36C24220B0015-124.pdf

PDF Posted

Attached to
Y1DA--630A4-17-610 DEMOLISH BUILDING 3
Solicitation number
36C24220B0015
Issued by

About this file

This document contains a federal contract opportunity solicitation and related laboratory test report. The solicitation is for demolition services for Building 3 at the Department of Veterans Affairs facility in Brooklyn, New York under solicitation number 36C24220B0015. The laboratory test report provides lead testing results for paint chip samples collected from a metal door frame at an unspecified location as part of project number 1/20/2016. The report identifies the client, laboratory, sample details, analytical methods used, and lead concentration results.

36C24220B0015 Brooklyn VA - Paint Chips.pdf

View the file

Other files

File Type Posted
36C24220B0015-153.docx DOCX document
36C24220B0015-152.docx DOCX document
36C24220B0015-151.docx DOCX document
36C24220B0015-123.pdf PDF
36C24220B0015-120.docx DOCX document
36C24220B0015-125.pdf PDF
36C24220B0015-121.pdf PDF
36C24220B0015-122.pdf PDF
36C24220B0015-101.docx DOCX document
36C24220B0015-096.zip ZIP file
36C24220B0015-098.zip ZIP file
36C24220B0015-095.docx DOCX document
36C24220B0015-097.zip ZIP file
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OrderID: 201600730

OrderID: 201600730

Client Sample Description ConcentrationLab ID Analyzed Lead

Collected

EMSL Analytical, Inc.

200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com

Attn: Tracy Brucato Environmental Health Investigations,Inc.

655 West Shore Trail

Sparta, NJ 07871

Received: 01/21/16 12:00 PM

1155-6049 A

Fax: (973) 729-5649 Phone: (973) 729-5649

Project:

1/20/2016Collected:

Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*

201600730 CustomerID: EHII50 CustomerPO:

ProjectID:

EMSL Order:

Site: 1st Floor- West Exit Metal Door Frame- Blue/White Desc: Paint

201600730-0001BVA-3-012016 A <0.010 % wt1/22/20161/20/2016

Site: 1st Floor- Metal Stair Riser/Stringer- Brown Paint 201600730-0002BVA-3-012016 B 0.30 % wt1/22/20161/20/2016

Site: 1st Floor- South Plaster Wall- White Paint 201600730-0003BVA-3-012016 C 0.10 % wt1/22/20161/20/2016

Site: Exterior- West Metal- Stairs- Blue Paint 201600730-0004BVA-3-012016 D 0.016 % wt1/22/20161/20/2016

Site: Interior 1st Floor- Door Frame Closet- White/Gray Desc: Paint

201600730-0005BVA-3-012016 E 0.35 % wt1/22/20161/20/2016

Site: Interior Stair Ceramic Tile Wall- White/Gray Paint 201600730-0006BVA-3-012016 F <0.010 % wt1/22/20161/20/2016

Site: 2nd Floor- North Plaster Wall- White/Gray Paint 201600730-0007BVA-3-012016 G 0.13 % wt1/22/20161/20/2016

Site: 2nd Floor- Interior Exit Door- Stair- Metal- White Desc: Red

201600730-0008BVA-3-012016 H 0.039 % wt1/22/20161/20/2016

Bill Chamberlin, Laboratory Director or other approved signatory or other approved signatory

Test Report ChmSnglePrm/nQC-7.32.3 Printed: 1/25/2016 12:06:13 PM

*Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.010 % wt based on the minimum sample weight per our SOP. Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements established by the AIHA-LAP, unless specifically indicated otherwise.

Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01

Initial report from 01/25/2016 11:59:58 http://www.EMSL.com mailto:cinnaminsonleadlab@emsl.com

Client Sample Description ConcentrationLab ID Analyzed Lead

Collected

EMSL Analytical, Inc.

200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com

Attn: Tracy Brucato Environmental Health Investigations,Inc.

655 West Shore Trail

Sparta, NJ 07871

Received: 01/21/16 12:00 PM

1155-6049 A

Fax: (973) 729-5649 Phone: (973) 729-5649

Project:

1/20/2016Collected:

Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*

201600730 CustomerID: EHII50 CustomerPO:

ProjectID:

EMSL Order:

Site: 1st Floor- West Exit Metal Door Frame- Blue/White Desc: Paint

201600730-0001BVA-3-012016 A <100 ppm1/22/20161/20/2016

Site: 1st Floor- Metal Stair Riser/Stringer- Brown Paint 201600730-0002BVA-3-012016 B 3000 ppm1/22/20161/20/2016

Site: 1st Floor- South Plaster Wall- White Paint 201600730-0003BVA-3-012016 C 1000 ppm1/22/20161/20/2016

Site: Exterior- West Metal- Stairs- Blue Paint 201600730-0004BVA-3-012016 D 160 ppm1/22/20161/20/2016

Site: Interior 1st Floor- Door Frame Closet- White/Gray Desc: Paint

201600730-0005BVA-3-012016 E 3500 ppm1/22/20161/20/2016

Site: Interior Stair Ceramic Tile Wall- White/Gray Paint 201600730-0006BVA-3-012016 F <100 ppm1/22/20161/20/2016

Site: 2nd Floor- North Plaster Wall- White/Gray Paint 201600730-0007BVA-3-012016 G 1300 ppm1/22/20161/20/2016

Site: 2nd Floor- Interior Exit Door- Stair- Metal- White Desc: Red

201600730-0008BVA-3-012016 H 390 ppm1/22/20161/20/2016

Bill Chamberlin, Laboratory Director or other approved signatory or other approved signatory

Test Report ChmSnglePrm/nQC-7.32.3 Printed: 1/25/2016 12:06:59 PM

*Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.010 % wt based on the minimum sample weight per our SOP. Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements established by the AIHA-LAP, unless specifically indicated otherwise.

Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01

Initial report from 01/25/2016 11:59:58 http://www.EMSL.com mailto:cinnaminsonleadlab@emsl.com

201600730_coc
201600730_004
201600730-%
201600730-ppm

File details come from the government source that posted it. Updated .