2025-0516_WSP_Server_Room_HVAC_DWG_IFC.pdf

PDF 5 MB Posted

Attached to
Server Room Cooling System State and local contract opportunity
Solicitation number
CIFB GD 25-35
Issued by
Montgomery County, Ohio

About this file

The provided file is a comprehensive set of architectural and engineering design drawings for the Server Room Cooling System project for the Greater Dayton Regional Transit Authority (GDRTA), located at Wright Stop Plaza in Dayton, Ohio. The project involves replacing the HVAC unit in the server room and associated electrical support work, with specific focus on the second floor and roof areas of the facility. The design documents include detailed mechanical, electrical, and demolition plans, covering aspects such as equipment placement, ductwork, piping, electrical connections, and system integration. The project involves installing a new CRAC (Computer Room Air Conditioning) unit, a condensing unit, and a steam humidifier, with careful consideration for existing building systems and infrastructure.

The technical specifications indicate a complex retrofit project with precise environmental control requirements for the server room. The new cooling system is designed to maintain a consistent humidity level of 40% relative humidity, with integrated control systems that will communicate with the building's DDC (Direct Digital Control) system. Electrical connections will be made to existing emergency distribution panels (EDP2 and EMB), with specific voltage and amperage requirements for each piece of equipment. The project includes detailed provisions for equipment mounting, refrigerant piping, electrical connections, and necessary demolition and repair work, ensuring minimal disruption to the existing facility while upgrading the critical server room cooling infrastructure.

View the file

Other files for this state and local contract opportunity

Other files attached to Server Room Cooling System, newest first.
File Type Posted
Server_Room_Cooling_System_(Addendum_#1_Revision).pdf PDF
2025-0516_WSP_Server_Room_HVAC_SPEC_IFC.pdf PDF
Combin_ICE_WSP_Server_Room_5192025.pdf PDF
Sample_Contract_(DO_NOT_COMPLETE).pdf PDF
RTA_Construction_Terms_and_Conditions.docx DOCX document
RTA_General_Terms_and_Conditions.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

V

A N

G U

A R

D B

L V

D

M

IA

M

IS

B

U R

G

O H

P H

O N

E

-0

T im e

D at e

SHEET:

F ile

R E

V

IS

IO

N

I N

F O

R M

A T

IO

N

D ra w in g

D is c ip lin e

S or t:

GENERAL NOTES

CODE DATA

/1

/2

:4 :3

P

M

A u to d e s k D o c s

/3

G re a te r D a y to n R

T A

S e rv e r

R o o m

/3 G

D R

T A

S R

M

V

.r v t

C O

V E

R S

H E

E T

G-001

G R

E A

T E

R D

A Y

T O

N R

E G

IO

N

A L T

R A

N S

IT

A

U T

H O

R

IT

Y

W R

IG

H

T S

T O

P P

L A

Z A

S

M

A

IN

S T

R E

E T

D

A Y

T O

N

O H

IO

FILE NO: 3761614

S E

R V

E R

R O

O M

C O

O L

IN

G S

Y S

T E

M

SERVER ROOM COOLING SYSTEM

GREATER DAYTON REGIONAL TRANSIT AUTHORITY

WRIGHT STOP PLAZA

4 S. MAIN STREET - DAYTON, OHIO 45402

G -0

C O

V E

R S

H E

E T

DRAWING INDEX

G-001 COVER SHEET

MG1-001 MECHANICAL GENERAL NOTES AND LEGEND

MD1-101 WSP SECOND FLOOR PLAN - DEMOLITION

MD1-102 WSP ROOF PLAN - DEMOLITION

MH1-101 WSP SECOND FLOOR PLAN

MH1-102 WSP ROOF PLAN

MH3-001 WSP SECTIONS

MH4-001 WSP ENLARGED PLANS

MH5-001 DETAILS

MH8-001 CONTROL DIAGRAMS

EG1-001 ELECTRICAL LEGEND

EG1-002 WSP SCHEDULES & ELECTRICAL ONE-LINE

EH1-101 WSP SECOND FLOOR ELECTRICAL PLAN

EH1-102 WSP ROOF ELECTRICAL PLAN

A. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH

ALL CODES, STANDARDS, AND GENERAL GOOD BUILDING

PRACTICES.

B. PRIOR TO STARTING CONSTRUCTION, CONTRACTOR(S)

SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL

REQUIRED PERMITS AND APPROVAL(S) HAVE BEEN

OBTAINED. NO CONSTRUCTION OR FABRICATION OF ANY

ITEM SHALL BEGIN UNTIL THE CONTRACTOR HAS

RECEIVED ALL PLANS AND ANY OTHER DOCUMENTATION

FROM ALL OF THE PERMIT AND REGULATORY

AUTHORITIES. FAILURE OF THE CONTRACTOR(S) TO

FOLLOW THIS PROCEDURE SHALL CAUSE THE

CONTRACTOR(S) TO ASSUME FULL RESPONSIBILITY FOR

ANY SUBSEQUENT MODIFICATION OF THE WORK, IN

ADDITION TO ANY PENALTIES AND FEES MANDATED BY

ANY REGULATORY AUTHORITY.

C. ALL CONTRACTOR(S) SHALL FIELD VERIFY ALL

DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE

STARTING WORK. COMMENCEMENT OF WORK IMPLIES

ACCEPTANCE OF CONDITIONS. IF DIMENSIONS ARE IN

QUESTION, THE CONTRACTOR(S) SHALL BE RESPONSIBLE

FOR OBTAINING CLARIFICATION FROM GDRTA BEFORE

CONTINUING WITH CONSTRUCTION.

D. EACH CONTRACTOR(S) SHALL BE SOLELY RESPONSIBLE

FOR TAKING ALL STEPS NECESSARY TO PROTECT THE

PUBLIC AND BUILDING OCCUPANTS FROM INJURY AND

ADJACENT PROPERTY FROM DAMAGE DURING

CONSTRUCTION AS REQUIRED BY CODES AND GENERAL

GOOD PRACTICE. CONTRACTOR(S) SHALL POST AND

MAINTAIN SIGNS, NOTICES, AND OTHER SAFEGUARDS

REQUIRED BY LAW OR ORDINANCE.

E. THE CONTRACTOR(S) IS/ARE RESPONSIBLE TO MAINTAIN A

PROTECTED MEANS OF EGRESS DURING CONSTRUCTION.

F. IT SHALL BE THE INDIVIDUAL CONTRACTOR'S

RESPONSIBILITY TO NOTIFY GDRTA OF ANY

DISCREPANCIES IN THE PLANS AND/OR SPECIFICATIONS

PRIOR TO BIDDING AND/OR INSTALLATION OF ANY OF

THOSE ITEMS NOTED ON THE PLAN.

G. LARGE SCALE DETAILS OF DRAWINGS SHALL GOVERN

SCALE DRAWINGS FOR WHICH THEY ARE INTENDED TO

AMPLIFY. DIMENSIONS SHALL BE CALCULATED RATHER

THAN DETERMINED BY SCALE OR RULE.

H. THE CONTRACTOR(S) HAS THE RESPONSIBILITY TO NOTIFY

GDRTA OF MATERIALS OR WORK SHOWN FOR WHICH NO

QUALITY OR GRADE OR CONSTRUCTION DETAILS ARE

CLEARLY SPECIFIED. UNDER NO CIRCUMSTANCES SHALL

THE CONTRACTOR ASSUME GRADE OR QUALITY OR

CONSTRUCTION DETAILS FOR PRODUCTS OR WORK

SHOWN.

I. WHENEVER THERE IS A CONFLICT IN THE CONTRACT

DOCUMENTS REGARDING QUALITY OR QUANTITY, THE

GREATER QUALITY OR QUANTITY SHALL APPLY. ANY

ASSOCIATED HOOK-UP, CONNECTIONS, WIRING, ETC. OF

GREATER QUANTITIES SHALL BE INCLUDED IN THE WORK.

J. PATCH AND REPAIR ALL FINISHES DISTURBED AS A

RESULT OF NEW CONSTRUCTION. RESTORE PORTIONS

OF THE BUILDING AND/OR SITE TO CONDITIONS AS THEY

EXISTED PRIOR TO COMMENCEMENT OF CONSTRUCTION.

K. COORDINATE PHASING AND SEQUENCING OF

CONSTRUCTION WORK WITH GDRTA.

SUMMARY OF WORK

THE WORK IS GENERALLY LIMITED TO SERVER ROOM HVAC

UNIT REPLACEMENT AND ASSOCIATED ELECTRICAL TO

SUPPORT THE NEW WORK, UNLESS OTHERWISE NOTED IN

THESE DOCUMENTS.

THIS PROJECT IS NOT A CHANGE IN USE.

EXISTING USE GROUPS: A-3, B, AND E

EXISTING CONSTRUCTION TYPE: 2C

PROJECT LOCATION

R E

V D

R C

H K

D A

T E

D

E S

C R

IP

T

IO

N

5/16/2025

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

FURNISH LABOR, INSTALL MATERIALS AND EQUIPMENT, AND INCLUDE SERVICES AND

INCIDENTALS PROPER TO THE INSTALLATION OF WORK INVOLVED FOR A COMPLETE AND

OPERATING FACILITY.

GUARANTEE WORK TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP FOR A

PERIOD OF ONE YEAR AFTER DATE OF FINAL ACCEPTANCE OR AS REQUIRED BY

SPECIFICATIONS.

THE CONTRACTOR TO OBTAIN AND PAY FOR REQUIRED PERMITS, FEES AND

INSPECTIONS FOR THE PROJECT.

PROVIDE EQUIPMENT THAT BEARS ACCEPTANCE LABEL FROM CERTIFIED TESTING

LABORATORY (UL OR OTHER).

COORDINATE WITH OTHER TRADES, SPECS AND DRAWINGS, AND OWNER'S DIRECTIONS.

PRIOR TO BID, SURVEY JOB SITE TO OBTAIN A FULL UNDERSTANDING OF THE WORK

INVOLVED IN CONNECTION WITH EXISTING CONDITIONS. ADDITIONAL FEES WILL NOT BE

PAID FOR MISSING OR OVERLOOKED CONDITIONS REQUIRING ADDITIONAL WORK IF

DETERMINED BY THE ENGINEER THAT SAID CONDITIONS COULD HAVE BEEN

REASONABLY DETECTED DURING THE JOB SURVEY.

EQUIPMENT SELECTION AS SHOWN ON THE DRAWING IS FOR DESIGN PURPOSES ONLY.

ACTUAL INSTALLED EQUIPMENT MAY DIFFER FROM THAT SHOWN. EQUIPMENT

PERFORMANCE CHARACTERISTICS AND TYPE ARE THE GOVERNING FACTORS IN

SUBSTITUTION "OR EQUAL". COORDINATE EQUIPMENT ELECTRICAL REQUIREMENTS WITH

ELECTRICAL DRAWINGS.

THE MECHANICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC AND SHOW THE

RELATIONSHIP BETWEEN EQUIPMENT AND CONNECTIONS. DO NOT SCALE THE

DRAWINGS FOR EXACT SIZE OR LOCATION. DETAILS AND ASSEMBLY DRAWINGS ARE

SPECIFIC AND SHOULD BE CLOSELY FOLLOWED.

INSTALL THE MECHANICAL SYSTEM IN ACCORDANCE WITH THE MANUFACTURER'S

RECOMMENDATION, 2024 OHIO BUILDING CODE, 2024 OHIO PLUMBING CODE, 2024 OHIO

MECHANICAL CODE, ETC.

INSTALL SLEEVES WHERE DUCTS OR PIPING PENETRATE FOUNDATION WALLS,

PARTITIONS, FLOOR OR ROOF. PACK AROUND SLEEVES AND SEAL WEATHER TIGHT.

INSTALL FLASHING AS REQUIRED.

UNLESS OTHERWISE NOTED, MOUNT WALL THERMOSTATS AT 4'-6" ABOVE FINISHED

FLOOR .

INTEGRATE EQUIPMENT MANUFACTURER PROVIDED CONTROLS WITH BAS IN

ACCORDANCE WITH SPECIFICATIONS AND MANUFACTURER'S RECOMMENDATIONS.

COORDINATE THE LOCATIONS OF EQUIPMENT TO PROVIDE NECESSARY CLEARANCES

FOR MAXIMUM PERFORMANCE AND MAINTENANCE.

SIZE REFRIGERANT LINES IN ACCORDANCE WITH DX EQUIPMENT MANUFACTURERS'

RECOMMENDATION, ASHRAE STANDARDS, APPLICABLE DETAILS AND SPECIFICATIONS,

WHERE CONDITIONS WARRANT, CONSIDER LENGTH OF RUN AND CHANGE IN ELEVATION

IN SIZING REFRIGERANT LINES. REFRIGERANT PIPE SIZES ON DRAWING ARE SHOWN FOR

REFERENCE ONLY.

GENERAL NOTES (MECHANICAL):

SUPPLY AIR CEILING DIFFUSER

RETURN AIR GRILLE / REGISTER

SIDEWALL SUPPLY AIR GRILLE/REGISTER

SIDEWALL RETURN AIR GRILLE/REGISTER

DUCT MT'D. SIDEWALL SUPPLY AIR GRILLE/REGISTER

SUPPLY DUCT RISE/DROP

RETURN DUCT RISE/DROP

EXHAUST DUCT RISE/DROP

TEMPERATURE / HUMIDITY SENSOR

SQUARE ELBOW WITH DOUBLE THICKNESS TURNING VANES

EMERGENCY POWER OFF SWITCH

DESCRIPTION ABBV.SYMBOL

HVAC LEGEND

FLEX.CONN.FLEXIBLE DUCT CONNECTOR

NEW DUCTWORK

EXISTING DUCTWORK TO BE REMOVED

EXISTING DUCTWORK TO REMAIN

MANUAL VOLUME DAMPER MVD

TS/HS

EPO

SUPPLY AIR

RETURN AIR

ABOVE FINISHED FLOOR

BOTTOM OF DUCT

CONNECT TO EXISTING

NOTE: DUCT RUNOUT TO

NECK SAME SIZE UNLESS

OTHERWISE NOTED

SA

RA

AFF

B.O.D.

DIFFUSER SCHEDULE

DIFFUSER NECK SIZE

CFM

##"Ø X-#

CFM

AIRFLOW DIRECTION SUPPLY

AIRFLOW DIRECTION RETURN / EXHAUST

THERMOSTATT

DESCRIPTION ABBV.SYMBOL

PIPING LEGEND

DCWDOMESTIC COLD WATER

CDCONDENSATE DRAIN

PIPE TURNED UP/DOWN

CAP OR PLUG

TEE

ELBOW

I.E. I.E.INVERT ELEVATION

HGREFRIGERANT LINE - HOT GAS

RLREFRIGERANT LINE - RETURN LINE

1.

2.

3.

4.

5.

6.

7.

8.

9.

COORDINATE ALL PHASES OF DEMOLITION WORK CLOSELY WITH OWNER. PROVIDE

OWNER WRITTEN NOTICE NO LESS THAN TEN (10) CALENDAR DAYS PRIOR TO

SHUTDOWN OF ANY PORTION OF MECHANICAL SYSTEM IN USE BY THE OWNER.

MAINTAIN DUST FREE SERVER ROOM DURING CONSTRUCTION. PROTECT ALL EXISTING

EQUIPMENT.

REMOVE AND DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN A MANNER

CONFORMING TO STATE AND LOCAL REGULATIONS AND AT NO ADDITIONAL EXPENSE TO

THE OWNER.

SCOPE OF DEMOLITION OF MATERIALS IDENTIFIED ON PLAN INCLUDES ANY ASSOCIATED

AUXILIARY MATERIAL NOT TO BE RE-USED. THIS INCLUDES, BUT IS NOT LIMITED TO:

INSULATION, HANGARS, MOUNTING BRACKETS, HANGAR ROD, CONDUIT, AND

CONDUCTORS.

DEMOLISH EXISTING CONTROLS MADE INOPERABLE BY SCOPE OF DEMOLITION. TURN

OVER CONTROL COMPONENTS TO OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO:

EQUIPMENT CONTROL PANELS, SENSORS, ACTUATORS, RELAYS, AND METERS.

WHERE SCOPE OF DEMOLITION WORK RESULTS IN AN OPEN WALL, FLOOR, OR ROOF

PENETRATION, PATCH OPENING WITH CONSTRUCTION MATCHING EXISTING ASSEMBLY

CONSTRUCTION OR AS APPROVED BY OWNER. WHERE ASSEMBLY IS FIRE RATED, PATCH

OPENINGS WITH U.L. LISTED METHOD THAT MAINTAINS FIRE RATING OF ASSEMBLY.

PRIOR TO DEMOLITION OF REFRIGERANT-CONTAINING EQUIPMENT, RECOVER AND

DISPOSE OF REFRIGERANT IN ACCORDANCE WITH EPA REQUIREMENTS. REFRIGERANT

RECOVERY SHALL BE PERFORMED BY AN EPA-LICENSED TECHNICIAN.

SERVER ROOM WALL & CEILING DEMOLITION AND REPAIR : AT NO ADDITIONAL COST TO

OWNER, ENGAGE THE SERVICES OF LICENSED CONTRACTOR TO REMOVE, RE-INSTALL,

AND PATCH GYPSUMBOARD WALL AND CEILING ASSEMBLIES IN SERVER ROOM. REMOVE

AND PATCH WALLS AND CEILINGS ONLY AS NEEDED TO IMPLEMENT DUCTWORK

DEMOLITION AND INSTALLATION OF NEW MECHANICAL DUCT AND PIPE. MAINTAIN

EXISTING RATED ASSEMBLIES. FINISH WALLS AND CEILINGS TO MATCH EXISTING

ASSEMBLIES. UPON COMPLETION OF WALL AND CEILING REPAIRS, PAINT PATCHED

CEILING AND WALLS TO MATCH ADJACENT ASSEMBLIES.

ROOF DEMOLITION AND REPAIR: AT NO ADDITIONAL COST TO OWNER, ENGAGE THE

SERVICES OF A LICENSED ROOFER TO REMOVE, RE-INSTALL, AND PATCH ROOM AS

NEEDED TO IMPLEMENT SCOPE OF WORK. ROOF PATCHING MEANS AND METHODS

SHALL CONFORM TO ANY ROOFING WARRANTY REQUIREMENTS.

GENERAL NOTES (DEMOLITION):

CRAC UNIT SCHEDULE

IDENT.

MANUFACTURER

MODEL NUMBER

TONS CFM ESP FAN HP

FILTER COOLING CAPACITY DX COOLING COIL REHEAT COIL INDOOR ELECTRICAL OUTDOOR ELECTRICAL WEIGHT (LBS)

REMARKS

AIR HANDLER COND. UNIT INDOOR UNIT OUTDOOR UNIT TYPE EFF TMBH SMBH AMBIENT

(DEG. F) REF TYPE SST KW STAGES FLA V/PH/HZ MOCP FLA V/PH/HZ MOCP INDOOR OUTDOOR

CRAC-1 ACCU-1 Vertiv/Liebert PX029DA1C809FV MCL055E1YD0WKQ 8 4300 0.5 4.15 2" PLEATED MERV 8 101 84 75 R-410A - 12 2 76.2 208/3/60 100 5.7 208/3/60 15 700 373 1,2,3,4,5,6,7,8,9,10,11,12,13,14

REMARKS:

1. LIEBERT ICOM CONTROLS, WITH WALL MOUNTED THERMOSTAT

2. DIGITAL SCROLL COMPRESSOR WITH VARIABLE SPEED EC FAN

3. UPFLOW TOP DISCHARGE MODEL WITH FLOOR RETURN

4. PROVIDE 24 INCH RETURN PLENUM STAND

5. FACTORY PROVIDED AND FIELD INSTALLED CONDENSATE PUMP POWERED BY UNIT

6. UNIT SMOKE DETECTOR AND CONTROLLER TO BE HARDWIRED TO THE RELEASING SYSTEM FIRE ALARM CONTROL PANEL

7. LOCKABLE DISCONNECT SWITCH

8. PROVIDE NETWORK INTERFACE CARD (BACNET) FOR FUTURE TIE-IN TO BUILDING MANAGEMENT CONTROL SYSTEM

9. MICROPROCESSOR BASED TEMPERATURE AND HUMIDITY CONTROLS

10. EXTERNAL STATIC PRESSURE (ESP) INCLUDES DIRTY FILTER LOSS

11. TOP SUPPLY PLENUM AND REAR RETURN PLENUM

12. PROVIDE AUXILIARY FLOAT SWITCH WITH AUTOMATIC UNIT SHUTOFF

13. UNIT POWER CONNECTED TO WALL MOUNTED EPO SWITCH

14. SYSTEM START-UP AND COMMISSIONING TO BE PROVIDED BY FACTORY

15. REMOTE HUMIDIFIER CONTACT

AIR DEVICE SCHEDULE

TAG DESCRIPTION MANUFACTURER MODEL NUMBER TYPE SIZE MOUNT NECK TYPE MAX NC LEVEL REMARKS

SG-1 SUPPLY GRILLE TITUS 300FL RECTANGULAR GRILLE, DOUBLE DEFLECTION

3/4" SPACING 24" X 12" DUCT RECTANGULAR 25 1,2,3,4

RG-1 RETURN GRILLE TITUS 350FL RECTANGULAR GRILLE, LOUVERED 3/4"

SPACING 24" X 16" DUCT RECTANGULAR 15 1,3,4

REMARKS

1. WHITE ENAMEL FINISH

2. ADJUSTABLE THROW DIRECTION

3. ALUMINUM CONSTRUCTION

4. NECK DAMPER

HUMIDIFIER SCHEDULE

AIRFLOW (CFM) DUCT SIZE W X H (IN)

WATER

CAPACITY

(LBS/HR)

EAT LAT ELECTRIC DATA

WEIGHT (LBS)

TAG DESCRIPTION LOCATION MANUFACTURER MODEL NUMBER SERVICE DB (F) WB (F) DB (F) WB (F) FLA V/PH/HZ REMARKS

H-1 ELECTRODE STEAM HUMIDIFIER MECHANICAL ROOM DRISTEEM XTP WSP 233 - 9 10.2 60.4 70.0 66.0 19 208/1/60 37 1,2,3,4

REMARKS:

1. PROVIDE STEAM DISPERSION UNIT REMOTE MOUNTED IN SERVER ROOM, MODEL NUMBER SDU-E (208/1/60, 17W)

2. PROVIDE NETWORK INTERFACE (BACNET) FOR FUTURE TIE-IN TO BUILDING MANAGEMENT CONTROL SYSTEM

3. HIGH LIMIT HUMIDITY TRANSMITTER IN SERVER ROOM

4. 1" DIAMETER STEAM HOSE

V

AN

G

UA

RD

B

LV

D M

IA

M

IS

BU

RG

, O H

PH

O

NE

(9 ) 4 -0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

5/ /2 9:

:3

AM

Au to de sk D oc s:

//3 G re at er D ay to n R

TA

S er ve r R oo m /3 _G D R

TA

SR

_M _V .rv t

M

EC

HA

NI

CA

L G

EN

ER

AL

N O

TE

S

AN

D

LE

G

EN

D

MG1-001

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R O O M C O O

LI

NG

S

YS

TE

M

M G 1- 1, M

EC

HA

NI

CA

L G

EN

ER

AL

N O

TE

S

AN

D

LE

G

EN

D

- G

EN

ER

AL

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

IO

N:

X1

MECHANICAL

ROOM

MEZZANINE

ELECTRICAL

ROOM

HALLWAY

KITCHEN & BREAK

ROOM

WOMEN'S

RESTROOM

MEN'S

RESTROOM

MIS

STAFF

DEMOLISH 3-TON

CRAC AND

ASSOCIATED PIPING

DEMOLISH 12" DIA

DUCT AND DIFFUSERS

(BOD = 8'-10")

EXISTING 1-HOUR FIRE-

RATED WALL. PATCH WALL

TO MATCH EXISTING

ASSEMBLY.

DEMOLISH ELEVATED 18"x18" DUCT

DEMOLISH 36"x24" GRILLE

SERVER ROOM

UP TO ROOF

DEMOLISH REFRIGERANT PIPING

UNIT HANGS FROM

OVERHEAD

STRUCTURE

FLOOR DRAIN

KEY PLAN

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

GENERAL NOTES

PLAN NORTH

5/

/2

9:

:3

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

W

SP

S

EC

O

ND

F

LO

O R

PL

AN

DE

M O

LI

TI

O N

MD1-101

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M D1

-1

W

SP

S

EC

O

ND

F

LO

O

R

PL

AN

DE

M

O

LI

TI

O

N

- D

EM

O

SCALE: 1/4" = 1'-0"MD1-101

1 WSP SECOND FLOOR PLAN - DEMOLITION

1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

DEMOLISH CONDENSING UNIT

DEMOLISH

REFRIGERANT PIPING

RETAIN PIPE

SUPPORTS FOR NEW

WORK PIPING.

DEMOLISH

DOGHOUSE

ABANDON SUPPORT RAIL IN

PLACE.

KEY PLAN

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

GENERAL NOTES

PLAN NORTH

5/

/2

9:

:3

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

W

SP

R O

O F

PL

AN

DE

M O

LI

TI

O N

MD1-102

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M D1

R

O O

F

PL

AN

DE

M

O

LI

TI

O

N

- D

EM

O

SCALE: 1/4" = 1'-0"MD1-102

1 WSP ROOF PLAN - DEMOLITION

1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

MECHANICAL

ROOM

MEZZANINE

ELECTRICAL

ROOM

HALLWAY

KITCHEN & BREAK

ROOM

WOMEN'S

RESTROOM

MEN'S

RESTROOM

MIS

STAFF

CRAC-1

H-1

EXISTING FLOOR DRAIN

HUMIDIFIER

DISPERSION UNIT

SERVER ROOM

MH4-001

UP TO ROOF

"x

" S

A

24"x18" SA

22"x24" RA

RG-1

RG-1

RG-1

RG-1

3/4" RL

1 1/8" HG

SG-1

SG-1

SG-1

SG-1

HG PIPE TO BE 7/8" IN VERTICAL

3/4" CD

RUNS ACROSS

FLOOR

PIPING FOLLOWS PATH OF

EXISTING PIPE.

KEY PLAN

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

GENERAL NOTES

PLAN NORTH

5/

/2

9:

:4

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

W

SP

S

EC

O

ND

F

LO

O R

PL

AN

MH1-101

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M H1

S

EC

O

ND

F

LO

O

R

PL

AN

PL

AN

S

SCALE: 1/4" = 1'-0"MH1-101

1 WSP SECOND FLOOR PLAN

1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

ACCU-1

EQUIPMENT CLEARANCE

1 1/8" HG

3/4" RL

PROVIDE NEW

DOGHOUSE

SUPPLEMENT EXISTING PIPE SUPPORTS

WITH NEW PRE-FAB NO-PENETRATION

TYPE SUPPORTS. MAXIMUM SUPPORT

SPACING SHALL BE 5 FEET O.C.

MOUNT ON NEW

EQUIPMENT RAILS

REFER TO

DETAIL

8/MH5-001

REFRIGERANT PIPING

PENETRATES ROOF AT

EXISTING PENETRATION

REFER TO DETAIL

6/MH5-001

KEY PLAN

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

GENERAL NOTES

PLAN NORTH

5/

/2

9:

:4

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

W

SP

R O

O F

PL

AN

MH1-102

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M H1

R

O O

F

PL

AN

PL

AN

S

SCALE: 1/4" = 1'-0"MH1-102

1 WSP ROOF PLAN

1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

CRAC-1

MAINTENANCE CLEARANCE

TYPICAL

MANUFACTURER

PROVIDED SUPPLY

PLENUM

MANUFACTURER PROVIDED

RETURN PLENUM

22"x24" RA

18"x30" SA

SG-1

12"x24" SA

18"x24" SA

12"x24" SA

SG-1

MH3-001

SERVER RACK

WORK STATION

RG-1

FLEXIBLE CONNECTION

FLEXIBLE CONNECTION

MH3-001

HUMIDIFIER

DISPERSION UNIT

RG-1

RG-1RG-1RG-1

24"x22" RA

CRAC-1

SERVER RACK

30"x18" SA

8' -4

"M

IN

PIPING CONTINUES

THROUGH EXISITING

WALL OPENING

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

5/

/2

9:

:4

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

W

SP

S

EC

TI

O

NS

MH3-001

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M H3

-0

S

EC

TI

O

NS

SE

CT

IO

NS

SCALE: 1/2" = 1'-0"MH3-001

1 WSP SERVER ROOM SECTION 1

SCALE: 1/2" = 1'-0"MH3-001

2 WSP SERVER ROOM SECTION 2

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

RG-1

RG-1

RG-1

RG-1

24"x16" RA

22"x24" RA

H-1

HUMIDIFIER

DISPERSION UNIT

CRAC-1

MAINTENANCE CLEARANCE

TYPICAL

24"x18" SA

30"x18" SA

SG-1

SG-1

SG-1

SG-1

SERVER RACKS

WORK STATION

RELOCATE

CAMERA. FINAL

LOCATION TO BE

APPROVED BY

RTA.

TIE IN TO EXISTING DCW

SERVER ROOM

MH3-001

MH3-001

DISCHARGE NOZZLE TO

BE LOCATED 8'-0" AFF

HT

RELOCATE CABLE TRAY HANGERS

MAINTAIN CLEARANCE FOR

CEILING ACCESS PANEL

1/2" CD

1 1/8" HG3/4" RL

3/8" DCW

3/4" CD

1/4" CD

1" DCW

CONTINUE REFRIGERANT

PIPING TO ROOF

TYPICAL

CONTINUE TO FLOOR DRAIN

PIPE PASSES THROUGH

WALL OPENING CREATED

BY DEMOLISHED DUCT.

SLEAVE AND SEAL AT

RATED ASSEMBLY PER

DETAILS ON SHEET

MH5-001.

PIPE PASSES THROUGH

EXISTING 1-HR RATER

WALL OPENING CREATED

BY DEMOLISHED DUCT

(SEE SHEET MD1-101).

SLEAVE AND SEAL AT

RATED ASSEMBLY PER

DETAILS ON SHEET

MH5-001.

KEY PLAN

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

GENERAL NOTES

PLAN NORTH

5/

/2

9:

:4

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

W

SP

E

NL

AR

G

ED

P

LA

NS

MH4-001

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M H4

-0

E

NL

AR

G

ED

P

LA

NS

EN

LA

RG

ED

PL

AN

S

SCALE: 1/2" = 1'-0"MH4-001

1 WSP SECOND FLOOR ENLARGED PLAN

1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

NOTE:

THE ASSEMBLY IS BASED ON U.L. PENETRATION ASSEMBLY WALL C-AJ-5001.

INSTALL PENETRATION IN ACCORDANCE WITH IT'S LISTING.

PIPE MAY BE:

12" DIAMETER OR SMALLER SCHEDULE 10 OR HEAVIER STEEL PIPE. 4"

DIAMETER OR SMALLER COPPER PIPE (TYPE L OR HEAVIER).

12" DIAMETER OR SMALLER SERVICE WEIGHT OR HEAVIER CAST IRON

PIPE.

INSULATED PIPE

ESCUTCHEON

WHERE EXPOSED

TO VIEW

1" THICK FIBERGLASS

PIPE INSULATION

THROUGH WALL

MINIMUM 1" THICK

MINERAL WOOL BATT

INSULATION

MINIMUM 1" THICK FIRE

BARRIER CAULKING

PIPE SLEEVE

1/2" TO 1 1/2"

ANNULAR SPACE

NOTE:

THE ASSEMBLY IS BASED ON U.L. PENETRATION ASSEMBLY C-AJ-1175.

INSTALL PENETRATION IN ACCORDANCE WITH IT'S LISTING

PIPE MAY BE:

8" DIAMETER OR SMALLER SCHEDULE 10 OR HEAVIER STEEL PIPE. 6"

DIAMETER OR SMALLER COPPER PIPE (TYPE L OR HEAVIER).

4" DIAMETER OR SMALLER CAST IRON PIPE.

UNINSULATED PIPE

ESCUTCHEON

WHERE EXPOSED TO

VIEW

MINIMUM 1" THICK MINERAL

WOOL BATT INSULATION

MINIMUM 1/2" THICK FIRE BARRIER CAULKING. IN

ADDITION, APPLY MINIMUM OF 1/4" BEAD OF CAULK AT

POINT OF CONTACT TO WALL (BOTH SIDES)

THROUGH WALL

PIPE SLEEVE

1 3/8" MAXIMUM

ANNULAR SPACE

HANGER ROD

ADJUSTABLE

CLEVIS MSS

SP-58 TYPE 1

ANVIL FIG. 260

OR EQUAL.

LOCK NUT

PIPE

HANGER ROD

ADJUSTABLE

CLEVIS MSS

SP-58 TYPE 1

LOCK NUT

PIPE

INSULATION

PROTECTION

SHIELD (180°)

MSS SP-58

TYPE 40

HIGH DENSITY ASBESTOS FREE

INSULATION, VAPOR BARRIER SEALED,

CONTINUOUSLY

NOTE:

VAPOR BARRIER SHALL EXTEND 2 INCHES BEYOND THE

PROTECTION SHIELD AND OVERLAP THE OUTSIDE

CIRCUMFERENCE BY 2 INCHES.

FOR PIPE SIZES TO: 20"

TEMPERATURES TO: 100° F. MAXIMUM

AXIAL MOVEMENT: 1"

FOR PIPE SIZES TO: 20"

TEMPERATURES TO: 100° F. MAXIMUM

AXIAL MOVEMENT: 1"

BARE PIPE INSULATED COLD PIPE

HANGER STRAPS

STRAPS TO BE TIGHT AGAINST DUCT

SELF TAPPING CADMIUM PLATED HEX

HEAD SHEET METAL SCREWS (TYP.)

SUPPORT ANGLE

(SEE NOTE 1)

HANGER ROD,

(SEE NOTE 1).

NOTE 1:

SEE SMACNA "HVAC DUCT CONSTRUCTION STANDARDS-

METAL AND FLEXIBLE" CHAPTER 5, FOR MINIMUM HANGER

SIZE AND SUPPORT SPACING FOR RECTANGULAR DUCT.

1/4"x1/4" HEX HEAD

LAG BOLT (WOOD

TRUSS ONLY)

TRUSS CORD OR

ROOF SUPPORT MEMBER

LOCK -NUT & WASHER

SCORE THREADS

(BAR-JOIST ONLY)

INSULATION

TRAPEZE TYPE HANGER STRAP TYPE HANGER

INSULATION

SIDE VIEW END SECTION VIEW

NOTE:

L=1/4 W (4" MIN.)

AIR FLOW

CLINCH COLLAR

(PER SMACNA)

BALANCING DAMPER

(AIR EXTRACTOR IS NOT REQUIRED WITH 45° COLLAR FITTING)

45°

W

L

RETURN

SUPPLY

VA

R

IE

S

(8 " T

AL

L

M

IN

IM

U

M

SPACING AS REQUIRED FOR UNIT DIMENSIONS

6" WIDE (NOMINAL)

4" TALL WOOD

NAILER (MINIMUM)

ATTACH CU TO SUPPORT RAILS

TO ANCHOR EQUIPMENT AND

RESIST WIND FORCES MINIMUM

TEK 1/4"-20 SDS @ 12"

JOIST PERPENDICULAR TO RAIL

ROOFING

EXTEND ROOF

MEMBRANE OVER

RAIL.

PREFABRICATED ROOF RAILS

ATTACH TO METAL DECK AND

JOIST WITH SUPPLIER SPECIFIED

CONNECTIONS. MINIMUM TEK

1/4"-20 SDS @12" ON ALL SIDES OF

EACH RAIL.

PROVIDE RAIL CAP. LENGTH OF

RAIL AS REQUIRED FOR

CONDENSING UNIT DIMENSIONS.

EACH END OF RAIL SHALL

EXTEND TO NEAREST JOIST.

TIMBER BLOCKING (TYP.)

L6x4x5/16 LLH SUPPORT

ANGLE (TYP.)

EXISTING

ROOF DECK

JOIST TOP

CHORD

3/16

20 GAUGE GALVANIZED SHEET

METAL WELDED WEATHERHOOD

WITH 1 1/2" THICK POLYISO

INSULATION

24" MIN.

D

EG

1" # 8 SCREW,

MIN. 2 PER SIDE

18"x18"x30" HIGH

MANUFACTURED

ROOF CURB

FILL SPACE WITH

INSULATION

ROOF

PIPES

PENETRATE

ROOF CURB

WITH PIPES

FRAME OPENING WITH

2 1/2"x2 1/2"x5/16"

ANGLE STEEL WELDED

TO ROOF FRAMING

SEE ARCHITECTURAL

DRAWINGS FOR ROOF

PENETRATION DETAIL

HUMIDIFIER

STEAM

GENERATOR

HUMIDIFIER

DISPERSION UNIT

12" MINIMUM

1" AIR GAP

3/4" DRAIN PITCH 1/8" PER FT

TOWARD DRAIN

3/4" DCW SUPPLY

CONDENSATE HOSE

WATER SEAL

DISCHARGE TO

OPEN DRAIN

1" MFG SUPPLIED

STEAM HOSE

HOSE CLAMP

PROVIDE COPPER TUBING

FOR PENETRATION OF 1-HR

RATED ASSEMBLYCONDENSING UNIT

INCLUDES FACTORY

PROVIDED INVERTED

TRAP. NO EXTERNAL

TRAP REQUIRED.

PRESSURE

TRANSDUSER

LIQUID

OPTIONAL FIELD

INSTALLED

FUSIBLE PLUG

HOT GAS

DISCHARGE

INTERCONNECTING

PIPING

TRAP AT BASE

OF RISERS OVER

5FT.

FOR RISERS OVER

25FT., TRAP EVERY 20

FT. OR EVENLY

DIVIDED.

CRAC

(EVAPORATOR)

1.

2.

NOTES:

TRAPS MUST BE INSTALLED AND HORIZONTAL LINES PITCHED TO

ENSURE PROPER OIL RETURN AND TO REDUCE LIQUID

FLOODBACK TO COMPRESSOR. PITCH HORIZONTAL HOT GAS

PIPING AT A MINIMUM OF 1/2" PER 10 FEET SO THAT GRAVITY WILL

AID IN MOVING OIL IN THE DIRECTION OF THE REFRIGERATION

FLOW.

DO NOT ISOLATE ANY REFRIGERANT CIRCUITS FROM OVER

PRESSURIZATION PROTECTION.

V

AN

G

UA

RD

B

LV

D

M

IA

M

IS

BU

RG

, O

H

PH

O

NE

(9

) 4

-0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O

N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

5/

/2

9:

:4

AM

Au to de sk

D oc s:

//3

G re at er

D ay to n

R

TA

S er ve r R oo m

/3

_G D

R

TA

SR

_M

_V

.rv t

DE

TA

IL

S

MH5-001

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R

O O

M C

O O

LI

NG

S

YS

TE

M

M H5

-0

DE

TA

IL

S

- D

ET

AI

LS

NTSMH5-001

2 FIRE RATED PIPE PENETRATION (INSULATED PIPE)

NTSMH5-001

3 FIRE RATED PIPE PENETRATION (UNINSULATED PIPE)

NTSMH5-001

1 PS-X CLEVIS HANGER

NTSMH5-001

4 DUCT HANGER SUPPORT

NTSMH5-001

5 BRANCH DUCT CONNECTION

NTSMH5-001

8 ROOFTOP EQUIPMENT SUPPORT RAIL DETAIL

NTSMH5-001

6 PIPE PENETRATION THRU ROOF

NTSMH5-001

9 HUMIDIFIER PIPING DIAGRAM

NTSMH5-001

7 REFRIGERANT PIPING DIAGRAM

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

T

TT TT

BINARY INPUT

BINARY OUTPUT

ANALOG INPUT

CONTROLS ABBREVIATION

DESCRIPTION

BI

BO

AI

ABBV.

ANALOG OUTPUT

SUPPLY AIR

RETURN AIR

AO

SA

RA

TEMPERATURE T

VARIABLE FREQUENCY DRIVEVFD

BUILDING AUTOMATION SYSTEMBAS

DESCRIPTIONSYMBOL

CONTROLS LEGEND

THERMOSTAT

HUMIDISTAT

T

H

CENTRIFUGAL FAN

E

C

DX

C

ELECTRIC COIL

DX COOLING COIL

AIR FILTER

DUCT TEMPERATURE SENSOR

1. GENERAL:

THE COMPUTER ROOM AIR HANDLING (CRAC) UNIT CONSISTS OF RETURN AIR FILTERS, DX COOLING

COIL, ELECTRIC REHEAT COIL, AND SUPPLY FAN.

THE COMPUTER ROOM AIR HANDLING UNIT SHALL BE CONTROLLED THROUGH A FACTORY

PROGRAMMED APPLICATIONS CONTROLLER.

THE CRAC UNIT SHALL OPERATE AS A SINGLE ZONE VARIABLE AIR VOLUME UNIT.

THE CRAC UNIT SHALL OPERATE AS NECESSARY TO SATISFY SPACE TEMPERATURE SETPOINTS 24/7.

SPACE TEMPERATURE SETPOINT SHALL BE 74°F (ADJUSTABLE) FOR COOLING AND 70°F (ADJUSTABLE)

FOR HEATING.

THE CRAC UNIT SHALL OPERATE AS NECESSARY TO SATISFY MAXIMUM HUMIDITY SETPOINTS 24/7.

SPACE MAXIMUM HUMIDITY SETPOINT SHALL BE 65%RH (ADJUSTABLE). ANY REQUIREMENT TO

INCREASE HUMIDITY MUST BE MET BY THE STAND ALONE HUMIDIFIER.

ALL ALARMS SHALL BE MONITORED BY THE CRAC UNIT CONTROLLER AND SIGNALED TO THE DDC

FRONT END.

2. SUPPLY FAN:

OPERATION:

IN COOLING OR DEHUMIDIFICATION MODE, AND UPON A CALL FOR COOLING, THE SUPPLY FAN VFD SHALL BEGIN OPERATION AT 30% AND MODULATE BETWEEN 30% AND 100% AS NEEDED TO MAINTAIN

THE SPACE TEMPERATURE SETPOINT.

IN HEATING MODE, AND UPON A CALL FOR HEATING, THE SUPPLY FAN VFD SHALL BEGIN OPERATION

AT 50% AND MODULATE BETWEEN 50% AND 100% AS NEEDED TO MAINTAIN THE SPACE

TEMPERATURE.

SUPPLY FAN OPERATION SHALL BE VERIFIED THROUGH UNIT CONTROLLER. IF THE SUPPLY FAN IS

NOT OPERATIONAL, THE UNIT CONTROLLER SHALL SIGNAL AN ALARM TO THE DDC PANEL.

3. DX COOLING COIL:

OPERATION:

COMPRESSOR SHALL MODULATE TO MAINTAIN LEAVING COIL TEMPERATURE SETPOINT OF 55°F

(ADJUSTABLE). ALARM SHALL BE SENT TO THE DDC IF THE SUPPLY AIR TEMPERATURE DROPS BELOW

40°F (ADJUSTABLE). MANUAL RESET IS REQUIRED.

4. ELECTRIC REHEAT COIL:

OPERATION:

ELECTRIC REHEAT COIL SHALL BE STAGED TO MAINTAIN SPACE TEMPERATURE OR SPACE RELATIVE HUMIDITY SETPOINT. ALARM SHALL BE SENT TO THE DDC IF THE SUPPLY AIR TEMPERATURE DROPS BELOW 40°F (ADJUSTABLE). UNIT SHALL SHUT UPON ALARM SIGNAL BEING SENT. MANUAL RESET IS

REQUIRED.

SEQUENCE OF OPERATION - CRAC-1/ACCU-1:

5. HUMIDITY CONTROL:

UPON DROP IN SPACE HUMIDITY BELOW 45% (ADJ.), REMOTE HUMIDITY CONTACTOR SHALL CLOSE TO

ENABLE HUMIDIFICATION BY REMOTE HUMIDIFIER (H-1).

6. FILTER MAINTENANCE:

DIFFERENTIAL PRESSURE SWITCH WITH SENSOR TAPS ON UPSTREAM AND DOWNSTREAM SIDE OF

THE MAIN FILTER BANKS SHALL SIGNAL CRAC UNIT CONTROLLER WHEN THE DIFFERENTIAL RESSURE IS EQUAL TO OR GREATER THAN THE SET POINT OF 0.5 IN WG. THE CONTROLLER SHALL INITIATE A

MAINTENANCE ALARM SIGNAL INDICATING A DIRTY FILTER.

7. FIRE ALARM SIGNAL:

ANY SIGNAL FROM THE FIRE ALARM SYSTEM DEDICATED TO THE SERVER ROOM SHALL DE-ENERGIZE

THE SUPPLY FAN, AND NOTIFY THE DDC SYSTEMS. THE DDC SYSTEM SHALL RETURN ALL

CONTROLLED ITEMS TO THEIR SHUTDOWN POSITION. MANUAL RESET IS REQUIRED.

8. BAS MONITORING POINTS:

AT TIME OF INSTALLATION, A DDC SYSTEM WILL NOT BE AVAILABLE TO CONNECT TO; HOWEVER, PROVISIONS SHOULD BE MADE FOR FUTURE CONNECTION. ONCE A DDC SYSTEM IS AVAILABLE, THE CRAC UNIT CONTROLLER SHALL COMMUNICATE THE FOLLOWING POINTS TO BE MONITORED BY THE

DDC SYSTEM VIA A BACNET PROTOCOL:

· SPACE TEMPERATURE

· SPACE HUMIDITY

· ALARM STATUS (GENERAL)

· COMPRESSOR PERCENTAGE

· ELECTRIC REHEAT COIL LEAVING AIR TEMPERATURE

· UNIT LEAVING AIR TEMPERATURE

9. ALARMS:

THE CRAC UNIT CONTROLLER SHALL BE ABLE TO COMMUNICATE THE FOLLOWING ALARMS TO THE

DDC SYSTEM:

· SUPPLY FAN FAILURE

· HIGH SUPPLY AIR TEMPERATURE ALARM (120°F) (ADJUSTABLE)

· LOW SUPPLY AIR TEMPERATURE ALARM (40°F) (ADJUSTABLE)

· HIGH SPACE TEMPERATURE ALARM (85°F) (ADJUSTABLE)

· DIRTY FILTER ALARM

· FIRE ALARM SIGNAL

VFD

DX

C

SUPPLY

AIR

RETURN

AIR

DPS

FACTORY

MOUNTED

INTEGRAL

CONTROLS

BI BICOMPUTER ROOM AIR

HANDLING UNIT

E

C

AI

AO AOBO

T

AI

SPACE

TEMPERATURE

SENSOR

OUTDOOR

CONDENSER

COMPRESSOR

H

AI

SPACE HUMIDITY

SENSOR

REMOVE HUMIDIFIER CONTACT

TO REMOTE

HUMIDIFIER

MASTER ENABLE

H-1

DISPERSION

UNIT

208V

SERVER ROOMMECHANICAL

ROOM

W

AL

L

AI

H

AI

UNIT MOUNTED

MANUFACTUER

CONTROL PANEL

TO BUILDING

CONTROL PANEL

(FUTURE)

DISPERSION UNIT

POWER CONNECTION

STEAM PIPE

1. GENERAL:

THE HUMIDIFIER CONSISTS OF A STEAM GENERATOR AND STEAM DISPERSION UNIT.

THE HUMIDIFIER SHALL BE CONTROLLED THROUGH A FACTORY PROGRAMMED

APPLICATIONS CONTROLLER.

THE HUMIDIFIER SHALL OPERATE AS NECESSARY TO SATISFY SPACE HUMIDITY SETPOINTS

24/7. SPACE HUMIDITY SETPOINT SHALL BE 40%RH (ADJUSTABLE).

ALL ALARMS SHALL BE MONITORED BY THE CRAC UNIT CONTROLLER AND SIGNALED TO

THE DDC FRONT END.

2. OPERATION:

UPON A CALL FOR HUMIDIFICATION, THE UNIT SHALL BEGIN OPERATION AND RUN AS

NEEDED TO MAINTAIN THE SPACE HUMIDITY SETPOINT.

3. MAINTENANCE:

DRAIN/FILL AND FLUSH CYCLES SHALL BE INITIATED AUTOMATICALLY BY UNIT

CONTROLLER.

4. BAS MONITORING POINTS:

THE HUMIDIFIER UNIT CONTROLLER SHALL COMMUNICATE THE FOLLOWING POINTS TO BE

MONITORED BY THE DDC SYSTEM THROUGH A BACNET PROTOCOL:

· SPACE HUMIDITY

· ALARM STATUS (GENERAL)

5. ALARMS:

THE HUMIDIFIER UNIT SHALL COMMUNICATE ALL ALARMS TO THE DDC SYSTEM.

SEQUENCE OF OPERATION - H-1:

MASTER

ENABLE

INPUT

HUMIDIFIER

ENABLE

SWITCH FROM

CRAC UNIT

V

AN

G

UA

RD

B

LV

D M

IA

M

IS

BU

RG

, O H

PH

O

NE

(9 ) 4 -0

Ti m e / D at e:

SHEET:

Fi le

RE

VI

SI

O N

IN

FO

RM

AT

IO

N

Dr aw in g:

Di sc ip lin e So rt:

5/ /2 9:

:4

AM

Au to de sk D oc s:

//3 G re at er D ay to n R

TA

S er ve r R oo m /3 _G D R

TA

SR

_M _V .rv t

CO

NT

RO

L

DI

AG

RA

M S

MH8-001

G

RE

AT

ER

D

AY

TO

N

RE

G

IO

NA

L

TR

AN

SI

T

AU

TH

O

RI

TY

W

RI

GH

T

ST

OP

P

LA

ZA

S.

M

AI

N

ST

RE

ET

DA

YT

ON

, O

HI

O

FILE NO: 3761614

SE

RV

ER

R O O M C O O

LI

NG

S

YS

TE

M

M H8 -0

CO

NT

RO

L

DI

AG

RA

M S

- C O

NT

RO

LS

NTSMH8-001

1 CRAC CONTROL DIAGRAM

NTSMH8-001

2 HUMIDIFIER CONTROL DIAGRAM

RE

V

DR

CH

K

DA

TE

DE

SC

RI

PT

SURFACE MOUNTED FLOOR BOX W/ NEMA 5-20 DUPLEX RECEPTACLE

UNLESS NOTED OTHERWISE

SURFACE MOUNTED FLOOR BOX W/ NEMA 5-20 QUAD RECEPTACLE

UNLESS NOTED OTHERWISE

POWER

A AMPERE

AC ABOVE COUNTER / ALTERNATING CURRENT

ACS ACCESS CONTROL SYSTEM

ADA AMERICANS WITH DISABILITIES ACT

AF AMPS FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIM ADRESSABLE INPUT MODULE

AL ALUMINUM

AOM ADDRESSABLE OUTPUT MODULE

AT AMPS TRIP

ATS AUTO TRANSFER SWITCH

A/V AUDIO/VISUAL

AWG AMERICAN WIRE GAUGE

#/C # OF CONDUCTOR(S)

C CONDUIT

CB CIRCUIT BREAKER

CCTV CLOSED CAPTION TELEVISION CAMERA

CKT CIRCUIT

COMM COMMUNICATIONS

CR CARD READER

CU COPPER

DC DIRECT CURRENT

DIM DIMENSION

DISC DISCONNECT

DP DISTRIBUTION PANEL

(E) EXISTING TO REMAIN

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EWC ELECTRICAL WATER COOLER

F PULL STATION

FE FURNISHED EQUIPMENT

FACP FIRE ALARM CONTROL PANEL

FAA FIRE ALARM ANNUNCIATOR

FM FREQUENCY MODULATION

FS FLOW SWITCH

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

HVAC HEATING, VENTILATION, AND AIR CONDITIONING

HP HORSEPOWER

HS HORN STROBE

HT HEIGHT

HZ HERTZ

J JUNCTION BOX

KAIC KILOAMPS INTERRUPTING CAPACITY

KVA KILO-VOLT AMPERES

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT EMITTING DIODE

LTG LIGHTING

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUGS ONLY

MTD MOUNTED

NC NORMALLY CLOSED

NEC NATIONAL ELECTRIC CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NF NON-FUSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NTS NOT TO SCALE

OS OCCUPANCY SENSOR

PH PHASE

PIR PASSIVE INFRARED

PIV PRESSURE INDICATING VALVE

PP POWER PACK RECEPTACLE

PRI PRIMARY

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE

RGS RIGID GALVANIZED STEEL

RP RECEPTACLE PANEL

RSFACU RELEASING SYSTEM FIRE ALARM CONTROL UNIT

RTA RADIO TRANSMITTER

SEC SECONDARY

SPD SURGE PROTECTION DEVICE

SNAC SUPERVISED NOTIFICATION APPLIANCE CIRCUIT

SS STAINLESS STEEL

SW SWITCH

SWBD SWITCHBOARD

TGB TELECOMMUNICATIONS GROUNDING BAR

TS TAMPER SWITCH

TV TELEVISION/MONITOR

TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR

UG UNDERGROUND

UON UNLESS OTHERWISE NOTED

V VOLT

VA VOLTAMPERE

VFD VARIABLE FREQUENCY DRIVE

W WATTS

WP WEATHERPROOF IN USE COVER

XFMR TRANSFORMER

XP EXPLOSION PROOF

ABBREVIATIONS

FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT

BASED ON MANUFACTURERS RECOMMENDATIONS

NEMA 5-20 DUPLEX RECEPTACLE (FLUSH/SURFACE) MOUNTED 18" AFF

JUNCTION BOX

UNFUSED DISCONNECT SWITCH. SIZE AS INDICATED ON DRAWINGS

SURFACE MOUNTED PANELBOARD. REFER TO PANEL SCHEDULES

FOR VOLTAGE CONFIGURATION. CROSS HATCHED AREA IN FRONT

OF PANELBOARD INDICATES EXTENT OF WORKING CLEARANCE.

LINE-FILLED BOX INIDICATES 480/277V PANEL AND SOLID-FILLED

INDICATES 208/120V PANEL.

MOTOR, # INDICATES MOTOR HP, F INDICATES FRACTIONAL

HORSEPOWER.

J

RECESSED MOUNTED PANELBOARD. LINE INDICATES WALL FACE.

REFER TO PANEL SCHEDULES FOR VOLTAGE CONFIGURATION.

CROSS HATCHED AREA IN FRONT OF PANELBOARD INDICATES

EXTENT OF WORKING CLEARANCE. LINE-FILLED BOX INIDICATES

480/277V PANEL AND SOLID-FILLED INDICATES 208/120V PANEL.

SPECIALTY RECEPTACLE. REFER TO KEYED NOTES FOR ADDITIONAL

INFORMATION.

MOTOR RATED, 20 AMP, 125 VOLT TOGGLE SWITCH

NEMA 5-20 SIMPLEX RECEPTACLE (FLUSH OR SURFACE) MOUNTED

18" AFF UNLESS NOTED OTHERWISE.

COMBINATION STARTER / DISCONNECT SWITCH. SIZE FOR

EQUIPMENT BASED ON MANUFACTURERS RECOMMENDATIONS

AV

SURFACE MOUNTED FLOOR BOX WITH NEMA 5-20 QUAD RECEPTACLE,

COMBINATION TELEPHONE/DATA, AND A/V JACKS. REFER TO

KEYED NOTE FOR SIZING AND ACCESSORIES.

M

BREAKER

LOAD CENTER WITH INTEGRAL TRANSFORMER

CURRENT TRANSFORMER (SHOWN AROUND FEEDER)

POTENTIAL TRANSFORMER (PT)

DIGITAL POWER METER. "A" INDICATES AMMETER ON

CT'S FOR FEEDER BREAKER

DPM

FUSE

SPD SURGE PROTECTION DEVICE

A AMMETER

PULL BOX. SUPERSCRIPT DENOTES TYPE OF PULL BOX:

P - POWER; F - FIBER OPTIC; L - LIGHTING CIRCUIT.

K KIRK KEY

VFD

X

VARIABLE FREQUENCY DRIVE

M METER

SINGLE POLE SWITCH

CP CONTROL PANEL

OVERLOAD SWITCH

MCC

TRANSFORMER (PLAN VIEWS)

MOTOR, HP NOT INDICATED.M

NEMA 5-20 QUAD RECEPTACLE (FLUSH/SURFACE) MOUNTED 18" AFF

P,F,L

POWER POLEPP

XX

PNL PANEL BOARD

A

GENERATOR.G

PB

V2

V1

TX

XX kVA

TRANSFORMER. "V1" INDICATES PRIMARY VOLTAGE,

"V2" INDICATES SECONDARY VOLTAGE, "TX"

INDICATES THE TRANSFORMER NAME, "XX kVA" IS

THE TRANSFORMER RATING.

STARTER. REFER TO SCHEDULE FOR

ADDITIONAL STARTER OPTIONS

AC

GFI

WP

CS

REF

UNLESS NOTED OTHERWISE. (AC INDICATES ABOVE COUNTER,

GFI INDICATES GROUND FAULT CIRCUIT INTERRUPTER, WP INDICATES

WEATHERPROOF IN-USE COVER, CS INDICATES CHILD SAFE, REF

INDICATES UNDERCOUNTER/FULL SIZE REFRIGERATOR.)

UNLESS NOTED OTHERWISE. (AC INDICATES ABOVE COUNTER,

GFI INDICATES GROUND FAULT CIRCUIT INTERRUPTER, WP INDICATES

WEATHERPROOF IN-USE COVER, CS INDICATES CHILD SAFE, REF

INDICATES UNDERCOUNTER/FULL SIZE REFRIGERATOR.)

DRAWOUT BREAKER

C CONTACTOR

TIME SWITCH

PUSHBUTTON

TS

SS

SWITCHED RECEPTACLE.

AC

GFI

WP

CS

REF

AC

GFI

WP

CS

REF

AC

GFI

WP

CS

REF

PP

POWER PACK, ON/OFF CONTROL (** = RECEPTACLE DESIGNATION);

SEE ELECTRICAL DETAILS FOR WIRING DIAGRAM

1. SOME SYMBOLS SHOWN ON THIS SHEET MIGHT NOT BE USED ON THIS

PROJECT.

2. INSTALLATION SHALL CONFORM TO THE APPLICABLE REQUIREMENTS OF

NFPA 70, NATIONAL ELECTRICAL CODE 2023 ALONG WITH APPLICABLE UFC

REQUIREMENTS.

3. CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES DURING

CONSTRUCTION.

4. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO INCLUDE

EVERY DETAIL OF REQUIRED CONSTRUCTION EQUIPMENT AND MATERIALS.

PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT NOT SPECIFICALLY SHOWN

ON THE DRAWINGS BUT WHICH ARE NECESSARY TO COMPLETE THE WORK.

INSTALLATION SHALL BE COORDINATED WITH PIPING, DUCTWORK,

STRUCTURAL STEEL ALONG WITH ROOM FINISHES.

5. CONDUIT ROUTING IS DIAGRAMMATIC. ROUTE PARALLEL AND

PERPENDICULAR TO LINES OF BUILDING STRUCTURE. FIELD VERIFY EXACT

ROUTING PER ACTUAL CONDITIONS. MINIMUM ACCEPTABLE CONDUIT SIZE IS

¾” ABOVE GRADE AND 1” UNDERGROUND.

6. CIRCUIT AMPACITY RATINGS ARE BASED ON RACEWAYS NOT EXCEEDING (3)

CURRENT-CARRYING CONDUCTORS PLUS NEUTRAL CONDUCTORS AND

EQUIPMENT GROUND CONDUCTOR PER NEC CODE. A SEPARATE NEUTRAL

CONDUCTOR SHALL BE PROVIDED FOR EACH CURRENT CARRYING

CONDUCTOR.

7. BOND ALL INTERIOR METALLIC PIPING SYSTEMS, INCLUDING NATURAL GAS, IN

ACCORDANCE WITH NFPA 70-250 REQUIREMENTS.

8. PROVIDE A GREEN-INSULATED GROUNDING CONDUCTOR, SIZED PER NEC

ARTICLE 250, IN ALL FEEDER AND BRANCH CIRCUIT RACEWAYS.

9. FIRE SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS.

10. DO NOT USE ANY LIGHT FIXTURE AS A RACEWAY FOR CONDUCTORS NOT

SERVING FIXTURE, UNLESS FIXTURE IS DESIGNATED AND UL-LISTED FOR USE

AS A RACEWAY.

11. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ELECTRICAL

OUTLETS WITH CASEWORK, FURNITURE AND MILLWORK. REFER TO

ARCHITECTURAL PLANS AND ELEVATIONS FOR DETAILS.

12. DO NOT ATTACH STARTERS AND DISCONNECTS FURNISHED FOR HVAC

EQUIPMENT DIRECTLY TO EQUIPMENT. PROVIDE WALL-MOUNT SUPPORT OR

INDEPENDENTLY SUPPORT ON STEEL ANGLE OR UNISTRUT RACK

CONSTRUCTED FOR THAT PURPOSE. LOCAL DISCONNECTS FOR HVAC

EQUIPMENT SHALL BE FURNISHED SEPARATELY FROM THE HVAC EQUIPMENT.

13. VERIFY EXACT MECHANICAL EQUIPMENT TO BE INSTALLED. ADJUST

CONDUIT, WIRING, DISCONNECT SIZE AND FUSING PER MANUFACTURER

FINAL REQUIREMENTS FOR ACTUAL EQUIPMENT INSTALLED.

14. CONTRACTOR SHALL VISIT THE PROJECT SITE AND CAREFULLY EXAMINE

THOSE PORTIONS OF THE SITE AFFECTED BY THIS WORK TO BECOME

FAMILIAR WITH EXISTING CONDITIONS THAT MAY AFFECT EXECUTION OF THE

WORK.

15. “PROVIDE” IS AN ALL-INCLUSIVE TERM REQUIRING THE CONTRACTOR TO

FURNISH, INSTALL, WIRE AND CONNECT ALL SPECIFIED EQUIPMENT AS WELL

AS COMPONENTS, ACCESSORIES, AND MOUNTING HARDWARE TO MEET

SYSTEM REQUIREMENTS.

16. “INSTALL” SPECIFIES THAT THE CONTRACTOR SHALL INSTALL EQUIPMENT

PROVIDED BY OTHERS. THE CONTRACTOR SHALL PROVIDE ALL ANCILLARY

EQUIPMENT FOR A COMPLETE INSTALLATION.

17. CONTRACTOR SHALL PROVIDE ARC-FLASH CALCULATIONS FROM A

REGISTERED ELECTRICAL ENGINEER. THE CONTRACTOR SHALL PROVIDE

ARC-FLASH LABELS FOR ELECTRICAL EQUIPMENT, MCC'S, DISCONNECTS,

PANELBOARDS, ETC. SEE SPECIFICATIONS FOR ARC-FLASH LABEL

REQUIREMENTS.

E-STOP PUSHBUTTON

C SECURITY CAMERA

18. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND

SHOWN FOR REFRENCE ONLY. CONTRACTOR SHALL VERIFY ALL EXISTING

CONDITIONS PRIOR TO WORK BEGINNING. THE CONTRACTOR IS RESPONSIBLE FOR

INFORMING THE ELECTRICAL ENGINEER OF ANY CONDITIONS THAT DIFFER FROM

THE INFORMATION INDICATED IN THE DRAWINGS.

19. LOCATION OF EXISTING EQUIPMENT, CONDUITS, OUTLETS, DEVICES, CONTROLS

AND ALL CONCEALED WORKS, ETC. ARE APPROXIMATE.

20. ALL EXISTING ELECTRICAL EQUIPMENT SHOWN TO BE REMOVED SHALL BE

REMOVED BY THE CONTRACTOR. EXISTING FIXTURES AND EQUIPMENT

CONSIDERED SALVAGEABLE BY THE OWNER AND NOT SHOWN TO BE REUSED

SHALL BE TURNED OVER TO THE OWNER OR REMOVED FROM SITE AS DIRECTED

BY OWNER.

21. THE CONTRACTOR IS TO PROTECT THE EXISTING TO REMAIN LIGHTING FIXTURES,

ELECTRICAL EQUIPMENT, DEVICES, AND FEEDERS.

22. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE

UNNECESSARY INCONVENIENCE OR DANGER TO USERS, AND NOT INTERFERE

WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE

PLANNED IN ADVANCE AND COORDINATED WITH THE OWNER.

23. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE

AS REQUIRED, AND REMOVE ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN

INACCESSIBLE LOCATIONS (WALLS TO REMAIN) MAY BE ABANDONED IN PLACE.

REMOVE UNUSED WIRING INCLUDING ABANDONED TELEPHONE, DATA AND OTHER

LOW VOLTAGE SYSTEMS CABLING AFTER CONFIRMING WITH THE OWNER THAT

CABLING IS ABANDONED AND WILL NOT BE RE-USED.

24. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL ELECTRICAL

EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL

EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE

"AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR AFFECTED PANELS.

25. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO

POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT AFFECT

ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE

OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND

OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.

26. ALL EXISTING BRANCH CIRCUITS BEING REMOVED SHALL BE REMOVED AS

COMPLETE AS POSSIBLE. EXISTING CONDUCTORS SHALL BE REMOVED

COMPLETELY FROM THEIR RACEWAYS, DISPOSED OF AS SCRAP, REMOVED FROM

SITE AND NOT REUSED EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. WHERE

AN EXISTING DEVICE IS SHOWN REMOVED FROM AN EXISTING CIRCUIT, NEW

WIRING SHALL BE PROVIDED AS REQUIRED TO INSURE CONTINUITY OF EXISTING TO

REMAIN CIRCUIT.

27. REMOVE ELECTRICAL CONNECTIONS TO ALL MECHANICAL EQUIPMENT BEING

REMOVED BY DIVISION 15. COORDINATE EQUIPMENT REMOVAL LOCATIONS WITH

MECHANICAL DRAWINGS.

GENERAL NOTES

V

A N

G U

A R

D B

L V

D

M

IA

M

IS

B

U R

G

O H

P H

O N

E

-0

T im e

D at e

SHEET:

F ile

R E

V

IS

IO

N

I N

F O

R M

A T

IO

N

D ra w in g

D is c ip lin e

S or t:

/8

/2

:5

:5

A

M

A u to d e s k D o c s /3

G re a te r D a y to n R

T A

S e rv e r

R o o m

/3 G

D R

T A

S R

E

V

.r v t

E L

E C

T R

IC

A

L L

E G

E N

D

EG1-001

G R

E A

T E

R D

A Y

T O

N R

E G

IO

N

A L

T R

A N

S

IT

A U

T H

O R

IT

Y

W R

IG

H

T S

T O

P P

L A

Z A

S

M

A

IN

S T

R E

E T

D

A Y

T O

N

O H

FILE NO: 3761614

S E

R V

E R

R O

O M

C O

O L

IN

G S

Y S

T E

M

E G

-0

E L E

C T

R

IC

A L L

E G

E N

D

.0

R E

V D

R C

H K

D A

T E

D

E S

C R

IP

T

IO

N

A

F B

W L

/0 /2

Is su e d f o r

B id s a n d

P e rm itt in g

05/09/2025

EMB

EXIST.

EMA

EXIST.

PASSENGER

ELEVATOR

EXISTING EMER. DISTRIBUTION PANEL

"EDP2"

SPD

STAIR

PRESSURIZATION

200A/3P 30A/3P

CRAC-1

2 3 4 5 6

ATS-1

EQUIPMENT CONNECTION SCHEDULE

TAG DESCRIPTION LOCATION

LOAD

FLA

VOLTS/

PHASE

BLDG_PANEL:

CIRCUIT

FEEDERS (HOMERUN) DISCONNECT/STARTER

(AT UNIT)

NOTES

KW HP Breaker WIRE GND CONDUIT

CRAC-1 AIR HANDLER SERVER ROOM 27.4 76.2 208/3 EDP2:20,22,24 100A/3P 3-#1 #6 1 1/2" 600V/3/100 (NF) 1

ACCU-1 CONDENSING UNIT ROOF 2 5.7 208/3 EMB: 37,39,41 Existing 25A/3P 3-#10 #10 1" 600V/3/30 (NF) 1

H-1 ELECTRODE STEAM HUMIDIFIER MECHANICAL ROOM 4.6 19.0 208/1 EMB:31,33 30A/2P 2-#10 #10 3/4" 600V/3/30 (NF) 2

NOTES:

1. PROVIDE NON-FUSED DISCONNECT , HEAVY DUTY, NEMA 12 - INDOORS OR NEMA 4X - OUTDOORS. FUSE PER MANUFACTURER'S RECOMMENDATIONS.

2. PROVIDE NON-FUSED DISCONNECT , HEAVY DUTY, NEMA 12 DISCONNECT SWITCH FOR STEAM GENERATION UNIT. PROVIDE MOTOR RATED SWITCH AT UNIT FOR STEAM DISPERSION UNIT REMOTE MOUNTED IN SERVER ROOM.

V

A N

G U

A R

D B

L V

D

M

IA

M

IS

B

U R

G

O H

P H

O N

E

-0

T im e

D at e

SHEET:

F ile

R E

V

IS

IO

N

I N

F O

R M

A T

IO

N

D ra w in g

D is c ip lin e

S or t:

GENERAL NOTES:

KEY NOTES:

/8

/2

:5

:0

A

M

A u to d e s k D o c s /3

G re a te r D a y to n R

T A

S e rv e r

R o o m

/3 G

D R

T A

S R

E

V

.r v t

W S

P S

C H

E D

U L

E S

E

L E

C T

R

IC

A L

O N

E -L

IN

E

EG1-002

G R

E A

T E

R D

A Y

T O

N R

E G

IO

N

A L

T R

A N

S

IT

A U

T H

O R

IT

Y

W R

IG

H

T S

T O

P P

L A

Z A

S

M

A

IN

S T

R E

E T

D

A Y

T O

N

O H

FILE NO: 3761614

S E

R V

E R

R O

O M

C O

O L

IN

G S

Y S

T E

M

E G

-0

W S

P S

C H

E D

U L E

S

E L E

C T

R

IC

A L O

N E

-L

IN

E

.0 NTS

1 EDP2 ONE-LINE DIAGRAM

EG1-002

1. PROVIDE NEW 100A/3P BREAKER IN EXISTING SPACE. MATCH THE TYPE/MODEL/KA RATING WITH

EXISTING BREAKERS IN THE PANEL.

2. REMOVE EXISTING SPARE BREAKERS AND PROVIDE NEW BREAKER. MATCH THE

TYPE/MODEL/KA RATING WITH EXISTING BREAKERS IN THE PANEL.

Enclosure: NEMA 1 Ground Bus: INCLUDED

MCB Trip: 600 A Neutral Bus: 100.00%

MCB Frame: Fault Rating:

Feeds: Bus Rating: 600AMPS

Mounting: SURFACE Bus Material:

ENCLOSURE DATA: BUS DATA Remarks and Accessories:

Total Est. Demand: 197 A

Total Conn.: 197 A

Total Est. Demand: 71.1 kVA

Spare 69000 VA 69000 VA Total Conn. Load: 71.1 kVA

HVAC 2054 VA 2054 VA

Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 197 A 197 A 197 A

Total Conn. Load: 23.7 kVA 23.7 kVA 23.7 kVA

9 ELEVATOR SHUNT TRIP 3 20 A 20 A 0.0 kVA 0.0 kVA 0.0 kVA

8 ELEVATOR 3 20 A 20 A 0.0 kVA 0.0 kVA 0.0 kVA

7 SPD 3 60 A 60 A 0.0 kVA 0.0 kVA 0.0 kVA

6 SPACE 3 -- -- -- -- --

5 HP2C 3 30 A 30 A 5.0 kVA 5.0 kVA 5.0 kVA

4 CRAC-1 3 100 A 100 A 0.7 kVA 0.7 kVA 0.7 kVA

3 ELEVATOR 3 400 A 400 A 4.0 kVA 4.0 kVA 4.0 kVA

2 PANELS EMA AND EMB 3 200 A 200 A 14.0 kVA 14.0 kVA 14.0 kVA

1 MAIN 3 600 A 600 A 0.0 kVA 0.0 kVA 0.0 kVA

CKT Circuit Description # of Poles Frame Size Trip Rating

LOAD

PHASE A PHASE B PHASE C

Remarks

ATS-1

Supply From:

Location:EDP2 Service: 208/120 Wye,3 ɸ,4 W

(EXISTING)

ELECTRICAL ROOM

EXISTING LOAD

R E

V D

R C

H K

D A

T E

D

E S

C R

IP

T

IO

N

A

F B

W L

/0 /2

Is su e d f o r

B id s a n d

P e rm itt in g

N/A N/A N/A

Enclosure: NEMA 1 Ground Bus:

MCB Trip: 225 A Neutral Bus: 100%

MCB Frame: Fault Rating: 10kA

Feeds: Bus Rating: 225 AMPS

Mounting: SURFACE Bus Material:

ENCLOSURE DATA BUS DATA Remarks and Accessories:

Total Est. Demand: 69 A

Total Conn.: 69 A

Total Est. Demand: 25 kVA

Spare 19000 VA 19000 VA Total Conn. Load: 25 kVA

HVAC 6006 VA 6006 VA

Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 56 A 85 A 72 A

Total Load: 6.7 kVA 10 kVA 8 kVA

41 0.7 1 1 20 A BOARDROOM LTS 42

39 0.7 1 1 20 A BOARDROOM LTS 40

ACCU-1 25 A 3

0.7 1 1 20 A BOARDROOM LTS 38

35 SPARE 20 A 1 0 0.8 1 20 A BOARDROOM ELEV LOBBY LTS 36

33 2 0.8 1 20 A MULTIPURPOSE ELEV LOBBY LTS 34

H-1 30 A 2

2 0 1 20 A MULTIPURPOSE RM LTS 32

29 ACCESS CONTROL 20 A 1 0.5 0.4 1 20 A ELEVATOR PIT LTS 30

27 DDC CONTROL 20 A 1 0.5 0 1 20 A ELEVATOR MECH RM FAN 28

25 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 1 20 A COOPER ELEVATOR CAR LTS 26

23 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 1 20 A SPARE 24

21 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 1 20 A SPARE 22

19 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 20

17 AMERICAN BLD EAST CONTROL 20 A 1 0.5 1 18

15 AMERICAN BLD EAST CONTROL 20 A 1 0.5 1

3 20 A LIEBERT AIR

13 CONCOURSE HIGHBAY LTS 20 A 1 0 1 1 20 A SPARE 14

11 CONCOURSE HIGHBAY LTS 20 A 1 0 1 1 20 A CONCOURSE HUGHBAY LTS 12

9 SPARE 20 A 1 0 1 1 20 A CONCOURSE EXIT SIGNS 10

7 SPARE 20 A 1 0 1 1 20 A DUMPSTER RM 124 LTS 8

5 MEZZANINE HIGHBAY LTS 20 A 1 1 1 1 20 A MEZZANINE LTS 6

3 MULTIPURPOSE RM EM LTS 20 A 1 1 1 1 20 A COOPER STAIRWAY LTS 4

1 SPARE 20 A 1 0 0 1 20 A COOPER STAIRWAY LTS 2

CKT Circuit Description Trip Poles A (kVA) B (kVA) C (kVA) Poles Trip Circuit Description CKT

Supply From:

Location:EMB Service: 208/120 Wye , 3 ϕ , 4 W

EDP-2

(EXISTING)

ELECTREICAL ROOM

ESTIMATED EXISTING LOADS

MLO

SM

EMA

EMB

EDP2

EMB: 31,33

CRAC-1

C

H-1

NF-H-1

EDP2:4

MECHANICAL ROOM

SERVER ROOM

ELECTRICAL ROOM

NF-CRAC-1

ATS-1

NEW

CONTACTOR

PANEL "CP-1"

KEY PLAN

V

A N

G U

A R

D B

L V

D

M

IA

M

IS

B

U R

G

O H

P H

O N

E

-0

T im e

D at e

SHEET:

F ile

R E

V

IS

IO

N

I N

F O

R M

A T

IO

N

D ra w in g

D is c ip lin e

S or t:

GENERAL NOTES:

KEY NOTES:

PLAN NORTH

E

R D

S T

MAIN ST

/8

/2

:5

:0

A

M

A u to d e s k D o c s /3

G re a te r D a y to n R

T A

S e rv e r

R o o m

/3 G

D R

T A

S R

E

V

.r v t

W S

P S

E C

O N

D F

L O

O R

E L

E C

T R

IC

A

L P

L A

N

EH1-101

G R

E A

T E

R D

A Y

T O

N R

E G

IO

N

A L

T R

A N

S

IT

A U

T H

O R

IT

Y

W R

IG

H

T S

T O

P P

L A

Z A

S

M

A

IN

S T

R E

E T

D

A Y

T O

N

O H

FILE NO: 3761614

S E

R V

E R

R O

O M

C O

O L

IN

G S

Y S

T E

M

E H

-1

W S

P S

E C

O N

D F

L O

O R

E L E

C T

R

IC

A L P

L A

N

.5

SCALE: 1/4" = 1'-0"

EH1-101

1 WSP SECOND FLOOR ELECTRICAL PLAN

1. COORDINATE RELOCATION OF SECURITY CAMERA WITH GDRTA PERSONNEL.

2. PROVIDE E-STOPS AND 24 POLE CONTACTOR PANEL TO SHUTDOWN ALL SERVER ROOM

ELECTRICAL AND HVAC EQUIPMENT AND CLOSE THE FIRE DAMPER OF CRAC-1. CIRCUITS

SHALL BE RE-ROUTED THROUGH CONTACTOR PANEL. FOR BIDDING PURPOSES, USE (12) 20A

CIRCUITS. COORDINATE ACTUAL QUANTITY IN FIELD WITH GDRTA.

3. DEMOLISH 3-TON CRAC.REMOVE FEED TO CRAC BACK TO PANEL EMB:16,18,20. MARK

EXISTING 35A BREAKER AS SPARE.

A. MINIMUM ACCEPTABLE CONDUIT SIZE IS ¾” ABOVE GRADE AND 1” UNDERGROUND.

B. CONDUCTORS SHALL BE THHN/THWN-2 COPPER. MINIMUM SIZE IS #12 AWG UON.

C. MATCH AIC RATINGS AND ALL OTHER CHARACTERISTICS OF EXISTING DEVICES IN MCC’S,

PANELBOARDS, SWITCHBOARDS, ETC. WHEN ADDING DEVICES TO THE EXISTING GEAR.

D. FIRE SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS.

R E

V D

R C

H K

D A

T E

D

E S

C R

IP

T

IO

N

A

F B

W L

/0 /2

Is su e d f o r

B id s a n d

P e rm itt in

ACCU-1

NF-ACCU-1

EMB: 37,39,41

KEY PLAN

V

A N

G U

A R

D B

L V

D

M

IA

M

IS

B

U R

G

O H

P H

O N

E

-0

T im e

D at e

SHEET:

F ile

R E

V

IS

IO

N

I N

F O

R M

A T

IO

N

D ra w in g

D is c ip lin e

S or t:

GENNERAL NOTES:

KEY NOTES:

PLAN NORTH

E

R D

S T

MAIN ST

/8

/2

:5

:0

A

M

A u to d e s k D o c s /3

G re a te r D a y to n R

T A

S e rv e r

R o o m

/3 G

D R

T A

S R

E

V

.r v t

W S

P R

O O

F E

L E

C T

R

IC

A L

P L

A N

EH1-102

G R

E A

T E

R D

A Y

T O

N R

E G

IO

N

A L

T R

A N

S

IT

A U

T H

O R

IT

Y

W R

IG

H

T S

T O

P P

L A

Z A

S

M

A

IN

S T

R E

E T

D

A Y

T O

N

O H

FILE NO: 3761614

S E

R V

E R

R O

O M

C O

O L

IN

G S

Y S

T E

M

E H

-1

W S

P R

O O

F E

L E

C T

R

IC

A L P

L A

N

.5

SCALE: 1/4" = 1'-0"

EH1-102

1 WSP ROOF ELECTRICAL PLAN

1. DEMOLISH CONDENSING UNIT (CU). REMOVE CONDUCTORS TO UNIT BACK TO PANEL

EMB:37,39,41. RE-USE EXISTING 25A BREAKER FOR NEW ACCU-1 UNIT. RE-USE EXISTING

CONDUITS WHERE POSSIBLE. CONTRACTOR SHALL REMOVE EXISTING SUPPORT RAILS AND

PATCH ALL AFFECTED ROOF AREAS IN ACCORDANCE WITH ROOFING MANUFACTURER’S

REQUIREMENTS TO MAINTAIN THE EXISTING ROOF WARRANTY. CONTRACTOR SHALL

COORDINATE WITH ROOFING SYSTEM PROVIDER PRIOR TO PERFORMING ANY WORK.

2. DISCONNECT SWITCH FOR NEW MECHANICAL EQUIPMENT. COORDINATE THE EXACT

LOCATION WITH THE MECHANICA EQUIPMENT SUBMITTAL. THE MAXIMUM LENGTH OF FLEXIBLE

CONDUIT FROM THE DISCONNECT SWITCH TO THE EQUIPMENT SHALL BE 6 FEET.

A. MINIMUM ACCEPTABLE CONDUIT SIZE IS ¾” ABOVE GRADE AND 1” UNDERGROUND.

B. CONDUCTORS SHALL BE THHN/THWN-2 COPPER. MINIMUM SIZE IS #12 AWG UON.

C. MATCH AIC RATINGS AND ALL OTHER CHARACTERISTICS OF EXISTING DEVICES IN MCC’S,

PANELBOARDS, SWITCHBOARDS, ETC. WHEN ADDING DEVICES TO THE EXISTING GEAR.

D. FIRE SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS.

R E

V D

R C

H K

D A

T E

D

E S

C R

IP

T

IO

N

A

F B

W L

/0 /2

Is su e d f o r

B id s a n d

P e rm itt in

G-001 - COVER SHEET
MG1-001 - MECHANICAL GENERAL NOTES AND LEGEND
MD1-101 - WSP SECOND FLOOR PLAN - DEMOLITION
MD1-102 - WSP ROOF PLAN - DEMOLITION
MH1-101 - WSP SECOND FLOOR PLAN
MH1-102 - WSP ROOF PLAN
MH3-001 - WSP SECTIONS
MH4-001 - WSP ENLARGED PLANS
MH5-001 - DETAILS
MH8-001 - CONTROL DIAGRAMS
EG1-001 - ELECTRICAL LEGEND
EG1-002 - WSP SCHEDULES & ELECTRICAL ONE-LINE
EH1-101 - WSP SECOND FLOOR ELECTRICAL PLAN
EH1-102 - WSP ROOF ELECTRICAL PLAN