36C10E19B0001-0005008.pdf

PDF 3 MB Posted

Attached to
AMO/DROC, BLD 47 | St. Pete Federal contract opportunity
Solicitation number
36C10E19B0001
Issued by
Department of Veterans Affairs Veterans Benefits Administration

About this file

36C10E19B0001 0005 S02 - Addendum 2 - Drawings.pdf

View the file

Other files for this federal contract opportunity

Other files attached to AMO/DROC, BLD 47 | St. Pete, newest first.
File Type Posted
36C10E19B0001-0006000.docx DOCX document
36C10E19B0001-0005004.dwg DWG drawing
36C10E19B0001-0005003.dwg DWG drawing
36C10E19B0001-0005002.dwg DWG drawing
36C10E19B0001-0003001.pdf PDF
36C10E19B0001-0003000.docx DOCX document
Amendment_A0002.pdf PDF
VB32226_CAD_Files_190502.zip ZIP file
VB3226_Const_Specs_190123.pdf PDF
Pre-Bid_RFI_Log_Final,_14_May_19.pdf PDF
Pre-Bid RFI Log Final, 14 May 19.pdf PDF
36C10E19B0001-0002040.docx DOCX document
36C10E19B0001-0001000.docx DOCX document
36C10E19B0001-067.dwg DWG drawing
36C10E19B0001-013.dwg DWG drawing
36C10E19B0001-033.dwg DWG drawing
36C10E19B0001-008.dwg DWG drawing
36C10E19B0001-063.dwg DWG drawing
36C10E19B0001-072.dwg DWG drawing
36C10E19B0001-014.dwg DWG drawing
36C10E19B0001-040.dwg DWG drawing
36C10E19B0001-056.dwg DWG drawing
36C10E19B0001-024.dwg DWG drawing
36C10E19B0001-051.dwg DWG drawing
36C10E19B0001-071.dwg DWG drawing
36C10E19B0001-041.dwg DWG drawing
36C10E19B0001-058.dwg DWG drawing
36C10E19B0001-038.dwg DWG drawing
36C10E19B0001-074.dwg DWG drawing
36C10E19B0001-061.dwg DWG drawing
36C10E19B0001-080.dwg DWG drawing
36C10E19B0001-004.pdf PDF
36C10E19B0001-035.dwg DWG drawing
36C10E19B0001-026.dwg DWG drawing
36C10E19B0001-027.dwg DWG drawing
36C10E19B0001-073.dwg DWG drawing
36C10E19B0001-036.dwg DWG drawing
36C10E19B0001-084.pdf PDF
36C10E19B0001-031.dwg DWG drawing
36C10E19B0001-002.pdf PDF
36C10E19B0001-083.dwg DWG drawing
36C10E19B0001-042.dwg DWG drawing
36C10E19B0001-046.dwg DWG drawing
36C10E19B0001-062.dwg DWG drawing
36C10E19B0001-082.dwg DWG drawing
36C10E19B0001-012.dwg DWG drawing
36C10E19B0001-069.dwg DWG drawing
36C10E19B0001-018.dwg DWG drawing
36C10E19B0001-006.dwg DWG drawing
36C10E19B0001-000.docx DOCX document
Show all 50

AMO/DROC, BLD 47 | St. Pete has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

T

T

T

T

T

T

T T

T

T T

T

T

T

T

T

T

T

T

T

T

1 2 3 4 5

A

B

C

D

E

MEN'S

ELECTRICAL

TELEPHONE

OPEN OFFICE

OPEN OFFICE

HK

WOMEN

WORK AREA

OFFICE

OFFICE

OFFICE

MEETING

MEETING

LACTATION

OFFICE

MEETING

WORK AREA

OFFICE

OFFICE

OFFICE

BREAK

MEETING

WORK AREA

CORRIDOR

WORK AREA

WORK AREA

CORRIDOR

CORRIDOR

CORRIDOR

ENTRY

10ø

12ø

3/4" CD

REFRIGERANT LINES UP CHASE TO

ROOF MOUNTED CONDENSING UNIT

DOWN COLUMN TO

GRADE LEVEL STORM

BRIDGE

40 CFM

LSD-8

50 CFM

LSD-8

55 CFM

LSD-7

155 CFM

LSD-4

6ø

10ø

6ø

10ø

(E)24ø

110 CFM

SD-1

110 CFM

SD-1

110 CFM

SD-1

110 CFM

SD-1

10ø

VAV-1

VAV-13

10ø

9ø

10ø

6ø

6ø

VAV-21

35 CFM

LSD-1

75 CFM

SD-2

75 CFM

SD-2

8ø

SD-4

300 CFM

SD-5

580 CFM

8ø

8ø

6ø

6ø

75 CFM

SD-2

75 CFM

SD-2

6ø 6ø

8ø

6ø

8ø

6ø

6ø

185 CFM

LST-1

6ø

6ø

6ø

90 CFM

LST-1

95 CFM

LST-1

FC-A2

VAV-13

VAV-1

(E)VAV-3

(E)VAV-4

(E)VAV-20

(E)VAV-5

(E)VAV-7 (E)VAV-8

(E)VAV-9

(E)VAV-10

(E)VAV-11

(E)VAV-12

(E)VAV-14

(E)VAV-15

(E)VAV-16

(E)VAV-17

(E)VAV-19

(E)VAV-18

(E)VAV-6

(E)VAV-2

(E)VAV-3

(E)VAV-20

(E)VAV-7

(E)VAV-8 (E)VAV-9

(E)VAV-10

(E)VAV-11

(E)VAV-12

(E)VAV-14

(E)VAV-19

(E)VAV-18

(E)VAV-4

(E)VAV-15

(E)VAV-2

1185 995

28x24

205300

210 CFM

(E)SD

210 CFM

(E)SD

200 CFM

(E)SD

210 CFM

(E)SD

210 CFM

(E)SD

210 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

160 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

165 CFM

(E)SD

165 CFM

(E)SD

165 CFM

(E)SD

175 CFM

(E)SD

165 CFM

(E)SD165 CFM

(E)SD

420 CFM

(E)SD

115 CFM

(E)SD

115 CFM

(E)SD

150 CFM

(E)SD

150 CFM

(E)SD

205 CFM

(E)SD

195 CFM

(E)SD

210 CFM

(E)SD

130 CFM

(E)SD

125 CFM

(E)SD

120 CFM

(E)SD

120 CFM

(E)SD

45 CFM

(E)SD

150 CFM

(E)SD

115 CFM

(E)SD

115 CFM

(E)SD

115 CFM

(E)SD

115 CFM

(E)SD

160 CFM

(E)SD

160 CFM

(E)SD

160 CFM

(E)SD

160 CFM

(E)SD

195 CFM

(E)SD 195 CFM

(E)SD

165 CFM

(E)SD

170 CFM

(E)SD

165 CFM

(E)SD

165 CFM

(E)SD

165 CFM

(E)SD

165 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

150 CFM

(E)SD

150 CFM

(E)SD

210 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

160 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

155 CFM

(E)SD

155 CFM

(E)SD

155 CFM

(E)SD

155 CFM

(E)SD

155 CFM

(E)SD

155 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

210 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

195 CFM

(E)SD

160 CFM

(E)SD

160 CFM

(E)SD

160 CFM

(E)SD

160 CFM

(E)SD

190 CFM

(E)SD

190 CFM

(E)SD

(E)VAV-17

(E)VAV-16

150 CFM

(E)SD

FC-A1

(E)VAV-6

(E)VAV-5

H

H

H

H

H

H

2 HR FIRE RATED WALL

3 HR FIRE RATED WALL

TYP.

TYP.

BUILDING 46

14ø

FC-A

BUILDING 47

TYP.

4ø OA

H

H H

6ø

8ø

GENERAL NOTES

A. EXISTING WORK TO REMAIN AS INDICATED WITH LIGHT LINE WEIGHT.

B. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.

C. COORDINATE ALL SYSTEM OUTAGES WITH OWNER.

D. PROVIDE AT LEAST 14 WORKING DAYS ADVANCE NOTICE TO THE COR

(CONTRACT OFFICER REPRESENTATIVE) FOR ANY UTILITY SHUT DOWNS.

E. LOCATE BALANCE DAMPERS SO THEY CAN BE ACCESSED THROUGH CEILING

TILE OR WITH REMOTE BALANCE DAMPER ADJUSTMENT DEVICE. PROVIDE

DURO-DYNE REMOTE, INTERNAL TYPE CABLE OPERATED BALANCE DAMPER OR

EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD CEILINGS,

TYPICAL.

F. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH

MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND

APPLICABLE CODES AND REGULATIONS.

G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER

DISCIPLINES: ARCHITECTURAL, PLUMBING, ELECTRICAL, ETC., SHOWN ON

OTHER CONTRACTOR DOCUMENTS.

H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND

PIPING INSULATION IS APPLIED.

I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN

ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND

DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD

PERFORMANCE.

J. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY

THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE

APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE

BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND

SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO

NOT SCALE DRAWINGS.

K. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCES AS RECOMMENDED

BY CODE AND MANUFACTURERS.

N TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENT SUBMISSION

Services

Engineering and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

LEO A DALY

1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036

9500 BAY PINES BLVD

BAY PINES, FL 33744

RENOVATION OF

BUILDING 47 FOR AMO 47

VB3226

C U s e rs \k y le g \D o c u m e n ts

\R e v it L o c a l F ile s \V

B A

-4

-M e c h

C

L W y s s k y le

.g u g g e n h e im .r v t

/7

/2

:3

:5

P M

06/06/201906/06/2019

MH1.02-1

HVAC 2ND FLOOR NEW WORK

PLAN - SUPPLY

GC KG

SCALE: 1/8" = 1'-0"

2ND FLOOR - NEW WORK PLAN - SUPPLY

DRAWING NOTES

1. PROVIDE NEW FAN COIL FC-A AND ALL ASSOCIATED DUCTWORK, CONDENSATE

DRAIN LINE, AIR DEVICES, AIR COOLED CONDENSING UNIT, REFRIGERANT

LINES, TEMPERATURE SENSORS, DAMPERS, ALL FOR A FULLY FUNCTIONAL

SYSTEM.

2. PROVIDE NEW VAV TERMINAL UNITS, TEMPERATURE AND HUMIDITY SENSORS

DUCTWORK, AIR DEVICES, DAMPERS, ALL FOR A FULLY FUNCTIONAL SYSTEM,

AND CONNECT TO EXISTING SYSTEM AT "CONNECT TO EXISTING" SYMBOL

LOCATIONS. MOUNT TEMPERATURE AND HUMIDITY SENSORS AT 70 INCHES

ABOVE FINISHED FLOOR WHERE REQUIRED TO AVOID CUBICLE PANELS IN

OPEN OFFICE AREAS, OTHERWISE MOUNT SENSORS AT 48 INCHES ABOVE

FINISHED FLOOR.

3. PROVIDE NEW EF-R-1 AND ASSOCIATED EXHAUST DUCT AND AIR DEVICES.

4. PROVIDE NEW TRANSFER DUCTWORK AND ASSOCIATED AIR DEVICES WITH

BALANCE DAMPERS.

5. CONTRACTOR TO BALANCE NEW AND EXISTING VAV TERMINAL UNITS,

EXHAUST FANS, AND ALL AIR DEVICES TO AIRFLOWS SHOWN AFTER RTUS AND

FAN COILS ARE PROVIDED. CONTRACTOR TO PROVIDE BALANCE DAMPERS

WHEREVER NEEDED AND OF TYPE NEEDED TO ACCOMPLISH DESIGN BALANCE.

SEE AIR BALANCE SCHEDULES AND SEQUENCES OF CONTROL.

6. EXISTING DDC ENGINEERING CONTROL CENTER IS LOCATED IN BUILDING 46.

COORDINATE WITH VA PERSONNEL ABOUT DDC SYSTEM TIE IN LOCATIONS.

Revisions: Date:

REV 1 - ADDENDUM #1 06/06/2019

T

T T

T

T

T T

T

T

T

T

T

T T

T

T

T T

T

T

TT

1 2 3 4 5

A

B

C

D

E

OPEN OFFICE

CORRIDOR

STORAGE

BREAK ROOM

OPEN OFFICE

OFFICE

OFFICE

328 OFFICE

OFFICE

CONF./ TRAINING

ROOM A

CONF. / TRAINING

ROOM B

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

317 OFFICE

OFFICE

OFFICE

OPEN OFFICE

OFFICE

OFFICE

HUDDLE

314WOMEN

HK

OFFICE

311 OFFICE

OFFICE

MEN

PUMP

ELEC

TEL

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

BRIDGE

16ø16ø

3/4" CD

REFRIGERANT LINES UP FROM FC-A

REFRIGERANT LINES TO ROOF

MOUNTED CONDENSING UNIT

DOWN COLUMN TO

GRADE LEVEL STORM

SD-4

860 CFM

SD-3

295 CFM

35 CFM

LSD-1

90 CFM

LSD-2

90 CFM

LSD-2

95 CFM

LSD-2

150 CFM

LSD-4

150 CFM

LSD-4

145 CFM

LSD-4

150 CFM

LSD-3

6ø

8ø

10ø

6ø

6ø

6ø

VAV-2VAV-9

22ø

12ø

10ø

8ø

8ø

8ø

8ø

14ø

20ø

9ø

VAV-4

VAV-3

VAV-12

VAV-5

8ø14ø

9ø

VAV-10

VAV-6

VAV-14

14ø

12ø

9ø

VAV-13

VAV-11

9ø

VAV-15

VAV-7

10ø

12ø

9ø

7ø

VAV-19

VAV-20

VAV-17

9ø

VAV-21

VAV-22

16ø

VAV-8

10ø VAV-18

VAV-16

90 CFM

LSD-2

85 CFM

LSD-2

85 CFM

LSD-2

90 CFM

LSD-2

90 CFM

LSD-2

90 CFM

LSD-2

90 CFM

LSD-2

90 CFM

LSD-2

135 CFM

LSD-3

130 CFM

LSD-3

130 CFM

LSD-3

135 CFM

LSD-3

110 CFM

LSD-7

110 CFM

LSD-7

155 CFM

LSD-4

155 CFM

LSD-4

155 CFM

LSD-4

75 CFM

LSD-7

75 CFM

LSD-7 75 CFM

LSD-7

80 CFM

LSD-7

135 CFM

LSD-3

135 CFM

LSD-3

130 CFM

LSD-3

130 CFM

LSD-3

135 CFM

LSD-3

135 CFM

LSD-3

135 CFM

LSD-3

135 CFM

LSD-3

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

35 CFM

LSD-1

95 CFM

LSD-2

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

75 CFM

LSD-7

90 CFM

LSD-2

85 CFM

LSD-2

90 CFM

LSD-2

85 CFM

LSD-2

80 CFM

LSD-2

80 CFM

LSD-2

80 CFM

LSD-2

95 CFM

LSD-2

100 CFM

LSD-2

100 CFM

LSD-2

95 CFM

LSD-2

85 CFM

LSD-2

85 CFM

LSD-2

85 CFM

LSD-2

85 CFM

LSD-2

95 CFM

LSD-2

100 CFM

LSD-2

95 CFM

LSD-2

100 CFM

LSD-2

130 CFM

LSD-3

130 CFM

LSD-3

135 CFM

LSD-3

135 CFM

LSD-3

80 CFM

LSD-2

UP TO RTU-N-2

DN

UP TO RTU-N-4

6ø

10ø

10ø

6ø 8ø

10ø

10ø

6ø

TYP.

10ø

6ø

6ø

8ø

6ø

6ø

6ø

8ø

10ø

8ø 8ø

12ø

8ø

6ø

125 CFM

SD-6

6ø

8ø6ø

125 CFM

SD-6

60 CFM

LSD-5

30 CFM

LSD-1

8ø

8ø6ø

6ø

6ø 6ø

25 CFM

LSD-6

10ø 6ø

8ø

6ø 6ø

6ø

10ø

6ø

8ø

6ø 6ø

6ø

12ø 8ø

8ø8ø

8ø

10ø

6ø

8ø 4ø

6ø 10ø

6ø 6ø 60 CFM

LSD-5

25 CFM

LSD-6

12ø

8ø

10ø

8ø

12ø

8ø8ø

10ø

8ø

12ø

8ø

10ø

8ø 8ø

10ø 6ø

4ø

6ø

6ø

4ø 35 CFM

LSD-1

6ø

60 CFM

LSD-5

30 CFM

LSD-1

30 CFM

LSD-6

60 CFM

LSD-5

9ø

8ø

6ø

60 CFM

LSD-5

4ø

6ø

35 CFM

LSD-1

60 CFM

LSD-5

6ø4ø

16ø

4ø

14ø

6ø

6ø 12ø 6ø

6ø

6ø

4ø

12ø

10ø

8ø

6ø

6ø 6ø

6ø

6ø 6ø

6ø

10ø

SD-4

290 CFM

6ø

6ø8ø

190 CFM

LST-1

6ø

8ø

35 CFM

LSD-1

VAV-2

VAV-9

VAV-10

VAV-11

VAV-20

VAV-19

VAV-16

VAV-17

VAV-15

VAV-13

VAV-14

VAV-18

VAV-8

VAV-7

VAV-6

VAV-5

VAV-4

VAV-3

VAV-22

VAV-21

FC-B1

8ø

14ø

95 CFM

LSD-295 CFM

LSD-2

FC-B2FC-B3

8ø

6ø

6ø

6ø

12ø

8ø

12ø

22ø

8ø

16ø

18ø

6ø

8ø

10ø

9ø14ø

8ø

9ø

26ø

8ø 12ø

10ø

8ø

4ø

6ø

8ø

RL/RS

H

H

6ø

H H

2 HR FIRE RATED WALL

3 HR FIRE RATED WALL

FD-2

2 HR FIRE

RATED WALL

TYP.

TYP.

TYP.

TYP.

6ø

8ø

4ø OA

4" UP TO ROOF-MOUNTED

OA INTAKE

OA DUCT

8ø

28x30

S

FC-B

14ø

SD-1 5

TYP.

TYP.

2 3

2 2

9ø

TYP.

6ø ø6

6ø

6ø

10ø

10ø1

VAV-12

GENERAL NOTES

A. EXISTING WORK TO REMAIN AS INDICATED WITH LIGHT LINE WEIGHT.

B. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.

C. COORDINATE ALL SYSTEM OUTAGES WITH OWNER.

D. PROVIDE AT LEAST 14 WORKING DAYS ADVANCE NOTICE TO THE COR

(CONTRACT OFFICER REPRESENTATIVE) FOR ANY UTILITY SHUT DOWNS.

E. LOCATE BALANCE DAMPERS SO THEY CAN BE ACCESSED THROUGH CEILING

TILE OR WITH REMOTE BALANCE DAMPER ADJUSTMENT DEVICE. PROVIDE

DURO-DYNE REMOTE, INTERNAL TYPE CABLE OPERATED BALANCE DAMPER OR

EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD CEILINGS,

TYPICAL.

F. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH

MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND

APPLICABLE CODES AND REGULATIONS.

G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER

DISCIPLINES: ARCHITECTURAL, PLUMBING, ELECTRICAL, ETC., SHOWN ON

OTHER CONTRACTOR DOCUMENTS.

H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND

PIPING INSULATION IS APPLIED.

I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN

ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND

DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD

PERFORMANCE.

J. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY

THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE

APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE

BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND

SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO

NOT SCALE DRAWINGS.

K. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCES AS RECOMMENDED

BY CODE AND MANUFACTURERS.

N TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENT SUBMISSION

Services

Engineering and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

LEO A DALY

1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036

9500 BAY PINES BLVD

BAY PINES, FL 33744

RENOVATION OF

BUILDING 47 FOR AMO 47

VB3226

C U s e rs \k y le g \D o c u m e n ts

\R e v it L o c a l F ile s \V

B A

-4

-M e c h

C

L W y s s k y le

.g u g g e n h e im .r v t

/7

/2

:3

:5

P M

06/06/201906/06/2019

MH1.03-1

HVAC 3RD FLOOR NEW WORK

PLAN - SUPPLY

GC KG

SCALE: 1/8" = 1'-0"

3RD FLOOR NEW WORK PLAN - SUPPLY

DRAWING NOTES

1. PROVIDE DURO-DYNE REMOTE INTERNAL TYPE CABLE OPERATED BALANCE

DAMPER OR EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD

CEILINGS.

2. PROVIDE NEW FAN COIL FC-B AND ALL ASSOCIATED DUCTWORK,

CONDENSATE DRAIN LINE, AIR DEVICES, AIR COOLED CONDENSING UNIT,

REFRIGERANT LINES, TEMPERATURE SENSORS, DAMPERS, ALL FOR A FULLY

FUNCTIONAL SYSTEM.

3. PROVIDE NEW VAV TERMINAL UNITS, TEMPERATURE AND HUMIDITY SENSORS

DUCTWORK, AIR DEVICES, DAMPERS, ALL FOR A FULLY FUNCTIONAL SYSTEM.

MOUNT TEMPERATURE AND HUMIDITY SENSORS AT 70 INCHES ABOVE

FINISHED FLOOR WHERE REQUIRED TO AVOID CUBICAL PANELS IN OPEN

OFFICE AREA, OTHERWISE MOUNT SENSORS AT 48" ABOVE FINISHED FLOOR.

4. CONTRACTOR TO BALANCE NEW VAV TERMINAL UNITS, AND ALL AIR DEVICES

TO AIRFLOWS SHOWN AFTER RTUS AND FAN COILS ARE PROVIDED.

CONTRACTOR TO PROVIDE BALANCE DAMPERS WHEREVER NEEDED AND OF

TYPE NEEDED TO ACCOMPLISH DESIGN BALANCE. SEE AIR BALANCE

SCHEDULES AND SEQUENCES OF CONTROL.

5. PROVIDE A NEW SMOKE DAMPER. SEE FIRE/SMOKE DAMPER AND DUCT

SMOKE DETECTOR DETAILS AND SCHEDULES.

6. MECHANICAL CONTRACTOR SHALL FURNISH SUPPLY AND RETURN FAN VFDS

TO SERVE NEW RTU-N-2 AND RTU-N-4. SEE RTU AND DDC SPECIFICATIONS.

ELECTRICAL CONTRACTOR SHALL INSTALL THE FOUR VFDS IN ARRAY ON THE

WALL NEXT TO THE DOOR OF ELECTRICAL ROOM 306. SEE ELECTRICAL

DRAWINGS.

7. MECHANICAL CONTRACTOR SHALL PROVIDE DOUBLE WALL DUCT WITH

PERFORATED INNER DUCT CASING AND COMBINATION

THERMAL/ACCOUSTICAL INSULATION PER SPECIFICATIONS. DOUBLE WALL

DUCT IS REPRESENTED WITH HATCHING. DOUBLE WALL DUCT EXPOSED TO

OPEN CEILING SHALL BE PAINTED PER ARCHITECURAL SPECIFICATIONS.

PROVIDE SILENCERS AT DUCT DROPS FROM BOTH RTUS PER DETAILS AND

SILENCER SHEDULE. DUCT NOT EXPOSED TO OPEN CEILING SHALL BE SINGLE

WALL WITH EXTERNAL INSULATION.

8. DOUBLE WALL DUCT SHOULD HAVE SOLID (NOT PERFORATED) INNER WALL.

Revisions: Date:

1 2 3 4 5

A

B

C

D

E

3/4" CD

REFRIGERANT LINES UP FROM FC-A

REFRIGERANT LINES TO ROOF

MOUNTED CONDENSING UNIT

DOWN COLUMN TO

GRADE LEVEL STORM

14x14 UP TO (E)EF-R-3 ON ROOF

(E)8x14 DOWN

14x14 UP TO (E)EF-R-2 ON ROOF

(E)8x10 DOWN

8ø

EG-2

10 CFM

EG-2

10 CFM

EG-1

150 CFM

EG-1

150 CFM

8ø

EG-3

100 CFM

EG-2

75 CFM

EG-2

75 CFM

16ø

10ø

16ø

850 CFM

RG-2

285 CFM

RG-3

DN

EG-4

225 CFM EG-2

25 CFM

75 CFM

LSR-1 75 CFM

LSR-1

75 CFM

LSR-1

80 CFM

LSR-1

180 CFM

LSR-3

180 CFM

LSR-3

180 CFM

LSR-3

175 CFM

LSR-3

180 CFM

LSR-3

175 CFM

LSR-3

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

6ø

95 CFM

LSR-2

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

75 CFM

LSR-1

10ø

8ø

6ø 6ø

12ø

14ø

8ø 8ø 8ø

8ø 8ø 8ø

26x1620ø

18ø

6ø

6ø

6ø

8ø

16ø 390 CFM

RS-1

18ø

530 CFM

RS-1

465 CFM

RS-1

240 CFM

RS-1

390 CFM

RS-1

220 CFM

RS-1

8ø

290 CFM

RS-1

295 CFM

RS-1

360 CFM

RS-1

270 CFM

RS-1

10ø

350 CFM

RS-1

16ø

12ø

420 CFM

RS-1

215 CFM

RS-1

8ø 12ø

ES-1

105 CFM

ES-1

105 CFM

245 CFM

RS-1

6ø

6ø

10ø

8ø

8ø

20ø

CONF./ TRAINING

ROOM A

CONF. / TRAINING

ROOM B

CORRIDOR

OPEN OFFICE

OPEN OFFICE

OPEN OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

WOMEN

HUDDLE

314 OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HK

PUMP

ELEC

MEN

TEL

BRIDGE

BREAK ROOM

STORAGE

12ø

10ø

6ø

34x20

8ø

8ø

6ø 6ø

16ø

6ø

18ø

UP

6ø

6ø

6ø

6ø

RL/RS

UP TO RTU-N-2

280 CFM

RG-3

EG-2

10 CFM

8ø

14ø

2 HR FIRE RATING

3 HR FIRE RATING

10ø

FD-3

14ø

FD-1

2 HR FIRE

RATED WALL

TYP.

TYP.

TYP.

10ø

10ø

12ø

10ø

10ø

8ø

10ø

10ø

10ø

10ø

BUILDING 47

BUILDING 46

6ø

6ø

4ø

6ø

UP TO EF-R-4

ON ROOF

60x24 RA (E)60x24 RA

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

14ø

FC-B

S

SD-2

2 3

2 2

TYP.

TYP.

4ø

HS

VAV-1511

HS

VAV-1211

12ø 6ø

10ø

VAV-3 11HS

6ø

6ø

GENERAL NOTES

A. EXISTING WORK TO REMAIN AS INDICATED WITH LIGHT LINE WEIGHT.

B. NEW WORK IS INDICATED WITH HEAVY LINE WEIGHT.

C. COORDINATE ALL SYSTEM OUTAGES WITH OWNER.

D. PROVIDE AT LEAST 14 WORKING DAYS ADVANCE NOTICE TO THE COR

(CONTRACT OFFICER REPRESENTATIVE) FOR ANY UTILITY SHUT DOWNS.

E. LOCATE BALANCE DAMPERS SO THEY CAN BE ACCESSED THROUGH CEILING

TILE OR WITH REMOTE BALANCE DAMPER ADJUSTMENT DEVICE. PROVIDE

DURO-DYNE REMOTE, INTERNAL TYPE CABLE OPERATED BALANCE DAMPER OR

EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE HARD CEILINGS,

TYPICAL.

F. INSTALL ALL EQUIPMENT AND ACCESSORIES IN ACCORDANCE WITH

MANUFACTURERS’ RECOMMENDATIONS, CONTRACT DOCUMENTS, AND

APPLICABLE CODES AND REGULATIONS.

G. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH OTHER

DISCIPLINES: ARCHITECTURAL, PLUMBING, ELECTRICAL, ETC., SHOWN ON

OTHER CONTRACTOR DOCUMENTS.

H. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT AND

PIPING INSULATION IS APPLIED.

I. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN

ACCESSIBLE LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND

DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD

PERFORMANCE.

J. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR REQUIRED BY

THE SPECIFICATIONS NOT DEFINITELY FIXED BY DIMENSIONS ARE

APPROXIMATE ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE

BEST RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND

SHALL HAVE THE APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO

NOT SCALE DRAWINGS.

K. INSTALL EQUIPMENT WITH MINIMUM ACCESS CLEARANCES AS RECOMMENDED

BY CODE AND MANUFACTURERS.

N TRUE

NORTH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENT SUBMISSION

Services

Engineering and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

LEO A DALY

1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036

9500 BAY PINES BLVD

BAY PINES, FL 33744

RENOVATION OF

BUILDING 47 FOR AMO 47

VB3226

C U s e rs \k y le g \D o c u m e n ts

\R e v it L o c a l F ile s \V

B A

-4

-M e c h

C

L W y s s k y le

.g u g g e n h e im .r v t

/7

/2

:3

:5

P M

06/06/201906/06/2019

MH1.03-2

HVAC 3RD FLOOR NEW WORK

PLAN - EXHAUST/RETURN

GC KG

SCALE: 1/8" = 1'-0"

3RD FLOOR NEW WORK PLAN - RETURN/EXHAUST

DRAWING NOTES

1. PROVIDE DURO-DYNE REMOTE INTERNAL TYPE CABLE OPERATED BALANCE

DAMPER OR EQUAL FOR OTHERWISE INACCESSIBLE LOCATIONS ABOVE

HARD CEILINGS.

2. PROVIDE NEW FAN COIL FC-B AND ALL ASSOCIATED DUCTWORK,

CONDENSATE DRAIN LINE, AIR DEVICES, AIR COOLED CONDENSING UNIT,

REFRIGERANT LINES, TEMPERATURE SENSORS, DAMPERS, ALL FOR A FULLY

FUNCTIONAL SYSTEM.

3. PROVIDE NEW EF-R-1 AND ASSOCIATED EXHAUST DUCT AND AIR DEVICES.

4. PROVIDE NEW EXHAUST DUCTWORK AND ASSOCIATED AIR DEVICES AND

BALANCE DAMPERS.

5. PROVIDE NEW TRANSFER DUCTWORK AND ASSOCIATED AIR DEVICES WITH

BALANCE DAMPERS.

6. CONTRACTOR TO BALANCE NEW EXHAUST FANS, AND ALL AIR DEVICES TO

AIRFLOWS SHOWN AFTER RTUS AND FAN COILS ARE PROVIDED.

CONTRACTOR TO PROVIDE BALANCE DAMPERS WHEREVER NEEDED AND OF

TYPE NEEDED TO ACCOMPLISH DESIGN BALANCE. SEE AIR BALANCE

SCHEDULES AND SEQUENCES OF CONTROL.

7. PROVIDE A NEW SMOKE DAMPER. SEE FIRE/SMOKE DAMPER AND DUCT

SMOKE DETECTOR DETAILS AND SCHEDULES.

8. PROVIDE NEW RETURN DUCTWORK AND ASSOCIATED AIR DEVICES AND

BALANCE DAMPERS.

9. MECHANICAL CONTRACTOR SHALL PROVIDE DOUBLE WALL DUCT WITH

PERFORATED INNER DUCT CASING AND COMBINATION

THERMAL/ACCOUSTICAL INSULATION PER SPECIFICATIONS. DOUBLE WALL

DUCT IS REPRESENTED WITH HATCHING. DOUBLE WALL DUCT EXPOSED TO

OPEN CEILING SHALL BE PAINTED PER ARCHITECURAL SPECIFICATIONS.

PROVIDE SILENCERS AT DUCT DROPS FROM BOTH RTUS PER DETAILS AND

SILENCER SHEDULE. DUCT NOT EXPOSED TO OPEN CEILING SHALL BE

SINGLE WALL WITH EXTERNAL INSULATION.

10. DOUBLE WALL DUCT SHOULD HAVE SOLID (NOT PERFORATED) INNER WALL.

11. PROVIDE A DUCT MOUNTED HUMIDITY SENSOR IN RETURN DUCT.

Revisions: Date:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

CONSTRUCTION

DOCUMENT SUBMISSION

Services

Engineering and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

F F E I n c Engineering and Technical Services 420 Springfield Pike Wyoming OH 45215 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

LEO A DALY

1200 Nineteenth Street NW Suite 220 Washington, D.C. 20036

9500 BAY PINES BLVD

BAY PINES, FL 33744

RENOVATION OF

BUILDING 47 FOR AMO 47

VB3226

C U s e rs \k y le g \D o c u m e n ts

\R e v it L o c a l F ile s \V

B A

-4

-M e c h

C

L W y s s k y le

.g u g g e n h e im .r v t

/7

/2

:3

:5

P M

06/06/201906/06/2019

MH6.01

HVAC CONTROLS

Checker Author

4.OCCUPIED MODE:

A. OCCUPIED SCHEDULE: OCCUPIED MODE STARTS BASED ON AN ADJUSTABLE SCHEDULE.

B. UPON A TRANSITION FROM PRE-OCCUPANCY OPTIMUM START MODE TO OCCUPIED MODE, THE FOLLOWING EVENTS OCCUR:

1. OPEN REMOTE EXHAUST FAN SHUTOFF DAMPERS AND FIRE/SMOKE DAMPERS.

2. OUTSIDE AIR DAMPER SHALL BE OPENED TO ITS MINIMUM OUTDOOR AIR POSITION.

3. WHEN OUTDOOR AND RELIEF AIR DAMPERS, REMOTE EXHAUST FAN SHUTOFF DAMPERS, AND FIRE/SMOKE DAMPERS ARE

FULLY OPEN, END SWITCHES SHALL ALLOW RTU SUPPLY AND REMOTE EXHAUST FANS TO START.

4. SUPPLY, RETURN, AND EXHAUST FANS RUN CONTINUOUSLY DURING OCCUPIED MODE, AND IF THEY ARE ALL RUNNING, THE

DDC SYSTEM INDEXES THE UNIT TO OCCUPIED MODE.

5. OCCUPIED SPACE SETPOINTS ARE AS FOLLOWS:

OCCUPIED HEATING SETPOINT 72°F, (ADJUSTABLE).

OCCUPIED COOLING SETPOINT 75°F, (ADJUSTABLE).

6. THE FOLLOWING RTU CONTROL LOOPS WILL OPERATE TO MAINTAIN SETPOINTS DURING OCCUPIED MODE:

A. COOLING DISCHARGE AIR TEMPERATURE CONTROL LOOP.

B. DEHUMIDIFICATION CONTROL LOOP.

C. MIXED AIR TEMPERATURE LOW LIMIT CONTROL LOOP.

D. MINIMUM OUTDOOR AIR CONTROL LOOP.

E. SUPPLY AIR DUCT STATIC CONTROL LOOP.

F. RETURN FAN AND BUILDING PRESSURIZATION CONTROL LOOP.

C) COOLING DISCHARGE AIR TEMPERATURE CONTROL LOOP:

1. MIXED AIR DAMPERS (OUTDOOR AND RETURN AIR DAMPERS) AND COOLING COIL VALVE SHALL MODULATE IN SEQUENCE

TO MAINTAIN A CONSTANT COOLING DISCHARGE AIR TEMPERATURE SETPOINT OF 50°F, (ADJUSTABLE) AT THE DISCHARGE

AIR TEMPERATURE SENSOR.

2. ECONOMIZER:

PROVIDE 100% INTEGRATED FIXED DRY-BULB ECONOMIZER WITH HIGH LIMIT SHUTOFF SETPOINT OF 65°F, (ADJUSTABLE).

PROVIDE ECONOMIZER FAULT DETECTION AND DIAGNOSTICS (FDD) SYSTEM AS DESCRIBED IN 2017 FLORIDA BUILDING CODE-ENERGY CONSERVATION, SECTION C403.2.4.7. ECONOMIZER SHALL BE AVAILABLE DURING BOTH OCCUPIED AND UNOCCUPIED COOL-DOWN MODES. EACH RTU SHALL BE PROVIDED WITH A RETURN FAN THAT PROVIDES RELIEF AT THE

RTU.

D) DEHUMIDIFICATION CONTROL LOOP:

1. UPON AN INCREASE IN RETURN AIR OR SPACE HUMIDITY ABOVE 60% RH (ADJUSTABLE) IN OCCUPIED MODE, A HIGH HUMIDITY ALARM SHALL BE GENERATED, RTU MIXING DAMPERS SHALL MODULATE TO MINIMUM OUTDOOR AIR POSITION, COOLING COIL VALVE SHALL OPEN 100%, AND TERMINAL UNIT ELECTRIC REHEAT COILS SHALL ENERGIZE, MODULATING AS

NECESSARY TO MAINTAIN SPACE TEMPERATURE SETPOINT OF 75°F, (ADJUSTABLE).

2. UPON AN INCREASE IN RETURN AIR OR SPACE HUMIDITY ABOVE 60% RH (ADJUSTABLE) IN UNOCCUPIED MODE, A HIGH

HUMIDITY ALARM SHALL BE GENERATED, MIXING DAMPERS SHALL REMAIN IN FULL RETURN MODE WITH OUTSIDE AND RELIEF AIR DAMPERS CLOSED, THE RTU FANS SHALL COME ON WITH RETURN FAN TRACKING SUPPLY BY A SPEED DIFFERENTIAL DETERMINED BY BALANCER, COOLING COIL VALVE SHALL OPEN 100%, AND TERMINAL UNIT ELECTRIC REHEAT COILS SHALL ENERGIZE, MODULATING AS NECESSARY TO MAINTAIN SPACE TEMPERATURE SETPOINT OF 78°F, (ADJUSTABLE).

3. ONCE HUMIDITY SETPOINT IS SATISFIED, THE UNIT SHALL RETURN TO ITS PRIOR MODE OF OPERATION.

E) MIXED AIR TEMPERATURE LOW LIMIT CONTROL LOOP:

1. IF THE MIXED AIR TEMPERATURE AS SENSED BY THE MIXED AIR TEMPERATURE LOW LIMIT SENSOR DROPS BELOW THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT OF 40°F (ADJUSTABLE), THE MIXED AIR DAMPERS (OUTDOOR AND RETURN AIR DAMPERS) SHALL MODULATE TO THE MINIMUM OUTDOOR AIRFLOW POSITION UNTIL THE MIXED AIR TEMPERATURE

RISES ABOVE THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT. A MIXED AIR TEMPERATURE LOW LIMIT WARNING ALARM

SHALL BE GENERATED.

2. IF THE MIXED AIR TEMPERATURE AS SENSED BY THE MIXED AIR TEMPERATURE LOW LIMIT SENSOR DROPS BELOW THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT OF 40°F (ADJUSTABLE) FOR MORE THAN 10 MINUTES (ADJUSTABLE), WITH THE MIXED AIR DAMPERS AT MINIMUM OUTDOOR AIRFLOW POSITION, THE MIXED AIR DAMPERS SHALL MODULATE TO FULL RETURN MODE (OUTDOOR AND RELIEF AIR DAMPERS CLOSED AND RETURN AIR DAMPER FULL OPEN) UNTIL THE MIXED AIR TEMPERATURE RISES ABOVE THE MIXED AIR TEMPERATURE LOW LIMIT SETPOINT MORE THAN 5 DEGREES F (ADJUSTABLE).

A MIXED AIR TEMPERATURE LOW LIMIT CRITICAL ALARM SHALL BE GENERATED.

F) MINIMUM OUTDOOR AIR CONTROL LOOP:

1. THE MIXED AIR DAMPERS (OUTDOOR AND RETURN AIR DAMPERS) AND SUPPLY AND RETURN FANS SHALL MODULATE IN

SEQUENCE TO MAINTAIN EACH RTU’S MINIMUM OUTDOOR AIR SETPOINT AS MEASURED AT THE MINIMUM OUTDOOR

AIRFLOW MEASURING STATION.

2. VENTILATION OPTIMIZATION CONTROL:

PROVIDE VENTILATION OPTIMIZATION CONTROL AS DEFINED BY APPENDIX A OF ASHRAE STANDARD 62.1 AS DESCRIBED IN

ASHRAE 90.1-2013, SECTION 6.5.3.3.

3. REMOTE EXHAUST FANS (E) EF-R-2, (E) EF-R-3, AND EF-R-4 SHALL RUN AT CONSTANT VOLUME CONTINUOUSLY DURING OCCUPIED MODE AND PROVIDE OUTDOOR AIR RELIEF ALONG WITH THE RELIEF AT EACH RTU. SEE AIR BALANCE

SCHEDULES.

G) SUPPLY AIR DUCT STATIC CONTROL LOOP:

1. SUPPLY FAN MODULATES TO MAINTAIN A RESET DUCT STATIC PRESSURE SETPOINT WHENEVER THE SUPPLY FAN RUNS.

DUCT STATIC PRESSURE SENSOR SHALL BE LOCATED AT THE RTU SUPPLY FAN.

2. SUPPLY AIR DUCT STATIC PRESSURE RESET LOGIC (TRIM & RESPOND):

STATIC PRESSURE SETPOINT SHALL BE RESET USING TRIM AND RESPOND LOGIC WITHIN THE RANGE 0.15 INWG (ADJUSTABLE) TO 2 INWG (ADJUSTABLE) AS SET BY BALANCE CONTRACTOR. WHEN FAN IS OFF, FREEZE SETPOINT AT THE MINIMUM VALUE. WHILE FAN IS PROVEN ON, EVERY 2 MINUTES (ADJUSTABLE), DECREASE SETPOINT BY 0.04 INWG (ADJUSTABLE) IF THERE ARE TWO (ADJUSTABLE) OR FEWER PRESSURE REQUESTS. [ADJUST THE “TWO” OR FEWER ZONE COOLING REQUESTS VALUE TO LIMIT DOMINANCE OF ROGUE ZONES.] IF THERE ARE MORE THAN TWO (ADJUSTABLE) PRESSURE REQUESTS, INCREASE THE SETPOINT BY 0.04 INWG (ADJUSTABLE). WHERE VAV ZONE DAMPER POSITION IS KNOWN, A PRESSURE REQUEST IS GENERATED WHEN ANY VAV DAMPER SERVED BY THE SYSTEM IS WIDE OPEN. WHERE VAV ZONE DAMPER POSITION IS UNKNOWN, A PRESSURE REQUEST IS MADE WHEN THE RATIO OF THE ZONE’S ACTUAL

SUPPLY AIRFLOW TO SUPPLY AIRFLOW SETPOINT IS LESS THAN 90% (ADJUSTABLE).

3. DDC SHALL AUTOMATICALLY DETECT ZONES THAT MAY BE EXCESSIVELY DRIVING THE RESET LOGIC AND SHALL GENERATE A ROGUE ZONE ALARM PER ASHRAE 90.1-2013, SECTION 6.5.3.2.3, A. CLEARLY IDENTIFY ON GRAPHICS WHICH ZONES ARE

ROGUE.

4. DDC SHALL ALLOW OPERATOR ABILITY TO REMOVE ZONES FROM THE RESET ALGORITHM PER ASHRAE 90.1-2013, SECTION 6.5.3.2.3, B.

H) RETURN FAN AND BUILDING PRESSURIZATION CONTROL LOOPS:

RETURN FAN CONTROL LOOP:

1. RETURN FAN OPERATES WHENEVER ASSOCIATED SUPPLY FAN IS PROVEN ON.

2. RETURN FAN SPEED IS CONTROLLED TO MAINTAIN A POSITIVE PRESSURE IN THE RETURN/RELIEF PLENUM TO ENSURE NO

BACKFLOW OF OUTDOOR AIR THROUGH THE RELIEF DAMPER. TO MINIMIZE ENERGY USE, THE PLENUM PRESSURE SETPINT SHALL BE RESET AS SHOWN IN FIGURE 1. SEE AIR BALANCE SCHEDULES FOR REQUIRED RELIEF AT EACH RTU FOR

BUILDING AIR BALANCE. BALANCER TO ADJUST SETPOINTS ACCORDINGLY.

3. HIGH PRESSURE PICKUP PROBE(S) ARE LOCATED PER MANUFACTURER’S INSTALLATION INSTRUCTIONS INSIDE THE

RETURN/RELIEF PLENUM.

4. LOW PRESSURE PICKUP PROBE(S) ARE LOCATED PER MANUFACTURER’S INSTALLATION INSTRUCTIONS OUTSIDE THE BUILDING. PICKUP(S) SHALL BE DESIGNED TO STABILIZE READINGS BY DAMPENING PRESSURE FLUCTUATIONS CAUSED BY WIND GUSTS. THESE PICKUPS, AVAILABLE FROM SEVERAL MANUFACTURERS, SHALL BE FITTED WITH A PNEUMATIC SIGNAL

DAMPENER TO FURTHER REDUCE SPIKES.

5. THE LOOP OUTPUT IS MAPPED TO FIRST OPEN THE RELIEF DAMPERS THEN TO RAISE THE RETURN/RELIEF PLENUM

PRESSURE SETPOINT FROM MIN TO MAX SETPOINT.

SEQUENCES OF OPERATION

A. GENERAL:

1. HVAC SYSTEMS SHALL BE CONTROLLED WITH DIRECT DIGITAL CONTROL (DDC) ACCORDING TO SEQUENCES SHOWN.

2. ADDITIONAL POINTS OR SOFTWARE PROGRAMMING NOT LISTED BUT WHICH ARE REQUIRED TO MEET THE FOLLOWING

SEQUENCES OF OPERATION SHALL BE PROVIDED FOR A COMPLETELY FUNCTIONAL SYSTEM THAT MEETS CODE.

3. HOUSE CONTROLLERS, RELAYS, TRANSDUCERS, AND OTHER COMPONENTS REQUIRED FOR STAND-ALONE CONTROL SHALL BE

PROVIDED INSIDE A NEMA 1 (INDOOR) OR NEMA 3R (OUTDOOR) ENCLOSURE WITH LOCKABLE DOOR.

4. ACTUATORS ON MOTORIZED VALVES AND DAMPERS ON ROOFTOP UNITS (RTUS), AND EXHAUST FAN SYSTEMS TO BE DDC. SEE

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

5. ALL FIRE/SMOKE DAMPERS SHALL BE MONITORED BY BAS FOR TROUBLE CONDITIONS.

6. ALL SYSTEM FIRE/SMOKE DAMPERS SHALL BE HARD-WIRE INTERLOCKED SUCH THAT THEY CLOSE FULLY WHEN RTU FANS STOP.

7. EACH OF THE TWO RTU SUPPLY FANS AND TWO RTU RETURN FANS (SERVING RTU-N-2 AND RTU-N-4) AND ALL THREE REMOTE EXHAUST FANS [(E) EF-R-2, (E) EF-R-3; EF-R-4] SHALL EACH HAVE A CURRENT SENSOR FOR STATUS. IF ANY OF THE RTU SUPPLY AND RETURN FAN STATUS POINTS OR ANY OF THE THREE REMOTE EXHAUST FANS INDICATE OFF, A HARDWIRED INTERLOCK CAUSES THE OTHER FANS TO GO OFF, OUTSIDE AND RELIEF AIR DAMPERS TO CLOSE, RETURN AIR DAMPER TO OPEN, FIRE/SMOKE DAMPERS TO CLOSE, AND EACH EXHAUST FAN SHUTOFF DAMPER TO CLOSE.

8. CONTROL SUBMITTALS INCLUDING DRAWINGS, SCHEDULES, SEQUENCES OF OPERATION, ETC., FOR ALL DDC CONTROLLED EQUIPMENT SHALL BE STORED AND ACCESSIBLE ON THE GRAPHICS SO THEY ARE ALWAYS AVAILABLE AND NOT LOST.

B. SETPOINTS:

1. ALL SETPOINTS GIVEN IN THE SEQUENCE OF OPERATIONS OR IN THE DRAWINGS ARE FOR SYSTEM STARTUP AND ARE

PRELIMINARY AND SHALL BE ADJUSTABLE.

2. ALL SETPOINTS SHALL BE ACCESSIBLE TO THE OWNER SO SYSTEM CAN BE TESTED. SETPOINTS AND SCREENS SHOULD HAVE UNIQUE PASSWORD PROTECTION CAPABILITY SHOULD THE OWNER DECIDE TO LIMIT ACCESSIBILITY. COORDINATE

ACCESSIBILITY AND GRAPHICS SETUP WITH OWNER BEFORE FINAL IMPLEMENTATION.

3. OPTIMUM OPERATING SETPOINTS MUST BE DETERMINED DURING ACTUAL OCCUPANCY AND WILL BE AFFECTED BY MANY

FACTORS. THESE MAY INCLUDE:

A. WEATHER CONDITIONS.

B. BUILDING OCCUPANCY.

C. BUILDING UTILIZATION PATTERNS.

D. VARIATIONS IN BUILDING CONSTRUCTION.

E. VARIATIONS IN OPERATING CHARACTERISTICS OF ACTUAL INSTALLED BUILDING EQUIPMENT.

IT IS THE RESPONSIBILITY OF THE BUILDING OPERATORS TO DETERMINE THOSE SETTINGS AND OPERATING METHODS WHICH PROVIDE THE BEST BALANCE OF OPERATING EFFICIENCY AND OCCUPANT COMFORT. THIS IS AN ONGOING PROCESS. OPTIMUM

SETTINGS CHANGE AS OPERATING CONDITIONS CHANGE.

C. RTU-N-2 AND RTU-N-4 AND REMOTE EXHAUST FANS (E) EF-R-2, (E) EF-R-3, AND EF-R-4

1. GENERAL:

A. RTU SUPPLY, RETURN, AND REMOTE EXHAUST FANS SHALL EACH BE INTERLOCKED THROUGH A DAMPER END SWITCH, SO

EACH CANNOT START UNTIL ITS RESPECTIVE OUTSIDE, RELIEF, EXHAUST SHUTOFF AND COMBINATION FIRE/SMOKE DAMPERS ARE FULLY OPEN. IF AN END SWITCH IS NOT SATISFIED WITHIN 10 MINUTES, (ADJUSTABLE), GENERATE A UNIQUE

END SWITCH ALARM IDENTIFYING WHICH END SWITCH WAS NOT SATISFIED.

B. THE RTU’S OCCUPIED, UNOCCUPIED, PRE-OCCUPANCY TIME PERIOD IS DETERMINED BY A TIME SCHEDULE AND

PROGRAMMING.

2.UNOCCUPIED MODE:

A. DURING UNOCCUPIED MODE, THE RTU IS OFF UNLESS THERE IS A CALL FOR HEATING OR COOLING OR DEHUMIDIFICATION TO

MAINTAIN UNOCCUPIED SPACE SETPOINTS OR FOR UNOCCUPIED MORNING WARM-UP OR COOL-DOWN CYCLE. WHEN THE RTU IS OFF, SUPPLY FAN, RETURN FAN, AND REMOTE EXHAUST FANS ARE OFF, AND ALL DAMPERS AND VALVES GO TO

NORMAL POSITIONS AS SHOWN ON THE RTU AND REMOTE EXHAUST FAN CONTROL SCHEMATICS.

B. UNOCCUPIED SPACE SETPOINTS ARE AS FOLLOWS:

UNOCCUPIED HEATING SETPOINT 62°F, (ADJUSTABLE).

UNOCCUPIED COOLING SETPOINT 80°F, (ADJUSTABLE).

WHENEVER RTU IS STARTED TO MAINTAIN UNOCCUPIED SPACE SETPOINTS, IT BEHAVES AS IF IN OCCUPIED MODE EXCEPT IN FULL RETURN MODE WITH RETURN FAN TRACKING SUPPLY AT A REDUCED SPEED DIFFERENTIAL DETERMINED BY BALANCER, OUTDOOR AND RELIEF AIR DAMPERS ARE CLOSED, AND REMOTE EXHAUST FANS REMAIN OFF. IF ECONOMIZER CAN BE USED, RTU IS CONTROLLED AS IT WOULD BE IN OCCUPIED MODE UNTIL SETPOINT IS SATISFIED. WHEN

UNOCCUPIED SPACE SETPOINTS ARE SATISFIED, THE RTU WILL STOP.

C) UNOCCUPIED HEATING SETBACK MODE IS MAINTAINED AS FOLLOWS: IF ANY SPACE SENSOR READS BELOW THE UNOCCUPIED HEATING SETPOINT, THE RTU WILL BE STARTED AND RUN UNTIL ALL UNOCCUPIED HEATING SPACE SETPOINTS ARE SATISFIED. THE RTU MIXING DAMPERS WILL MODULATE TO FULL RETURN MODE TO MAINTAIN THE HIGHEST SUPPLY AIR TEMPERATURE SETPOINT POSSIBLE. TERMINAL UNITS IN UNSATISFIED SPACES WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL

SETPOINT IS SATISFIED.

D) UNOCCUPIED COOLING SETUP MODE IS MAINTAINED AS FOLLOWS: IF ANY SPACE SENSOR READS ABOVE THE UNOCCUPIED COOLING SETPOINT, THE RTU WILL BE STARTED AND RUN UNTIL ALL UNOCCUPIED COOLING SPACE SETPOINTS ARE SATISFIED. THE RTU COOLING COIL VALVE WILL MODULATE OPEN TO MAINTAIN THE RTU SUPPLY AIR TEMPERATURE SETPOINT. TERMINAL UNITS IN UNSATISFIED SPACES WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL SETPOINT IS SATISFIED.

IF ECONOMIZER CAN BE USED, RTU IS CONTROLLED AS IT WOULD BE IN OCCUPIED MODE UNTIL SETPOINT IS SATISFIED.

3. PRE-OCCUPANCY OPTIMUM START MODE:

A. PRE-OCCUPANCY OPTIMUM START MODE IS INITIALLY SCHEDULED, AND THE SCHEDULED START TIME IS OPTIMIZED BASED

ON INSIDE AND OUTSIDE AIR TEMPERATURE AND SYSTEM HISTORY OF PERFORMANCE. THE DDC CONTROLLER CALCULATES THE OPTIMUM PRE-OCCUPANCY MODE HEATING/COOLING TIME NECESSARY TO BRING BUILDING TO OCCUPIED

TEMPERATURE IN EITHER WARM-UP OR COOL-DOWN CYCLES.

B. UPON INITIATION OF A START IN PRE-OCCUPANCY OPTIMUM START MODE (WARM-UP OR COOL-DOWN CYCLE), THE

FOLLOWING EVENTS OCCUR:

1. OPEN RETURN AIR DAMPER UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN CYCLE.

2. OPEN FIRE/SMOKE DAMPERS.

3. OUTSIDE AND RELIEF AIR DAMPERS SHALL REMAIN CLOSED UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED

FOR COOL-DOWN CYCLE.

4. REMOTE EXHAUST FANS SHALL REMAIN OFF UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN

CYCLE.

5. WHEN RTU RETURN AND FIRE/SMOKE DAMPERS ARE FULLY OPEN, END SWITCHES SHALL ALLOW RTU SUPPLY AND

RETURN FANS TO START WITH RETURN FAN TRACKING SUPPLY FAN AT REDUCED SPEED DIFFERENTIAL DETERMINED BY BALANCER UNLESS ECONOMIZER CAN BE USED. IF ECONOMIZER CAN BE USED, RETURN FAN IS CONTROLLED AS IT WOULD

BE IN OCCUPIED MODE.

C) PRE-OCCUPANCY WARM-UP CYCLE: DURING PRE-OCCUPANCY MODE, THE DDC SYSTEM OPERATES THE UNIT IN ITS WARM- UP CYCLE IF THE AVERAGE SPACE TEMPERATURE OF THE VAV BOX ZONES SERVED BY THE RTU IS BELOW 72°F

(ADJUSTABLE). THE FOLLOWING EVENTS OCCUR DURING PRE-OCCUPANCY WARM-UP CYCLE:

1. OUTSIDE AND RELIEF AIR DAMPERS ARE CLOSED.

2. RETURN AIR DAMPER AND FIRE/SMOKE DAMPERS ARE OPEN.

3. REMOTE EXHAUST FANS ARE OFF.

4. RTU COOLING COIL VALVE IS CLOSED TO COIL.

5. THE RTU MIXING DAMPERS WILL MODULATE TO FULL RETURN MODE TO MAINTAIN THE SUPPLY AIR TEMPERATURE

SETPOINT. SUPPLY FAN WILL MODULATE TO MAINTAIN SUPPLY DUCT STATIC PRESSURE AT SETPOINT. RETURN FAN WILL

TRACK SUPPLY FAN BY A REDUCED SPEED DIFFERENTIAL DETERMINED BY BALANCER.

6. TERMINAL UNITS WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL EACH OCCUPIED SPACE SETPOINT IS SATISFIED.

7. WARM-UP MODE IS TERMINATED WHEN THE RTU IS INDEXED TO ITS OCCUPIED MODE TIME PERIOD, OR WHEN ALL SPACES

REACH THEIR OCCUPIED HEATING SPACE TEMPERATURE SETPOINTS BEFORE OCCUPIED MODE TIME PERIOD BEGINS. SEE

OCCUPIED MODE SEQUENCE FOR OCCUPIED SPACE TEMPERATURE SETPOINTS.

D) PRE-OCCUPANCY COOL-DOWN CYCLE: DURING PRE-OCCUPANCY MODE, THE DDC SYSTEM OPERATES THE UNIT IN ITS COOL- DOWN CYCLE IF THE AVERAGE SPACE TEMPERATURE OF THE VAV BOX ZONES SERVED BY THE UNIT IS ABOVE 75°F

(ADJUSTABLE). THE FOLLOWING EVENTS OCCUR DURING PRE-OCCUPANCY COOL-DOWN CYCLE:

1. OUTSIDE AND RELIEF AIR DAMPERS ARE CLOSED UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-

DOWN CYCLE.

2. RETURN AIR DAMPER IS OPEN UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN CYCLE.

3. FIRE/SMOKE DAMPERS ARE OPEN.

4. REMOTE EXHAUST FANS ARE OFF UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE USED FOR COOL-DOWN CYCLE.

5. THE RTU MIXING DAMPERS WILL MODULATE TO FULL RETURN MODE, UNLESS SYSTEM DETERMINES ECONOMIZER CAN BE

USED FOR COOL-DOWN CYCLE, AND THE RTU COOLING COIL VALVE WILL MODULATE OPEN TO MAINTAIN THE RTU SUPPLY

AIR TEMPERATURE SETPOINT.

6. SUPPLY FAN WILL MODULATE TO MAINTAIN RESET SUPPLY DUCT STATIC PRESSURE AT SETPOINT AS IT WOULD IN OCCUPIED MODE. SEE SUPPLY DUCT STATIC PRESSURE RESET SCHEDULE IN OCCUPIED MODE SEQUENCES.

7. RETURN FAN WILL TRACK SUPPLY FAN AT A REDUCED SPEED DETERMINED BY BALANCER UNLESS ECONOMIZER CAN BE USED. IF ECONOMIZER CAN BE USED, RETURN FAN IS CONTROLLED AS IT WOULD BE IN OCCUPIED MODE.

8. TERMINAL UNITS WILL BEHAVE AS IF IN OCCUPIED MODE UNTIL EACH OCCUPIED SPACE SETPOINT IS SATISFIED.

9. COOL-DOWN MODE IS TERMINATED WHEN THE UNIT IS INDEXED TO ITS OCCUPIED MODE TIME PERIOD, OR WHEN ALL

SPACES REACH THEIR OCCUPIED COOLING SPACE TEMPERATURE SETPOINTS BEFORE OCCUPIED MODE TIME PERIOD

BEGINS. SEE OCCUPIED MODE SEQUENCE FOR OCCUPIED SPACE TEMPERATURE SETPOINTS.

6. RETURN FAN SPEED SHALL BE CONTROLLED TO MAINTAIN RETURN FAN DISCHARGE STATIC PRESSURE AT SETPOINT. THE SETPOINT SHALL BE RESET LINEARLY FROM RFSPMIN (RETURN FAN STATIC PRESSURE MINIMUM) TO RFSPMAX. SETPOINTS

ARE DETERMINED IN CONJUCTION WITH THE AIR BALANCER AS FOLLOWS:

A. RFSPMIN: STATIC PRESSURE SETPOINT REQUIRED TO DELIVER THE DESIGN RETURN AIR VOLUME ACROSS THE RETURN AIR DAMPER WHEN THE SUPPLY AIR FAN IS AT DESIGN AIRFLOW AND ON MINIMUM OUTDOOR AIR. THIS SETPOINT SHALL

BE NO LESS THAN 0.01 INCHES (ADJUSTABLE) TO MAINTAIN POSITIVE DISCHARGE FLOW.

B. RFSPMAX: STATIC PRESSURE SETPOINT REQUIRED TO EXHAUST ENOUGH AIR TO MAINTAIN BUILDING STATIC PRESSURE AT SETPOINT OF 0.05 INCHES (ADJUSTABLE) WHEN THE SUPPLY AIR FAN IS AT DESIGN AIRFLOW AND ON 100% OUTDOOR

AIR.

BUILDING PRESSURIZATION CONTROL LOOP:

7. EXHAUST DAMPERS SHALL ONLY BE ENABLED WHEN THE ASSOCIATED SUPPLY AND RETURN FANS ARE PROVEN ON AND THE MINIMUM OUTDOOR AIR DAMPER IS OPEN. THE EXHAUST DAMPERS SHALL BE CLOSED WHEN RTU IS DISABLED.

8. EXHAUST DAMPERS ARE CONTROLLED TO MAINTAIN BUILDING PRESSURE DIRECTLY USING A DIFFERENTIAL PRESSURE SENSOR WITH PRESSURE SENSOR PICKUP PROBE(S) LOCATED IN A REPRESENTATIVE SPACE INSIDE THE BUILDING AND PRESSURE SENSOR PICKUP PROBE(S) LOCATED OUTDOORS. SEE AIR BALANCE SCHEDULES FOR RELIEF REQUIRED FOR

BUILDING AIR BALANCE.

9. BUILDING STATIC PRESSURE SHALL BE TIME AVERAGED WITH A SLIDING 5-MINUTE (ADJUSTABLE) WINDOW TO DAMPEN

FLUCTUATIONS. THE AVERAGED VALUE SHALL BE THAT DISPLAYED AND USED FOR CONTROL.

10. DUE TO THE POTENTIAL FOR INTERACTION BETWEEN THE BUILDING PRESSURIZATION AND RETURN FAN CONTROL LOOPS, EXTRA CARE MUST BE TAKEN IN SELECTING CONTROL LOOP GAINS. TO PREVENT EXCESSIVE CONTROL LOOP INTERACTION,THE CLOSED LOOP RESPONSE TIME OF THE BUILDING PRESSURIZATION LOOP SHOULD NOT EXCEED 1/5 OF THE CLOSED LOOP RESPONSE TIME OF THE RETURN FAN CONTROL LOOP. THIS CAN BE ACCOMPLISHED BY DECREASING THE GAIN OF THE BUILDING PRESSURIZATION CONTROLLER. IN OTHER WORDS, THE BUILDING PRESSURE CONTROL LOOP MUST BE VERY SLOW RELATIVE TO THE RETURN FAN CONTROL LOOP, AND THE BUILDING PRESSURE CONTROL POINT SHOULD NOT BE THE REALTIME DIFFERENTIAL PRESSURE READING BUT INSTEAD A MOVING AVERAGE OF THE DIFFERENTIAL PRESSURE READING TO PREVENT SPIKES FROM CAUSING RELIEF DAMPER COTNROL INSTABILITY.

11. WHEN EXHAUST DAMPERS ARE ENABLED, A CONTROL LOOP SHALL MODULATE EXHAUST DAMPERS TO MAINTAIN THE BUILDING PRESSURE AT A SETPOINT OF 0.05 INCHES (ADJUSTABLE). THE RANGE OF THE SENSOR MAY BE AS LOW AS +0.1 INCHES (ADJUSTABLE) BUT SPIKES DUE TO WIND AND OTHER FACTORS MAY CAUSE A HIGHER RANGE OF PRESSURES TO

OCCUR SO A +0.25 INCH RANGE (ADJUSTABLE) IS RECOMMENDED.

12. LOCATE INDOOR PLATE HIGH PRESSURE PORT PICKUP(S) PER MANUFACTURER’S INSTALLATION INSTRUCTIONS INSIDE AN INTERIOR SPACE(S) PHYSICALLY SEPARATED BY WALLS FROM EXTERIOR DOORS AND ELEVATOR LOBBIES IN EITHER A PERMANENT CEILING OR WALL THAT WILL NOT LIKELY BE REMOVED WHEN TENANT IMPROVEMENT UPGRADES ARE MADE IN

THE FUTURE.

13. LOCATE AMBIENT (OUTDOOR) PLATE LOW PRESSURE PORT PICKUP(S) PER MANUFACTURER’S INSTALLATION INSTRUCTIONS OUTDOORS. PICKUP(S) SHALL BE DESIGNED TO STABILIZE READINGS BY DAMPENING PRESSURE FLUCTUATIONS CAUSED BY WIND GUSTS. THESE PICKUPS, AVAILABLE FROM SEVERAL MANUFACTURERS, SHALL BE FITTED

WITH A PNEUMATIC SIGNAL DAMPENER TO FURTHER REDUCE SPIKES.

14. GENERATE A HIGH BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS +0.25 INCHES

(ADJUSTABLE).

15. GENERATE A LOW BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.0 INCHES

(ADJUSTABLE).

I) RTU SHUTDOWN MODE: UPON RTU SUPPLY FAN, RETURN FAN, AND REMOTE EXHAUST FAN SHUTDOWN, ALL REMOTE EXHAUST FAN SHUTOFF DAMPERS, AND FIRE/SMOKE DAMPERS SHALL CLOSE FULLY. OUTSIDE AND RELIEF AIR DAMPERS SHALL CLOSE FULLY, AND RETURN AIR DAMPERS SHALL OPEN FULLY. RTU CONTROL SYSTEM SHALL BE SET UP AND ADJUSTED SUCH THAT CLOSING OF FIRE/SMOKE DAMPERS WILL BE DELAYED UNTIL FAN ROLLS TO NEAR STOP.

1. SAFETIES:

2. ALL SAFETY/EMERGENCY CONTROLS SHALL BE HARD-WIRE INTERLOCKED SUCH THAT THEY ARE NOT DEPENDENT UPON

DDC SYSTEM SOFTWARE.

3. END SWITCHES ARE PROVIDED AS SAFETIES. ANY OF THESE DEVICES WILL KEEP THE DRIVE OFF IN THE EVENT OF A

PROBLEM.

4. SMOKE CONTROL:

A. DUCT MOUNTED AIR SMOKE DETECTORS WILL BE FURNISHED AND INSTALLED AS SHOWN. PROVIDE POWER AND ALARM, CONTROL AND INTERLOCK WIRING.

B. WHENEVER ANY DUCT-MOUNTED SMOKE DETECTOR GOES INTO ALARM, IT SHALL PERFORM THE FOLLOWING:

1. STOP ALL UNIT FANS.

2. CLOSE ALL ASSOCIATED FIRE/SMOKE DAMPERS.

3. NOTIFY THE FIRE ALARM SYSTEM.

4. THIS CONTROL MUST BE MANUALLY RESET.

5. FIRE/SMOKE ALARMS AFFECT ONLY AIR SYSTEMS SERVING THE ZONE IN ALARM. AIR SYSTEMS SERVING THE OTHER

ZONES CONTINUE TO OPERATE NORMALLY.

5. FREEZE PROTECTION:

A. IF THE AIR TEMPERATURE SENSED BY THE LOW LIMIT THERMOSTAT (FREEZESTAT) FALLS BELOW 40°F (ADJUSTABLE), A

FREEZESTAT WARNING ALARM SHALL INDICATE AT THE OPERATOR CONTROL PANEL.

B. IF THIS TEMPERATURE FALLS BELOW 38°F (ADJUSTABLE), THE SUPPLY FAN, RETURN FAN, AND REMOTE EXHAUST FANS SHALL SHUT DOWN, THE COOLING VALVE SHALL BE SET AT 20% OPEN (ADJUSTABLE); THE CHILLED WATER PUMP SHALL PROVIDE CONTINUOUS FLOW THROUGH CHILLED WATER COILS ALL UNTIL ALARM IS CLEARED, AND A CRITICAL ALARM

SHALL BE GENERATED.

6. HIGH STATIC PRESSURE AT RTU SUPPLY FAN

A. IF THE STATIC PRESSURE HIGH LIMIT SWITCH DOWNSTREAM OF THE RTU SUPPLY FAN SENSES A STATIC PRESSURE

CONDITION ABOVE ITS SETPOINT OF +3 INWG (ADJUSTABLE), REMOTE EXHAUST FANS AND THE RTU SUPPLY AND RETURN FANS SHALL BE DISABLED, AND CONTROLS SHALL GO TO THEIR NORMAL POSITIONS UNTIL SAFETY THAT TRIPPED IS RESET MANUALLY. A HIGH SUPPLY FAN STATIC PRESSURE LIMIT SWITCH ALARM WILL BE GENERATED.

B. IF THE STATIC PRESSURE LOW LIMIT SWITCH UPSTREAM OF THE RTU RETURN FAN SENSES A STATIC PRESSURE CONDITION BELOW ITS SETPOINT OF -3 INWG (ADJUSTABLE), REMOTE EXHAUST FANS AND THE RTU SUPPLY AND RETURN FANS SHALL BE DISABLED, AND CONTROLS SHALL GO TO THEIR NORMAL POSITIONS UNTIL SAFETY THAT TRIPPED IS RESET MANUALLY. A LOW RETURN FAN STATIC PRESSURE LIMIT SWITCH ALARM WILL BE GENERATED.

7. ALARMS: THE DDC GENERATES AN ALARM WHENEVER ANY OF THE FOLLOWING OCCURS:

A. THE SUPPLY FAN IS COMMANDED ON AND FAILS TO RUN.

B. THE RETURN FAN IS COMMANDED ON AND FAILS TO RUN.

C. THE SUPPLY FAN IS COMMANDED OFF BUT RUNS.

D. THE RETURN FAN IS COMMANDED OFF BUT RUNS.

E. THE SUPPLY FAN SPEED DRIVE FAULT CONTACT IS ON.

F. THE RETURN FAN SPEED DRIVE FAULT CONTACT IS ON.

G. ANY EXHAUST FAN IS COMMANDED ON AND FAILS TO RUN.

H. ANY EXHAUST FAN IS COMMANDED OFF BUT RUNS.

I. IF ANY END SWITCH IS NOT SATISFIED WITHIN 10 MINUTES, (ADJUSTABLE), GENERATE A UNIQUE END SWITCH ALARM

IDENTIFYING WHICH END SWITCH WAS NOT SATISFIED.

J. THE LOW TEMPERATURE CUTOUT (FREEZESTAT) IS ACTIVATED. GENERATE A FREEZESTAT WARNING ALARM IF TEMPERATURE BELOW 40°F, (ADJUSTABLE), IS DETECTED. GENERATE A CRITICAL FREEZESTAT ALARM IF TEMPERATURE

BELOW 38°F (ADJUSTABLE), IS DETECTED.

K. STATIC PRESSURE HIGH LIMIT PRESSURE SWITCH IS ACTIVATED WHEN PRESSURE EXCEEDS +3 INWG, (ADJUSTABLE).

PROVIDE UNIQUE ALARM FOR EACH PRESSURE SWITCH WITH UNIQUE TAGS.

L. STATIC PRESSURE LOW LIMIT PRESSURE SWITCH IS ACTIVEATED WHEN PRESSURE EXCEEDS -3 INWG, (ADJUSTABLE).

PROVIDE UNIQUE ALARM FOR EACH PRESSURE SWITCH WITH UNIQUE TAGS.

M. THE SUPPLY AIR STATIC PRESSURE SENSOR FAILS (PRESSURE MORE THAN 10% ABOVE FINAL HIGH SETPOINT, ADJUSTABLE).

N. THE RETURN AIR STATIC PRESSURE SENSOR FAILS (PRESSURE MORE THAN 10% ABOVE FINAL HIGH SETPOINT, ADJUSTABLE).

O. THE BUILDING PRESSURE DIFFERENTIAL PRESSURE SWITCH SENSOR FAILS (PRESSURE MORE THAN 20% ABOVE FINAL

HIGH SETPOINT, ADJUSTABLE).

P. UPON AN INCREASE IN RETURN AIR OR SPACE HUMIDITY ABOVE 60% RH (ADJUSTABLE) IN UNOCCUPIED MODE, A HIGH

HUMIDITY ALARM SHALL BE GENERATED.

Q. MIXED AIR TEMPERATURE LOW LIMIT SENSOR FAILS (LESS THAN 0°F, ADJUSTABLE OR MORE THAN 120°F, ADJUSTABLE).

R. MIXED AIR TEMPERATURE LOW LIMIT SENSOR FALLS BELOW 40°F, (ADJUSTABLE). GENERATE A MIXED AIR TEMPERATURE

LOW LIMIT WARNING ALARM.

S. MIXED AIR TEMPERATURE LOW LIMIT SENSOR FALLS BELOW 40°F, (ADJUSTABLE) FOR MORE THAN 10 MINUTES, (ADJUSTABLE). GENERATE A MIXED AIR TEMPERATURE LOW LIMIT CRITICAL ALARM.

T. DISCHARGE AIR TEMPERATURE SENSOR FAILS (LESS THAN 20°F, ADJUSTABLE OR MORE THAN 120°F, ADJUSTABLE).

U. RETURN AIR TEMPERATURE SENSOR FAILS (LESS THAN 20°F, ADJUSTABLE OR MORE THAN 120°F, ADJUSTABLE).

V. RETURN AIR HUMIDITY SENSOR FAILS (LESS THAN 10%RH, ADJUSTABLE OR MORE THAN 100%RH, ADJUSTABLE).

W.OUTDOOR AIR TEMPERATURE SENSOR FAILS (LESS THAN -30°F, ADJUSTABLE OR MORE THAN 130°F, ADJUSTABLE).

X. THE OUTSIDE AIRFLOW RATE IS LESS THAN 75% (ADJUSTABLE) OF MINIMUM OUTSIDE AIRFLOW SETPOINT, FOR A TIME

PERIOD GREATER THAN 15 MINUTES (ADJUSTABLE), WHEN OUTSIDE/RETURN AIR DAMPER OPERATION HAS BEEN ENABLED.

Y. GENERATE ROGUE ZONE ALARMS PER ASHRAE 90.1-2013, SECTION 6.5.3.2.3, A., AND CLEARLY IDENTIFY ON GRAPHICS

WHICH ZONES ARE ROGUE.

Z. GENERATE DUCT SMOKE DETECTOR ALARMS CLEARLY IDENTIFYING WHICH DUCT SMOKE DETECTOR IS IN ALARM ON THE

GRAPHICS.

AA. GENERATE A DIRTY FILTER ALARM WHEN THE FILTER DIFFERENTIAL PRESSURE SWITCH INDICATES A PRESSURE

DIFFERENTIAL VALUE OF 0.5 IN.WG. (ADJUSTABLE). OWNER CAN DETERMINE AND UPDATE ACTUAL ALARM SETPOINT VALUE THE FIRST TIME DIRTY FILTERS ARE CHANGED.FIGURE 1: RELIEF DAMPER CONTROL AND RETURN FAN SETPOINT RESET

BB. GENERATE A HIGH BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS +0.25 INCHES

(ADJUSTABLE).

CC. GENERATE A LOW BUILDING PRESSURE ALARM WHEN BUILDING DIFFERENTIAL STATIC PRESSURE EXCEEDS 0.0 INCHES

(ADJUSTABLE).

D. NEW VARIABLE AIR VOLUME TERMINAL UNITS WITH SCR ELECTRIC REHEAT

1. DIRECT DIGITAL AIRFLOW CONTROLLER, DIFFERENTIAL PRESSURE SENSOR, AND ELECTRONIC DAMPER ACTUATOR SHALL BE FURNISHED UNDER THIS SECTION BUT SHALL BE FACTORY MOUNTED BY THE TERMINAL UNIT MANUFACTURER. AIRFLOW MEASURING STATION AND ELECTRIC REHEAT COILS SHALL BE FACTORY MOUNTED BY THE VAV BOX MANUFACTURER.

2. SPACE COOLING AND HEATING SETPOINTS SHALL HAVE SEPARATE OCCUPIED AND UNOCCUPIED SETTINGS, AND CONTROLLER SHALL AUTOMATICALLY SHIFT BETWEEN OCCUPIED AND UNOCCUPIED SETTINGS WHEN ASSOCIATED RTU SETTING IS SHIFTED.

SEE UNOCCUPIED AND OCCUPIED SPACE SETPOINTS SECTIONS OF RTU SEQUENCES.

3. SETPOINT SHALL BE ADJUSTABLE BY OCCUPANT AT SPACE TEMPERATURE SENSOR BY PLUS OR MINUS 2-DEGREES FAHRENHEIT (ADJUSTABLE) AND AT OPERATOR WORKSTATION. ALL SETPOINTS MAY BE OVERRIDDEN AT THE OPERATOR’S WORKSTATION.

4. SPACE TEMPERATURE SENSOR SHALL HAVE A MANUAL OVERRIDE BUTTON THAT ALLOWS TEMPORARY OCCUPIED OPERATION OF THE RTU SYSTEM SERVED FOR UP TO TWO HOURS, (TIME PERIOD VALUE ADJUSTABLE AT OPERATOR’S WORKSTATION).

5. CONTROLLER SHALL BE PRESSURE INDEPENDENT AND MAINTAIN SUPPLY AIR VOLUME SETTING REGARDLESS OF SYSTEM STATIC PRESSURE BY DIRECTLY MEASURING AIR FLOW AND CONTROLLING TERMINAL UNIT DAMPER.

A. MAXIMUM AIR VOLUME SHALL BE PRESET TO EQUAL THE SUM OF ALL ATTACHED DIFFUSERS AND REGISTERS WHICH SHOULD

MATCH THE SCHEDULED MAXIMUM AIR VOLUME FOR EACH TERMINAL UNIT.

B. MINIMUM AIR VOLUME SHALL BE PRESET TO THE VOLUME LISTED IN SCHEDULE.

6. TEMPERATURE CONTROL:

A. CONTROLLER SHALL MODULATE AIR VOLUME BETWEEN MINIMUM AND MAXIMUM SETTINGS TO MAINTAIN SPACE

TEMPERATURE SETPOINT. TERMINAL UNIT SCHEDULE SHOWS SEPARATE COOLING MINIMUM, HEATING MINIMUM, AND COOLING MAXIMUM AIRFLOW SETPOINTS. SOME TERMINAL UNITS HAVE THE SAME COOLING AND HEATING MINIMUM AIRFLOW SETPOINT WHILE OTHERS HAVE SEPARATE COOLING AND HEATING MINIMUM AIRFLOW SETPOINTS. SEE TERMINAL

UNIT SCHEDULES.

B. ON A CALL FOR COOLING, DAMPER SHALL MODULATE OPEN. ELECTRIC REHEAT COIL SHALL BE OFF. DURING COOLING MODE, DAMPER CAN MODULATE CLOSED TO COOLING MINIMUM AIRFLOW SETPOINT WHICH MAY BE LOWER THAN HEATING MINIMUM

AIRFLOW SETPOINT.

C. ON A CALL FOR HEATING, DAMPER FIRST MODULATES CLOSED TO MINIMUM HEATING POSITION. AFTER DAMPER IS AT MINIMUM HEATING POSITION, ELECTRIC REHEAT COIL MODULATES THROUGH SCR CONTROL TO MAINTAIN SPACE

TEMPERATURE SETPOINT.

D. MONITOR AND DISPLAY TERMINAL UNIT DISCHARGE AIR TEMPERATURE SENSOR VALUE ON GRAPHICS.

E. GENERATE A UNIQUE REHEAT TROUBLE ALARM IF TERMINAL UNIT DISCHARGE AIR TEMPERATURE SENSOR DOES NOT SENSE

A TEMPERATURE INCREASE TO AT LEAST 60°F, (ADJUSTABLE) WHEN REHEAT IS COMMANDED ON FOR 10 MINUTES

(ADJUSTABLE).

F. INTEGRATE ANY ALARMS GENERATED BY TERMINAL UNIT MANUFACTURER WITH BAS AND DISPLAY ON GRAPHICS.

7. DEHUMIDIFICATION CONTROL: SEE RTU DEHUMIDIFICATION CONTROL SEQUENCE.

E. EXISTING RTU-N-2 VAV TERMINAL UNITS WITH STAGED ELECTRIC REHEAT

1. SEE RTU-N-2 EXISTING VAV TERMINAL UNIT SCHEDULE TO IDENTIFY APPLICABLE TERMINAL UNITS.

2. SPACE TEMPERATURE WILL BE MAINTAINED, AS SENSED BY ROOM THERMOSTAT. SETPOINT IS ADJUSTABLE AND CAN BE LIMITED

IN SOFTWARE. THE DISCHARGE AIR TEMPERATURE IS MONITORED AND DISPLAYED ON GRAPHICS.

3. ON A RISE IN SPACE TEMPERATURE THE VAV WILL MODULATE OPEN. ON A DECREASE IN SPACE TEMPERATURE THE VAV WILL

MODULATE TO MINIMUM FLOW; ON A FURTHER DECREASE IN SPACE TEMPERATURE THE STAGED ELECTRIC STRIP HEAT WILL

ENERGIZE. ON A RISE IN SPACE TEMPERATURE THE REVERSE WILL OCCUR.

4. INTEGRATE EXISTING TERMINAL UNIT CONTROLS WITH NEW RTU SEQUENCES. ONE NOT ALL- INCLUSIVE EXAMPLE WOULD BE TO INTEGRATE EXISTING TERMINAL UNIT DAMPER CONTROL POSITION STATUS WITH NEW RTU-N-2 STATIC PRESSURE RESET

SEQUENCE.

5. GENERATE A UNIQUE REHEAT TROUBLE ALARM IF TERMINAL UNIT DISCHARGE AIR TEMPERATURE SENSOR DOES NOT SENSE A TEMPERATURE INCREASE TO AT LEAST 60°F, (ADJUSTABLE) WHEN REHEAT IS COMMANDED ON FOR 10 MINUTES (ADJUSTABLE).

6. INTEGRATE ANY ALARMS GENERATED BY TERMINAL UNIT MANUFACTURER WITH BAS AND DISPLAY ON GRAPHICS.

7. DEHUMIDIFICATION CONTROL: SEE RTU DEHUMIDIFICATION CONTROL SEQUENCE.

F. (E) EF-1 AND RTU-N-2

1. EXISTING CONSTANT VOLUME (250 CFM) INLINE (E) EF-1 SERVING 222 BREAK ROOM ON SECOND FLOOR IS INTERLOCKED WITH A

0-1 HOUR WALL MOUNTED TWIST TIMER.

2. PROVIDE A CURRENT SWITCH STATUS FOR (E) EF-1 THAT NOTIFIES THE BAS WHEN (E) EF-1 IS ON AND INTEGRATE THE STATUS WITH THE RTU-N-2 VENTILATION OPTIMIZATION CONTROL SEQUENCE SERVED BY (E) VAV-5, (E) VAV-6; (E) VAV-7 SO ADEQUATE

MAKEUP AIR IS PROVIDED WITH OUTDOOR AIR WHENEVER (E) EF-1 IS ON.

4. PROVIDE A MOTORIZED SHUTOFF DAMPER.

G. FC-A, ACCU-A, EF-R-1, FC-B, ACCU-B; EF-B

1. FAN COILS FC-A AND FC-B ARE CONSTANT VOLUME DX SPLIT SYSTEM FAN COIL UNITS WITH ASSOCIATED AIR-COOLED CONDENSING UNITS ACCU-A AND ACCU-B. FC-A AND FC-B SHALL EACH HAVE THEIR OWN SPACE TEMPERATURE SENSOR IN EACH ROOM SERVED AND SHALL RUN CONTINOUSLY (WITH OPTIONAL ADJUSTABLE SCHEDULE) TO SATISFY THEIR RESPECTIVE SPACES TO MAINTAIN ALL ROOMS AT TEMPERATURE SETPOINT OF 75°F, (ADJUSTABLE). FC-A SERVES TWO SPACES, AND FC-B SERVES THREE. IF ONE SPACE IS SATISFIED, BUT ANOTHER IS NOT, THE FAN COIL WILL COOL UNTIL ALL SPACES ARE AT

SETPOINT OR COOLER.

2. EF-R-1 SHALL BE INTERLOCKED TO RUN CONTINOUSLY WHENEVER FC-A OR FC-B IS ON.

3. PROVIDE A CURRENT SENSOR STATUS FOR FC-A, FC-B, AND EF-R-1, AND EF-B AND GENERATE AN ALARM IF STATUS DOES NOT

MATCH COMMAND.

4. PROVIDE A UNIQUE HIGH TEMPERATURE ALARM FOR FC-A AND FC-B WHENEVER THE SPACE…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.