE (FT.)
TUBING (FT.)
5 FT
THRU 3/4
1 1 1/4
1 1/2
HANGER ROD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH
COMPRESSIVE
STRENGHTH INSULATION
(9 PSF MIN. DENSITY)
UNDER INSULATION
SHIELD
INSULATION SHIELD AT
HANGER
WELD
SADDLE
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS
1/2" DIA. HANGER RODS WITH 36"
MAX. SPACING ON EACH CHANNEL
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2" x 2" x 1/4" ANGLE
NOTES:
SEE SPECIFICATIONS FOR DETAILED
HANGER REQUIREMENTS.
SIDE VIEW TRAPEZE HANGER FOR
UP TO 1000 LB. UNIFORM LOAD
1" MAX.
PROVIDE INSULATION SHIELD &
INSERT FOR ALL PIPING (8" MIN.)
2 2 1/2 3 4 5 6 8 10 12
11 12 14 16 17 19 22 23
9 10 12 13 14 16 - -
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTES:
1. RIGID STRAIGHT TERMINAL UNIT INLET LENGTH SHALL BE A MINIMUM OF 3
TIMES THE DIAMETER OF INLET.
2. A FLEXIBLE AIR DUCT CONNECTOR IS NOT MANDATORY FOR INLET TO THIS BOX,
BUT ALLOWED TO ACCOMODATE MINOR OFFSETS. MAXIMUM LENGTH 3'-0".
3. A BRANCH DUCT SERVING AN INDIVIDUAL BOX MAY BE THE SAME SIZE AS THE
BOX INLET, PROVIDED THE EQUIVALENT LENGTH OF THE BRANCH DUCT, AS
SHOWN, DOES NOT EXCEED 10 FEET. FOR LONGER LENGTHS, INCREASE THE
DUCT SIZE AND PROVIDE A DUCT TRANSITION TO MAINTAIN THE DUCT STATIC
PRESSURE DROP AT OR BELOW 0.2"/100'.
4. FLEXIBLE AIR DUCT CONNECTORS, WHEN USED FROM TERMINAL UNIT SUPPLY
AIR DUCT TO DIFFUSER, SHALL NOT EXCEED 5'-0". PROVIDE RIGID ELBOWS FOR
CHANGE OF DIRECTION GREATER THAN 45°.
5. COMPONENT ARRANGEMENT MAY VARY BY MANUFACTURER. PROVIDE
INSULATION WITH VAPOR BARRIER FOR CONNECTING DUCT SECTIONS.
AIR TERMINAL UNIT
(CV OR VAV)
SEE NOTE 5
SEE SPECIFICATIONS FOR
CLAMPS AND SEALANT (TYP.)
AIR DISTRIBUTION VARIES
WITH ROOM LAYOUT
FLEXIBLE AIR DUCT
CONNECTOR. SEE DETAIL
REHEAT COIL
SEE NOTE 1
SEE NOTE 2
SEE NOTE 3
S U
P P
L Y
A
I R
D
U C
T
S E
E
N
O T
E
RETURN
SUPPLY
COIL
DRAIN VALVE WITH HOSE
CONNECTION
MANUAL AIR VENT
UNION (TYPICAL)
2-WAY MODULATING
CONTROL VALVE
STRAINER WITH
DRAIN VALVE AND
HOSE CONNECTION
TEMPERATURE/PRESSURE TEST PORT
ISOLATION VALVE
CONCENTRIC REDUCERS,
IF REQUIRED (TYP.)
1-1/4 X 1-1/4 X
3/16
ANGLE IRON
SUPPORTS
1/2" THREADED
ROD(TYP)
1/2" BOLT AND
NUT
W/2" 1/2 WASHER
STRUCTURAL
JOIST
NUTS AND
WASHERS BOTH
SIDES OF
ANGLE(TYP)
MAIN SUPPLY
DUCT
PROVIDE VOLUME
DAMPER
PROVIDE
VOLUME
DAMPER
1/4 W OR
4" MIN.
SUPPLY REGISTER OR
BRANCH DUCT
MAIN SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
TURNING VANES
AIR FLOW
AIR FLOW
A
F
O
W
AIR SPLIT DUCT TAKE-OFF
PLAN VIEW
BRANCH DUCT TAKE-OFF
PLAN VIEW
AIR FLOW
AI
R
FL
OW
W
MAIN SUPPLY
DUCT
CONICAL TAP
TERMINAL UNIT DUCT TAKE-OFF
PLAN VIEW
AIR FLOW
AI
R
FL
OW
W
AUTOMATIC DRAIN
SHUTOFF VALVE
SHUTOFF VALVE
WATER PURIFIER
DOMESTIC COLD WATER
PURIFIED DOMESTIC
COLD WATER
BACKBOARD
UNISTRUT SUPPORTS
FLOOR
1/2"
DCW
SHUTOFF VALVE
MOUNT ON WALL WITH
MANUFACTURER
PROVIDED WALL
MOUNT.
HUMIDIFIER
OPEN HUB DRAIN
P-TRAP
TRAP PRIMER
1/4" DCW
OCCUPANCY SENSOR LOCATED
BELOW HUMIDIFIER
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
DUCT - AIR TERMINAL UNITS
2-WAY VAV COIL PIPING DETAIL
DUCT HANGER DETAIL SUPPLY DUCT TAKEOFFS FCU PIPING CONNECTIONS
MINIMUM 13"
WATER FILTRATION DETAIL
SPACE HUMIDIFIER DETAIL
www.acg-pa.com
919-858-7420
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
POINT NAME:
ZONE TEMPERATURE
ZONE TEMPERATURE SETPOINT ADJUST
AIRFLOW
DISCHARGE AIR TEMPERATURE
ZONE DAMPER
REHEATING VALVE
AIRFLOW SETPOINT
HEATING MODE
HEATING SETPOINT
COOLING SETPOINT
DISCHARGE TEMPERATURE
HARDWARE POINTS
AI AO
X
X
X
X
BI BO
SOFTWARE POINTS
AV BV LOOP SCHED TREND ALARM SHOW ON GRAPHIC
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
ZONE DIFF PRESSURE SETPOINT ADJUST X X
ZONE DIFF PRESSURE X XX X
X X
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
RETURN AIR
PRESSURE SWITCH HIGH TO DISABLE FAN
WHEN HIGH PRESSURE LIMIT SETPOINT IS
REACHED (TYPICAL)
STEAM
HUMIDIFIER
LPS
SMOKE
DETECTOR
RS
RL
EXISTING DDC GLOBAL
POINT - OA TEMP
ECONOMIZER/OUTSIDE AIR SUPPLY FAN
(2 FAN ARRAY)
SPS
SP-1
HHL
HL-1
HT
H-2
PSH
SD1
DPS
TT
T-1
SST
SF
HS
CS
IT-2
VFD
SPD
SF
TT
T-6
TT
T-3
TT
T-5
TSL
TSL-1
C O
C
O O
L I N
G
C O
P
R E
H E
A T
A F
T E
R F
I L
T E
R
P R
E F
I L
T E
R
HT
H-1
TT
T4
TT
T-2
A F
M D
DPS
D-1
D-2
P R
E F
I L
T E
R
DPS
D-3
FT
AF-1
RELIEF AIR
SUPPLY AIR TO
TERMINAL UNIT
STEAM
CONDENSATE
CURRENT TRANSMITTER
FOR FAN STATUS (TYP.)
RETURN FAN
(TWO FAN ARRAY)
SST
RF
VFD HS
SPD
RF
ALA
RF
COMM
IT-1
CS
1 2
CV-STX3-1
LPS
STEAM
CONDENSATE
ALA
SF
COMM
SP-1
R E
T U
N
R
CV-STX3-2
CV-HX3-1
CV-HX3-2
ACCU
MANUFACTURER'S
CONTROL PANEL
IT-4
CS SST
ACCU
COMM
AREA
EXHAUST
FAN
SST
EF
CS
IT-3
MS
EXISTING POINT
1 GENERAL FAN/TEMPERATURE CONTROL
1.1 COOLING-OCCUPIED: AHU SUPPLY AIR FAN AND RETURN AIR FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY. AHU WILL BE INTERLOCKED WITH ASSOCIATED AREA EXHAUST FANS, SO EACH EXHAUST FAN WILL OPERATE WHENEVER ITS ASSOCIATED AHU IS ENERGIZED. AHU SUPPLY FAN SPEED SHALL BE DETERMINED BY DISCHARGE AIR PRESSURE AND POLLING OF VAV BOX DAMPER POSITIONS. DISCHARGE AIR PRESSURE SHALL INCLUDE A "CRITICAL ZONE RESET STRATEGY" WHICH REDUCES DISCHARGE AIR PRESSURE UNTIL AT LEAST ONE ZONE VAV BOX DAMPER IS 95% OPEN. THE INITIAL MAX AIR PRESSURE SETPOINT SHALL BE 5" WG (ADJUSTABLE).
THE AHU RETURN AIR FAN SHALL BE INTERLOCKED WITH THE SUPPLY AIR FAN. THE RETURN AIR FAN SPEED OFFSET SHALL BE DETERMINED DURING THE INITIAL TAB WORK. AS SPACE PRESSURIZATION RISES ABOVE 0.1" WG, THE RELIEF AIR SHALL MODULATE UP TO MAINTAIN SPACE PRESSURIZATION AT 0.1" WG (ADJUSTABLE).
OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN MINIMUM SCHEDULED OUTSIDE AIR UNLESS ECONOMIZER MODE IS AVAILABLE. WHEN DISCHARGE AIR TEMPERATURE RISES ABOVE 56°F, DISCHARGE AIR TEMPERATURE CONTROLLER THRU DDC CONTROL SHALL ENABLE THE ACCU TO MAINTAIN 55°F LEAVING AIR TEMPERATURE. THE STEAM VALVES SHALL BE CLOSED TO THE PRE-HEAT COIL AND HUMIDIFIER.
1.2 HEATING-OCCUPIED: AHU FANS, EXHAUST FANS, AND DAMPERS SHALL OPERATE AS IN COOLING-OCCUPIED MODE. WHEN DISCHARGE AIR TEMPERATURE DROPS BELOW 52°F, DISCHARGE AIR TEMPERATURE CONTROLLER THRU DDC CONTROL SHALL MODULATE THE STEAM VALVES TO MAINTAIN 55°F LEAVING AIR TEMPERATURE.
THE ACCU SHALL BE DE-ENERGIZED.
2 HUMIDIFICATION CONTROL
2.1 THE SUPPLY AIR HIGH LIMIT HUMIDITY SENSOR SETPOINT SHALL BE CAPABLE OF BEING ADJUSTED FROM EITHER THE CENTRAL OR LOCAL ECC CONTROL PANEL.
2.2 THE RETURN AIR HUMIDITY SENSOR LOCATED IN THE RETURN AIR DUCT SHALL MODULATE THE UNIT'S HUMIDIFIER STEAM CONTROL VALVES TO MAINTAIN THE SPACE HUMIDITY.
2.3 THE OUTDOOR AIR TEMPERATURE SENSOR SHALL CLOSE OFF THE HUMIDIFIER STEAM SUPPLY VALVES WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 60°F & OPEN THE HUMIDIFIER STEAM SUPPLY VALVE WHEN OUTSIDE AIR TEMPERATURE IS BELOW 60°F.
2.4 THE HUMIDIFIER STEAM CONDENSATE RETURN TEMPERATURE SWITCH SHALL FUNCTION TO SHUT THE HUMIDIFIER CONTROL VALVE UNTIL THE CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE. THE HUMIDIFIER CONTROL VALVE AND THE HUMIDIFIER STEAM SUPPLY VALVE WILL BE CLOSED TO THE HUMIDIFIER
WHENEVER THE SUPPLY FAN IS OFF.
3 ECONOMIZER CONTROL
3.1 A COMPARATIVE ENTHALPY ECONOMIZER STRATEGY SHALL BE UTILIZED. THE OUTSIDE AIR DAMPER SHALL MODULATE OPEN AND THE RETURN AIR DAMPER SHALL MODULATE CLOSED WHEN OA ENTHALPY IS LESS THAN RETURN AIR ENTHALPY IN COOLING MODE.
4 SAFTEY CONTROL/PROTECTION
4.1 THE FIRE ALARM CONTRACTOR SHALL PROVIDE SMOKE DETECTOR. THROUGH DDC CONTROL IT SHALL DE-ENERGIZE THE ASSOCIATED AHU, ALL ASSOCIATED EXHAUST FANS (INCLUDING INTERLOCKS), SIGNAL FIRE ALARM PANEL, AND CLOSE THE OUTSIDE AIR DAMPER UPON THE DETECTION OF THE PRODUCTS OF COMBUSTION.
4.2 FREEZE PROTECTION: IF STEAM HEATING COIL DISCHARGE AIR TEMPERATURE FALLS BELOW 40°F DURING HEATING MODE, THE FREEZESTAT SHALL CLOSE THE OUTSIDE AIR DAMPER, DE-ENERGIZE THE AHU SUPPLY AIR FAN AND FULLY OPEN THE PRIMARY HEATING VALVES TO THE COIL.
4.3 PRESSURE PROTECTION: A HIGH-PRESSURE TRANSMITTER LOCATED AT THE SUPPLY FAN DISCHARGE SHALL DE-ENERGIZE THE SUPPLY AIR FAN IF ITS SETPOINT, 5” WG, IS REACHED.
5 ALARMS
5.1 ALARM FOR DIRTY FILTER WHEN PRESSURE DROP EXCEEDS 0.5” WG ABOVE INITIAL PRESSURE DROP. ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR DROPS BELOW 50°F IN HEATING MODE. ALARM IF AHU SUPPLY OR RETURN AIR FAN FAILS TO START OR FAILS DURING OPERATION. ALARM IF UNIT
DISCHARGE STATIC PRESSURE EXCEEDS 5” WG. ALARM UPON SMOKE DETECTOR ACTIVATION.
STEAM
HUMIDIFIER
LPS
SMOKE
DETECTOR
CWR
CWS
EXISTING DDC GLOBAL
POINT - OA TEMP
OUTSIDE AIR
SUPPLY FAN
SD1
DPS
TT
T-1
SST
SF
HS
CS
IT-2
VFD
SPD
SF
TT
T-6
TT
T-3
TT
T-5
TSL
TSL-1
C O
O O
L I N
G
C O
R E
H E
A T
A F
T E
R F
I L
T E
R
P R
E F
I L
T E
R
TT
T-2
DPS
D-1
P R
E F
I L
T E
R
DPS
STEAM
CONDENSATE
1 2
SCV-1
LPS
STEAM
CONDENSATE
ALA
SF
COMM
SCV-2
SHCV-1
SHCV-2
AREA
EXHAUST
FAN
SST
EF
CS
IT-3
MS
EXISTING POINT
HUMIDITY
SENSOR
H
1 GENERAL FAN/TEMPERATURE CONTROL
1.1 COOLING-OCCUPIED: AHU SUPPLY AIR FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY. AHU WILL BE INTERLOCKED WITH ASSOCIATED AREA EXHAUST FANS, SO EACH EXHAUST FAN WILL OPERATE WHENEVER ITS
ASSOCIATED AHU IS ENERGIZED. OUTSIDE AIR DAMPER SHALL BE FULLY OPEN. WHEN DISCHARGE AIR TEMPERATURE RISES ABOVE 56°F, DISCHARGE AIR TEMPERATURE CONTROLLER THRU DDC CONTROL SHALL MODULATE
THE CHILLED WATER VALVE TO MAINTAIN 55°F LEAVING AIR TEMPERATURE. THE STEAM VALVES SHALL BE CLOSED TO THE PRE-HEAT COIL AND HUMIDIFIER. IF A VFD IS PRESENT, IT SHALL ONLY MODULATE MANUALLY FOR
BALANCING PURPOSES.
1.2 HEATING-OCCUPIED: AHU SUPPLY FAN, EXHAUST FANS, AND OUTSIDE AIR DAMPER SHALL OPERATE AS IN COOLING-OCCUPIED MODE. WHEN DISCHARGE AIR TEMPERATURE DROPS BELOW 52°F, DISCHARGE AIR
TEMPERATURE CONTROLLER THRU DDC CONTROL SHALL MODULATE THE STEAM VALVES TO MAINTAIN 55°F LEAVING AIR TEMPERATURE. THE CHILLED WATER COIL CONTROL VALVE SHALL BE CLOSED TO THE COIL.
2 HUMIDIFICATION CONTROL
2.1 THE SUPPLY AIR HIGH LIMIT HUMIDITY SENSOR SETPOINT SHALL BE CAPABLE OF BEING ADJUSTED FROM EITHER THE CENTRAL OR LOCAL DDC CONTROL PANEL.
2.2 THE SUPPLY AIR HUMIDITY SENSOR LOCATED IN THE SUPPLY AIR DUCT SHALL MODULATE THE UNIT'S HUMIDIFIER STEAM CONTROL VALVES TO MAINTAIN THE DISCHARGE AIR HUMIDITY AT 90% (ADJUSTABLE).
2.3 THE OUTDOOR AIR TEMPERATURE SENSOR SHALL SHUT THE HUMIDIFIER STEAM SUPPLY VALVES WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 60°F & OPEN THE HUMIDIFIER STEAM SUPPLY VALVE WHEN OUTSIDE AIR
TEMPERATURE IS BELOW 60°F.
2.4 THE HUMIDIFIER STEAM CONDENSATE RETURN TEMPERATURE SWITCH SHALL FUNCTION TO SHUT THE HUMIDIFIER CONTROL VALVE UNTIL THE CONDENSATE TEMPERATURE APPROACHES STEAM TEMPERATURE. THE
HUMIDIFIER CONTROL VALVE AND THE HUMIDIFIER STEAM SUPPLY VALVE WILL BE CLOSED TO THE HUMIDIFIER WHENEVER THE SUPPLY FAN IS OFF.
3 SAFTEY CONTROL/PROTECTION
3.1 THE FIRE ALARM CONTRACTOR SHALL PROVIDE THE SMOKE DETECTOR. THROUGH DDC CONTROL IT SHALL DE-ENERGIZE THE ASSOCIATED AHU, ASSOCIATED EXHAUST FANS (INCLUDING INTERLOCKS), SIGNAL FIRE ALARM
PANEL, AND CLOSE THE OUTSIDE AIR DAMPER UPON THE DETECTION OF THE PRODUCTS OF COMBUSTION.
3.2 FREEZE PROTECTION: IF STEAM HEATING COIL DISCHARGE AIR TEMPERATURE FALLS BELOW 40°F DURING HEATING MODE, THE FREEZESTAT SHALL CLOSE THE OUTSIDE AIR DAMPER, DE-ENERGIZE THE AHU SUPPLY AIR FAN
AND FULLY OPEN THE PRIMARY HEATING VALVES AND CHILLED WATER VALVES TO THE COIL.
4 ALARMS
4.1 ALARM FOR DIRTY FILTER WHEN PRESSURE DROP EXCEEDS 0.5” WG ABOVE INITIAL PRESSURE DROP. ALARM IF LEAVING AIR TEMPERATURE EXCEEDS 60°F IN COOLING MODE OR DROPS BELOW 50°F IN HEATING MODE. ALARM
IF AHU SUPPLY OR RETURN AIR FAN FAILS TO START OR FAILS DURING OPERATION. ALARM UPON SMOKE DETECTOR ACTIVATION.
CCV-1
Raleigh, NC
Indianapolis, IN
Pittsburgh, PA
Virginia Beach, VA
Atlanta, GA
Fort Collins, CO
RETURN AIR
PRESSURE SWITCH HIGH TO DISABLE FAN
WHEN HIGH PRESSURE LIMIT SETPOINT IS
REACHED (TYPICAL)
STEAM
HUMIDIFIER
LPS
SMOKE
DETECTOR
EXISTING DDC GLOBAL
POINT - OA TEMP
ECONOMIZER/OUTSIDE AIR SUPPLY FAN
(2 FAN ARRAY)
SPS
SP-1
HHL
HL-1
HT
H-2
PSH
SD1
DPS
TT
T-1
SST
SF
HS
CS
IT-2
VFD
SPD
SF
TT
T-6
TT
T-3
TT
T-5
TSL
TSL-1
C O
R E
H E
A T
A F
T E
R F
I L
T E
R
P R
E F
I L
T E
R
HT
H-1
TT
T4
TT
T-2
A F
M D
DPS
D-1
D-2
P R
E F
I L
T E
R
DPS
D-3
FT
AF-1
RELIEF AIR
SUPPLY AIR TO
TERMINAL UNIT
STEAM
CONDENSATE
CURRENT TRANSMITTER
FOR FAN STATUS (TYP.)
RETURN FAN
(TWO FAN ARRAY)
SST
RF
VFD HS
SPD
RF
ALA
RF
COMM
IT-1
CS
1 2
CV-STX3-1
LPS
STEAM
CONDENSATE
ALA
SF
COMM
SP-1
R E
T U
R
CV-STX3-2
CV-HX3-1
CV-HX3-2
AREA
EXHAUST
FAN
SST
EF
CS
IT-3
MS
EXISTING POINT
1 GENERAL FAN/TEMPERATURE CONTROL
1.1 COOLING-OCCUPIED: AHU SUPPLY AIR FAN AND RETURN AIR FAN SHALL BE ENERGIZED AND RUN CONTINUOUSLY. AHU WILL BE INTERLOCKED WITH ASSOCIATED AREA EXHAUST FANS, SO EACH EXHAUST FAN WILL OPERATE WHENEVER ITS ASSOCIATED AHU IS ENERGIZED. AHU
SUPPLY FAN SPEED SHALL BE DETERMINED BY DISCHARGE AIR PRESSURE AND POLLING OF VAV BOX DAMPER POSITIONS. DISCHARGE AIR PRESSURE SHALL INCLUDE A "CRITICAL ZONE RESET STRATEGY" WHICH REDUCES DISCHARGE AIR PRESSURE UNTIL AT LEAST ONE ZONE VAV
BOX DAMPER IS 95% OPEN. THE INITIAL MAX AIR PRESSURE SETPOINT SHALL BE 5" WG (ADJUSTABLE). THE AHU RETURN AIR FAN SHALL BE INTERLOCKED WITH THE SUPPLY AIR FAN. THE RETURN AIR FAN SPEED OFFSET SHALL BE DETERMINED DURING THE INITIAL TAB WORK. AS SPACE
PRESSURIZATION RISES ABOVE 0.1" WG, THE RELIEF AIR SHALL MODULATE UP TO MAINTAIN SPACE PRESSURIZATION AT 0.1" WG (ADJUSTABLE). OUTSIDE AIR DAMPER SHALL MODULATE TO MAINTAIN MINIMUM SCHEDULED OUTSIDE AIR UNLESS ECONOMIZER MODE IS AVAILABLE. WHEN
DISCHARGE AIR TEMPERATURE RISES ABOVE 56°F, DISCHARGE AIR TEMPERATURE CONTROLLER THRU DDC CONTROL SHALL MODULATE THE CHILLED WATER VALVE TO MAINTAIN 55°F LEAVING AIR TEMPERATURE. THE STEAM VALVES SHALL BE CLOSED TO THE PRE-HEAT COIL AND
HUMIDIFIER.
1.2 HEATING-OCCUPIED: AHU FANS, EXHAUST FANS, AND DAMPERS SHALL OPERATE AS IN COOLING-OCCUPIED MODE.