This attachment to a federal solicitation specifies the technical requirements for 144 Eaton Powerware PWHR12390W4FR batteries or equivalent batteries to replace batteries in two Eaton 93PM uninterruptible power supply systems. The new batteries must be manufactured no more than six months before installation, delivered freight prepaid to the Air Force Research Laboratory loading dock within 90 days of award, and the old batteries must be removed and disposed of using EPA-approved methods. The installation must be performed by original equipment manufacturer-employed and certified technicians, with labor and travel covered Monday through Friday from 8am to 5pm. A three-year parts and labor warranty is required on the batteries starting from installation, to be handled by the reseller rather than the Air Force Research Laboratory directly with the original equipment manufacturer. Battery commissioning tests are to be reset at baseline, and repair services by certified technicians covered if the uninterruptible power supply installation damages other portions of the system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 23q178 Attch 2 Offeror Representations and Certifications--Commercial Products and Commercial Services.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Attachment #1
FA8751-23-Q-XXXX
Qty of 144 (EA) each Eaton Powerware PWHR12390W4FR batteries, or manufacturer equal to this Eaton model of Battery.
-The make and model of the unit(s) the batteries are going into is an Eaton 93PM
93PM-160-200 S/N: EL144UXX08 (72 batteries) 93PM-160-200 S/N: EL072UXX03 (72 batteries)
- KVA: 200
- KW: 200
- # of Strings: 2
- # of Trays/Str: 9
- # Jars/Tray: 4
TECHNICAL SPECIFICATIONS
Cells (per battery) 6 Voltage (per battery) 12 Rating 390W @ 15 minute-rate to 1.67V per cell @ 77°F (25°C) Weight Approx. 72.75 lb. (33 kg) Lead weight Approx. 51.17 lb. (23.21 kg) Maximum discharge current 800 A (5 seconds) Short circuit current 2779 A Internal resistance (approximate) Approx. 3 mΩ *Operating temperature range Discharge: -15°C to 50°C (5°F to 122°F)
Charge: -15°C to 40°C (5°F to 104°F)Storage: -15°C to 40°C (5°F to 104°F)
Float charging voltage 13.5 to 13.8 VDC/unit Average at 77°F (25˚C)
Container material Polypropylene Dimensions
* It is recommended to keep the ambient air temperature the battery is used in at 25°C (77°F) for optimal battery life and discharge performance.
1.New batteries with a manufactured date code not to exceed 6 months earlier than the date of installation.
2.Freight pre-paid to AFRL loading dock within 90 days of award.
3.Removal and EPA approved disposal of old lead batteries.
4. Installation of new batteries by OEM employed and certified technicians.
5. Labor and travel 5x8 (Mon thru Friday 8 to 5).
6. Three Year Parts and 3 Year Labor warranty starting from the time of installation for all batteries.
Battery warranty issues handled by reseller not AFRL to OEM.
7. Resetting/baseline battery commissioning test codes. - Repair services by OEM certified technicians if any other portion of the UPS is damaged by installation technicians