RFI 001 prebid responses SYR VA Garage pdf format 02.pdf
PDF 267 KB Posted
- Attached to
- Z1DA--528A7-22-177 REPAIR GARAGE BEAMS
- Solicitation number
- 36C24223B0016
About this file
This document contains a Request for Information (RFI) and responses related to a federal contract opportunity for repair work at the Syracuse VA Medical Center parking garage. The RFI addresses questions on post-tensioned concrete repair certification requirements, traffic coating installation qualifications, concrete reinforcement details, responsibility for road closures during repairs, and allowance amounts for rebar replacement. Responses provide clarification on required special inspector qualifications, contractor qualification by the membrane manufacturer, joint reinforcement specifications, unreinforced concrete elements, responsibility for coordinating road closures with the city, and use of the rebar allowance. Additionally, the related federal contract opportunity is for repairs to parking garage floors, beams, slabs, columns, walls, curbs, post-tensioned tendons, cracks, railings and other miscellaneous elements, to be provided by the contractor per drawings, specifications and contract documents for the Syracuse VAMC. The work is to be awarded through the Department of Veterans Affairs Veterans Health Administration VISN 2.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24223B0016 0003.docx | DOCX document | |
| RFI 002 prebid responses SYR VA Garage pdf format.pdf | ||
| 36C24223B0016 0002_1.docx | DOCX document | |
| 36C24223B0016 0001.docx | DOCX document | |
| 36C24223B0016.docx | DOCX document | |
| Combined Specs 528A7_22_177.pdf | ||
| Wage Determination 1-6-23 Heavy and Highway.pdf | ||
| 230111_VA-REHAB Bid Documents 22pages.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFI #001
Date: 5/2/23 Project: Repair Garage Slabs and Beams, Syracuse VA Medical Center Syracuse, NY
QUESTION(s):
1. For all post tension repairs, please advise if Post-Tensioned Institute Certification Level 1 is required.
• Response: Refer to page 01 45 35-5 of the contract specifications. Special Inspector shall have a PTI Level 2 Unbonded PT Inspector Certificate or a Registered Professional Engineer with related experience. An Associate Special Inspector shall have a PTI Level 1 Unbonded PT Inspector Certificate with one year of related experience, or EIT with one year of related experience. Refer to paragraphs E and F of specification 01 45 35-2, 1.4.
2. For all traffic coatings installation, please advise if contractors must be approved qualified installers by the manufacturer and how many years of experience is required.
• Response: Contractor must be approved as a qualified installer by the manufacturer.
3. For the slab on grade repairs, please advise to the type of reinforcement required as none is shown on the details on drawing S-301.
• Response: No reinforcement required. Provide joint reinforcement per B1 & B1a S-301.
4. For the topping slab replacement on detail C3/S-302, please advise of the type of reinforcement required as none is shown on detail.
• Response: Topping slab is unreinforced.
5. For detail B4/S-301, PT Concrete Beam Repair, the existing conditions in the field vary from the existing detail, the repairs needed in the field are at the mid span of the beam, where most likely the PT Tendons will be at the lowest part. These repairs might need extensive shoring.
Please advise if the shoring will be address by change order on a as needed basis.
• Response: Shoring to be provided on an as needed basis.
6. During the pre-bid meeting, it was stated that the existing coating on the 1st Level, would have to be removed, please advise if a full removal is required or if a re-coat suffices, the re-coat will also get the required 5-year warranty per specs. There is no mention on the bid documents of any existing membrane.
• Response: Existing Level 1 Striping Plan, detail G4/B-112, note 1 states “Remove Existing Urethane Membrane on All Drive Surfaces”.
7. Under the Bid Concrete Repair Quantities Table on Drawing S-301, work item for Beam Repair – Reinf. Steel for 500 LBS, please provide detail and description of the scope of work.
• Response: This is an allowance for replacement rebar as required per A2/S-301 note J.4.b. Refer to attached JD-S1 defining rebar splicing.
8. For all the repairs at the 1st floor level directly above Van Buren Street, please advise who will be responsible for road closures as required. Also, if road closures are on the contractors, advise if the costs will be as needed thru change orders, or should the contractors carry an allowance towards the road closures.
• Response: The contractor shall be responsible for all costs associated with road closures and shall coordinate road closures with the City of Syracuse. Refer to https://www.syr.gov/Departments/Central-Permit-Office , and contact the city permit office at 315-448-8600 for fees and requirements for temporary road closures.
Attachment:
1. JD-S1
https://www.syr.gov/Departments/Central-Permit-Office
A1
S-302
B1
S-302
D:RPDET1104
WELD SPLICE DETAIL AND TABLE
NO SCALE
SECTION PLAN DETAIL
C
C
C
C
NOTES:
1. ELECTRODE E70XX
2. WELDING TO CONFORM TO ANSI/AWS D1.4 WELDING OF REINFORCEMENT REQUIRES A
PREHEAT OF 300° F FOR #6 BARS AND SMALLER AND 400° F FOR #7 BAR AND LARGER.
3. STEEL ANGLE..............................ASTM A36.
4. MECHANICAL COUPLERS MAY BE USED IN LIEU OF WELDED SPLICES WHERE FEASIBLE.
5. MINIMUM 1" CONCRETE COVER OVER ANGLE.
SEE TABLE
NEW BAREXG. BAR
SEE
TABLE
SEE
TABLE
ANGLE, SEE
TABLE OF SIZE
SPLICE TABLE
1/4" x 2 1/2" x 8"
BAR ANGLE SIZE WELDS
ALTERNATE
STEEL PLATE
#4 L 2x2x3/8 x 8" LG
1/4 3
1/4" x 3 1/2" x 8"#5 L 2x2x3/8 x 8" LG
3/8 3
3/8" x 3 1/2" x 8"#6 L 2x2x3/8 x 8" LG
3/8 3
7/16" x 4" x 10"#7 L 3x3x7/16 x 10" LG
3/8 4
1/2" x 4 1/2" x 12"#8 L 3 1/2x3 1/2x1/2 x 10" LG
3/8 4
1/2" x 5" x 12"#9 L 3x3x1/2 x 12" LG
3/8 5 1/2
SEE TABLE
FOR SIZE &
LENGTH
D:RPDET1105
CONCRETE REINFORCING BAR LAP TABLE
NO SCALE
REINFORCING BAR LAP TABLE
BAR SIZE LAP d
#3
#4
#5
#6 28 in.
24 in.
19 in.
16 in.
BAR SIZE LAP d
#7
#8
#9
92 in.#10
54 in.
48 in.
42 in.
05-08-2023DATE:
DRAWING No.
JOB No.: 221152.00 DRWN. BY: CHKD. BY: EN DETAIL No.: A1/B1FROM SHEET: S-302
JOB DETAIL
JD-S1
sdb
JOHN P. STOPEN
ENGINEERING, LLP
P.O. BOX 29, SUITE 400
SYRACUSE, NEW YORK 13201
450 SOUTH SALINA STREET
(315) 472-5238 FAX (315) 472-8430
NEW REBAR SPLICE DETAIL & LENGTH TABLES
FLOORS AND BEAMS
V.A. MEDICAL CENTER, SYRACUSE, NY
REPAIR PARKING GARAGE
V.A. Project # 528A7-22-177 / V.A. Building # 19