36C24219R0176-013.docx

DOCX document 26 KB Posted

Attached to
LVT Flooring Installation Building 4AB Montrose Federal contract opportunity
Solicitation number
36C24219R0176
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2

About this file

36C24219R0176 096519 Resilient Tile Flooring EDITED.docx

View the file

Other files for this federal contract opportunity

Other files attached to LVT Flooring Installation Building 4AB Montrose, newest first.
File Type Posted
36C24219C0232-000.docx DOCX document
36C24219R0176-0001000.docx DOCX document
36C24219R0176-012.docx DOCX document
36C24219R0176-017.pdf PDF
36C24219R0176-016.docx DOCX document
36C24219R0176-010.docx DOCX document
36C24219R0176-014.docx DOCX document
36C24219R0176-018.pdf PDF
36C24219R0176-015.doc DOC document
36C24219R0176-011.docx DOCX document
36C24219R0176-009.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VAMC MONTROSE, NY

“REPLACE FLOORING, 1ST FLOOR, BLDG.4 at FDR”

SECTION 09 65 19

RESILIENT TILE FLOORING

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies the installation of luxury vinyl tile and accessories required for a complete installation.

1.2 SUBMITTALS:

A.Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.
B.Manufacturer's Literature and Data:
1.Description of each product.
2.Resilient material manufacturer’s recommendations for adhesives, underlayment, primers, and polish.
3.Application, installation and maintenance instructions.
C.Samples:
1.Tile: Each type, color, thickness and finish.
D.Shop Drawings:
1.Layout of patterns as shown on the construction documents.
E.Test Reports:
1.Abrasion resistance: Depth of wear for each tile type and color and volume loss of tile, certified by independent laboratory. Tested per ASTM F510/F510M.

1.3 DELIVERY:

A.Deliver materials to the site in original sealed packages or containers, clearly marked with the manufacturer's name or brand, type and color, production run number and date of manufacture.
B.Materials from containers which have been distorted, damaged or opened prior to installation are not acceptable.

1.4 STORAGE:

A. Store materials in a clean, dry, enclosed space off the ground, protected from harmful weather conditions and at temperature and humidity conditions recommended by the manufacturer. Protect adhesives from freezing. Store flooring, adhesives, and accessories in the spaces where they will be installed for at least 48 hours before beginning installation.

1.5 QUALITY ASSURANCE:

A. Installer Qualifications: A company specializing in installation with minimum three (3) years’ experience and employs experienced flooring installers who have retained, and currently hold, an INSTALL Certification, or a certification from a comparable certification program.

1. Installers to be certified by INSTALL or a comparable certification program with the following minimum criteria:

a. US Department of Labor approved four (4) year apprenticeship program, 160 hours a year.

b. Career long training.

c. Manufacturer endorsed training.

d. Fundamental journeyman skills certification.

B. Furnish product type materials from the same production run.

1.6 warranty:

A. Construction Warranty: Comply with FAR clause 52.246-21, “Warranty of Construction”. Limited Ten (10) year commercial warranty for Luxury Vinyl Floor Tile.

1.7 APPLICABLE PUBLICATIONS:

A.The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B.ASTM International (ASTM):
D2047-11Test Method for Static Coefficient of Friction of Polish-Coated Flooring Surfaces as Measured by the James Machine
D2240-05(R2010)Test Method for Rubber Property—Durometer Hardness
D4078-02(R2008)Water Emulsion Floor Finish
E648-14cCritical Radiant Flux of Floor Covering Systems Using a Radiant Energy Source
E662-14Specific Optical Density of Smoke Generated by Solid Materials
E1155/E1155M-14Determining Floor Flatness and Floor Levelness Numbers
F510/F510M-14Resistance to Abrasion of Resilient Floor Coverings Using an Abrader with a Grit Feed Method
F710-11Preparing Concrete Floors to Receive Resilient Flooring
F925-13Test Method for Resistance to Chemicals of Resilient Flooring
F1344-12(R2013)Rubber Floor Tile
F1700-13aSolid Vinyl Floor Tile
F1869-11Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride
F2170-11Test Method for Determining Relative Humidity in Concrete Floor Slabs Using in Situ Probes
F2195-13Linoleum Floor Tile
C.Code of Federal Regulation (CFR):
40 CFR 59Determination of Volatile Matter Content, Water Content, Density Volume Solids, and Weight Solids of Surface Coating

D. International Standards and Training Alliance (INSTALL):

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS FOR LUXURY VINYL TILE FLOORING:

A.Provide adhesives, underlayment, primers, and polish recommended by resilient floor material manufacturer.
B.Critical Radiant Flux: 0.45 watts per sq. cm or more, Class I, per ASTM E648.
C.Smoke Density: Less than 450 per ASTM E662.

D. Slip Resistance – Not less than 0.5 when tested with ASTM D2047.

E. Flexibility - ASTM F137 - Passes - ≤ 1.0 in., no cracks or breaks

F. Dimensional Stability - ASTM F2199 - Passes - ≤ 0.020 in. per linear foot G. Static Load Limit - ASTM F970 - Passes, modified - 1000 psi H. Residual Indentation - ASTM F1914 - Passes - Average less than 8%I I. Resistance to Chemicals ASTM F925 - Passes - No Change J. Resistance to Light - ASTM F1515 - Passes - ΔE ≤ 8 K. Resistance to Heat - ASTM F1514 - Passes - ΔE ≤ 8

2.2 Luxury Vinyl Tile SALIENT CHARACTERISTICS:

A. ASTM F1700, Class III, Printed Film Vinyl Tile, Type A. Glue down.

B. Thickness: 12 mil (1/8 inch)

C. Squareness:ASTM F2055 - shall not exceed 0.010 in.
D. Size and ToleranceASTM F2055 - +/- 0.016 in. per linear foot

C. Wear Layer: 20 mil (0.5 mm) with Enhance Urethane & Glue Down D. Limited Ten (10) year commercial warranty E. Provide products with recycled content with not less than 30 percent.

F. Sustainability: FloorScore Certified – Made in USA

2.3 ADHESIVES:

A. Provide water resistant type adhesive for flooring, base and accessories as recommended by the manufacturer to suit substrate conditions. VOC content to be less than the 50 grams/L when calculated according to 40 CFR 59 (EPA Method 24). Submit manufacturer’s descriptive data, documentation stating physical characteristics, and mildew and germicidal characteristics.

2.4 PRIMER FOR CONCRETE SUBFLOORS:

A. Provide in accordance with Section 09 05 16, SUBSURFACE PREPARATION FOR FLOOR FINISHES.

2.5 LEVELING COMPOUND For Concrete Floors:

A. Provide cementitious products with latex or polyvinyl acetate resins in the mix in accordance with Section 09 05 16, SUBSURFACE PREPARATION FOR FLOOR FINISHES.

PART 3 - EXECUTION

3.1 environmental requirements:

A. Maintain flooring materials and areas to receive resilient flooring at a temperature above 20 degrees C (68 degrees F) for three (3) days before application, during application and two (2) days after application, unless otherwise directly by the flooring manufacturer for the flooring being installed. Maintain a minimum temperature of 13 degrees C (55 degrees F) thereafter. Provide adequate ventilation to remove moisture from area and to comply with regulations limiting concentrations of hazardous vapors.

3.2 SUBFLOOR TESTING AND PREPARATION:

A. Prepare and test surfaces to receive resilient tile and adhesive as per Section 09 05 16, SUBSURFACE PREPARATION FOR FLOOR FINISHES.

1. Remove existing resilient floor and existing adhesive.

B. Prepare concrete substrates in accordance with ASTM F710.

3.3 INSTALLATION:

A.Install in accordance with manufacturer's instructions for application and installation unless specified otherwise.
B.Mix tile from at least two containers. An apparent line either of shades or pattern variance is not acceptable.
C.Tile Layout:
1.Layout shown on construction drawings is for information only. Coordinate layout with the VA COR prior to submission of the required layout shop drawings. Installing flooring in accordance with the shop drawings approved by the VA.
2.Vary edge width as necessary to maintain full size tiles in the field, no edge tile to be less than 1/2 the field tile size, except where irregular shaped rooms make it impossible.
3.Place tile pattern in the same direction; do not alternate tiles unless specifically indicated in the construction documents to the contrary.
D.Application:
1.Adhere floor tile to flooring substrates using a full spread of adhesive applied to substrate to produce a completed installation without open cracks, voids, raising and puckering at joints, telegraphing of adhesive spreader marks, and other surface imperfections.
2.Scribe, cut, and fit floor tiles to butt neatly and tightly to vertical surfaces and permanent fixtures including built-in furniture, cabinets, pipes, outlets, and door frames.
3.Extend floor tiles into toe spaces, door reveals, closets, and similar openings. Extend floor tiles to center of door openings.

4. Roll tile floor with a minimum 45 kg (100 pound) roller.

3.4 CLEANING AND PROTECTION:

A.Clean adhesive marks on exposed surfaces during the application of resilient materials before the adhesive sets. Exposed adhesive is not acceptable.
B.Keep traffic off resilient material for a minimum 72 hours after installation.
C.Clean flooring as recommended in accordance with manufacturer’s printed maintenance instructions and within the recommended time frame.
D.When construction traffic occurs over tile, cover resilient materials with reinforced kraft paper properly secured and maintained until removal is directed by COR. At entrances and where wheeled vehicles or carts are used, cover tile with plywood, hardboard, or particle board over paper, secured and maintained until removal is directed by COR.
E.When protective materials are removed and immediately prior to acceptance, replace damaged tile, re-clean resilient materials.

3.5 LOCATION:

A. Where shown on contract drawings.

- - - E N D - - - 09 65 19 - 1