36C24222R0033 0003.docx

DOCX document 26 KB Posted

Attached to
Y1DA-- REPLACE OXYGEN TANK | 630-22-116 Federal contract opportunity
Solicitation number
36C24222R0033
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

This solicitation package includes a Request for Proposal (RFP) to design-build a project to replace an oxygen tank at the Veterans Affairs Medical Center in New York. Key requirements include providing all labor, materials, and design-build services to design and construct a new oxygen tank system, including drawings, specifications, estimates, and site preparation. The contractor will design and install a 9,000-gallon liquid oxygen tank, associated vaporizers, and related infrastructure. The contractor must complete design reviews at 30%, 60%, and 95% stages and incorporate comments. Construction must be completed within 120 days of notice to proceed. The Department of Veterans Affairs will administer the contract and oversee the project.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DA-- REPLACE OXYGEN TANK | 630-22-116, newest first.
File Type Posted
36C24222R0033 0002.docx DOCX document
KBA OXYGEN TANK 6000 Gals.pdf PDF
9000 Gallon Tank.pdf PDF
36C24222R0033 0001.docx DOCX document
36C24222R0033_1.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7.

ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF

PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE

OF YOUR

ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERE

D CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES

SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendmen t, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED

STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF

CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF

SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 630-22-116 36C242 Department of Veterans Affairs Network Contracting Office 2 James J. Peters VA Medical Center 130 West Kingsbridge Road Bronx NY 10468-3904 36C242 Department of Veterans Affairs James J. Peters VA Medical Center Network Contracting Office 2 130 West Kingsbridge Road Bronx NY 10468-3904 To all Offerors/Bidders

36C24222R0033 03-16-2022

X X X

Amendment 0003 Replace Oxygen Tank

This amendment is to address RFI's.

The response date is now March 24,2022 at 2:00pm.

See attached responses.

No further questions will be accepted.

CONTINUATION PAGE

Replace Oxygen Tank Project Number: 630-22-116 – Responses to RFI’s

1) Solicitation page 16 of 110 SOW line-item no.1 states Install temporary oxygen supply system as noted on the plans. --- There are no plans, these plans are missing from the bid document.

Temporary Oxygen supply system has been installed by VA. See reference in Design Build Specs 00 11 21

2) Solicitation page 16 of 110 SOW line-item no.2 states Remove 6000-gallon permanent oxygen tank. – During the site visit we found that this tank is already removed.

The Existing oxygen tank has been removed.

3) SOW line item 3 states Provide and install new 6000-gallon liquid oxygen tank on prepared foundation:

a) Please clarify if contractor must supply the tank or VA will provide the tank and contractor must install only? See recommended AE design for 9000 Gallon Tank, need coordination with Vendor for installation requirements.

b) If incase contractor must supply the tank, we did quick research and found that a 6,000-gallon tank size is approx. 26’ – 0” ht x 8’ – 0” diameter and weight is 85,000 pounds. Please advise if this will be acceptable to the agency as this height tank will then extend through the roof. See reference design & requirement for installation of a 9000 Gallon oxygen tank. The oxygen tank will extend through the roof through an existing opening.

4) SOW line-item no.5 states Remove the temporary oxygen supply system. – Please advise where is the location of this temporary oxygen supply? Temporary oxygen supply system has been installed. AE/ Contractor to verify with equipment vendor and conduct site investigation and conditions.

5) Please advise the connection point of the new oxygen supply piping. Also, this new piping must run below the grade or above the grade. Please clarify in detail. Reference to Vander equipment manual & requirements. Piping is to be run below grade.

6) SOW line-item states Coordinate and install new 6000/ 9000-gallon liquid oxygen tank on prepared foundation. --- Please clarify if the new tank capacity is 6,000 or 9,000 gallons, again we did quick research on the 9,000 gallon tank and found that 9,000 gallon tank size is 32’ – 0” height x 10’ – 2” diameter and weight is 130,000 pounds. So, there is big difference in size and weight of 6,000 and 9,000 gallon tanks. 9,000 Gallon tank.

7) SOW states Provide Feasibility Study for Oxygen Tank (options 6000-gal tank, cost proposal / 9000 gal, cost etc.) --- Please clarify what capacity tank is required? Accordingly, contractor can provide a feasibility study on the one tank. Study for the 9,000 Gallon

8) SOW states provide 50’ soil bore at the location for Geotech testing of site. – Instead of 50’ soil bore a 100’ soil bore should be done to find out more details of the soil strata. 100’ soil bore, verify with Vendor and equipment installation requirements

9) SOW states provide structural engineered drawings for the existing 1 story building. – Please define the correct scope of the work for the existing 1 story building accordingly contractor can prepare the drawings. For the 1 story building.

10) SOW states provide architectural drawings of a new exterior wall to match existing in height… -- Please clarify why are we removing part of the wall? Yes, you are removing one part of the wall. And building a wall for the 2 hydraulics pumps in the back.

11) SOW states Provide Mechanical, Electrical, Plumbing, (MEP) Drawings. --- Please advise what is the scope of the work for the mechanical and plumbing work.

Reference to 00 11 21 Design Build VA Specs and Equipment installation requirements work shall include electrical outlets, lights and water for water house to de-ice the new vaporizers.

12) SOW states See reference drawing from KBA Engineering P.C (G200, G201 and G202 for 6000).

For 9000 gal tank refer Air Products DWGS. --- All these drawings are missing, please provide the required drawings. Reference to 9000 Gallon design DWGs. Details will become available when project is finalized.

13) SOW states Reconfigure Building #2 to accommodate both a larger tank and larger vaporizers. – Please provide the details of the tank and vaporizers, also who is supplying the larger tank and larger vaporizers? If this is contractors’ responsibility, then please provide all the details including the size and dimensions. We don’t have a contractor, but we need to support the new upcoming tanks / vaporizers. Contractor to coordinate with Equipment vendor

14) SOW states Create a new room within the south bay to specifically house the hydraulic equipment for the parking lot lifts. --- Please provide detailed information/drawing for this hydraulic equipment. Building a wall/ door to have access and make it up to code for electrical sprinkler etc.

15) SOW states Install a new 16-inch-thick slab reinforced and material specified similar to the seismic slab currently provided to the projects group. Grade the slab such that it is 1-1/2 inches higher at the back side and slopes to the overhead doors. – Please advise if floor drains can be installed in the concrete slab? No floor drains.

16) SOW states Remove all existing wall and ceiling conduits... – Please advise if all the existing devices will be removed and installed new. Yes, remove all and install new

17) SOW states Tuck point repair the exterior walls. --- As per our field observations North wall will need a partial or complete reconstruction. Please advise. Need complete reconstruction

18) SOW states replace both bays roll-up doors with new galvanized steel exterior roll- up security grill. – Please specify the size of the new roll up doors or is it a in kind replacement. Same size

19) Based on the scope of the work and if the new oxygen tank is to be supplied by contractor, then the magnitude of construction $500,000 and $1,000,000 seems very less.

Scope of Work is for site prep and restoration. Oxygen tank is leased and supplied by others.

20) If possible, can agency provide soil boring report of the project area. There are no soil boring reports to provide.

21) How will the new LOX tank connect to the hospital? Will temporary lines be supported on scaffolding as per the drawings G201? Yes, per drawings. Contractor to provide means and methods, see Equipment installation requirement.

22) Has the temporary oxygen supply trailer on drawing G202 been completed by the hospital? No

23) There is no mention of a concrete foundation for the Vaporizers or any other required components for a complete install. The new foundation needs to support a 9,000-gallon tank, 1,500-gallon tank & 2 vaporizers.

24) We do not have a diagram of the complete LOX tank, vaporizers, pumps, control panels, alarm panel, etc. to refer to. Need coordination with AE in Design and reference drawing to be provided when project is finalized

25) Do the vaporizers fit in the existing structure or are they projecting through the roof as well?

This will be a need to make an opening at the roof for the new tank and vaporizer fit. See 9000 Gallons design as reference.

Responses to RFIs End