36C10E19B0001-0005008.pdf
PDF 3 MB Posted
- Attached to
- AMO/DROC, BLD 47 | St. Pete Federal contract opportunity
- Solicitation number
- 36C10E19B0001
About this file
36C10E19B0001 0005 S02 - Addendum 2 - Drawings.pdf
View the file
Other files for this federal contract opportunity
Show all 50
AMO/DROC, BLD 47 | St. Pete has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
T
T
T
T
T
T T
T
T T
T
T
T
T
T
T
T
T
T
T
1 2 3 4 5
A
B
C
D
E
MEN'S
ELECTRICAL
TELEPHONE
OPEN OFFICE
OPEN OFFICE
HK
WOMEN
WORK AREA
OFFICE
OFFICE
OFFICE
MEETING
MEETING
LACTATION
OFFICE
MEETING
WORK AREA
OFFICE
OFFICE
OFFICE
BREAK
MEETING
WORK AREA
CORRIDOR
WORK AREA
WORK AREA
CORRIDOR
CORRIDOR
CORRIDOR
ENTRY
10ø
12ø
3/4" CD
REFRIGERANT LINES UP CHASE TO
ROOF MOUNTED CONDENSING UNIT
DOWN COLUMN TO
GRADE LEVEL STORM
BRIDGE
40 CFM
LSD-8
50 CFM
LSD-8
55 CFM
LSD-7
155 CFM
LSD-4
6ø
10ø
6ø
10ø
(E)24ø
110 CFM
SD-1
110 CFM
SD-1
110 CFM
SD-1
110 CFM
SD-1
10ø
VAV-1
VAV-13
10ø
9ø
10ø
6ø
6ø
VAV-21
35 CFM
LSD-1
75 CFM
SD-2
75 CFM
SD-2
8ø
SD-4
300 CFM
SD-5
580 CFM
8ø
8ø
6ø
6ø
75 CFM
SD-2
75 CFM
SD-2
6ø 6ø
8ø
6ø
8ø
6ø
6ø
185 CFM
LST-1
6ø
6ø
6ø
90 CFM
LST-1
95 CFM
LST-1
FC-A2
VAV-13
VAV-1
(E)VAV-3
(E)VAV-4
(E)VAV-20
(E)VAV-5
(E)VAV-7 (E)VAV-8
(E)VAV-9
(E)VAV-10
(E)VAV-11
(E)VAV-12
(E)VAV-14
(E)VAV-15
(E)VAV-16
(E)VAV-17
(E)VAV-19
(E)VAV-18
(E)VAV-6
(E)VAV-2
(E)VAV-3
(E)VAV-20
(E)VAV-7
(E)VAV-8 (E)VAV-9
(E)VAV-10
(E)VAV-11
(E)VAV-12
(E)VAV-14
(E)VAV-19
(E)VAV-18
(E)VAV-4
(E)VAV-15
(E)VAV-2
1185 995
28x24
205300
210 CFM
(E)SD
210 CFM
(E)SD
200 CFM
(E)SD
210 CFM
(E)SD
210 CFM
(E)SD
210 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
160 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
165 CFM
(E)SD
165 CFM
(E)SD
165 CFM
(E)SD
175 CFM
(E)SD
165 CFM
(E)SD165 CFM
(E)SD
420 CFM
(E)SD
115 CFM
(E)SD
115 CFM
(E)SD
150 CFM
(E)SD
150 CFM
(E)SD
205 CFM
(E)SD
195 CFM
(E)SD
210 CFM
(E)SD
130 CFM
(E)SD
125 CFM
(E)SD
120 CFM
(E)SD
120 CFM
(E)SD
45 CFM
(E)SD
150 CFM
(E)SD
115 CFM
(E)SD
115 CFM
(E)SD
115 CFM
(E)SD
115 CFM
(E)SD
160 CFM
(E)SD
160 CFM
(E)SD
160 CFM
(E)SD
160 CFM
(E)SD
195 CFM
(E)SD 195 CFM
(E)SD
165 CFM
(E)SD
170 CFM
(E)SD
165 CFM
(E)SD
165 CFM
(E)SD
165 CFM
(E)SD
165 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
150 CFM
(E)SD
150 CFM
(E)SD
210 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
160 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
155 CFM
(E)SD
155 CFM
(E)SD
155 CFM
(E)SD
155 CFM
(E)SD
155 CFM
(E)SD
155 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
210 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
195 CFM
(E)SD
160 CFM
(E)SD
160 CFM
(E)SD
160 CFM
(E)SD
160 CFM
(E)SD
190 CFM
(E)SD
190 CFM
(E)SD
(E)VAV-17
(E)VAV-16
150 CFM
(E)SD
FC-A1
(E)VAV-6
(E)VAV-5
H
H
H
H
H
H
2 HR FIRE RATED WALL
3 HR FIRE RATED WALL
TYP.
TYP.
BUILDING 46
14ø
FC-A
BUILDING 47
TYP.
4ø OA
H
H H
6ø
8ø
GENERAL NOTES
A. EXISTING WORK TO REMAIN AS INDICATED WITH LIGHT LINE WEIGHT.
B. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.
C. COORDINATE ALL SYSTEM OUTAGES WITH OWNER.
D. PROVIDE AT LEAST 14 WORKING DAYS ADVANCE NOTICE TO THE COR
(CONTRACT OFFICER REPRESENTATIVE) FOR ANY UTILITY SHUT DOWNS.
E. LOCATE BALANCE DAMPERS SO THEY CAN BE ACCESSED THROUGH CEILING
TILE OR WITH REMOTE BALANCE DAMPER ADJUSTMENT DEVICE. PROVIDE
DURO-DYNE REMOTE, INTERNAL TYPE CABLE OPERATED BALANCE DAMPER OR
EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD CEILINGS,
TYPICAL.
F. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH
MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER
DISCIPLINES: ARCHITECTURAL, PLUMBING, ELECTRICAL, ETC., SHOWN ON
OTHER CONTRACTOR DOCUMENTS.
H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND
PIPING INSULATION IS APPLIED.
I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN
ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND
DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD
PERFORMANCE.
J. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY
THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE
APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE
BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND
SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO
NOT SCALE DRAWINGS.
K. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCES AS RECOMMENDED
BY CODE AND MANUFACTURERS.
N TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENT SUBMISSION
Services
Engineering and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
LEO A DALY
1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036
9500 BAY PINES BLVD
BAY PINES, FL 33744
RENOVATION OF
BUILDING 47 FOR AMO 47
VB3226
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \V
B A
-4
-M e c h
C
L W y s s k y le
.g u g g e n h e im .r v t
/7
/2
:3
:5
P M
06/06/201906/06/2019
MH1.02-1
HVAC 2ND FLOOR NEW WORK
PLAN - SUPPLY
GC KG
SCALE: 1/8" = 1'-0"
2ND FLOOR - NEW WORK PLAN - SUPPLY
DRAWING NOTES
1. PROVIDE NEW FAN COIL FC-A AND ALL ASSOCIATED DUCTWORK, CONDENSATE
DRAIN LINE, AIR DEVICES, AIR COOLED CONDENSING UNIT, REFRIGERANT
LINES, TEMPERATURE SENSORS, DAMPERS, ALL FOR A FULLY FUNCTIONAL
SYSTEM.
2. PROVIDE NEW VAV TERMINAL UNITS, TEMPERATURE AND HUMIDITY SENSORS
DUCTWORK, AIR DEVICES, DAMPERS, ALL FOR A FULLY FUNCTIONAL SYSTEM,
AND CONNECT TO EXISTING SYSTEM AT "CONNECT TO EXISTING" SYMBOL
LOCATIONS. MOUNT TEMPERATURE AND HUMIDITY SENSORS AT 70 INCHES
ABOVE FINISHED FLOOR WHERE REQUIRED TO AVOID CUBICLE PANELS IN
OPEN OFFICE AREAS, OTHERWISE MOUNT SENSORS AT 48 INCHES ABOVE
FINISHED FLOOR.
3. PROVIDE NEW EF-R-1 AND ASSOCIATED EXHAUST DUCT AND AIR DEVICES.
4. PROVIDE NEW TRANSFER DUCTWORK AND ASSOCIATED AIR DEVICES WITH
BALANCE DAMPERS.
5. CONTRACTOR TO BALANCE NEW AND EXISTING VAV TERMINAL UNITS,
EXHAUST FANS, AND ALL AIR DEVICES TO AIRFLOWS SHOWN AFTER RTUS AND
FAN COILS ARE PROVIDED. CONTRACTOR TO PROVIDE BALANCE DAMPERS
WHEREVER NEEDED AND OF TYPE NEEDED TO ACCOMPLISH DESIGN BALANCE.
SEE AIR BALANCE SCHEDULES AND SEQUENCES OF CONTROL.
6. EXISTING DDC ENGINEERING CONTROL CENTER IS LOCATED IN BUILDING 46.
COORDINATE WITH VA PERSONNEL ABOUT DDC SYSTEM TIE IN LOCATIONS.
Revisions: Date:
REV 1 - ADDENDUM #1 06/06/2019
T
T T
T
T
T T
T
T
T
T
T
T T
T
T
T T
T
T
TT
1 2 3 4 5
A
B
C
D
E
OPEN OFFICE
CORRIDOR
STORAGE
BREAK ROOM
OPEN OFFICE
OFFICE
OFFICE
328 OFFICE
OFFICE
CONF./ TRAINING
ROOM A
CONF. / TRAINING
ROOM B
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
317 OFFICE
OFFICE
OFFICE
OPEN OFFICE
OFFICE
OFFICE
HUDDLE
314WOMEN
HK
OFFICE
311 OFFICE
OFFICE
MEN
PUMP
ELEC
TEL
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
BRIDGE
16ø16ø
3/4" CD
REFRIGERANT LINES UP FROM FC-A
REFRIGERANT LINES TO ROOF
MOUNTED CONDENSING UNIT
DOWN COLUMN TO
GRADE LEVEL STORM
SD-4
860 CFM
SD-3
295 CFM
35 CFM
LSD-1
90 CFM
LSD-2
90 CFM
LSD-2
95 CFM
LSD-2
150 CFM
LSD-4
150 CFM
LSD-4
145 CFM
LSD-4
150 CFM
LSD-3
6ø
8ø
10ø
6ø
6ø
6ø
VAV-2VAV-9
22ø
12ø
10ø
8ø
8ø
8ø
8ø
14ø
20ø
9ø
VAV-4
VAV-3
VAV-12
VAV-5
8ø14ø
9ø
VAV-10
VAV-6
VAV-14
14ø
12ø
9ø
VAV-13
VAV-11
9ø
VAV-15
VAV-7
10ø
12ø
9ø
7ø
VAV-19
VAV-20
VAV-17
9ø
VAV-21
VAV-22
16ø
VAV-8
10ø VAV-18
VAV-16
90 CFM
LSD-2
85 CFM
LSD-2
85 CFM
LSD-2
90 CFM
LSD-2
90 CFM
LSD-2
90 CFM
LSD-2
90 CFM
LSD-2
90 CFM
LSD-2
135 CFM
LSD-3
130 CFM
LSD-3
130 CFM
LSD-3
135 CFM
LSD-3
110 CFM
LSD-7
110 CFM
LSD-7
155 CFM
LSD-4
155 CFM
LSD-4
155 CFM
LSD-4
75 CFM
LSD-7
75 CFM
LSD-7 75 CFM
LSD-7
80 CFM
LSD-7
135 CFM
LSD-3
135 CFM
LSD-3
130 CFM
LSD-3
130 CFM
LSD-3
135 CFM
LSD-3
135 CFM
LSD-3
135 CFM
LSD-3
135 CFM
LSD-3
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
35 CFM
LSD-1
95 CFM
LSD-2
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
75 CFM
LSD-7
90 CFM
LSD-2
85 CFM
LSD-2
90 CFM
LSD-2
85 CFM
LSD-2
80 CFM
LSD-2
80 CFM
LSD-2
80 CFM
LSD-2
95 CFM
LSD-2
100 CFM
LSD-2
100 CFM
LSD-2
95 CFM
LSD-2
85 CFM
LSD-2
85 CFM
LSD-2
85 CFM
LSD-2
85 CFM
LSD-2
95 CFM
LSD-2
100 CFM
LSD-2
95 CFM
LSD-2
100 CFM
LSD-2
130 CFM
LSD-3
130 CFM
LSD-3
135 CFM
LSD-3
135 CFM
LSD-3
80 CFM
LSD-2
UP TO RTU-N-2
DN
UP TO RTU-N-4
6ø
10ø
10ø
6ø 8ø
10ø
10ø
6ø
TYP.
10ø
6ø
6ø
8ø
6ø
6ø
6ø
8ø
10ø
8ø 8ø
12ø
8ø
6ø
125 CFM
SD-6
6ø
8ø6ø
125 CFM
SD-6
60 CFM
LSD-5
30 CFM
LSD-1
8ø
8ø6ø
6ø
6ø 6ø
25 CFM
LSD-6
10ø 6ø
8ø
6ø 6ø
6ø
10ø
6ø
8ø
6ø 6ø
6ø
12ø 8ø
8ø8ø
8ø
10ø
6ø
8ø 4ø
6ø 10ø
6ø 6ø 60 CFM
LSD-5
25 CFM
LSD-6
12ø
8ø
10ø
8ø
12ø
8ø8ø
10ø
8ø
12ø
8ø
10ø
8ø 8ø
10ø 6ø
4ø
6ø
6ø
4ø 35 CFM
LSD-1
6ø
60 CFM
LSD-5
30 CFM
LSD-1
30 CFM
LSD-6
60 CFM
LSD-5
9ø
8ø
6ø
60 CFM
LSD-5
4ø
6ø
35 CFM
LSD-1
60 CFM
LSD-5
6ø4ø
16ø
4ø
14ø
6ø
6ø 12ø 6ø
6ø
6ø
4ø
12ø
10ø
8ø
6ø
6ø 6ø
6ø
6ø 6ø
6ø
10ø
SD-4
290 CFM
6ø
6ø8ø
190 CFM
LST-1
6ø
8ø
35 CFM
LSD-1
VAV-2
VAV-9
VAV-10
VAV-11
VAV-20
VAV-19
VAV-16
VAV-17
VAV-15
VAV-13
VAV-14
VAV-18
VAV-8
VAV-7
VAV-6
VAV-5
VAV-4
VAV-3
VAV-22
VAV-21
FC-B1
8ø
14ø
95 CFM
LSD-295 CFM
LSD-2
FC-B2FC-B3
8ø
6ø
6ø
6ø
12ø
8ø
12ø
22ø
8ø
16ø
18ø
6ø
8ø
10ø
9ø14ø
8ø
9ø
26ø
8ø 12ø
10ø
8ø
4ø
6ø
8ø
RL/RS
H
H
6ø
H H
2 HR FIRE RATED WALL
3 HR FIRE RATED WALL
FD-2
2 HR FIRE
RATED WALL
TYP.
TYP.
TYP.
TYP.
6ø
8ø
4ø OA
4" UP TO ROOF-MOUNTED
OA INTAKE
OA DUCT
8ø
28x30
S
FC-B
14ø
SD-1 5
TYP.
TYP.
2 3
2 2
9ø
TYP.
6ø ø6
6ø
6ø
10ø
10ø1
VAV-12
GENERAL NOTES
A. EXISTING WORK TO REMAIN AS INDICATED WITH LIGHT LINE WEIGHT.
B. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.
C. COORDINATE ALL SYSTEM OUTAGES WITH OWNER.
D. PROVIDE AT LEAST 14 WORKING DAYS ADVANCE NOTICE TO THE COR
(CONTRACT OFFICER REPRESENTATIVE) FOR ANY UTILITY SHUT DOWNS.
E. LOCATE BALANCE DAMPERS SO THEY CAN BE ACCESSED THROUGH CEILING
TILE OR WITH REMOTE BALANCE DAMPER ADJUSTMENT DEVICE. PROVIDE
DURO-DYNE REMOTE, INTERNAL TYPE CABLE OPERATED BALANCE DAMPER OR
EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD CEILINGS,
TYPICAL.
F. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH
MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER
DISCIPLINES: ARCHITECTURAL, PLUMBING, ELECTRICAL, ETC., SHOWN ON
OTHER CONTRACTOR DOCUMENTS.
H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND
PIPING INSULATION IS APPLIED.
I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN
ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND
DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD
PERFORMANCE.
J. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY
THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE
APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE
BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND
SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO
NOT SCALE DRAWINGS.
K. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCES AS RECOMMENDED
BY CODE AND MANUFACTURERS.
N TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENT SUBMISSION
Services
Engineering and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
LEO A DALY
1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036
9500 BAY PINES BLVD
BAY PINES, FL 33744
RENOVATION OF
BUILDING 47 FOR AMO 47
VB3226
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \V
B A
-4
-M e c h
C
L W y s s k y le
.g u g g e n h e im .r v t
/7
/2
:3
:5
P M
06/06/201906/06/2019
MH1.03-1
HVAC 3RD FLOOR NEW WORK
PLAN - SUPPLY
GC KG
SCALE: 1/8" = 1'-0"
3RD FLOOR NEW WORK PLAN - SUPPLY
DRAWING NOTES
1. PROVIDE DURO-DYNE REMOTE INTERNAL TYPE CABLE OPERATED BALANCE
DAMPER OR EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD
CEILINGS.
2. PROVIDE NEW FAN COIL FC-B AND ALL ASSOCIATED DUCTWORK,
CONDENSATE DRAIN LINE, AIR DEVICES, AIR COOLED CONDENSING UNIT,
REFRIGERANT LINES, TEMPERATURE SENSORS, DAMPERS, ALL FOR A FULLY
FUNCTIONAL SYSTEM.
3. PROVIDE NEW VAV TERMINAL UNITS, TEMPERATURE AND HUMIDITY SENSORS
DUCTWORK, AIR DEVICES, DAMPERS, ALL FOR A FULLY FUNCTIONAL SYSTEM.
MOUNT TEMPERATURE AND HUMIDITY SENSORS AT 70 INCHES ABOVE
FINISHED FLOOR WHERE REQUIRED TO AVOID CUBICAL PANELS IN OPEN
OFFICE AREA, OTHERWISE MOUNT SENSORS AT 48" ABOVE FINISHED FLOOR.
4. CONTRACTOR TO BALANCE NEW VAV TERMINAL UNITS, AND ALL AIR DEVICES
TO AIRFLOWS SHOWN AFTER RTUS AND FAN COILS ARE PROVIDED.
CONTRACTOR TO PROVIDE BALANCE DAMPERS WHEREVER NEEDED AND OF
TYPE NEEDED TO ACCOMPLISH DESIGN BALANCE. SEE AIR BALANCE
SCHEDULES AND SEQUENCES OF CONTROL.
5. PROVIDE A NEW SMOKE DAMPER. SEE FIRE/SMOKE DAMPER AND DUCT
SMOKE DETECTOR DETAILS AND SCHEDULES.
6. MECHANICAL CONTRACTOR SHALL FURNISH SUPPLY AND RETURN FAN VFDS
TO SERVE NEW RTU-N-2 AND RTU-N-4. SEE RTU AND DDC SPECIFICATIONS.
ELECTRICAL CONTRACTOR SHALL INSTALL THE FOUR VFDS IN ARRAY ON THE
WALL NEXT TO THE DOOR OF ELECTRICAL ROOM 306. SEE ELECTRICAL
DRAWINGS.
7. MECHANICAL CONTRACTOR SHALL PROVIDE DOUBLE WALL DUCT WITH
PERFORATED INNER DUCT CASING AND COMBINATION
THERMAL/ACCOUSTICAL INSULATION PER SPECIFICATIONS. DOUBLE WALL
DUCT IS REPRESENTED WITH HATCHING. DOUBLE WALL DUCT EXPOSED TO
OPEN CEILING SHALL BE PAINTED PER ARCHITECURAL SPECIFICATIONS.
PROVIDE SILENCERS AT DUCT DROPS FROM BOTH RTUS PER DETAILS AND
SILENCER SHEDULE. DUCT NOT EXPOSED TO OPEN CEILING SHALL BE SINGLE
WALL WITH EXTERNAL INSULATION.
8. DOUBLE WALL DUCT SHOULD HAVE SOLID (NOT PERFORATED) INNER WALL.
Revisions: Date:
1 2 3 4 5
A
B
C
D
E
3/4" CD
REFRIGERANT LINES UP FROM FC-A
REFRIGERANT LINES TO ROOF
MOUNTED CONDENSING UNIT
DOWN COLUMN TO
GRADE LEVEL STORM
14x14 UP TO (E)EF-R-3 ON ROOF
(E)8x14 DOWN
14x14 UP TO (E)EF-R-2 ON ROOF
(E)8x10 DOWN
8ø
EG-2
10 CFM
EG-2
10 CFM
EG-1
150 CFM
EG-1
150 CFM
8ø
EG-3
100 CFM
EG-2
75 CFM
EG-2
75 CFM
16ø
10ø
16ø
850 CFM
RG-2
285 CFM
RG-3
DN
EG-4
225 CFM EG-2
25 CFM
75 CFM
LSR-1 75 CFM
LSR-1
75 CFM
LSR-1
80 CFM
LSR-1
180 CFM
LSR-3
180 CFM
LSR-3
180 CFM
LSR-3
175 CFM
LSR-3
180 CFM
LSR-3
175 CFM
LSR-3
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
6ø
95 CFM
LSR-2
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
75 CFM
LSR-1
10ø
8ø
6ø 6ø
12ø
14ø
8ø 8ø 8ø
8ø 8ø 8ø
26x1620ø
18ø
6ø
6ø
6ø
8ø
16ø 390 CFM
RS-1
18ø
530 CFM
RS-1
465 CFM
RS-1
240 CFM
RS-1
390 CFM
RS-1
220 CFM
RS-1
8ø
290 CFM
RS-1
295 CFM
RS-1
360 CFM
RS-1
270 CFM
RS-1
10ø
350 CFM
RS-1
16ø
12ø
420 CFM
RS-1
215 CFM
RS-1
8ø 12ø
ES-1
105 CFM
ES-1
105 CFM
245 CFM
RS-1
6ø
6ø
10ø
8ø
8ø
20ø
CONF./ TRAINING
ROOM A
CONF. / TRAINING
ROOM B
CORRIDOR
OPEN OFFICE
OPEN OFFICE
OPEN OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
WOMEN
HUDDLE
314 OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HK
PUMP
ELEC
MEN
TEL
BRIDGE
BREAK ROOM
STORAGE
12ø
10ø
6ø
34x20
8ø
8ø
6ø 6ø
16ø
6ø
18ø
UP
6ø
6ø
6ø
6ø
RL/RS
UP TO RTU-N-2
280 CFM
RG-3
EG-2
10 CFM
8ø
14ø
2 HR FIRE RATING
3 HR FIRE RATING
10ø
FD-3
14ø
FD-1
2 HR FIRE
RATED WALL
TYP.
TYP.
TYP.
10ø
10ø
12ø
10ø
10ø
8ø
10ø
10ø
10ø
10ø
BUILDING 47
BUILDING 46
6ø
6ø
4ø
6ø
UP TO EF-R-4
ON ROOF
60x24 RA (E)60x24 RA
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
14ø
FC-B
S
SD-2
2 3
2 2
TYP.
TYP.
4ø
HS
VAV-1511
HS
VAV-1211
12ø 6ø
10ø
VAV-3 11HS
6ø
6ø
GENERAL NOTES
A. EXISTING WORK TO REMAIN AS INDICATED WITH LIGHT LINE WEIGHT.
B. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.
C. COORDINATE ALL SYSTEM OUTAGES WITH OWNER.
D. PROVIDE AT LEAST 14 WORKING DAYS ADVANCE NOTICE TO THE COR
(CONTRACT OFFICER REPRESENTATIVE) FOR ANY UTILITY SHUT DOWNS.
E. LOCATE BALANCE DAMPERS SO THEY CAN BE ACCESSED THROUGH CEILING
TILE OR WITH REMOTE BALANCE DAMPER ADJUSTMENT DEVICE. PROVIDE
DURO-DYNE REMOTE, INTERNAL TYPE CABLE OPERATED BALANCE DAMPER OR
EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD CEILINGS,
TYPICAL.
F. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH
MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND
APPLICABLE CODES AND REGULATIONS.
G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER
DISCIPLINES: ARCHITECTURAL, PLUMBING, ELECTRICAL, ETC., SHOWN ON
OTHER CONTRACTOR DOCUMENTS.
H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND
PIPING INSULATION IS APPLIED.
I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN
ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND
DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD
PERFORMANCE.
J. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY
THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE
APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE
BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND
SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO
NOT SCALE DRAWINGS.
K. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCES AS RECOMMENDED
BY CODE AND MANUFACTURERS.
N TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENT SUBMISSION
Services
Engineering and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
LEO A DALY
1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036
9500 BAY PINES BLVD
BAY PINES, FL 33744
RENOVATION OF
BUILDING 47 FOR AMO 47
VB3226
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \V
B A
-4
-M e c h
C
L W y s s k y le
.g u g g e n h e im .r v t
/7
/2
:3
:5
P M
06/06/201906/06/2019
MH1.03-2
HVAC 3RD FLOOR NEW WORK
PLAN - EXHAUST/RETURN
GC KG
SCALE: 1/8" = 1'-0"
3RD FLOOR NEW WORK PLAN - RETURN/EXHAUST
DRAWING NOTES
1. PROVIDE DURO-DYNE REMOTE INTERNAL TYPE CABLE OPERATED BALANCE
DAMPER OR EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE
HARD CEILINGS.
2. PROVIDE NEW FAN COIL FC-B AND ALL ASSOCIATED DUCTWORK,
CONDENSATE DRAIN LINE, AIR DEVICES, AIR COOLED CONDENSING UNIT,
REFRIGERANT LINES, TEMPERATURE SENSORS, DAMPERS, ALL FOR A FULLY
FUNCTIONAL SYSTEM.
3. PROVIDE NEW EF-R-1 AND ASSOCIATED EXHAUST DUCT AND AIR DEVICES.
4. PROVIDE NEW EXHAUST DUCTWORK AND ASSOCIATED AIR DEVICES AND
BALANCE DAMPERS.
5. PROVIDE NEW TRANSFER DUCTWORK AND ASSOCIATED AIR DEVICES WITH
BALANCE DAMPERS.
6. CONTRACTOR TO BALANCE NEW EXHAUST FANS, AND ALL AIR DEVICES TO
AIRFLOWS SHOWN AFTER RTUS AND FAN COILS ARE PROVIDED.
CONTRACTOR TO PROVIDE BALANCE DAMPERS WHEREVER NEEDED AND OF
TYPE NEEDED TO ACCOMPLISH DESIGN BALANCE. SEE AIR BALANCE
SCHEDULES AND SEQUENCES OF CONTROL.
7. PROVIDE A NEW SMOKE DAMPER. SEE FIRE/SMOKE DAMPER AND DUCT
SMOKE DETECTOR DETAILS AND SCHEDULES.
8. PROVIDE NEW RETURN DUCTWORK AND ASSOCIATED AIR DEVICES AND
BALANCE DAMPERS.
9. MECHANICAL CONTRACTOR SHALL PROVIDE DOUBLE WALL DUCT WITH
PERFORATED INNER DUCT CASING AND COMBINATION
THERMAL/ACCOUSTICAL INSULATION PER SPECIFICATIONS. DOUBLE WALL
DUCT IS REPRESENTED WITH HATCHING. DOUBLE WALL DUCT EXPOSED TO
OPEN CEILING SHALL BE PAINTED PER ARCHITECURAL SPECIFICATIONS.
PROVIDE SILENCERS AT DUCT DROPS FROM BOTH RTUS PER DETAILS AND
SILENCER SHEDULE. DUCT NOT EXPOSED TO OPEN CEILING SHALL BE
SINGLE WALL WITH EXTERNAL INSULATION.
10. DOUBLE WALL DUCT SHOULD HAVE SOLID (NOT PERFORATED) INNER WALL.
11. PROVIDE A DUCT MOUNTED HUMIDITY SENSOR IN RETURN DUCT.
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENT SUBMISSION
Services
Engineering and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
LEO A DALY
1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036
9500 BAY PINES BLVD
BAY PINES, FL 33744
RENOVATION OF
BUILDING 47 FOR AMO 47
VB3226
C U s e rs \k y le g \D o c u m e n ts
\R e v it L o c a l F ile s \V
B A
-4
-M e c h
C
L W y s s k y le
.g u g g e n h e im .r v t
/7
/2
:3
:5
P M
06/06/201906/06/2019
MH6.01
HVAC CONTROLS
Checker Author
4.OCCUPIED MODE:
A. OCCUPIED SCHEDULE: OCCUPIED MODE STARTS BASED ON AN ADJUSTABLE SCHEDULE.
B. UPON A TRANSITION FROM PRE-OCCUPANCY OPTIMUM START MODE TO OCCUPIED MODE, THE FOLLOWING EVENTS OCCUR:
1. OPEN REMOTE EXHAUST FAN SHUTOFF DAMPERS AND FIRE/SMOKE DAMPERS.
2. OUTSIDE AIR DAMPER SHALL BE OPENED TO ITS MINIMUM OUTDOOR AIR POSITION.
3. WHEN OUTDOOR AND RELIEF AIR DAMPERS, REMOTE EXHAUST FAN SHUTOFF DAMPERS, AND FIRE/SMOKE DAMPERS ARE
FULLY OPEN, END SWITCHES SHALL ALLOW RTU SUPPLY AND REMOTE EXHAUST FANS TO START.
4. SUPPLY, RETURN, AND EXHAUST FANS RUN CONTINUOUSLY DURING OCCUPIED MODE, AND IF THEY ARE ALL RUNNING, THE
DDC SYSTEM INDEXES THE UNIT TO OCCUPIED MODE.
5. OCCUPIED SPACE SETPOINTS ARE AS FOLLOWS:
OCCUPIED HEATING SETPOINT 72°F, (ADJUSTABLE).
OCCUPIED COOLING SETPOINT 75°F, (ADJUSTABLE).
6. THE FOLLOWING RTU CONTROL LOOPS WILL OPERATE TO MAINTAIN SETPOINTS DURING OCCUPIED MODE:
A. COOLING DISCHARGE AIR TEMPERATURE CONTROL LOOP.
B. DEHUMIDIFICATION CONTROL LOOP.
C. MIXED AIR TEMPERATURE LOW LIMIT CONTROL LOOP.
D. MINIMUM OUTDOOR AIR CONTROL LOOP.
E. SUPPLY AIR DUCT STATIC CONTROL LOOP.
F. RETURN FAN AND BUILDING PRESSURIZATION CONTROL LOOP.
C) COOLING DISCHARGE AIR TEMPERATURE CONTROL LOOP:
1. MIXED AIR DAMPERS (OUTDOOR AND RETURN AIR DAMPERS) AND COOLING COIL VALVE SHALL MODULATE IN SEQUENCE
TO MAINTAIN A CONSTANT COOLING DISCHARGE AIR TEMPERATURE SETPOINT OF 50°F, (ADJUSTABLE) AT THE DISCHARGE
AIR TEMPERATURE SENSOR.
2. ECONOMIZER:
PROVIDE 100% INTEGRATED FIXED DRY-BULB ECONOMIZER WITH HIGH LIMIT SHUTOFF SETPOINT OF 65°F, (ADJUSTABLE).
PROVIDE ECONOMIZER FAULT DETECTION AND DIAGNOSTICS (FDD) SYSTEM AS DESCRIBED IN 2017 FLORIDA BUILDING CODE-ENERGY CONSERVATION, SECTION C403.2.4.7. ECONOMIZER SHALL BE AVAILABLE DURING BOTH OCCUPIED AND UNOCCUPIED COOL-DOWN MODES. EACH RTU SHALL BE PROVIDED WITH A RETURN FAN THAT PROVIDES RELIEF AT THE
RTU.
D) DEHUMIDIFICATION CONTROL LOOP:
1. UPON AN INCREASE IN RETURN AIR OR SPACE HUMIDITY ABOVE 60% RH (ADJUSTABLE) IN OCCUPIED MODE, A HIGH HUMIDITY ALARM SHALL BE GENERATED, RTU MIXING DAMPERS SHALL MODULATE TO MINIMUM OUTDOOR AIR POSITION, COOLING COIL VALVE SHALL OPEN 100%, AND TERMINAL UNIT ELECTRIC REHEAT COILS SHALL ENERGIZE, MODULATING AS
NECESSARY TO MAINTAIN SPACE TEMPERATURE SETPOINT OF 75°F, (ADJUSTABLE).
2. UPON AN INCREASE IN RETURN AIR OR SPACE HUMIDITY ABOVE 60% RH (ADJUSTABLE) IN UNOCCUPIED MODE, A HIGH
HUMIDITY ALARM SHALL BE GENERATED, MIXING DAMPERS SHALL REMAIN IN FULL RETURN MODE WITH OUTSIDE AND RELIEF AIR DAMPERS CLOSED, THE RTU FANS SHALL COME ON WITH RETURN FAN TRACKING SUPPLY BY A SPEED DIFFERENTIAL DETERMINED BY BALANCER, COOLING COIL VALVE SHALL OPEN 100%, AND TERMINAL UNIT ELECTRIC REHEAT COILS SHALL ENERGIZE, MODULATING AS NECESSARY TO MAINTAIN SPACE TEMPERATURE SETPOINT OF 78°F, (ADJUSTABLE).
3. ONCE HUMIDITY SETPOINT IS SATISFIED, THE UNIT SHALL RETURN TO ITS PRIOR MODE OF OPERATION.
E) MIXED AIR TEMPERATURE LOW LIMIT CONTROL LOOP:
1. IF THE MIXED AIR TEMPERATURE AS SENSED BY THE MIXED AIR TEMPERATURE LOW LIMIT SENSOR DROPS BELOW THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT OF 40°F (ADJUSTABLE), THE MIXED AIR DAMPERS (OUTDOOR AND RETURN AIR DAMPERS) SHALL MODULATE TO THE MINIMUM OUTDOOR AIRFLOW POSITION UNTIL THE MIXED AIR TEMPERATURE
RISES ABOVE THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT. A MIXED AIR TEMPERATURE LOW LIMIT WARNING ALARM
SHALL BE GENERATED.
2. IF THE MIXED AIR TEMPERATURE AS SENSED BY THE MIXED AIR TEMPERATURE LOW LIMIT SENSOR DROPS BELOW THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT OF 40°F (ADJUSTABLE) FOR MORE THAN 10 MINUTES (ADJUSTABLE), WITH THE MIXED AIR DAMPERS AT MINIMUM OUTDOOR AIRFLOW POSITION, THE MIXED AIR DAMPERS SHALL MODULATE TO FULL RETURN MODE (OUTDOOR AND RELIEF AIR DAMPERS CLOSED AND RETURN AIR DAMPER FULL OPEN) UNTIL THE MIXED AIR TEMPERATURE RISES ABOVE THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT MORE THAN 5 DEGREES F (ADJUSTABLE).
A MIXED AIR TEMPERATURE LOW LIMIT CRITICAL ALARM SHALL BE GENERATED.
F) MINIMUM OUTDOOR AIR CONTROL LOOP:
1. THE MIXED AIR DAMPERS (OUTDOOR AND RETURN AIR DAMPERS) AND SUPPLY AND RETURN FANS SHALL MODULATE IN
SEQUENCE TO MAINTAIN EACH RTU’S MINIMUM OUTDOOR AIR SETPOINT AS MEASURED AT THE MINIMUM OUTDOOR
AIRFLOW MEASURING STATION.
2. VENTILATION OPTIMIZATION CONTROL:
PROVIDE VENTILATION OPTIMIZATION CONTROL AS DEFINED BY APPENDIX A OF ASHRAE STANDARD 62.1 AS DESCRIBED IN
ASHRAE 90.1-2013, SECTION 6.5.3.3.
3. REMOTE EXHAUST FANS (E) EF-R-2, (E) EF-R-3, AND EF-R-4 SHALL RUN AT CONSTANT VOLUME CONTINUOUSLY DURING OCCUPIED MODE AND PROVIDE OUTDOOR AIR RELIEF ALONG WITH THE RELIEF AT EACH RTU. SEE AIR BALANCE
SCHEDULES.
G) SUPPLY AIR DUCT STATIC CONTROL LOOP:
1. SUPPLY FAN MODULATES TO MAINTAIN A RESET DUCT STATIC PRESSURE SETPOINT WHENEVER THE SUPPLY FAN RUNS.
DUCT STATIC PRESSURE SENSOR SHALL BE LOCATED AT THE RTU SUPPLY FAN.
2. SUPPLY AIR DUCT STATIC PRESSURE RESET LOGIC (TRIM & RESPOND):
STATIC PRESSURE SETPOINT SHALL BE RESET USING TRIM AND RESPOND LOGIC WITHIN THE RANGE 0.15 INWG (ADJUSTABLE) TO 2 INWG (ADJUSTABLE) AS SET BY BALANCE CONTRACTOR. WHEN FAN IS OFF, FREEZE SETPOINT AT THE MINIMUM VALUE. WHILE FAN IS PROVEN ON, EVERY 2 MINUTES (ADJUSTABLE), DECREASE SETPOINT BY 0.04 INWG (ADJUSTABLE) IF THERE ARE TWO (ADJUSTABLE) OR FEWER PRESSURE REQUESTS. [ADJUST THE “TWO” OR FEWER ZONE COOLING REQUESTS VALUE TO LIMIT DOMINANCE OF ROGUE ZONES.] IF THERE ARE MORE THAN TWO (ADJUSTABLE) PRESSURE REQUESTS, INCREASE THE SETPOINT BY 0.04 INWG (ADJUSTABLE). WHERE VAV ZONE DAMPER POSITION IS KNOWN, A PRESSURE REQUEST IS GENERATED WHEN ANY VAV DAMPER SERVED BY THE SYSTEM IS WIDE OPEN. WHERE VAV ZONE DAMPER POSITION IS UNKNOWN, A PRESSURE REQUEST IS MADE WHEN THE RATIO OF THE ZONE’S ACTUAL
SUPPLY AIRFLOW TO SUPPLY AIRFLOW SETPOINT IS LESS THAN 90% (ADJUSTABLE).
3. DDC SHALL AUTOMATICALLY DETECT ZONES THAT MAY BE EXCESSIVELY DRIVING THE RESET LOGIC AND SHALL GENERATE A ROGUE ZONE ALARM PER ASHRAE 90.1-2013, SECTION 6.5.3.2.3, A. CLEARLY IDENTIFY ON GRAPHICS WHICH ZONES ARE
ROGUE.
4. DDC SHALL ALLOW OPERATOR ABILITY TO REMOVE ZONES FROM THE RESET ALGORITHM PER ASHRAE 90.1-2013, SECTION 6.5.3.2.3, B.
H) RETURN FAN AND BUILDING PRESSURIZATION CONTROL LOOPS:
RETURN FAN CONTROL LOOP:
1. RETURN FAN OPERATES WHENEVER ASSOCIATED SUPPLY FAN IS PROVEN ON.
2. RETURN FAN SPEED IS CONTROLLED TO MAINTAIN A POSITIVE PRESSURE IN THE RETURN/RELIEF PLENUM TO ENSURE NO
BACKFLOW OF OUTDOOR AIR THROUGH THE RELIEF DAMPER. TO MINIMIZE ENERGY USE, THE PLENUM PRESSURE SETPINT SHALL BE RESET AS SHOWN IN FIGURE 1. SEE AIR BALANCE SCHEDULES FOR REQUIRED RELIEF AT EACH RTU FOR
BUILDING AIR BALANCE. BALANCER TO ADJUST SETPOINTS ACCORDINGLY.
3. HIGH PRESSURE PICKUP PROBE(S) ARE LOCATED PER MANUFACTURER’S INSTALLATION INSTRUCTIONS INSIDE THE
RETURN/RELIEF PLENUM.
4. LOW PRESSURE PICKUP PROBE(S) ARE LOCATED PER MANUFACTURER’S INSTALLATION INSTRUCTIONS OUTSIDE THE BUILDING. PICKUP(S) SHALL BE DESIGNED TO STABILIZE READINGS BY DAMPENING PRESSURE FLUCTUATIONS CAUSED BY WIND GUSTS. THESE PICKUPS, AVAILABLE FROM SEVERAL MANUFACTURERS, SHALL BE FITTED WITH A PNEUMATIC SIGNAL
DAMPENER TO FURTHER REDUCE SPIKES.
5. THE LOOP OUTPUT IS MAPPED TO FIRST OPEN THE RELIEF DAMPERS THEN TO RAISE THE RETURN/RELIEF PLENUM
PRESSURE SETPOINT FROM MIN TO MAX SETPOINT.
SEQUENCES OF OPERATION
A. GENERAL:
1. HVAC SYSTEMS SHALL BE CONTROLLED WITH DIRECT DIGITAL CONTROL (DDC) ACCORDING TO SEQUENCES SHOWN.
2. ADDITIONAL POINTS OR SOFTWARE PROGRAMMING NOT LISTED BUT WHICH ARE REQUIRED TO MEET THE FOLLOWING
SEQUENCES OF OPERATION SHALL BE PROVIDED FOR A COMPLETELY FUNCTIONAL SYSTEM THAT MEETS CODE.
3. HOUSE CONTROLLERS, RELAYS, TRANSDUCERS, AND OTHER COMPONENTS REQUIRED FOR STAND-ALONE CONTROL SHALL BE
PROVIDED INSIDE A NEMA 1 (INDOOR) OR NEMA 3R (OUTDOOR) ENCLOSURE WITH LOCKABLE DOOR.
4. ACTUATORS ON MOTORIZED VALVES AND DAMPERS ON ROOFTOP UNITS (RTUS), AND EXHAUST FAN SYSTEMS TO BE DDC. SEE
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
5. ALL FIRE/SMOKE DAMPERS SHALL BE MONITORED BY BAS FOR TROUBLE CONDITIONS.
6. ALL SYSTEM FIRE/SMOKE DAMPERS SHALL BE HARD-WIRE INTERLOCKED SUCH THAT THEY CLOSE FULLY WHEN RTU FANS STOP.
7. EACH OF THE TWO RTU SUPPLY FANS AND TWO RTU RETURN FANS (SERVING RTU-N-2 AND RTU-N-4) AND ALL THREE REMOTE EXHAUST FANS [(E) EF-R-2, (E) EF-R-3; EF-R-4] SHALL EACH HAVE A CURRENT SENSOR FOR STATUS. IF ANY OF THE RTU SUPPLY AND RETURN FAN STATUS POINTS OR ANY OF THE THREE REMOTE EXHAUST FANS INDICATE OFF, A HARDWIRED INTERLOCK CAUSES THE OTHER FANS TO GO OFF, OUTSIDE AND RELIEF AIR DAMPERS TO CLOSE, RETURN AIR DAMPER TO OPEN, FIRE/SMOKE DAMPERS TO CLOSE, AND EACH EXHAUST FAN SHUTOFF DAMPER TO CLOSE.
8. CONTROL SUBMITTALS INCLUDING DRAWINGS, SCHEDULES, SEQUENCES OF OPERATION, ETC., FOR ALL DDC CONTROLLED EQUIPMENT SHALL BE STORED AND ACCESSIBLE ON THE GRAPHICS SO THEY ARE ALWAYS AVAILABLE AND NOT LOST.
B. SETPOINTS:
1. ALL SETPOINTS GIVEN IN THE SEQUENCE OF OPERATIONS OR IN THE DRAWINGS ARE FOR SYSTEM STARTUP AND ARE
PRELIMINARY AND SHALL BE ADJUSTABLE.
2. ALL SETPOINTS SHALL BE ACCESSIBLE TO THE OWNER SO SYSTEM CAN BE TESTED. SETPOINTS AND SCREENS SHOULD HAVE UNIQUE PASSWORD PROTECTION CAPABILITY SHOULD THE OWNER DECIDE TO LIMIT ACCESSIBILITY. COORDINATE
ACCESSIBILITY AND GRAPHICS SETUP WITH OWNER BEFORE FINAL IMPLEMENTATION.
3. OPTIMUM OPERATING SETPOINTS MUST BE DETERMINED DURING ACTUAL OCCUPANCY AND WILL BE AFFECTED BY MANY
FACTORS. THESE MAY INCLUDE:
A. WEATHER CONDITIONS.
B. BUILDING OCCUPANCY.
C. BUILDING UTILIZATION PATTERNS.
D. VARIATIONS IN BUILDING CONSTRUCTION.
E. VARIATIONS IN OPERATING CHARACTERISTICS OF ACTUAL INSTALLED BUILDING EQUIPMENT.
IT IS THE RESPONSIBILITY OF THE BUILDING OPERATORS TO DETERMINE THOSE SETTINGS AND OPERATING METHODS WHICH PROVIDE THE BEST BALANCE OF OPERATING EFFICIENCY AND OCCUPANT COMFORT. THIS IS AN ONGOING PROCESS. OPTIMUM
SETTINGS CHANGE AS OPERATING CONDITIONS CHANGE.
C. RTU-N-2 AND RTU-N-4 AND REMOTE EXHAUST FANS (E) EF-R-2, (E) EF-R-3, AND EF-R-4
1. GENERAL:
A. RTU SUPPLY, RETURN, AND REMOTE EXHAUST FANS SHALL EACH BE INTERLOCKED THROUGH A DAMPER END SWITCH, SO
EACH CANNOT START UNTIL ITS RESPECTIVE OUTSIDE, RELIEF, EXHAUST SHUTOFF AND COMBINATION FIRE/SMOKE DAMPERS ARE FULLY OPEN. IF AN END SWITCH IS NOT SATISFIED WITHIN 10 MINUTES, (ADJUSTABLE), GENERATE A UNIQUE
END SWITCH ALARM IDENTIFYING WHICH END SWITCH WAS NOT SATISFIED.
B. THE RTU’S OCCUPIED, UNOCCUPIED, PRE-OCCUPANCY TIME PERIOD IS DETERMINED BY A TIME SCHEDULE AND
PROGRAMMING.
2.UNOCCUPIED MODE:
A. DURING UNOCCUPIED MODE, THE RTU IS OFF UNLESS THERE IS A CALL FOR HEATING OR COOLING OR DEHUMIDIFICATION TO
MAINTAIN UNOCCUPIED SPACE SETPOINTS OR FOR UNOCCUPIED MORNING WARM-UP OR COOL-DOWN CYCLE. WHEN THE RTU IS OFF, SUPPLY FAN, RETURN FAN, AND REMOTE EXHAUST FANS ARE OFF, AND ALL DAMPERS AND VALVES GO TO
NORMAL POSITIONS AS SHOWN ON THE RTU AND REMOTE EXHAUST FAN CONTROL SCHEMATICS.
B. UNOCCUPIED SPACE SETPOINTS ARE AS FOLLOWS:
UNOCCUPIED HEATING SETPOINT 62°F, (ADJUSTABLE).
UNOCCUPIED COOLING SETPOINT 80°F, (ADJUSTABLE).
WHENEVER RTU IS STARTED TO MAINTAIN UNOCCUPIED SPACE SETPOINTS, IT BEHAVES AS IF IN OCCUPIED MODE EXCEPT IN FULL RETURN MODE WITH RETURN FAN TRACKING SUPPLY AT A REDUCED SPEED DIFFERENTIAL DETERMINED BY BALANCER, OUTDOOR AND RELIEF AIR DAMPERS ARE CLOSED, AND REMOTE EXHAUST FANS REMAIN OFF. IF ECONOMIZER CAN BE USED, RTU IS CONTROLLED AS IT WOULD BE IN OCCUPIED MODE UNTIL SETPOINT IS SATISFIED. WHEN
UNOCCUPIED SPACE SETPOINTS ARE SATISFIED, THE RTU WILL STOP.
C) UNOCCUPIED HEATING SETBACK MODE IS MAINTAINED AS FOLLOWS: IF ANY SPACE SENSOR READS BELOW THE UNOCCUPIED HEATING SETPOINT, THE RTU WILL BE STARTED AND RUN UNTIL ALL UNOCCUPIED HEATING SPACE SETPOINTS ARE SATISFIED. THE RTU MIXING DAMPERS WILL MODULATE TO FULL RETURN MODE TO MAINTAIN THE HIGHEST SUPPLY AIR TEMPERATURE SETPOINT POSSIBLE. TERMINAL UNITS IN UNSATISFIED SPACES WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL
SETPOINT IS SATISFIED.
D) UNOCCUPIED COOLING SETUP MODE IS MAINTAINED AS FOLLOWS: IF ANY SPACE SENSOR READS ABOVE THE UNOCCUPIED COOLING SETPOINT, THE RTU WILL BE STARTED AND RUN UNTIL ALL UNOCCUPIED COOLING SPACE SETPOINTS ARE SATISFIED. THE RTU COOLING COIL VALVE WILL MODULATE OPEN TO MAINTAIN THE RTU SUPPLY AIR TEMPERATURE SETPOINT. TERMINAL UNITS IN UNSATISFIED SPACES WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL SETPOINT IS SATISFIED.
IF ECONOMIZER CAN BE USED, RTU IS CONTROLLED AS IT WOULD BE IN OCCUPIED MODE UNTIL SETPOINT IS SATISFIED.
3. PRE-OCCUPANCY OPTIMUM START MODE:
A. PRE-OCCUPANCY OPTIMUM START MODE IS INITIALLY SCHEDULED, AND THE SCHEDULED START TIME IS OPTIMIZED BASED
ON INSIDE AND OUTSIDE AIR TEMPERATURE AND SYSTEM HISTORY OF PERFORMANCE. THE DDC CONTROLLER CALCULATES THE OPTIMUM PRE-OCCUPANCY MODE HEATING/COOLING TIME NECESSARY TO BRING BUILDING TO OCCUPIED
TEMPERATURE IN EITHER WARM-UP OR COOL-DOWN CYCLES.
B. UPON INITIATION OF A START IN PRE-OCCUPANCY OPTIMUM START MODE (WARM-UP OR COOL-DOWN CYCLE), THE
FOLLOWING EVENTS OCCUR:
1. OPEN RETURN AIR DAMPER UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN CYCLE.
2. OPEN FIRE/SMOKE DAMPERS.
3. OUTSIDE AND RELIEF AIR DAMPERS SHALL REMAIN CLOSED UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED
FOR COOL-DOWN CYCLE.
4. REMOTE EXHAUST FANS SHALL REMAIN OFF UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN
CYCLE.
5. WHEN RTU RETURN AND FIRE/SMOKE DAMPERS ARE FULLY OPEN, END SWITCHES SHALL ALLOW RTU SUPPLY AND
RETURN FANS TO START WITH RETURN FAN TRACKING SUPPLY FAN AT REDUCED SPEED DIFFERENTIAL DETERMINED BY BALANCER UNLESS ECONOMIZER CAN BE USED. IF ECONOMIZER CAN BE USED, RETURN FAN IS CONTROLLED AS IT WOULD
BE IN OCCUPIED MODE.
C) PRE-OCCUPANCY WARM-UP CYCLE: DURING PRE-OCCUPANCY MODE, THE DDC SYSTEM OPERATES THE UNIT IN ITS WARM- UP CYCLE IF THE AVERAGE SPACE TEMPERATURE OF THE VAV BOX ZONES SERVED BY THE RTU IS BELOW 72°F
(ADJUSTABLE). THE FOLLOWING EVENTS OCCUR DURING PRE-OCCUPANCY WARM-UP CYCLE:
1. OUTSIDE AND RELIEF AIR DAMPERS ARE CLOSED.
2. RETURN AIR DAMPER AND FIRE/SMOKE DAMPERS ARE OPEN.
3. REMOTE EXHAUST FANS ARE OFF.
4. RTU COOLING COIL VALVE IS CLOSED TO COIL.
5. THE RTU MIXING DAMPERS WILL MODULATE TO FULL RETURN MODE TO MAINTAIN THE SUPPLY AIR TEMPERATURE
SETPOINT. SUPPLY FAN WILL MODULATE TO MAINTAIN SUPPLY DUCT STATIC PRESSURE AT SETPOINT. RETURN FAN WILL
TRACK SUPPLY FAN BY A REDUCED SPEED DIFFERENTIAL DETERMINED BY BALANCER.
6. TERMINAL UNITS WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL EACH OCCUPIED SPACE SETPOINT IS SATISFIED.
7. WARM-UP MODE IS TERMINATED WHEN THE RTU IS INDEXED TO ITS OCCUPIED MODE TIME PERIOD, OR WHEN ALL SPACES
REACH THEIR OCCUPIED HEATING SPACE TEMPERATURE SETPOINTS BEFORE OCCUPIED MODE TIME PERIOD BEGINS. SEE
OCCUPIED MODE SEQUENCE FOR OCCUPIED SPACE TEMPERATURE SETPOINTS.
D) PRE-OCCUPANCY COOL-DOWN CYCLE: DURING PRE-OCCUPANCY MODE, THE DDC SYSTEM OPERATES THE UNIT IN ITS COOL- DOWN CYCLE IF THE AVERAGE SPACE TEMPERATURE OF THE VAV BOX ZONES SERVED BY THE UNIT IS ABOVE 75°F
(ADJUSTABLE). THE FOLLOWING EVENTS OCCUR DURING PRE-OCCUPANCY COOL-DOWN CYCLE:
1. OUTSIDE AND RELIEF AIR DAMPERS ARE CLOSED UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-
DOWN CYCLE.
2. RETURN AIR DAMPER IS OPEN UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN CYCLE.
3. FIRE/SMOKE DAMPERS ARE OPEN.
4. REMOTE EXHAUST FANS ARE OFF UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN CYCLE.
5. THE RTU MIXING DAMPERS WILL MODULATE TO FULL RETURN MODE, UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE
USED FOR COOL-DOWN CYCLE, AND THE RTU COOLING COIL VALVE WILL MODULATE OPEN TO MAINTAIN THE RTU SUPPLY
AIR TEMPERATURE SETPOINT.
6. SUPPLY FAN WILL MODULATE TO MAINTAIN RESET SUPPLY DUCT STATIC PRESSURE AT SETPOINT AS IT WOULD IN OCCUPIED MODE. SEE SUPPLY DUCT STATIC PRESSURE RESET SCHEDULE IN OCCUPIED MODE SEQUENCES.
7. RETURN FAN WILL TRACK SUPPLY FAN AT A REDUCED SPEED DETERMINED BY BALANCER UNLESS ECONOMIZER CAN BE USED. IF ECONOMIZER CAN BE USED, RETURN FAN IS CONTROLLED AS IT WOULD BE IN OCCUPIED MODE.
8. TERMINAL UNITS WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL EACH OCCUPIED SPACE SETPOINT IS SATISFIED.
9. COOL-DOWN MODE IS TERMINATED WHEN THE UNIT IS INDEXED TO ITS OCCUPIED MODE TIME PERIOD, OR WHEN ALL
SPACES REACH THEIR OCCUPIED COOLING SPACE TEMPERATURE SETPOINTS BEFORE OCCUPIED MODE TIME PERIOD
BEGINS. SEE OCCUPIED MODE SEQUENCE FOR OCCUPIED SPACE TEMPERATURE SETPOINTS.
6. RETURN FAN SPEED SHALL BE CONTROLLED TO MAINTAIN RETURN FAN DISCHARGE STATIC PRESSURE AT SETPOINT. THE SETPOINT SHALL BE RESET LINEARLY FROM RFSPMIN (RETURN FAN STATIC PRESSURE MINIMUM) TO RFSPMAX. SETPOINTS
ARE DETERMINED IN CONJUCTION WITH THE AIR BALANCER AS FOLLOWS:
A. RFSPMIN: STATIC PRESSURE SETPOINT REQUIRED TO DELIVER THE DESIGN RETURN AIR VOLUME ACROSS THE RETURN AIR DAMPER WHEN THE SUPPLY AIR FAN IS AT DESIGN AIRFLOW AND ON MINIMUM OUTDOOR AIR. THIS SETPOINT SHALL
BE NO LESS THAN 0.01 INCHES (ADJUSTABLE) TO MAINTAIN POSITIVE DISCHARGE FLOW.
B. RFSPMAX: STATIC PRESSURE SETPOINT REQUIRED TO EXHAUST ENOUGH AIR TO MAINTAIN BUILDING STATIC PRESSURE AT SETPOINT OF 0.05 INCHES (ADJUSTABLE) WHEN THE SUPPLY AIR FAN IS AT DESIGN AIRFLOW AND ON 100% OUTDOOR
AIR.
BUILDING PRESSURIZATION CONTROL LOOP:
7. EXHAUST DAMPERS SHALL ONLY BE ENABLED WHEN THE ASSOCIATED SUPPLY AND RETURN FANS ARE PROVEN ON AND THE MINIMUM OUTDOOR AIR DAMPER IS OPEN. THE EXHAUST DAMPERS SHALL BE CLOSED WHEN RTU IS DISABLED.
8. EXHAUST DAMPERS ARE CONTROLLED TO MAINTAIN BUILDING PRESSURE DIRECTLY USING A DIFFERENTIAL PRESSURE SENSOR WITH PRESSURE SENSOR PICKUP PROBE(S) LOCATED IN A REPRESENTATIVE SPACE INSIDE THE BUILDING AND PRESSURE SENSOR PICKUP PROBE(S) LOCATED OUTDOORS. SEE AIR BALANCE SCHEDULES FOR RELIEF REQUIRED FOR
BUILDING AIR BALANCE.
9. BUILDING STATIC PRESSURE SHALL BE TIME AVERAGED WITH A SLIDING 5-MINUTE (ADJUSTABLE) WINDOW TO DAMPEN
FLUCTUATIONS. THE AVERAGED VALUE SHALL BE THAT DISPLAYED AND USED FOR CONTROL.
10. DUE TO THE POTENTIAL FOR INTERACTION BETWEEN THE BUILDING PRESSURIZATION AND RETURN FAN CONTROL LOOPS, EXTRA CARE MUST BE TAKEN IN SELECTING CONTROL LOOP GAINS. TO PREVENT EXCESSIVE CONTROL LOOP INTERACTION,THE CLOSED LOOP RESPONSE TIME OF THE BUILDING PRESSURIZATION LOOP SHOULD NOT EXCEED 1/5 OF THE CLOSED LOOP RESPONSE TIME OF THE RETURN FAN CONTROL LOOP. THIS CAN BE ACCOMPLISHED BY DECREASING THE GAIN OF THE BUILDING PRESSURIZATION CONTROLLER. IN OTHER WORDS, THE BUILDING PRESSURE CONTROL LOOP MUST BE VERY SLOW RELATIVE TO THE RETURN FAN CONTROL LOOP, AND THE BUILDING PRESSURE CONTROL POINT SHOULD NOT BE THE REALTIME DIFFERENTIAL PRESSURE READING BUT INSTEAD A MOVING AVERAGE OF THE DIFFERENTIAL PRESSURE READING TO PREVENT SPIKES FROM CAUSING RELIEF DAMPER COTNROL INSTABILITY.
11. WHEN EXHAUST DAMPERS ARE ENABLED, A CONTROL LOOP SHALL MODULATE EXHAUST DAMPERS TO MAINTAIN THE BUILDING PRESSURE AT A SETPOINT OF 0.05 INCHES (ADJUSTABLE). THE RANGE OF THE SENSOR MAY BE AS LOW AS +0.1 INCHES (ADJUSTABLE) BUT SPIKES DUE TO WIND AND OTHER FACTORS MAY CAUSE A HIGHER RANGE OF PRESSURES TO
OCCUR SO A +0.25 INCH RANGE (ADJUSTABLE) IS RECOMMENDED.
12. LOCATE INDOOR PLATE HIGH PRESSURE PORT PICKUP(S) PER MANUFACTURER’S INSTALLATION INSTRUCTIONS INSIDE AN INTERIOR SPACE(S) PHYSICALLY SEPARATED BY WALLS FROM EXTERIOR DOORS AND ELEVATOR LOBBIES IN EITHER A PERMANENT CEILING OR WALL THAT WILL NOT LIKELY BE REMOVED WHEN TENANT IMPROVEMENT UPGRADES ARE MADE IN
THE FUTURE.
13. LOCATE AMBIENT (OUTDOOR) PLATE LOW PRESSURE PORT PICKUP(S) PER MANUFACTURER’S INSTALLATION INSTRUCTIONS OUTDOORS. PICKUP(S) SHALL BE DESIGNED TO STABILIZE READINGS BY DAMPENING PRESSURE FLUCTUATIONS CAUSED BY WIND GUSTS. THESE PICKUPS, AVAILABLE FROM SEVERAL MANUFACTURERS, SHALL BE FITTED
WITH A PNEUMATIC SIGNAL DAMPENER TO FURTHER REDUCE SPIKES.
14. GENERATE A HIGH BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS +0.25 INCHES
(ADJUSTABLE).
15. GENERATE A LOW BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.0 INCHES
(ADJUSTABLE).
I) RTU SHUTDOWN MODE: UPON RTU SUPPLY FAN, RETURN FAN, AND REMOTE EXHAUST FAN SHUTDOWN, ALL REMOTE EXHAUST FAN SHUTOFF DAMPERS, AND FIRE/SMOKE DAMPERS SHALL CLOSE FULLY. OUTSIDE AND RELIEF AIR DAMPERS SHALL CLOSE FULLY, AND RETURN AIR DAMPERS SHALL OPEN FULLY. RTU CONTROL SYSTEM SHALL BE SET UP AND ADJUSTED SUCH THAT CLOSING OF FIRE/SMOKE DAMPERS WILL BE DELAYED UNTIL FAN ROLLS TO NEAR STOP.
1. SAFETIES:
2. ALL SAFETY/EMERGENCY CONTROLS SHALL BE HARD-WIRE INTERLOCKED SUCH THAT THEY ARE NOT DEPENDENT UPON
DDC SYSTEM SOFTWARE.
3. END SWITCHES ARE PROVIDED AS SAFETIES. ANY OF THESE DEVICES WILL KEEP THE DRIVE OFF IN THE EVENT OF A
PROBLEM.
4. SMOKE CONTROL:
A. DUCT MOUNTED AIR SMOKE DETECTORS WILL BE FURNISHED AND INSTALLED AS SHOWN. PROVIDE POWER AND ALARM, CONTROL AND INTERLOCK WIRING.
B. WHENEVER ANY DUCT-MOUNTED SMOKE DETECTOR GOES INTO ALARM, IT SHALL PERFORM THE FOLLOWING:
1. STOP ALL UNIT FANS.
2. CLOSE ALL ASSOCIATED FIRE/SMOKE DAMPERS.
3. NOTIFY THE FIRE ALARM SYSTEM.
4. THIS CONTROL MUST BE MANUALLY RESET.
5. FIRE/SMOKE ALARMS AFFECT ONLY AIR SYSTEMS SERVING THE ZONE IN ALARM. AIR SYSTEMS SERVING THE OTHER
ZONES CONTINUE TO OPERATE NORMALLY.
5. FREEZE PROTECTION:
A. IF THE AIR TEMPERATURE SENSED BY THE LOW LIMIT THERMOSTAT (FREEZESTAT) FALLS BELOW 40°F (ADJUSTABLE), A
FREEZESTAT WARNING ALARM SHALL INDICATE AT THE OPERATOR CONTROL PANEL.
B. IF THIS TEMPERATURE FALLS BELOW 38°F (ADJUSTABLE), THE SUPPLY FAN, RETURN FAN, AND REMOTE EXHAUST FANS SHALL SHUT DOWN, THE COOLING VALVE SHALL BE SET AT 20% OPEN (ADJUSTABLE); THE CHILLED WATER PUMP SHALL PROVIDE CONTINUOUS FLOW THROUGH CHILLED WATER COILS ALL UNTIL ALARM IS CLEARED, AND A CRITICAL ALARM
SHALL BE GENERATED.
6. HIGH STATIC PRESSURE AT RTU SUPPLY FAN
A. IF THE STATIC PRESSURE HIGH LIMIT SWITCH DOWNSTREAM OF THE RTU SUPPLY FAN SENSES A STATIC PRESSURE
CONDITION ABOVE ITS SETPOINT OF +3 INWG (ADJUSTABLE), REMOTE EXHAUST FANS AND THE RTU SUPPLY AND RETURN FANS SHALL BE DISABLED, AND CONTROLS SHALL GO TO THEIR NORMAL POSITIONS UNTIL SAFETY THAT TRIPPED IS RESET MANUALLY. A HIGH SUPPLY FAN STATIC PRESSURE LIMIT SWITCH ALARM WILL BE GENERATED.
B. IF THE STATIC PRESSURE LOW LIMIT SWITCH UPSTREAM OF THE RTU RETURN FAN SENSES A STATIC PRESSURE CONDITION BELOW ITS SETPOINT OF -3 INWG (ADJUSTABLE), REMOTE EXHAUST FANS AND THE RTU SUPPLY AND RETURN FANS SHALL BE DISABLED, AND CONTROLS SHALL GO TO THEIR NORMAL POSITIONS UNTIL SAFETY THAT TRIPPED IS RESET MANUALLY. A LOW RETURN FAN STATIC PRESSURE LIMIT SWITCH ALARM WILL BE GENERATED.
7. ALARMS: THE DDC GENERATES AN ALARM WHENEVER ANY OF THE FOLLOWING OCCURS:
A. THE SUPPLY FAN IS COMMANDED ON AND FAILS TO RUN.
B. THE RETURN FAN IS COMMANDED ON AND FAILS TO RUN.
C. THE SUPPLY FAN IS COMMANDED OFF BUT RUNS.
D. THE RETURN FAN IS COMMANDED OFF BUT RUNS.
E. THE SUPPLY FAN SPEED DRIVE FAULT CONTACT IS ON.
F. THE RETURN FAN SPEED DRIVE FAULT CONTACT IS ON.
G. ANY EXHAUST FAN IS COMMANDED ON AND FAILS TO RUN.
H. ANY EXHAUST FAN IS COMMANDED OFF BUT RUNS.
I. IF ANY END SWITCH IS NOT SATISFIED WITHIN 10 MINUTES, (ADJUSTABLE), GENERATE A UNIQUE END SWITCH ALARM
IDENTIFYING WHICH END SWITCH WAS NOT SATISFIED.
J. THE LOW TEMPERATURE CUTOUT (FREEZESTAT) IS ACTIVATED. GENERATE A FREEZESTAT WARNING ALARM IF TEMPERATURE BELOW 40°F, (ADJUSTABLE), IS DETECTED. GENERATE A CRITICAL FREEZESTAT ALARM IF TEMPERATURE
BELOW 38°F (ADJUSTABLE), IS DETECTED.
K. STATIC PRESSURE HIGH LIMIT PRESSURE SWITCH IS ACTIVATED WHEN PRESSURE EXCEEDS +3 INWG, (ADJUSTABLE).
PROVIDE UNIQUE ALARM FOR EACH PRESSURE SWITCH WITH UNIQUE TAGS.
L. STATIC PRESSURE LOW LIMIT PRESSURE SWITCH IS ACTIVEATED WHEN PRESSURE EXCEEDS -3 INWG, (ADJUSTABLE).
PROVIDE UNIQUE ALARM FOR EACH PRESSURE SWITCH WITH UNIQUE TAGS.
M. THE SUPPLY AIR STATIC PRESSURE SENSOR FAILS (PRESSURE MORE THAN 10% ABOVE FINAL HIGH SETPOINT, ADJUSTABLE).
N. THE RETURN AIR STATIC PRESSURE SENSOR FAILS (PRESSURE MORE THAN 10% ABOVE FINAL HIGH SETPOINT, ADJUSTABLE).
O. THE BUILDING PRESSURE DIFFERENTIAL PRESSURE SWITCH SENSOR FAILS (PRESSURE MORE THAN 20% ABOVE FINAL
HIGH SETPOINT, ADJUSTABLE).
P. UPON AN INCREASE IN RETURN AIR OR SPACE HUMIDITY ABOVE 60% RH (ADJUSTABLE) IN UNOCCUPIED MODE, A HIGH
HUMIDITY ALARM SHALL BE GENERATED.
Q. MIXED AIR TEMPERATURE LOW LIMIT SENSOR FAILS (LESS THAN 0°F, ADJUSTABLE OR MORE THAN 120°F, ADJUSTABLE).
R. MIXED AIR TEMPERATURE LOW LIMIT SENSOR FALLS BELOW 40°F, (ADJUSTABLE). GENERATE A MIXED AIR TEMPERATURE
LOW LIMIT WARNING ALARM.
S. MIXED AIR TEMPERATURE LOW LIMIT SENSOR FALLS BELOW 40°F, (ADJUSTABLE) FOR MORE THAN 10 MINUTES, (ADJUSTABLE). GENERATE A MIXED AIR TEMPERATURE LOW LIMIT CRITICAL ALARM.
T. DISCHARGE AIR TEMPERATURE SENSOR FAILS (LESS THAN 20°F, ADJUSTABLE OR MORE THAN 120°F, ADJUSTABLE).
U. RETURN AIR TEMPERATURE SENSOR FAILS (LESS THAN 20°F, ADJUSTABLE OR MORE THAN 120°F, ADJUSTABLE).
V. RETURN AIR HUMIDITY SENSOR FAILS (LESS THAN 10%RH, ADJUSTABLE OR MORE THAN 100%RH, ADJUSTABLE).
W.OUTDOOR AIR TEMPERATURE SENSOR FAILS (LESS THAN -30°F, ADJUSTABLE OR MORE THAN 130°F, ADJUSTABLE).
X. THE OUTSIDE AIRFLOW RATE IS LESS THAN 75% (ADJUSTABLE) OF MINIMUM OUTSIDE AIRFLOW SETPOINT, FOR A TIME
PERIOD GREATER THAN 15 MINUTES (ADJUSTABLE), WHEN OUTSIDE/RETURN AIR DAMPER OPERATION HAS BEEN ENABLED.
Y. GENERATE ROGUE ZONE ALARMS PER ASHRAE 90.1-2013, SECTION 6.5.3.2.3, A., AND CLEARLY IDENTIFY ON GRAPHICS
WHICH ZONES ARE ROGUE.
Z. GENERATE DUCT SMOKE DETECTOR ALARMS CLEARLY IDENTIFYING WHICH DUCT SMOKE DETECTOR IS IN ALARM ON THE
GRAPHICS.
AA. GENERATE A DIRTY FILTER ALARM WHEN THE FILTER DIFFERENTIAL PRESSURE SWITCH INDICATES A PRESSURE
DIFFERENTIAL VALUE OF 0.5 IN.WG. (ADJUSTABLE). OWNER CAN DETERMINE AND UPDATE ACTUAL ALARM SETPOINT VALUE THE FIRST TIME DIRTY FILTERS ARE CHANGED.FIGURE 1: RELIEF DAMPER CONTROL AND RETURN FAN SETPOINT RESET
BB. GENERATE A HIGH BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS +0.25 INCHES
(ADJUSTABLE).
CC. GENERATE A LOW BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.0 INCHES
(ADJUSTABLE).
D. NEW VARIABLE AIR VOLUME TERMINAL UNITS WITH SCR ELECTRIC REHEAT
1. DIRECT DIGITAL AIRFLOW CONTROLLER, DIFFERENTIAL PRESSURE SENSOR, AND ELECTRONIC DAMPER ACTUATOR SHALL BE FURNISHED UNDER THIS SECTION BUT SHALL BE FACTORY MOUNTED BY THE TERMINAL UNIT MANUFACTURER. AIRFLOW MEASURING STATION AND ELECTRIC REHEAT COILS SHALL BE FACTORY MOUNTED BY THE VAV BOX MANUFACTURER.
2. SPACE COOLING AND HEATING SETPOINTS SHALL HAVE SEPARATE OCCUPIED AND UNOCCUPIED SETTINGS, AND CONTROLLER SHALL AUTOMATICALLY SHIFT BETWEEN OCCUPIED AND UNOCCUPIED SETTINGS WHEN ASSOCIATED RTU SETTING IS SHIFTED.
SEE UNOCCUPIED AND OCCUPIED SPACE SETPOINTS SECTIONS OF RTU SEQUENCES.
3. SETPOINT SHALL BE ADJUSTABLE BY OCCUPANT AT SPACE TEMPERATURE SENSOR BY PLUS OR MINUS 2-DEGREES FAHRENHEIT (ADJUSTABLE) AND AT OPERATOR WORKSTATION. ALL SETPOINTS MAY BE OVERRIDDEN AT THE OPERATOR’S WORKSTATION.
4. SPACE TEMPERATURE SENSOR SHALL HAVE A MANUAL OVERRIDE BUTTON THAT ALLOWS TEMPORARY OCCUPIED OPERATION OF THE RTU SYSTEM SERVED FOR UP TO TWO HOURS, (TIME PERIOD VALUE ADJUSTABLE AT OPERATOR’S WORKSTATION).
5. CONTROLLER SHALL BE PRESSURE INDEPENDENT AND MAINTAIN SUPPLY AIR VOLUME SETTING REGARDLESS OF SYSTEM STATIC PRESSURE BY DIRECTLY MEASURING AIR FLOW AND CONTROLLING TERMINAL UNIT DAMPER.
A. MAXIMUM AIR VOLUME SHALL BE PRESET TO EQUAL THE SUM OF ALL ATTACHED DIFFUSERS AND REGISTERS WHICH SHOULD
MATCH THE SCHEDULED MAXIMUM AIR VOLUME FOR EACH TERMINAL UNIT.
B. MINIMUM AIR VOLUME SHALL BE PRESET TO THE VOLUME LISTED IN SCHEDULE.
6. TEMPERATURE CONTROL:
A. CONTROLLER SHALL MODULATE AIR VOLUME BETWEEN MINIMUM AND MAXIMUM SETTINGS TO MAINTAIN SPACE
TEMPERATURE SETPOINT. TERMINAL UNIT SCHEDULE SHOWS SEPARATE COOLING MINIMUM, HEATING MINIMUM, AND COOLING MAXIMUM AIRFLOW SETPOINTS. SOME TERMINAL UNITS HAVE THE SAME COOLING AND HEATING MINIMUM AIRFLOW SETPOINT WHILE OTHERS HAVE SEPARATE COOLING AND HEATING MINIMUM AIRFLOW SETPOINTS. SEE TERMINAL
UNIT SCHEDULES.
B. ON A CALL FOR COOLING, DAMPER SHALL MODULATE OPEN. ELECTRIC REHEAT COIL SHALL BE OFF. DURING COOLING MODE, DAMPER CAN MODULATE CLOSED TO COOLING MINIMUM AIRFLOW SETPOINT WHICH MAY BE LOWER THAN HEATING MINIMUM
AIRFLOW SETPOINT.
C. ON A CALL FOR HEATING, DAMPER FIRST MODULATES CLOSED TO MINIMUM HEATING POSITION. AFTER DAMPER IS AT MINIMUM HEATING POSITION, ELECTRIC REHEAT COIL MODULATES THROUGH SCR CONTROL TO MAINTAIN SPACE
TEMPERATURE SETPOINT.
D. MONITOR AND DISPLAY TERMINAL UNIT DISCHARGE AIR TEMPERATURE SENSOR VALUE ON GRAPHICS.
E. GENERATE A UNIQUE REHEAT TROUBLE ALARM IF TERMINAL UNIT DISCHARGE AIR TEMPERATURE SENSOR DOES NOT SENSE
A TEMPERATURE INCREASE TO AT LEAST 60°F, (ADJUSTABLE) WHEN REHEAT IS COMMANDED ON FOR 10 MINUTES
(ADJUSTABLE).
F. INTEGRATE ANY ALARMS GENERATED BY TERMINAL UNIT MANUFACTURER WITH BAS AND DISPLAY ON GRAPHICS.
7. DEHUMIDIFICATION CONTROL: SEE RTU DEHUMIDIFICATION CONTROL SEQUENCE.
E. EXISTING RTU-N-2 VAV TERMINAL UNITS WITH STAGED ELECTRIC REHEAT
1. SEE RTU-N-2 EXISTING VAV TERMINAL UNIT SCHEDULE TO IDENTIFY APPLICABLE TERMINAL UNITS.
2. SPACE TEMPERATURE WILL BE MAINTAINED, AS SENSED BY ROOM THERMOSTAT. SETPOINT IS ADJUSTABLE AND CAN BE LIMITED
IN SOFTWARE. THE DISCHARGE AIR TEMPERATURE IS MONITORED AND DISPLAYED ON GRAPHICS.
3. ON A RISE IN SPACE TEMPERATURE THE VAV WILL MODULATE OPEN. ON A DECREASE IN SPACE TEMPERATURE THE VAV WILL
MODULATE TO MINIMUM FLOW; ON A FURTHER DECREASE IN SPACE TEMPERATURE THE STAGED ELECTRIC STRIP HEAT WILL
ENERGIZE. ON A RISE IN SPACE TEMPERATURE THE REVERSE WILL OCCUR.
4. INTEGRATE EXISTING TERMINAL UNIT CONTROLS WITH NEW RTU SEQUENCES. ONE NOT ALL- INCLUSIVE EXAMPLE WOULD BE TO INTEGRATE EXISTING TERMINAL UNIT DAMPER CONTROL POSITION STATUS WITH NEW RTU-N-2 STATIC PRESSURE RESET
SEQUENCE.
5. GENERATE A UNIQUE REHEAT TROUBLE ALARM IF TERMINAL UNIT DISCHARGE AIR TEMPERATURE SENSOR DOES NOT SENSE A TEMPERATURE INCREASE TO AT LEAST 60°F, (ADJUSTABLE) WHEN REHEAT IS COMMANDED ON FOR 10 MINUTES (ADJUSTABLE).
6. INTEGRATE ANY ALARMS GENERATED BY TERMINAL UNIT MANUFACTURER WITH BAS AND DISPLAY ON GRAPHICS.
7. DEHUMIDIFICATION CONTROL: SEE RTU DEHUMIDIFICATION CONTROL SEQUENCE.
F. (E) EF-1 AND RTU-N-2
1. EXISTING CONSTANT VOLUME (250 CFM) INLINE (E) EF-1 SERVING 222 BREAK ROOM ON SECOND FLOOR IS INTERLOCKED WITH A
0-1 HOUR WALL MOUNTED TWIST TIMER.
2. PROVIDE A CURRENT SWITCH STATUS FOR (E) EF-1 THAT NOTIFIES THE BAS WHEN (E) EF-1 IS ON AND INTEGRATE THE STATUS WITH THE RTU-N-2 VENTILATION OPTIMIZATION CONTROL SEQUENCE SERVED BY (E) VAV-5, (E) VAV-6; (E) VAV-7 SO ADEQUATE
MAKEUP AIR IS PROVIDED WITH OUTDOOR AIR WHENEVER (E) EF-1 IS ON.
4. PROVIDE A MOTORIZED SHUTOFF DAMPER.
G. FC-A, ACCU-A, EF-R-1, FC-B, ACCU-B; EF-B
1. FAN COILS FC-A AND FC-B ARE CONSTANT VOLUME DX SPLIT SYSTEM FAN COIL UNITS WITH ASSOCIATED AIR-COOLED CONDENSING UNITS ACCU-A AND ACCU-B. FC-A AND FC-B SHALL EACH HAVE THEIR OWN SPACE TEMPERATURE SENSOR IN EACH ROOM SERVED AND SHALL RUN CONTINOUSLY (WITH OPTIONAL ADJUSTABLE SCHEDULE) TO SATISFY THEIR RESPECTIVE SPACES TO MAINTAIN ALL ROOMS AT TEMPERATURE SETPOINT OF 75°F, (ADJUSTABLE). FC-A SERVES TWO SPACES, AND FC-B SERVES THREE. IF ONE SPACE IS SATISFIED, BUT ANOTHER IS NOT, THE FAN COIL WILL COOL UNTIL ALL SPACES ARE AT
SETPOINT OR COOLER.
2. EF-R-1 SHALL BE INTERLOCKED TO RUN CONTINOUSLY WHENEVER FC-A OR FC-B IS ON.
3. PROVIDE A CURRENT SENSOR STATUS FOR FC-A, FC-B, AND EF-R-1, AND EF-B AND GENERATE AN ALARM IF STATUS DOES NOT
MATCH COMMAND.
4. PROVIDE A UNIQUE HIGH TEMPERATURE ALARM FOR FC-A AND FC-B WHENEVER THE SPACE…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.