P09_-_Attachement_1,_AHU_Upgrade_Specifications.pdf

PDF 43 KB Posted

Attached to
Replace Air Handler Units | Jackson RO Federal contract opportunity
Solicitation number
36C10E18R0165
Issued by
Department of Veterans Affairs Veterans Benefits Administration

About this file

P09 - Attachement 1, AHU Upgrade Specifications

View the file

Other files for this federal contract opportunity

Other files attached to Replace Air Handler Units | Jackson RO, newest first.
File Type Posted
36C10E18R0165-0004000.docx DOCX document
S02_-_Jackson_RO_Drawings_9.pdf PDF
S02_-_Jackson_RO_Drawings_15.pdf PDF
S02_-_Jackson_RO_Drawings_8.pdf PDF
P09_-_SOW_Air_Handlers_(22_August_2018).pdf PDF
36C10E18R0165_0003.docx DOCX document
S02_-_Jackson_RO_Drawings_18.pdf PDF
S02_-_Jackson_RO_Drawings_12.pdf PDF
S02_-_Jackson_RO_Drawings_20.pdf PDF
S02_-_Jackson_RO_Drawings_5.pdf PDF
S02_-_Jackson_RO_Drawings_2.pdf PDF
S02_-_Jackson_RO_Drawings_10.pdf PDF
S02_-_Jackson_RO_Drawings_4.pdf PDF
S02_-_Jackson_RO_Drawings_13.pdf PDF
S02_-_Jackson_RO_Drawings_6.pdf PDF
S02_-_Jackson_RO_Drawings_17.pdf PDF
S02_-_Jackson_RO_Drawings_7.pdf PDF
S02_-_Jackson_RO_Drawings_16.pdf PDF
S02_-_Jackson_RO_Drawings_14.pdf PDF
S02_-_Jackson_RO_Drawings_1.pdf PDF
S02_-_Jackson_RO_Drawings_11.pdf PDF
S02_-_Jackson_RO_Drawings_3.pdf PDF
S02_-_Jackson_RO_Drawings_19.pdf PDF
S05_-_Vendor_Questions_with_Answers_Final.xlsx XLSX spreadsheet
36C10E18R0165-0002000.docx DOCX document
36C10E18R0165-0001001.pdf PDF
36C10E18R0165-0001000.docx DOCX document
36C10E18R0165-0001002.pdf PDF
36C10E18R0165-001.docx DOCX document
36C10E18R0165-003.pdf PDF
36C10E18R0165-002.docx DOCX document
36C10E18R0165-000.docx DOCX document
Show all 32

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Attachement: 1

TAG Location Area Served Fan/HP CFM Supply CFM OA External Static Fan Total Static

13-AHU1 Roof 1st and 2nd Floor

West

SF1/40HP 27,000 4100 2.40'' 5.6''

RF1/10HP 22,000 1.0''

13-AHU2 Roof 3rd Floor West SF2/20HP 11,000 1700 2.15'' 5.2''

RF2/5HP 9,500 .08''

13-AHU3 Roof 1st and 2nd Floor

East

SF3/40HP 28,500 5200 2.10'' 5.80''

RF3/10HP 23,000 1.0''

13-AHU4 Roof 3rd Floor East SF4/30HP 17,000 2500 2.60'' 5.60''

RF4/7.5HP 14,500 .80''

TAG System CFM VEL-FPM Max SP. Loss GPM Fluid Inlet Temp. Min BTU

13-CC1 13-AHU1 27,000 500 0.7'' 150 45 1100000

13-CC2 13-AHU2 11,000 500 1.0'' 73 45 506300

13-CC3 13-AHU3 28,500 500 .90'' 152 45 1244000

13-CC4 13-AHU4 17,000 500 .65'' 112 45 784000

VA Regional Office Jackson, MS Minimum AHU Design Capabilities

Entering and leaving air design conditions for all coils

ENT. AIR Temp Dry Bulb 86.0 Wet Bulb 68.8

LVG. Air Temp Dry Bulb 54.0 Wet Bulb 54.8