TAG Location Area Served Fan/HP CFM Supply CFM OA External Static Fan Total Static
13-AHU1 Roof 1st and 2nd Floor
West
SF1/40HP 27,000 4100 2.40'' 5.6''
RF1/10HP 22,000 1.0''
13-AHU2 Roof 3rd Floor West SF2/20HP 11,000 1700 2.15'' 5.2''
RF2/5HP 9,500 .08''
13-AHU3 Roof 1st and 2nd Floor
East
SF3/40HP 28,500 5200 2.10'' 5.80''
RF3/10HP 23,000 1.0''
13-AHU4 Roof 3rd Floor East SF4/30HP 17,000 2500 2.60'' 5.60''
RF4/7.5HP 14,500 .80''
TAG System CFM VEL-FPM Max SP. Loss GPM Fluid Inlet Temp. Min BTU
13-CC1 13-AHU1 27,000 500 0.7'' 150 45 1100000
13-CC2 13-AHU2 11,000 500 1.0'' 73 45 506300
13-CC3 13-AHU3 28,500 500 .90'' 152 45 1244000
13-CC4 13-AHU4 17,000 500 .65'' 112 45 784000
VA Regional Office Jackson, MS Minimum AHU Design Capabilities
Entering and leaving air design conditions for all coils
ENT. AIR Temp Dry Bulb 86.0 Wet Bulb 68.8
LVG. Air Temp Dry Bulb 54.0 Wet Bulb 54.8