2025-0516_WSP_Server_Room_HVAC_DWG_IFC.pdf
PDF 5 MB Posted
- Attached to
- Server Room Cooling System State and local contract opportunity
- Solicitation number
- CIFB GD 25-35
- Issued by
- Montgomery County, Ohio
About this file
The provided file is a comprehensive set of architectural and engineering design drawings for the Server Room Cooling System project for the Greater Dayton Regional Transit Authority (GDRTA), located at Wright Stop Plaza in Dayton, Ohio. The project involves replacing the HVAC unit in the server room and associated electrical support work, with specific focus on the second floor and roof areas of the facility. The design documents include detailed mechanical, electrical, and demolition plans, covering aspects such as equipment placement, ductwork, piping, electrical connections, and system integration. The project involves installing a new CRAC (Computer Room Air Conditioning) unit, a condensing unit, and a steam humidifier, with careful consideration for existing building systems and infrastructure.
The technical specifications indicate a complex retrofit project with precise environmental control requirements for the server room. The new cooling system is designed to maintain a consistent humidity level of 40% relative humidity, with integrated control systems that will communicate with the building's DDC (Direct Digital Control) system. Electrical connections will be made to existing emergency distribution panels (EDP2 and EMB), with specific voltage and amperage requirements for each piece of equipment. The project includes detailed provisions for equipment mounting, refrigerant piping, electrical connections, and necessary demolition and repair work, ensuring minimal disruption to the existing facility while upgrading the critical server room cooling infrastructure.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| Server_Room_Cooling_System_(Addendum_#1_Revision).pdf | ||
| 2025-0516_WSP_Server_Room_HVAC_SPEC_IFC.pdf | ||
| Combin_ICE_WSP_Server_Room_5192025.pdf | ||
| Sample_Contract_(DO_NOT_COMPLETE).pdf | ||
| RTA_Construction_Terms_and_Conditions.docx | DOCX document | |
| RTA_General_Terms_and_Conditions.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
V
A N
G U
A R
D B
L V
D
M
IA
M
IS
B
U R
G
O H
P H
O N
E
-0
T im e
D at e
SHEET:
F ile
R E
V
IS
IO
N
I N
F O
R M
A T
IO
N
D ra w in g
D is c ip lin e
S or t:
GENERAL NOTES
CODE DATA
/1
/2
:4 :3
P
M
A u to d e s k D o c s
/3
G re a te r D a y to n R
T A
S e rv e r
R o o m
/3 G
D R
T A
S R
M
V
.r v t
C O
V E
R S
H E
E T
G-001
G R
E A
T E
R D
A Y
T O
N R
E G
IO
N
A L T
R A
N S
IT
A
U T
H O
R
IT
Y
W R
IG
H
T S
T O
P P
L A
Z A
S
M
A
IN
S T
R E
E T
D
A Y
T O
N
O H
IO
FILE NO: 3761614
S E
R V
E R
R O
O M
C O
O L
IN
G S
Y S
T E
M
SERVER ROOM COOLING SYSTEM
GREATER DAYTON REGIONAL TRANSIT AUTHORITY
WRIGHT STOP PLAZA
4 S. MAIN STREET - DAYTON, OHIO 45402
G -0
C O
V E
R S
H E
E T
DRAWING INDEX
G-001 COVER SHEET
MG1-001 MECHANICAL GENERAL NOTES AND LEGEND
MD1-101 WSP SECOND FLOOR PLAN - DEMOLITION
MD1-102 WSP ROOF PLAN - DEMOLITION
MH1-101 WSP SECOND FLOOR PLAN
MH1-102 WSP ROOF PLAN
MH3-001 WSP SECTIONS
MH4-001 WSP ENLARGED PLANS
MH5-001 DETAILS
MH8-001 CONTROL DIAGRAMS
EG1-001 ELECTRICAL LEGEND
EG1-002 WSP SCHEDULES & ELECTRICAL ONE-LINE
EH1-101 WSP SECOND FLOOR ELECTRICAL PLAN
EH1-102 WSP ROOF ELECTRICAL PLAN
A. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH
ALL CODES, STANDARDS, AND GENERAL GOOD BUILDING
PRACTICES.
B. PRIOR TO STARTING CONSTRUCTION, CONTRACTOR(S)
SHALL BE RESPONSIBLE FOR VERIFYING THAT ALL
REQUIRED PERMITS AND APPROVAL(S) HAVE BEEN
OBTAINED. NO CONSTRUCTION OR FABRICATION OF ANY
ITEM SHALL BEGIN UNTIL THE CONTRACTOR HAS
RECEIVED ALL PLANS AND ANY OTHER DOCUMENTATION
FROM ALL OF THE PERMIT AND REGULATORY
AUTHORITIES. FAILURE OF THE CONTRACTOR(S) TO
FOLLOW THIS PROCEDURE SHALL CAUSE THE
CONTRACTOR(S) TO ASSUME FULL RESPONSIBILITY FOR
ANY SUBSEQUENT MODIFICATION OF THE WORK, IN
ADDITION TO ANY PENALTIES AND FEES MANDATED BY
ANY REGULATORY AUTHORITY.
C. ALL CONTRACTOR(S) SHALL FIELD VERIFY ALL
DIMENSIONS, ELEVATIONS, AND SITE CONDITIONS BEFORE
STARTING WORK. COMMENCEMENT OF WORK IMPLIES
ACCEPTANCE OF CONDITIONS. IF DIMENSIONS ARE IN
QUESTION, THE CONTRACTOR(S) SHALL BE RESPONSIBLE
FOR OBTAINING CLARIFICATION FROM GDRTA BEFORE
CONTINUING WITH CONSTRUCTION.
D. EACH CONTRACTOR(S) SHALL BE SOLELY RESPONSIBLE
FOR TAKING ALL STEPS NECESSARY TO PROTECT THE
PUBLIC AND BUILDING OCCUPANTS FROM INJURY AND
ADJACENT PROPERTY FROM DAMAGE DURING
CONSTRUCTION AS REQUIRED BY CODES AND GENERAL
GOOD PRACTICE. CONTRACTOR(S) SHALL POST AND
MAINTAIN SIGNS, NOTICES, AND OTHER SAFEGUARDS
REQUIRED BY LAW OR ORDINANCE.
E. THE CONTRACTOR(S) IS/ARE RESPONSIBLE TO MAINTAIN A
PROTECTED MEANS OF EGRESS DURING CONSTRUCTION.
F. IT SHALL BE THE INDIVIDUAL CONTRACTOR'S
RESPONSIBILITY TO NOTIFY GDRTA OF ANY
DISCREPANCIES IN THE PLANS AND/OR SPECIFICATIONS
PRIOR TO BIDDING AND/OR INSTALLATION OF ANY OF
THOSE ITEMS NOTED ON THE PLAN.
G. LARGE SCALE DETAILS OF DRAWINGS SHALL GOVERN
SCALE DRAWINGS FOR WHICH THEY ARE INTENDED TO
AMPLIFY. DIMENSIONS SHALL BE CALCULATED RATHER
THAN DETERMINED BY SCALE OR RULE.
H. THE CONTRACTOR(S) HAS THE RESPONSIBILITY TO NOTIFY
GDRTA OF MATERIALS OR WORK SHOWN FOR WHICH NO
QUALITY OR GRADE OR CONSTRUCTION DETAILS ARE
CLEARLY SPECIFIED. UNDER NO CIRCUMSTANCES SHALL
THE CONTRACTOR ASSUME GRADE OR QUALITY OR
CONSTRUCTION DETAILS FOR PRODUCTS OR WORK
SHOWN.
I. WHENEVER THERE IS A CONFLICT IN THE CONTRACT
DOCUMENTS REGARDING QUALITY OR QUANTITY, THE
GREATER QUALITY OR QUANTITY SHALL APPLY. ANY
ASSOCIATED HOOK-UP, CONNECTIONS, WIRING, ETC. OF
GREATER QUANTITIES SHALL BE INCLUDED IN THE WORK.
J. PATCH AND REPAIR ALL FINISHES DISTURBED AS A
RESULT OF NEW CONSTRUCTION. RESTORE PORTIONS
OF THE BUILDING AND/OR SITE TO CONDITIONS AS THEY
EXISTED PRIOR TO COMMENCEMENT OF CONSTRUCTION.
K. COORDINATE PHASING AND SEQUENCING OF
CONSTRUCTION WORK WITH GDRTA.
SUMMARY OF WORK
THE WORK IS GENERALLY LIMITED TO SERVER ROOM HVAC
UNIT REPLACEMENT AND ASSOCIATED ELECTRICAL TO
SUPPORT THE NEW WORK, UNLESS OTHERWISE NOTED IN
THESE DOCUMENTS.
THIS PROJECT IS NOT A CHANGE IN USE.
EXISTING USE GROUPS: A-3, B, AND E
EXISTING CONSTRUCTION TYPE: 2C
PROJECT LOCATION
R E
V D
R C
H K
D A
T E
D
E S
C R
IP
T
IO
N
5/16/2025
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
FURNISH LABOR, INSTALL MATERIALS AND EQUIPMENT, AND INCLUDE SERVICES AND
INCIDENTALS PROPER TO THE INSTALLATION OF WORK INVOLVED FOR A COMPLETE AND
OPERATING FACILITY.
GUARANTEE WORK TO BE FREE FROM DEFECTS IN MATERIAL AND WORKMANSHIP FOR A
PERIOD OF ONE YEAR AFTER DATE OF FINAL ACCEPTANCE OR AS REQUIRED BY
SPECIFICATIONS.
THE CONTRACTOR TO OBTAIN AND PAY FOR REQUIRED PERMITS, FEES AND
INSPECTIONS FOR THE PROJECT.
PROVIDE EQUIPMENT THAT BEARS ACCEPTANCE LABEL FROM CERTIFIED TESTING
LABORATORY (UL OR OTHER).
COORDINATE WITH OTHER TRADES, SPECS AND DRAWINGS, AND OWNER'S DIRECTIONS.
PRIOR TO BID, SURVEY JOB SITE TO OBTAIN A FULL UNDERSTANDING OF THE WORK
INVOLVED IN CONNECTION WITH EXISTING CONDITIONS. ADDITIONAL FEES WILL NOT BE
PAID FOR MISSING OR OVERLOOKED CONDITIONS REQUIRING ADDITIONAL WORK IF
DETERMINED BY THE ENGINEER THAT SAID CONDITIONS COULD HAVE BEEN
REASONABLY DETECTED DURING THE JOB SURVEY.
EQUIPMENT SELECTION AS SHOWN ON THE DRAWING IS FOR DESIGN PURPOSES ONLY.
ACTUAL INSTALLED EQUIPMENT MAY DIFFER FROM THAT SHOWN. EQUIPMENT
PERFORMANCE CHARACTERISTICS AND TYPE ARE THE GOVERNING FACTORS IN
SUBSTITUTION "OR EQUAL". COORDINATE EQUIPMENT ELECTRICAL REQUIREMENTS WITH
ELECTRICAL DRAWINGS.
THE MECHANICAL DRAWINGS ARE GENERALLY DIAGRAMMATIC AND SHOW THE
RELATIONSHIP BETWEEN EQUIPMENT AND CONNECTIONS. DO NOT SCALE THE
DRAWINGS FOR EXACT SIZE OR LOCATION. DETAILS AND ASSEMBLY DRAWINGS ARE
SPECIFIC AND SHOULD BE CLOSELY FOLLOWED.
INSTALL THE MECHANICAL SYSTEM IN ACCORDANCE WITH THE MANUFACTURER'S
RECOMMENDATION, 2024 OHIO BUILDING CODE, 2024 OHIO PLUMBING CODE, 2024 OHIO
MECHANICAL CODE, ETC.
INSTALL SLEEVES WHERE DUCTS OR PIPING PENETRATE FOUNDATION WALLS,
PARTITIONS, FLOOR OR ROOF. PACK AROUND SLEEVES AND SEAL WEATHER TIGHT.
INSTALL FLASHING AS REQUIRED.
UNLESS OTHERWISE NOTED, MOUNT WALL THERMOSTATS AT 4'-6" ABOVE FINISHED
FLOOR .
INTEGRATE EQUIPMENT MANUFACTURER PROVIDED CONTROLS WITH BAS IN
ACCORDANCE WITH SPECIFICATIONS AND MANUFACTURER'S RECOMMENDATIONS.
COORDINATE THE LOCATIONS OF EQUIPMENT TO PROVIDE NECESSARY CLEARANCES
FOR MAXIMUM PERFORMANCE AND MAINTENANCE.
SIZE REFRIGERANT LINES IN ACCORDANCE WITH DX EQUIPMENT MANUFACTURERS'
RECOMMENDATION, ASHRAE STANDARDS, APPLICABLE DETAILS AND SPECIFICATIONS,
WHERE CONDITIONS WARRANT, CONSIDER LENGTH OF RUN AND CHANGE IN ELEVATION
IN SIZING REFRIGERANT LINES. REFRIGERANT PIPE SIZES ON DRAWING ARE SHOWN FOR
REFERENCE ONLY.
GENERAL NOTES (MECHANICAL):
SUPPLY AIR CEILING DIFFUSER
RETURN AIR GRILLE / REGISTER
SIDEWALL SUPPLY AIR GRILLE/REGISTER
SIDEWALL RETURN AIR GRILLE/REGISTER
DUCT MT'D. SIDEWALL SUPPLY AIR GRILLE/REGISTER
SUPPLY DUCT RISE/DROP
RETURN DUCT RISE/DROP
EXHAUST DUCT RISE/DROP
TEMPERATURE / HUMIDITY SENSOR
SQUARE ELBOW WITH DOUBLE THICKNESS TURNING VANES
EMERGENCY POWER OFF SWITCH
DESCRIPTION ABBV.SYMBOL
HVAC LEGEND
FLEX.CONN.FLEXIBLE DUCT CONNECTOR
NEW DUCTWORK
EXISTING DUCTWORK TO BE REMOVED
EXISTING DUCTWORK TO REMAIN
MANUAL VOLUME DAMPER MVD
TS/HS
EPO
SUPPLY AIR
RETURN AIR
ABOVE FINISHED FLOOR
BOTTOM OF DUCT
CONNECT TO EXISTING
NOTE: DUCT RUNOUT TO
NECK SAME SIZE UNLESS
OTHERWISE NOTED
SA
RA
AFF
B.O.D.
DIFFUSER SCHEDULE
DIFFUSER NECK SIZE
CFM
##"Ø X-#
CFM
AIRFLOW DIRECTION SUPPLY
AIRFLOW DIRECTION RETURN / EXHAUST
THERMOSTATT
DESCRIPTION ABBV.SYMBOL
PIPING LEGEND
DCWDOMESTIC COLD WATER
CDCONDENSATE DRAIN
PIPE TURNED UP/DOWN
CAP OR PLUG
TEE
ELBOW
I.E. I.E.INVERT ELEVATION
HGREFRIGERANT LINE - HOT GAS
RLREFRIGERANT LINE - RETURN LINE
1.
2.
3.
4.
5.
6.
7.
8.
9.
COORDINATE ALL PHASES OF DEMOLITION WORK CLOSELY WITH OWNER. PROVIDE
OWNER WRITTEN NOTICE NO LESS THAN TEN (10) CALENDAR DAYS PRIOR TO
SHUTDOWN OF ANY PORTION OF MECHANICAL SYSTEM IN USE BY THE OWNER.
MAINTAIN DUST FREE SERVER ROOM DURING CONSTRUCTION. PROTECT ALL EXISTING
EQUIPMENT.
REMOVE AND DISPOSE OF DEMOLISHED MATERIALS OFF-SITE IN A MANNER
CONFORMING TO STATE AND LOCAL REGULATIONS AND AT NO ADDITIONAL EXPENSE TO
THE OWNER.
SCOPE OF DEMOLITION OF MATERIALS IDENTIFIED ON PLAN INCLUDES ANY ASSOCIATED
AUXILIARY MATERIAL NOT TO BE RE-USED. THIS INCLUDES, BUT IS NOT LIMITED TO:
INSULATION, HANGARS, MOUNTING BRACKETS, HANGAR ROD, CONDUIT, AND
CONDUCTORS.
DEMOLISH EXISTING CONTROLS MADE INOPERABLE BY SCOPE OF DEMOLITION. TURN
OVER CONTROL COMPONENTS TO OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO:
EQUIPMENT CONTROL PANELS, SENSORS, ACTUATORS, RELAYS, AND METERS.
WHERE SCOPE OF DEMOLITION WORK RESULTS IN AN OPEN WALL, FLOOR, OR ROOF
PENETRATION, PATCH OPENING WITH CONSTRUCTION MATCHING EXISTING ASSEMBLY
CONSTRUCTION OR AS APPROVED BY OWNER. WHERE ASSEMBLY IS FIRE RATED, PATCH
OPENINGS WITH U.L. LISTED METHOD THAT MAINTAINS FIRE RATING OF ASSEMBLY.
PRIOR TO DEMOLITION OF REFRIGERANT-CONTAINING EQUIPMENT, RECOVER AND
DISPOSE OF REFRIGERANT IN ACCORDANCE WITH EPA REQUIREMENTS. REFRIGERANT
RECOVERY SHALL BE PERFORMED BY AN EPA-LICENSED TECHNICIAN.
SERVER ROOM WALL & CEILING DEMOLITION AND REPAIR : AT NO ADDITIONAL COST TO
OWNER, ENGAGE THE SERVICES OF LICENSED CONTRACTOR TO REMOVE, RE-INSTALL,
AND PATCH GYPSUMBOARD WALL AND CEILING ASSEMBLIES IN SERVER ROOM. REMOVE
AND PATCH WALLS AND CEILINGS ONLY AS NEEDED TO IMPLEMENT DUCTWORK
DEMOLITION AND INSTALLATION OF NEW MECHANICAL DUCT AND PIPE. MAINTAIN
EXISTING RATED ASSEMBLIES. FINISH WALLS AND CEILINGS TO MATCH EXISTING
ASSEMBLIES. UPON COMPLETION OF WALL AND CEILING REPAIRS, PAINT PATCHED
CEILING AND WALLS TO MATCH ADJACENT ASSEMBLIES.
ROOF DEMOLITION AND REPAIR: AT NO ADDITIONAL COST TO OWNER, ENGAGE THE
SERVICES OF A LICENSED ROOFER TO REMOVE, RE-INSTALL, AND PATCH ROOM AS
NEEDED TO IMPLEMENT SCOPE OF WORK. ROOF PATCHING MEANS AND METHODS
SHALL CONFORM TO ANY ROOFING WARRANTY REQUIREMENTS.
GENERAL NOTES (DEMOLITION):
CRAC UNIT SCHEDULE
IDENT.
MANUFACTURER
MODEL NUMBER
TONS CFM ESP FAN HP
FILTER COOLING CAPACITY DX COOLING COIL REHEAT COIL INDOOR ELECTRICAL OUTDOOR ELECTRICAL WEIGHT (LBS)
REMARKS
AIR HANDLER COND. UNIT INDOOR UNIT OUTDOOR UNIT TYPE EFF TMBH SMBH AMBIENT
(DEG. F) REF TYPE SST KW STAGES FLA V/PH/HZ MOCP FLA V/PH/HZ MOCP INDOOR OUTDOOR
CRAC-1 ACCU-1 Vertiv/Liebert PX029DA1C809FV MCL055E1YD0WKQ 8 4300 0.5 4.15 2" PLEATED MERV 8 101 84 75 R-410A - 12 2 76.2 208/3/60 100 5.7 208/3/60 15 700 373 1,2,3,4,5,6,7,8,9,10,11,12,13,14
REMARKS:
1. LIEBERT ICOM CONTROLS, WITH WALL MOUNTED THERMOSTAT
2. DIGITAL SCROLL COMPRESSOR WITH VARIABLE SPEED EC FAN
3. UPFLOW TOP DISCHARGE MODEL WITH FLOOR RETURN
4. PROVIDE 24 INCH RETURN PLENUM STAND
5. FACTORY PROVIDED AND FIELD INSTALLED CONDENSATE PUMP POWERED BY UNIT
6. UNIT SMOKE DETECTOR AND CONTROLLER TO BE HARDWIRED TO THE RELEASING SYSTEM FIRE ALARM CONTROL PANEL
7. LOCKABLE DISCONNECT SWITCH
8. PROVIDE NETWORK INTERFACE CARD (BACNET) FOR FUTURE TIE-IN TO BUILDING MANAGEMENT CONTROL SYSTEM
9. MICROPROCESSOR BASED TEMPERATURE AND HUMIDITY CONTROLS
10. EXTERNAL STATIC PRESSURE (ESP) INCLUDES DIRTY FILTER LOSS
11. TOP SUPPLY PLENUM AND REAR RETURN PLENUM
12. PROVIDE AUXILIARY FLOAT SWITCH WITH AUTOMATIC UNIT SHUTOFF
13. UNIT POWER CONNECTED TO WALL MOUNTED EPO SWITCH
14. SYSTEM START-UP AND COMMISSIONING TO BE PROVIDED BY FACTORY
15. REMOTE HUMIDIFIER CONTACT
AIR DEVICE SCHEDULE
TAG DESCRIPTION MANUFACTURER MODEL NUMBER TYPE SIZE MOUNT NECK TYPE MAX NC LEVEL REMARKS
SG-1 SUPPLY GRILLE TITUS 300FL RECTANGULAR GRILLE, DOUBLE DEFLECTION
3/4" SPACING 24" X 12" DUCT RECTANGULAR 25 1,2,3,4
RG-1 RETURN GRILLE TITUS 350FL RECTANGULAR GRILLE, LOUVERED 3/4"
SPACING 24" X 16" DUCT RECTANGULAR 15 1,3,4
REMARKS
1. WHITE ENAMEL FINISH
2. ADJUSTABLE THROW DIRECTION
3. ALUMINUM CONSTRUCTION
4. NECK DAMPER
HUMIDIFIER SCHEDULE
AIRFLOW (CFM) DUCT SIZE W X H (IN)
WATER
CAPACITY
(LBS/HR)
EAT LAT ELECTRIC DATA
WEIGHT (LBS)
TAG DESCRIPTION LOCATION MANUFACTURER MODEL NUMBER SERVICE DB (F) WB (F) DB (F) WB (F) FLA V/PH/HZ REMARKS
H-1 ELECTRODE STEAM HUMIDIFIER MECHANICAL ROOM DRISTEEM XTP WSP 233 - 9 10.2 60.4 70.0 66.0 19 208/1/60 37 1,2,3,4
REMARKS:
1. PROVIDE STEAM DISPERSION UNIT REMOTE MOUNTED IN SERVER ROOM, MODEL NUMBER SDU-E (208/1/60, 17W)
2. PROVIDE NETWORK INTERFACE (BACNET) FOR FUTURE TIE-IN TO BUILDING MANAGEMENT CONTROL SYSTEM
3. HIGH LIMIT HUMIDITY TRANSMITTER IN SERVER ROOM
4. 1" DIAMETER STEAM HOSE
V
AN
G
UA
RD
B
LV
D M
IA
M
IS
BU
RG
, O H
PH
O
NE
(9 ) 4 -0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
5/ /2 9:
:3
AM
Au to de sk D oc s:
//3 G re at er D ay to n R
TA
S er ve r R oo m /3 _G D R
TA
SR
_M _V .rv t
M
EC
HA
NI
CA
L G
EN
ER
AL
N O
TE
S
AN
D
LE
G
EN
D
MG1-001
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R O O M C O O
LI
NG
S
YS
TE
M
M G 1- 1, M
EC
HA
NI
CA
L G
EN
ER
AL
N O
TE
S
AN
D
LE
G
EN
D
- G
EN
ER
AL
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
IO
N:
X1
MECHANICAL
ROOM
MEZZANINE
ELECTRICAL
ROOM
HALLWAY
KITCHEN & BREAK
ROOM
WOMEN'S
RESTROOM
MEN'S
RESTROOM
MIS
STAFF
DEMOLISH 3-TON
CRAC AND
ASSOCIATED PIPING
DEMOLISH 12" DIA
DUCT AND DIFFUSERS
(BOD = 8'-10")
EXISTING 1-HOUR FIRE-
RATED WALL. PATCH WALL
TO MATCH EXISTING
ASSEMBLY.
DEMOLISH ELEVATED 18"x18" DUCT
DEMOLISH 36"x24" GRILLE
SERVER ROOM
UP TO ROOF
DEMOLISH REFRIGERANT PIPING
UNIT HANGS FROM
OVERHEAD
STRUCTURE
FLOOR DRAIN
KEY PLAN
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
GENERAL NOTES
PLAN NORTH
5/
/2
9:
:3
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
W
SP
S
EC
O
ND
F
LO
O R
PL
AN
DE
M O
LI
TI
O N
MD1-101
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M D1
-1
W
SP
S
EC
O
ND
F
LO
O
R
PL
AN
DE
M
O
LI
TI
O
N
- D
EM
O
SCALE: 1/4" = 1'-0"MD1-101
1 WSP SECOND FLOOR PLAN - DEMOLITION
1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
DEMOLISH CONDENSING UNIT
DEMOLISH
REFRIGERANT PIPING
RETAIN PIPE
SUPPORTS FOR NEW
WORK PIPING.
DEMOLISH
DOGHOUSE
ABANDON SUPPORT RAIL IN
PLACE.
KEY PLAN
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
GENERAL NOTES
PLAN NORTH
5/
/2
9:
:3
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
W
SP
R O
O F
PL
AN
DE
M O
LI
TI
O N
MD1-102
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M D1
R
O O
F
PL
AN
DE
M
O
LI
TI
O
N
- D
EM
O
SCALE: 1/4" = 1'-0"MD1-102
1 WSP ROOF PLAN - DEMOLITION
1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
MECHANICAL
ROOM
MEZZANINE
ELECTRICAL
ROOM
HALLWAY
KITCHEN & BREAK
ROOM
WOMEN'S
RESTROOM
MEN'S
RESTROOM
MIS
STAFF
CRAC-1
H-1
EXISTING FLOOR DRAIN
HUMIDIFIER
DISPERSION UNIT
SERVER ROOM
MH4-001
UP TO ROOF
"x
" S
A
24"x18" SA
22"x24" RA
RG-1
RG-1
RG-1
RG-1
3/4" RL
1 1/8" HG
SG-1
SG-1
SG-1
SG-1
HG PIPE TO BE 7/8" IN VERTICAL
3/4" CD
RUNS ACROSS
FLOOR
PIPING FOLLOWS PATH OF
EXISTING PIPE.
KEY PLAN
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
GENERAL NOTES
PLAN NORTH
5/
/2
9:
:4
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
W
SP
S
EC
O
ND
F
LO
O R
PL
AN
MH1-101
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M H1
S
EC
O
ND
F
LO
O
R
PL
AN
PL
AN
S
SCALE: 1/4" = 1'-0"MH1-101
1 WSP SECOND FLOOR PLAN
1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
ACCU-1
EQUIPMENT CLEARANCE
1 1/8" HG
3/4" RL
PROVIDE NEW
DOGHOUSE
SUPPLEMENT EXISTING PIPE SUPPORTS
WITH NEW PRE-FAB NO-PENETRATION
TYPE SUPPORTS. MAXIMUM SUPPORT
SPACING SHALL BE 5 FEET O.C.
MOUNT ON NEW
EQUIPMENT RAILS
REFER TO
DETAIL
8/MH5-001
REFRIGERANT PIPING
PENETRATES ROOF AT
EXISTING PENETRATION
REFER TO DETAIL
6/MH5-001
KEY PLAN
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
GENERAL NOTES
PLAN NORTH
5/
/2
9:
:4
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
W
SP
R O
O F
PL
AN
MH1-102
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M H1
R
O O
F
PL
AN
PL
AN
S
SCALE: 1/4" = 1'-0"MH1-102
1 WSP ROOF PLAN
1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
CRAC-1
MAINTENANCE CLEARANCE
TYPICAL
MANUFACTURER
PROVIDED SUPPLY
PLENUM
MANUFACTURER PROVIDED
RETURN PLENUM
22"x24" RA
18"x30" SA
SG-1
12"x24" SA
18"x24" SA
12"x24" SA
SG-1
MH3-001
SERVER RACK
WORK STATION
RG-1
FLEXIBLE CONNECTION
FLEXIBLE CONNECTION
MH3-001
HUMIDIFIER
DISPERSION UNIT
RG-1
RG-1RG-1RG-1
24"x22" RA
CRAC-1
SERVER RACK
30"x18" SA
8' -4
"M
IN
PIPING CONTINUES
THROUGH EXISITING
WALL OPENING
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
5/
/2
9:
:4
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
W
SP
S
EC
TI
O
NS
MH3-001
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M H3
-0
S
EC
TI
O
NS
SE
CT
IO
NS
SCALE: 1/2" = 1'-0"MH3-001
1 WSP SERVER ROOM SECTION 1
SCALE: 1/2" = 1'-0"MH3-001
2 WSP SERVER ROOM SECTION 2
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
RG-1
RG-1
RG-1
RG-1
24"x16" RA
22"x24" RA
H-1
HUMIDIFIER
DISPERSION UNIT
CRAC-1
MAINTENANCE CLEARANCE
TYPICAL
24"x18" SA
30"x18" SA
SG-1
SG-1
SG-1
SG-1
SERVER RACKS
WORK STATION
RELOCATE
CAMERA. FINAL
LOCATION TO BE
APPROVED BY
RTA.
TIE IN TO EXISTING DCW
SERVER ROOM
MH3-001
MH3-001
DISCHARGE NOZZLE TO
BE LOCATED 8'-0" AFF
HT
RELOCATE CABLE TRAY HANGERS
MAINTAIN CLEARANCE FOR
CEILING ACCESS PANEL
1/2" CD
1 1/8" HG3/4" RL
3/8" DCW
3/4" CD
1/4" CD
1" DCW
CONTINUE REFRIGERANT
PIPING TO ROOF
TYPICAL
CONTINUE TO FLOOR DRAIN
PIPE PASSES THROUGH
WALL OPENING CREATED
BY DEMOLISHED DUCT.
SLEAVE AND SEAL AT
RATED ASSEMBLY PER
DETAILS ON SHEET
MH5-001.
PIPE PASSES THROUGH
EXISTING 1-HR RATER
WALL OPENING CREATED
BY DEMOLISHED DUCT
(SEE SHEET MD1-101).
SLEAVE AND SEAL AT
RATED ASSEMBLY PER
DETAILS ON SHEET
MH5-001.
KEY PLAN
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
GENERAL NOTES
PLAN NORTH
5/
/2
9:
:4
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
W
SP
E
NL
AR
G
ED
P
LA
NS
MH4-001
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M H4
-0
E
NL
AR
G
ED
P
LA
NS
EN
LA
RG
ED
PL
AN
S
SCALE: 1/2" = 1'-0"MH4-001
1 WSP SECOND FLOOR ENLARGED PLAN
1. REFER TO GENERAL NOTES AND DEMOLITION GENERAL NOTES ON SHEET MG1-001
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
NOTE:
THE ASSEMBLY IS BASED ON U.L. PENETRATION ASSEMBLY WALL C-AJ-5001.
INSTALL PENETRATION IN ACCORDANCE WITH IT'S LISTING.
PIPE MAY BE:
12" DIAMETER OR SMALLER SCHEDULE 10 OR HEAVIER STEEL PIPE. 4"
DIAMETER OR SMALLER COPPER PIPE (TYPE L OR HEAVIER).
12" DIAMETER OR SMALLER SERVICE WEIGHT OR HEAVIER CAST IRON
PIPE.
INSULATED PIPE
ESCUTCHEON
WHERE EXPOSED
TO VIEW
1" THICK FIBERGLASS
PIPE INSULATION
THROUGH WALL
MINIMUM 1" THICK
MINERAL WOOL BATT
INSULATION
MINIMUM 1" THICK FIRE
BARRIER CAULKING
PIPE SLEEVE
1/2" TO 1 1/2"
ANNULAR SPACE
NOTE:
THE ASSEMBLY IS BASED ON U.L. PENETRATION ASSEMBLY C-AJ-1175.
INSTALL PENETRATION IN ACCORDANCE WITH IT'S LISTING
PIPE MAY BE:
8" DIAMETER OR SMALLER SCHEDULE 10 OR HEAVIER STEEL PIPE. 6"
DIAMETER OR SMALLER COPPER PIPE (TYPE L OR HEAVIER).
4" DIAMETER OR SMALLER CAST IRON PIPE.
UNINSULATED PIPE
ESCUTCHEON
WHERE EXPOSED TO
VIEW
MINIMUM 1" THICK MINERAL
WOOL BATT INSULATION
MINIMUM 1/2" THICK FIRE BARRIER CAULKING. IN
ADDITION, APPLY MINIMUM OF 1/4" BEAD OF CAULK AT
POINT OF CONTACT TO WALL (BOTH SIDES)
THROUGH WALL
PIPE SLEEVE
1 3/8" MAXIMUM
ANNULAR SPACE
HANGER ROD
ADJUSTABLE
CLEVIS MSS
SP-58 TYPE 1
ANVIL FIG. 260
OR EQUAL.
LOCK NUT
PIPE
HANGER ROD
ADJUSTABLE
CLEVIS MSS
SP-58 TYPE 1
LOCK NUT
PIPE
INSULATION
PROTECTION
SHIELD (180°)
MSS SP-58
TYPE 40
HIGH DENSITY ASBESTOS FREE
INSULATION, VAPOR BARRIER SEALED,
CONTINUOUSLY
NOTE:
VAPOR BARRIER SHALL EXTEND 2 INCHES BEYOND THE
PROTECTION SHIELD AND OVERLAP THE OUTSIDE
CIRCUMFERENCE BY 2 INCHES.
FOR PIPE SIZES TO: 20"
TEMPERATURES TO: 100° F. MAXIMUM
AXIAL MOVEMENT: 1"
FOR PIPE SIZES TO: 20"
TEMPERATURES TO: 100° F. MAXIMUM
AXIAL MOVEMENT: 1"
BARE PIPE INSULATED COLD PIPE
HANGER STRAPS
STRAPS TO BE TIGHT AGAINST DUCT
SELF TAPPING CADMIUM PLATED HEX
HEAD SHEET METAL SCREWS (TYP.)
SUPPORT ANGLE
(SEE NOTE 1)
HANGER ROD,
(SEE NOTE 1).
NOTE 1:
SEE SMACNA "HVAC DUCT CONSTRUCTION STANDARDS-
METAL AND FLEXIBLE" CHAPTER 5, FOR MINIMUM HANGER
SIZE AND SUPPORT SPACING FOR RECTANGULAR DUCT.
1/4"x1/4" HEX HEAD
LAG BOLT (WOOD
TRUSS ONLY)
TRUSS CORD OR
ROOF SUPPORT MEMBER
LOCK -NUT & WASHER
SCORE THREADS
(BAR-JOIST ONLY)
INSULATION
TRAPEZE TYPE HANGER STRAP TYPE HANGER
INSULATION
SIDE VIEW END SECTION VIEW
NOTE:
L=1/4 W (4" MIN.)
AIR FLOW
CLINCH COLLAR
(PER SMACNA)
BALANCING DAMPER
(AIR EXTRACTOR IS NOT REQUIRED WITH 45° COLLAR FITTING)
45°
W
L
RETURN
SUPPLY
VA
R
IE
S
(8 " T
AL
L
M
IN
IM
U
M
SPACING AS REQUIRED FOR UNIT DIMENSIONS
6" WIDE (NOMINAL)
4" TALL WOOD
NAILER (MINIMUM)
ATTACH CU TO SUPPORT RAILS
TO ANCHOR EQUIPMENT AND
RESIST WIND FORCES MINIMUM
TEK 1/4"-20 SDS @ 12"
JOIST PERPENDICULAR TO RAIL
ROOFING
EXTEND ROOF
MEMBRANE OVER
RAIL.
PREFABRICATED ROOF RAILS
ATTACH TO METAL DECK AND
JOIST WITH SUPPLIER SPECIFIED
CONNECTIONS. MINIMUM TEK
1/4"-20 SDS @12" ON ALL SIDES OF
EACH RAIL.
PROVIDE RAIL CAP. LENGTH OF
RAIL AS REQUIRED FOR
CONDENSING UNIT DIMENSIONS.
EACH END OF RAIL SHALL
EXTEND TO NEAREST JOIST.
TIMBER BLOCKING (TYP.)
L6x4x5/16 LLH SUPPORT
ANGLE (TYP.)
EXISTING
ROOF DECK
JOIST TOP
CHORD
3/16
20 GAUGE GALVANIZED SHEET
METAL WELDED WEATHERHOOD
WITH 1 1/2" THICK POLYISO
INSULATION
24" MIN.
D
EG
1" # 8 SCREW,
MIN. 2 PER SIDE
18"x18"x30" HIGH
MANUFACTURED
ROOF CURB
FILL SPACE WITH
INSULATION
ROOF
PIPES
PENETRATE
ROOF CURB
WITH PIPES
FRAME OPENING WITH
2 1/2"x2 1/2"x5/16"
ANGLE STEEL WELDED
TO ROOF FRAMING
SEE ARCHITECTURAL
DRAWINGS FOR ROOF
PENETRATION DETAIL
HUMIDIFIER
STEAM
GENERATOR
HUMIDIFIER
DISPERSION UNIT
12" MINIMUM
1" AIR GAP
3/4" DRAIN PITCH 1/8" PER FT
TOWARD DRAIN
3/4" DCW SUPPLY
CONDENSATE HOSE
WATER SEAL
DISCHARGE TO
OPEN DRAIN
1" MFG SUPPLIED
STEAM HOSE
HOSE CLAMP
PROVIDE COPPER TUBING
FOR PENETRATION OF 1-HR
RATED ASSEMBLYCONDENSING UNIT
INCLUDES FACTORY
PROVIDED INVERTED
TRAP. NO EXTERNAL
TRAP REQUIRED.
PRESSURE
TRANSDUSER
LIQUID
OPTIONAL FIELD
INSTALLED
FUSIBLE PLUG
HOT GAS
DISCHARGE
INTERCONNECTING
PIPING
TRAP AT BASE
OF RISERS OVER
5FT.
FOR RISERS OVER
25FT., TRAP EVERY 20
FT. OR EVENLY
DIVIDED.
CRAC
(EVAPORATOR)
1.
2.
NOTES:
TRAPS MUST BE INSTALLED AND HORIZONTAL LINES PITCHED TO
ENSURE PROPER OIL RETURN AND TO REDUCE LIQUID
FLOODBACK TO COMPRESSOR. PITCH HORIZONTAL HOT GAS
PIPING AT A MINIMUM OF 1/2" PER 10 FEET SO THAT GRAVITY WILL
AID IN MOVING OIL IN THE DIRECTION OF THE REFRIGERATION
FLOW.
DO NOT ISOLATE ANY REFRIGERANT CIRCUITS FROM OVER
PRESSURIZATION PROTECTION.
V
AN
G
UA
RD
B
LV
D
M
IA
M
IS
BU
RG
, O
H
PH
O
NE
(9
) 4
-0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O
N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
5/
/2
9:
:4
AM
Au to de sk
D oc s:
//3
G re at er
D ay to n
R
TA
S er ve r R oo m
/3
_G D
R
TA
SR
_M
_V
.rv t
DE
TA
IL
S
MH5-001
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R
O O
M C
O O
LI
NG
S
YS
TE
M
M H5
-0
DE
TA
IL
S
- D
ET
AI
LS
NTSMH5-001
2 FIRE RATED PIPE PENETRATION (INSULATED PIPE)
NTSMH5-001
3 FIRE RATED PIPE PENETRATION (UNINSULATED PIPE)
NTSMH5-001
1 PS-X CLEVIS HANGER
NTSMH5-001
4 DUCT HANGER SUPPORT
NTSMH5-001
5 BRANCH DUCT CONNECTION
NTSMH5-001
8 ROOFTOP EQUIPMENT SUPPORT RAIL DETAIL
NTSMH5-001
6 PIPE PENETRATION THRU ROOF
NTSMH5-001
9 HUMIDIFIER PIPING DIAGRAM
NTSMH5-001
7 REFRIGERANT PIPING DIAGRAM
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
T
TT TT
BINARY INPUT
BINARY OUTPUT
ANALOG INPUT
CONTROLS ABBREVIATION
DESCRIPTION
BI
BO
AI
ABBV.
ANALOG OUTPUT
SUPPLY AIR
RETURN AIR
AO
SA
RA
TEMPERATURE T
VARIABLE FREQUENCY DRIVEVFD
BUILDING AUTOMATION SYSTEMBAS
DESCRIPTIONSYMBOL
CONTROLS LEGEND
THERMOSTAT
HUMIDISTAT
T
H
CENTRIFUGAL FAN
E
C
DX
C
ELECTRIC COIL
DX COOLING COIL
AIR FILTER
DUCT TEMPERATURE SENSOR
1. GENERAL:
THE COMPUTER ROOM AIR HANDLING (CRAC) UNIT CONSISTS OF RETURN AIR FILTERS, DX COOLING
COIL, ELECTRIC REHEAT COIL, AND SUPPLY FAN.
THE COMPUTER ROOM AIR HANDLING UNIT SHALL BE CONTROLLED THROUGH A FACTORY
PROGRAMMED APPLICATIONS CONTROLLER.
THE CRAC UNIT SHALL OPERATE AS A SINGLE ZONE VARIABLE AIR VOLUME UNIT.
THE CRAC UNIT SHALL OPERATE AS NECESSARY TO SATISFY SPACE TEMPERATURE SETPOINTS 24/7.
SPACE TEMPERATURE SETPOINT SHALL BE 74°F (ADJUSTABLE) FOR COOLING AND 70°F (ADJUSTABLE)
FOR HEATING.
THE CRAC UNIT SHALL OPERATE AS NECESSARY TO SATISFY MAXIMUM HUMIDITY SETPOINTS 24/7.
SPACE MAXIMUM HUMIDITY SETPOINT SHALL BE 65%RH (ADJUSTABLE). ANY REQUIREMENT TO
INCREASE HUMIDITY MUST BE MET BY THE STAND ALONE HUMIDIFIER.
ALL ALARMS SHALL BE MONITORED BY THE CRAC UNIT CONTROLLER AND SIGNALED TO THE DDC
FRONT END.
2. SUPPLY FAN:
OPERATION:
IN COOLING OR DEHUMIDIFICATION MODE, AND UPON A CALL FOR COOLING, THE SUPPLY FAN VFD SHALL BEGIN OPERATION AT 30% AND MODULATE BETWEEN 30% AND 100% AS NEEDED TO MAINTAIN
THE SPACE TEMPERATURE SETPOINT.
IN HEATING MODE, AND UPON A CALL FOR HEATING, THE SUPPLY FAN VFD SHALL BEGIN OPERATION
AT 50% AND MODULATE BETWEEN 50% AND 100% AS NEEDED TO MAINTAIN THE SPACE
TEMPERATURE.
SUPPLY FAN OPERATION SHALL BE VERIFIED THROUGH UNIT CONTROLLER. IF THE SUPPLY FAN IS
NOT OPERATIONAL, THE UNIT CONTROLLER SHALL SIGNAL AN ALARM TO THE DDC PANEL.
3. DX COOLING COIL:
OPERATION:
COMPRESSOR SHALL MODULATE TO MAINTAIN LEAVING COIL TEMPERATURE SETPOINT OF 55°F
(ADJUSTABLE). ALARM SHALL BE SENT TO THE DDC IF THE SUPPLY AIR TEMPERATURE DROPS BELOW
40°F (ADJUSTABLE). MANUAL RESET IS REQUIRED.
4. ELECTRIC REHEAT COIL:
OPERATION:
ELECTRIC REHEAT COIL SHALL BE STAGED TO MAINTAIN SPACE TEMPERATURE OR SPACE RELATIVE HUMIDITY SETPOINT. ALARM SHALL BE SENT TO THE DDC IF THE SUPPLY AIR TEMPERATURE DROPS BELOW 40°F (ADJUSTABLE). UNIT SHALL SHUT UPON ALARM SIGNAL BEING SENT. MANUAL RESET IS
REQUIRED.
SEQUENCE OF OPERATION - CRAC-1/ACCU-1:
5. HUMIDITY CONTROL:
UPON DROP IN SPACE HUMIDITY BELOW 45% (ADJ.), REMOTE HUMIDITY CONTACTOR SHALL CLOSE TO
ENABLE HUMIDIFICATION BY REMOTE HUMIDIFIER (H-1).
6. FILTER MAINTENANCE:
DIFFERENTIAL PRESSURE SWITCH WITH SENSOR TAPS ON UPSTREAM AND DOWNSTREAM SIDE OF
THE MAIN FILTER BANKS SHALL SIGNAL CRAC UNIT CONTROLLER WHEN THE DIFFERENTIAL RESSURE IS EQUAL TO OR GREATER THAN THE SET POINT OF 0.5 IN WG. THE CONTROLLER SHALL INITIATE A
MAINTENANCE ALARM SIGNAL INDICATING A DIRTY FILTER.
7. FIRE ALARM SIGNAL:
ANY SIGNAL FROM THE FIRE ALARM SYSTEM DEDICATED TO THE SERVER ROOM SHALL DE-ENERGIZE
THE SUPPLY FAN, AND NOTIFY THE DDC SYSTEMS. THE DDC SYSTEM SHALL RETURN ALL
CONTROLLED ITEMS TO THEIR SHUTDOWN POSITION. MANUAL RESET IS REQUIRED.
8. BAS MONITORING POINTS:
AT TIME OF INSTALLATION, A DDC SYSTEM WILL NOT BE AVAILABLE TO CONNECT TO; HOWEVER, PROVISIONS SHOULD BE MADE FOR FUTURE CONNECTION. ONCE A DDC SYSTEM IS AVAILABLE, THE CRAC UNIT CONTROLLER SHALL COMMUNICATE THE FOLLOWING POINTS TO BE MONITORED BY THE
DDC SYSTEM VIA A BACNET PROTOCOL:
· SPACE TEMPERATURE
· SPACE HUMIDITY
· ALARM STATUS (GENERAL)
· COMPRESSOR PERCENTAGE
· ELECTRIC REHEAT COIL LEAVING AIR TEMPERATURE
· UNIT LEAVING AIR TEMPERATURE
9. ALARMS:
THE CRAC UNIT CONTROLLER SHALL BE ABLE TO COMMUNICATE THE FOLLOWING ALARMS TO THE
DDC SYSTEM:
· SUPPLY FAN FAILURE
· HIGH SUPPLY AIR TEMPERATURE ALARM (120°F) (ADJUSTABLE)
· LOW SUPPLY AIR TEMPERATURE ALARM (40°F) (ADJUSTABLE)
· HIGH SPACE TEMPERATURE ALARM (85°F) (ADJUSTABLE)
· DIRTY FILTER ALARM
· FIRE ALARM SIGNAL
VFD
DX
C
SUPPLY
AIR
RETURN
AIR
DPS
FACTORY
MOUNTED
INTEGRAL
CONTROLS
BI BICOMPUTER ROOM AIR
HANDLING UNIT
E
C
AI
AO AOBO
T
AI
SPACE
TEMPERATURE
SENSOR
OUTDOOR
CONDENSER
COMPRESSOR
H
AI
SPACE HUMIDITY
SENSOR
REMOVE HUMIDIFIER CONTACT
TO REMOTE
HUMIDIFIER
MASTER ENABLE
H-1
DISPERSION
UNIT
208V
SERVER ROOMMECHANICAL
ROOM
W
AL
L
AI
H
AI
UNIT MOUNTED
MANUFACTUER
CONTROL PANEL
TO BUILDING
CONTROL PANEL
(FUTURE)
DISPERSION UNIT
POWER CONNECTION
STEAM PIPE
1. GENERAL:
THE HUMIDIFIER CONSISTS OF A STEAM GENERATOR AND STEAM DISPERSION UNIT.
THE HUMIDIFIER SHALL BE CONTROLLED THROUGH A FACTORY PROGRAMMED
APPLICATIONS CONTROLLER.
THE HUMIDIFIER SHALL OPERATE AS NECESSARY TO SATISFY SPACE HUMIDITY SETPOINTS
24/7. SPACE HUMIDITY SETPOINT SHALL BE 40%RH (ADJUSTABLE).
ALL ALARMS SHALL BE MONITORED BY THE CRAC UNIT CONTROLLER AND SIGNALED TO
THE DDC FRONT END.
2. OPERATION:
UPON A CALL FOR HUMIDIFICATION, THE UNIT SHALL BEGIN OPERATION AND RUN AS
NEEDED TO MAINTAIN THE SPACE HUMIDITY SETPOINT.
3. MAINTENANCE:
DRAIN/FILL AND FLUSH CYCLES SHALL BE INITIATED AUTOMATICALLY BY UNIT
CONTROLLER.
4. BAS MONITORING POINTS:
THE HUMIDIFIER UNIT CONTROLLER SHALL COMMUNICATE THE FOLLOWING POINTS TO BE
MONITORED BY THE DDC SYSTEM THROUGH A BACNET PROTOCOL:
· SPACE HUMIDITY
· ALARM STATUS (GENERAL)
5. ALARMS:
THE HUMIDIFIER UNIT SHALL COMMUNICATE ALL ALARMS TO THE DDC SYSTEM.
SEQUENCE OF OPERATION - H-1:
MASTER
ENABLE
INPUT
HUMIDIFIER
ENABLE
SWITCH FROM
CRAC UNIT
V
AN
G
UA
RD
B
LV
D M
IA
M
IS
BU
RG
, O H
PH
O
NE
(9 ) 4 -0
Ti m e / D at e:
SHEET:
Fi le
RE
VI
SI
O N
IN
FO
RM
AT
IO
N
Dr aw in g:
Di sc ip lin e So rt:
5/ /2 9:
:4
AM
Au to de sk D oc s:
//3 G re at er D ay to n R
TA
S er ve r R oo m /3 _G D R
TA
SR
_M _V .rv t
CO
NT
RO
L
DI
AG
RA
M S
MH8-001
G
RE
AT
ER
D
AY
TO
N
RE
G
IO
NA
L
TR
AN
SI
T
AU
TH
O
RI
TY
W
RI
GH
T
ST
OP
P
LA
ZA
S.
M
AI
N
ST
RE
ET
DA
YT
ON
, O
HI
O
FILE NO: 3761614
SE
RV
ER
R O O M C O O
LI
NG
S
YS
TE
M
M H8 -0
CO
NT
RO
L
DI
AG
RA
M S
- C O
NT
RO
LS
NTSMH8-001
1 CRAC CONTROL DIAGRAM
NTSMH8-001
2 HUMIDIFIER CONTROL DIAGRAM
RE
V
DR
CH
K
DA
TE
DE
SC
RI
PT
SURFACE MOUNTED FLOOR BOX W/ NEMA 5-20 DUPLEX RECEPTACLE
UNLESS NOTED OTHERWISE
SURFACE MOUNTED FLOOR BOX W/ NEMA 5-20 QUAD RECEPTACLE
UNLESS NOTED OTHERWISE
POWER
A AMPERE
AC ABOVE COUNTER / ALTERNATING CURRENT
ACS ACCESS CONTROL SYSTEM
ADA AMERICANS WITH DISABILITIES ACT
AF AMPS FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIM ADRESSABLE INPUT MODULE
AL ALUMINUM
AOM ADDRESSABLE OUTPUT MODULE
AT AMPS TRIP
ATS AUTO TRANSFER SWITCH
A/V AUDIO/VISUAL
AWG AMERICAN WIRE GAUGE
#/C # OF CONDUCTOR(S)
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CAPTION TELEVISION CAMERA
CKT CIRCUIT
COMM COMMUNICATIONS
CR CARD READER
CU COPPER
DC DIRECT CURRENT
DIM DIMENSION
DISC DISCONNECT
DP DISTRIBUTION PANEL
(E) EXISTING TO REMAIN
EF EXHAUST FAN
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EWC ELECTRICAL WATER COOLER
F PULL STATION
FE FURNISHED EQUIPMENT
FACP FIRE ALARM CONTROL PANEL
FAA FIRE ALARM ANNUNCIATOR
FM FREQUENCY MODULATION
FS FLOW SWITCH
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
HVAC HEATING, VENTILATION, AND AIR CONDITIONING
HP HORSEPOWER
HS HORN STROBE
HT HEIGHT
HZ HERTZ
J JUNCTION BOX
KAIC KILOAMPS INTERRUPTING CAPACITY
KVA KILO-VOLT AMPERES
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
LTG LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MTD MOUNTED
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NF NON-FUSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
OS OCCUPANCY SENSOR
PH PHASE
PIR PASSIVE INFRARED
PIV PRESSURE INDICATING VALVE
PP POWER PACK RECEPTACLE
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
RGS RIGID GALVANIZED STEEL
RP RECEPTACLE PANEL
RSFACU RELEASING SYSTEM FIRE ALARM CONTROL UNIT
RTA RADIO TRANSMITTER
SEC SECONDARY
SPD SURGE PROTECTION DEVICE
SNAC SUPERVISED NOTIFICATION APPLIANCE CIRCUIT
SS STAINLESS STEEL
SW SWITCH
SWBD SWITCHBOARD
TGB TELECOMMUNICATIONS GROUNDING BAR
TS TAMPER SWITCH
TV TELEVISION/MONITOR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT
VA VOLTAMPERE
VFD VARIABLE FREQUENCY DRIVE
W WATTS
WP WEATHERPROOF IN USE COVER
XFMR TRANSFORMER
XP EXPLOSION PROOF
ABBREVIATIONS
FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT
BASED ON MANUFACTURERS RECOMMENDATIONS
NEMA 5-20 DUPLEX RECEPTACLE (FLUSH/SURFACE) MOUNTED 18" AFF
JUNCTION BOX
UNFUSED DISCONNECT SWITCH. SIZE AS INDICATED ON DRAWINGS
SURFACE MOUNTED PANELBOARD. REFER TO PANEL SCHEDULES
FOR VOLTAGE CONFIGURATION. CROSS HATCHED AREA IN FRONT
OF PANELBOARD INDICATES EXTENT OF WORKING CLEARANCE.
LINE-FILLED BOX INIDICATES 480/277V PANEL AND SOLID-FILLED
INDICATES 208/120V PANEL.
MOTOR, # INDICATES MOTOR HP, F INDICATES FRACTIONAL
HORSEPOWER.
J
RECESSED MOUNTED PANELBOARD. LINE INDICATES WALL FACE.
REFER TO PANEL SCHEDULES FOR VOLTAGE CONFIGURATION.
CROSS HATCHED AREA IN FRONT OF PANELBOARD INDICATES
EXTENT OF WORKING CLEARANCE. LINE-FILLED BOX INIDICATES
480/277V PANEL AND SOLID-FILLED INDICATES 208/120V PANEL.
SPECIALTY RECEPTACLE. REFER TO KEYED NOTES FOR ADDITIONAL
INFORMATION.
MOTOR RATED, 20 AMP, 125 VOLT TOGGLE SWITCH
NEMA 5-20 SIMPLEX RECEPTACLE (FLUSH OR SURFACE) MOUNTED
18" AFF UNLESS NOTED OTHERWISE.
COMBINATION STARTER / DISCONNECT SWITCH. SIZE FOR
EQUIPMENT BASED ON MANUFACTURERS RECOMMENDATIONS
AV
SURFACE MOUNTED FLOOR BOX WITH NEMA 5-20 QUAD RECEPTACLE,
COMBINATION TELEPHONE/DATA, AND A/V JACKS. REFER TO
KEYED NOTE FOR SIZING AND ACCESSORIES.
M
BREAKER
LOAD CENTER WITH INTEGRAL TRANSFORMER
CURRENT TRANSFORMER (SHOWN AROUND FEEDER)
POTENTIAL TRANSFORMER (PT)
DIGITAL POWER METER. "A" INDICATES AMMETER ON
CT'S FOR FEEDER BREAKER
DPM
FUSE
SPD SURGE PROTECTION DEVICE
A AMMETER
PULL BOX. SUPERSCRIPT DENOTES TYPE OF PULL BOX:
P - POWER; F - FIBER OPTIC; L - LIGHTING CIRCUIT.
K KIRK KEY
VFD
X
VARIABLE FREQUENCY DRIVE
M METER
SINGLE POLE SWITCH
CP CONTROL PANEL
OVERLOAD SWITCH
MCC
TRANSFORMER (PLAN VIEWS)
MOTOR, HP NOT INDICATED.M
NEMA 5-20 QUAD RECEPTACLE (FLUSH/SURFACE) MOUNTED 18" AFF
P,F,L
POWER POLEPP
XX
PNL PANEL BOARD
A
GENERATOR.G
PB
V2
V1
TX
XX kVA
TRANSFORMER. "V1" INDICATES PRIMARY VOLTAGE,
"V2" INDICATES SECONDARY VOLTAGE, "TX"
INDICATES THE TRANSFORMER NAME, "XX kVA" IS
THE TRANSFORMER RATING.
STARTER. REFER TO SCHEDULE FOR
ADDITIONAL STARTER OPTIONS
AC
GFI
WP
CS
REF
UNLESS NOTED OTHERWISE. (AC INDICATES ABOVE COUNTER,
GFI INDICATES GROUND FAULT CIRCUIT INTERRUPTER, WP INDICATES
WEATHERPROOF IN-USE COVER, CS INDICATES CHILD SAFE, REF
INDICATES UNDERCOUNTER/FULL SIZE REFRIGERATOR.)
UNLESS NOTED OTHERWISE. (AC INDICATES ABOVE COUNTER,
GFI INDICATES GROUND FAULT CIRCUIT INTERRUPTER, WP INDICATES
WEATHERPROOF IN-USE COVER, CS INDICATES CHILD SAFE, REF
INDICATES UNDERCOUNTER/FULL SIZE REFRIGERATOR.)
DRAWOUT BREAKER
C CONTACTOR
TIME SWITCH
PUSHBUTTON
TS
SS
SWITCHED RECEPTACLE.
AC
GFI
WP
CS
REF
AC
GFI
WP
CS
REF
AC
GFI
WP
CS
REF
PP
POWER PACK, ON/OFF CONTROL (** = RECEPTACLE DESIGNATION);
SEE ELECTRICAL DETAILS FOR WIRING DIAGRAM
1. SOME SYMBOLS SHOWN ON THIS SHEET MIGHT NOT BE USED ON THIS
PROJECT.
2. INSTALLATION SHALL CONFORM TO THE APPLICABLE REQUIREMENTS OF
NFPA 70, NATIONAL ELECTRICAL CODE 2023 ALONG WITH APPLICABLE UFC
REQUIREMENTS.
3. CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES DURING
CONSTRUCTION.
4. THE DRAWINGS ARE DIAGRAMMATIC AND ARE NOT INTENDED TO INCLUDE
EVERY DETAIL OF REQUIRED CONSTRUCTION EQUIPMENT AND MATERIALS.
PROVIDE ALL LABOR, MATERIALS AND EQUIPMENT NOT SPECIFICALLY SHOWN
ON THE DRAWINGS BUT WHICH ARE NECESSARY TO COMPLETE THE WORK.
INSTALLATION SHALL BE COORDINATED WITH PIPING, DUCTWORK,
STRUCTURAL STEEL ALONG WITH ROOM FINISHES.
5. CONDUIT ROUTING IS DIAGRAMMATIC. ROUTE PARALLEL AND
PERPENDICULAR TO LINES OF BUILDING STRUCTURE. FIELD VERIFY EXACT
ROUTING PER ACTUAL CONDITIONS. MINIMUM ACCEPTABLE CONDUIT SIZE IS
¾” ABOVE GRADE AND 1” UNDERGROUND.
6. CIRCUIT AMPACITY RATINGS ARE BASED ON RACEWAYS NOT EXCEEDING (3)
CURRENT-CARRYING CONDUCTORS PLUS NEUTRAL CONDUCTORS AND
EQUIPMENT GROUND CONDUCTOR PER NEC CODE. A SEPARATE NEUTRAL
CONDUCTOR SHALL BE PROVIDED FOR EACH CURRENT CARRYING
CONDUCTOR.
7. BOND ALL INTERIOR METALLIC PIPING SYSTEMS, INCLUDING NATURAL GAS, IN
ACCORDANCE WITH NFPA 70-250 REQUIREMENTS.
8. PROVIDE A GREEN-INSULATED GROUNDING CONDUCTOR, SIZED PER NEC
ARTICLE 250, IN ALL FEEDER AND BRANCH CIRCUIT RACEWAYS.
9. FIRE SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS.
10. DO NOT USE ANY LIGHT FIXTURE AS A RACEWAY FOR CONDUCTORS NOT
SERVING FIXTURE, UNLESS FIXTURE IS DESIGNATED AND UL-LISTED FOR USE
AS A RACEWAY.
11. COORDINATE EXACT LOCATION AND MOUNTING HEIGHT OF ELECTRICAL
OUTLETS WITH CASEWORK, FURNITURE AND MILLWORK. REFER TO
ARCHITECTURAL PLANS AND ELEVATIONS FOR DETAILS.
12. DO NOT ATTACH STARTERS AND DISCONNECTS FURNISHED FOR HVAC
EQUIPMENT DIRECTLY TO EQUIPMENT. PROVIDE WALL-MOUNT SUPPORT OR
INDEPENDENTLY SUPPORT ON STEEL ANGLE OR UNISTRUT RACK
CONSTRUCTED FOR THAT PURPOSE. LOCAL DISCONNECTS FOR HVAC
EQUIPMENT SHALL BE FURNISHED SEPARATELY FROM THE HVAC EQUIPMENT.
13. VERIFY EXACT MECHANICAL EQUIPMENT TO BE INSTALLED. ADJUST
CONDUIT, WIRING, DISCONNECT SIZE AND FUSING PER MANUFACTURER
FINAL REQUIREMENTS FOR ACTUAL EQUIPMENT INSTALLED.
14. CONTRACTOR SHALL VISIT THE PROJECT SITE AND CAREFULLY EXAMINE
THOSE PORTIONS OF THE SITE AFFECTED BY THIS WORK TO BECOME
FAMILIAR WITH EXISTING CONDITIONS THAT MAY AFFECT EXECUTION OF THE
WORK.
15. “PROVIDE” IS AN ALL-INCLUSIVE TERM REQUIRING THE CONTRACTOR TO
FURNISH, INSTALL, WIRE AND CONNECT ALL SPECIFIED EQUIPMENT AS WELL
AS COMPONENTS, ACCESSORIES, AND MOUNTING HARDWARE TO MEET
SYSTEM REQUIREMENTS.
16. “INSTALL” SPECIFIES THAT THE CONTRACTOR SHALL INSTALL EQUIPMENT
PROVIDED BY OTHERS. THE CONTRACTOR SHALL PROVIDE ALL ANCILLARY
EQUIPMENT FOR A COMPLETE INSTALLATION.
17. CONTRACTOR SHALL PROVIDE ARC-FLASH CALCULATIONS FROM A
REGISTERED ELECTRICAL ENGINEER. THE CONTRACTOR SHALL PROVIDE
ARC-FLASH LABELS FOR ELECTRICAL EQUIPMENT, MCC'S, DISCONNECTS,
PANELBOARDS, ETC. SEE SPECIFICATIONS FOR ARC-FLASH LABEL
REQUIREMENTS.
E-STOP PUSHBUTTON
C SECURITY CAMERA
18. THE EXISTING CONDITIONS SHOWN ARE FROM AVAILABLE RECORD DRAWINGS AND
SHOWN FOR REFRENCE ONLY. CONTRACTOR SHALL VERIFY ALL EXISTING
CONDITIONS PRIOR TO WORK BEGINNING. THE CONTRACTOR IS RESPONSIBLE FOR
INFORMING THE ELECTRICAL ENGINEER OF ANY CONDITIONS THAT DIFFER FROM
THE INFORMATION INDICATED IN THE DRAWINGS.
19. LOCATION OF EXISTING EQUIPMENT, CONDUITS, OUTLETS, DEVICES, CONTROLS
AND ALL CONCEALED WORKS, ETC. ARE APPROXIMATE.
20. ALL EXISTING ELECTRICAL EQUIPMENT SHOWN TO BE REMOVED SHALL BE
REMOVED BY THE CONTRACTOR. EXISTING FIXTURES AND EQUIPMENT
CONSIDERED SALVAGEABLE BY THE OWNER AND NOT SHOWN TO BE REUSED
SHALL BE TURNED OVER TO THE OWNER OR REMOVED FROM SITE AS DIRECTED
BY OWNER.
21. THE CONTRACTOR IS TO PROTECT THE EXISTING TO REMAIN LIGHTING FIXTURES,
ELECTRICAL EQUIPMENT, DEVICES, AND FEEDERS.
22. DEMOLITION WORK SHALL BE DONE IN A MANNER WHICH WILL NOT CAUSE
UNNECESSARY INCONVENIENCE OR DANGER TO USERS, AND NOT INTERFERE
WITH ITS OPERATION. ANY DEMOLITION WORK TO BE PERFORMED MUST BE
PLANNED IN ADVANCE AND COORDINATED WITH THE OWNER.
23. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDUIT/WIRING RUNS, REUSE
AS REQUIRED, AND REMOVE ALL UNUSED CONDUIT/WIRING. UNUSED CONDUIT IN
INACCESSIBLE LOCATIONS (WALLS TO REMAIN) MAY BE ABANDONED IN PLACE.
REMOVE UNUSED WIRING INCLUDING ABANDONED TELEPHONE, DATA AND OTHER
LOW VOLTAGE SYSTEMS CABLING AFTER CONFIRMING WITH THE OWNER THAT
CABLING IS ABANDONED AND WILL NOT BE RE-USED.
24. CONTRACTOR TO VERIFY CIRCUIT NUMBER AND LOADS FOR ALL ELECTRICAL
EQUIPMENT PRIOR TO INSTALLATION OF NEW OR RELOCATED ELECTRICAL
EQUIPMENT. REASSIGN CIRCUITS AND LOADS ACCORDINGLY. PROVIDE COMPLETE
"AS BUILT" DRAWINGS AND TYPEWRITTEN DIRECTORIES FOR AFFECTED PANELS.
25. WHERE NECESSARY TO SHUT OFF UTILITY SERVICES OR CAUSE INTERRUPTION TO
POWER OR SIGNAL SYSTEMS WHILE A BUILDING IS OCCUPIED OR THAT AFFECT
ADJACENT BUILDINGS, SCHEDULE OUTAGES OR INTERRUPTIONS WITH THE
OWNER, BUILDING OCCUPANTS AND/OR ADJACENT BUILDING OWNER(S) AND
OCCUPANTS PRIOR TO CONDUCTING OUTAGE(S) OR INTERRUPTIONS.
26. ALL EXISTING BRANCH CIRCUITS BEING REMOVED SHALL BE REMOVED AS
COMPLETE AS POSSIBLE. EXISTING CONDUCTORS SHALL BE REMOVED
COMPLETELY FROM THEIR RACEWAYS, DISPOSED OF AS SCRAP, REMOVED FROM
SITE AND NOT REUSED EXCEPT WHERE SPECIFICALLY NOTED OTHERWISE. WHERE
AN EXISTING DEVICE IS SHOWN REMOVED FROM AN EXISTING CIRCUIT, NEW
WIRING SHALL BE PROVIDED AS REQUIRED TO INSURE CONTINUITY OF EXISTING TO
REMAIN CIRCUIT.
27. REMOVE ELECTRICAL CONNECTIONS TO ALL MECHANICAL EQUIPMENT BEING
REMOVED BY DIVISION 15. COORDINATE EQUIPMENT REMOVAL LOCATIONS WITH
MECHANICAL DRAWINGS.
GENERAL NOTES
V
A N
G U
A R
D B
L V
D
M
IA
M
IS
B
U R
G
O H
P H
O N
E
-0
T im e
D at e
SHEET:
F ile
R E
V
IS
IO
N
I N
F O
R M
A T
IO
N
D ra w in g
D is c ip lin e
S or t:
/8
/2
:5
:5
A
M
A u to d e s k D o c s /3
G re a te r D a y to n R
T A
S e rv e r
R o o m
/3 G
D R
T A
S R
E
V
.r v t
E L
E C
T R
IC
A
L L
E G
E N
D
EG1-001
G R
E A
T E
R D
A Y
T O
N R
E G
IO
N
A L
T R
A N
S
IT
A U
T H
O R
IT
Y
W R
IG
H
T S
T O
P P
L A
Z A
S
M
A
IN
S T
R E
E T
D
A Y
T O
N
O H
FILE NO: 3761614
S E
R V
E R
R O
O M
C O
O L
IN
G S
Y S
T E
M
E G
-0
E L E
C T
R
IC
A L L
E G
E N
D
.0
R E
V D
R C
H K
D A
T E
D
E S
C R
IP
T
IO
N
A
F B
W L
/0 /2
Is su e d f o r
B id s a n d
P e rm itt in g
05/09/2025
EMB
EXIST.
EMA
EXIST.
PASSENGER
ELEVATOR
EXISTING EMER. DISTRIBUTION PANEL
"EDP2"
SPD
STAIR
PRESSURIZATION
200A/3P 30A/3P
CRAC-1
2 3 4 5 6
ATS-1
EQUIPMENT CONNECTION SCHEDULE
TAG DESCRIPTION LOCATION
LOAD
FLA
VOLTS/
PHASE
BLDG_PANEL:
CIRCUIT
FEEDERS (HOMERUN) DISCONNECT/STARTER
(AT UNIT)
NOTES
KW HP Breaker WIRE GND CONDUIT
CRAC-1 AIR HANDLER SERVER ROOM 27.4 76.2 208/3 EDP2:20,22,24 100A/3P 3-#1 #6 1 1/2" 600V/3/100 (NF) 1
ACCU-1 CONDENSING UNIT ROOF 2 5.7 208/3 EMB: 37,39,41 Existing 25A/3P 3-#10 #10 1" 600V/3/30 (NF) 1
H-1 ELECTRODE STEAM HUMIDIFIER MECHANICAL ROOM 4.6 19.0 208/1 EMB:31,33 30A/2P 2-#10 #10 3/4" 600V/3/30 (NF) 2
NOTES:
1. PROVIDE NON-FUSED DISCONNECT , HEAVY DUTY, NEMA 12 - INDOORS OR NEMA 4X - OUTDOORS. FUSE PER MANUFACTURER'S RECOMMENDATIONS.
2. PROVIDE NON-FUSED DISCONNECT , HEAVY DUTY, NEMA 12 DISCONNECT SWITCH FOR STEAM GENERATION UNIT. PROVIDE MOTOR RATED SWITCH AT UNIT FOR STEAM DISPERSION UNIT REMOTE MOUNTED IN SERVER ROOM.
V
A N
G U
A R
D B
L V
D
M
IA
M
IS
B
U R
G
O H
P H
O N
E
-0
T im e
D at e
SHEET:
F ile
R E
V
IS
IO
N
I N
F O
R M
A T
IO
N
D ra w in g
D is c ip lin e
S or t:
GENERAL NOTES:
KEY NOTES:
/8
/2
:5
:0
A
M
A u to d e s k D o c s /3
G re a te r D a y to n R
T A
S e rv e r
R o o m
/3 G
D R
T A
S R
E
V
.r v t
W S
P S
C H
E D
U L
E S
E
L E
C T
R
IC
A L
O N
E -L
IN
E
EG1-002
G R
E A
T E
R D
A Y
T O
N R
E G
IO
N
A L
T R
A N
S
IT
A U
T H
O R
IT
Y
W R
IG
H
T S
T O
P P
L A
Z A
S
M
A
IN
S T
R E
E T
D
A Y
T O
N
O H
FILE NO: 3761614
S E
R V
E R
R O
O M
C O
O L
IN
G S
Y S
T E
M
E G
-0
W S
P S
C H
E D
U L E
S
E L E
C T
R
IC
A L O
N E
-L
IN
E
.0 NTS
1 EDP2 ONE-LINE DIAGRAM
EG1-002
1. PROVIDE NEW 100A/3P BREAKER IN EXISTING SPACE. MATCH THE TYPE/MODEL/KA RATING WITH
EXISTING BREAKERS IN THE PANEL.
2. REMOVE EXISTING SPARE BREAKERS AND PROVIDE NEW BREAKER. MATCH THE
TYPE/MODEL/KA RATING WITH EXISTING BREAKERS IN THE PANEL.
Enclosure: NEMA 1 Ground Bus: INCLUDED
MCB Trip: 600 A Neutral Bus: 100.00%
MCB Frame: Fault Rating:
Feeds: Bus Rating: 600AMPS
Mounting: SURFACE Bus Material:
ENCLOSURE DATA: BUS DATA Remarks and Accessories:
Total Est. Demand: 197 A
Total Conn.: 197 A
Total Est. Demand: 71.1 kVA
Spare 69000 VA 69000 VA Total Conn. Load: 71.1 kVA
HVAC 2054 VA 2054 VA
Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 197 A 197 A 197 A
Total Conn. Load: 23.7 kVA 23.7 kVA 23.7 kVA
9 ELEVATOR SHUNT TRIP 3 20 A 20 A 0.0 kVA 0.0 kVA 0.0 kVA
8 ELEVATOR 3 20 A 20 A 0.0 kVA 0.0 kVA 0.0 kVA
7 SPD 3 60 A 60 A 0.0 kVA 0.0 kVA 0.0 kVA
6 SPACE 3 -- -- -- -- --
5 HP2C 3 30 A 30 A 5.0 kVA 5.0 kVA 5.0 kVA
4 CRAC-1 3 100 A 100 A 0.7 kVA 0.7 kVA 0.7 kVA
3 ELEVATOR 3 400 A 400 A 4.0 kVA 4.0 kVA 4.0 kVA
2 PANELS EMA AND EMB 3 200 A 200 A 14.0 kVA 14.0 kVA 14.0 kVA
1 MAIN 3 600 A 600 A 0.0 kVA 0.0 kVA 0.0 kVA
CKT Circuit Description # of Poles Frame Size Trip Rating
LOAD
PHASE A PHASE B PHASE C
Remarks
ATS-1
Supply From:
Location:EDP2 Service: 208/120 Wye,3 ɸ,4 W
(EXISTING)
ELECTRICAL ROOM
EXISTING LOAD
R E
V D
R C
H K
D A
T E
D
E S
C R
IP
T
IO
N
A
F B
W L
/0 /2
Is su e d f o r
B id s a n d
P e rm itt in g
N/A N/A N/A
Enclosure: NEMA 1 Ground Bus:
MCB Trip: 225 A Neutral Bus: 100%
MCB Frame: Fault Rating: 10kA
Feeds: Bus Rating: 225 AMPS
Mounting: SURFACE Bus Material:
ENCLOSURE DATA BUS DATA Remarks and Accessories:
Total Est. Demand: 69 A
Total Conn.: 69 A
Total Est. Demand: 25 kVA
Spare 19000 VA 19000 VA Total Conn. Load: 25 kVA
HVAC 6006 VA 6006 VA
Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 56 A 85 A 72 A
Total Load: 6.7 kVA 10 kVA 8 kVA
41 0.7 1 1 20 A BOARDROOM LTS 42
39 0.7 1 1 20 A BOARDROOM LTS 40
ACCU-1 25 A 3
0.7 1 1 20 A BOARDROOM LTS 38
35 SPARE 20 A 1 0 0.8 1 20 A BOARDROOM ELEV LOBBY LTS 36
33 2 0.8 1 20 A MULTIPURPOSE ELEV LOBBY LTS 34
H-1 30 A 2
2 0 1 20 A MULTIPURPOSE RM LTS 32
29 ACCESS CONTROL 20 A 1 0.5 0.4 1 20 A ELEVATOR PIT LTS 30
27 DDC CONTROL 20 A 1 0.5 0 1 20 A ELEVATOR MECH RM FAN 28
25 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 1 20 A COOPER ELEVATOR CAR LTS 26
23 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 1 20 A SPARE 24
21 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 1 20 A SPARE 22
19 AMERICAN BLD EAST CONTROL 20 A 1 0.5 0 20
17 AMERICAN BLD EAST CONTROL 20 A 1 0.5 1 18
15 AMERICAN BLD EAST CONTROL 20 A 1 0.5 1
3 20 A LIEBERT AIR
13 CONCOURSE HIGHBAY LTS 20 A 1 0 1 1 20 A SPARE 14
11 CONCOURSE HIGHBAY LTS 20 A 1 0 1 1 20 A CONCOURSE HUGHBAY LTS 12
9 SPARE 20 A 1 0 1 1 20 A CONCOURSE EXIT SIGNS 10
7 SPARE 20 A 1 0 1 1 20 A DUMPSTER RM 124 LTS 8
5 MEZZANINE HIGHBAY LTS 20 A 1 1 1 1 20 A MEZZANINE LTS 6
3 MULTIPURPOSE RM EM LTS 20 A 1 1 1 1 20 A COOPER STAIRWAY LTS 4
1 SPARE 20 A 1 0 0 1 20 A COOPER STAIRWAY LTS 2
CKT Circuit Description Trip Poles A (kVA) B (kVA) C (kVA) Poles Trip Circuit Description CKT
Supply From:
Location:EMB Service: 208/120 Wye , 3 ϕ , 4 W
EDP-2
(EXISTING)
ELECTREICAL ROOM
ESTIMATED EXISTING LOADS
MLO
SM
EMA
EMB
EDP2
EMB: 31,33
CRAC-1
C
H-1
NF-H-1
EDP2:4
MECHANICAL ROOM
SERVER ROOM
ELECTRICAL ROOM
NF-CRAC-1
ATS-1
NEW
CONTACTOR
PANEL "CP-1"
KEY PLAN
V
A N
G U
A R
D B
L V
D
M
IA
M
IS
B
U R
G
O H
P H
O N
E
-0
T im e
D at e
SHEET:
F ile
R E
V
IS
IO
N
I N
F O
R M
A T
IO
N
D ra w in g
D is c ip lin e
S or t:
GENERAL NOTES:
KEY NOTES:
PLAN NORTH
E
R D
S T
MAIN ST
/8
/2
:5
:0
A
M
A u to d e s k D o c s /3
G re a te r D a y to n R
T A
S e rv e r
R o o m
/3 G
D R
T A
S R
E
V
.r v t
W S
P S
E C
O N
D F
L O
O R
E L
E C
T R
IC
A
L P
L A
N
EH1-101
G R
E A
T E
R D
A Y
T O
N R
E G
IO
N
A L
T R
A N
S
IT
A U
T H
O R
IT
Y
W R
IG
H
T S
T O
P P
L A
Z A
S
M
A
IN
S T
R E
E T
D
A Y
T O
N
O H
FILE NO: 3761614
S E
R V
E R
R O
O M
C O
O L
IN
G S
Y S
T E
M
E H
-1
W S
P S
E C
O N
D F
L O
O R
E L E
C T
R
IC
A L P
L A
N
.5
SCALE: 1/4" = 1'-0"
EH1-101
1 WSP SECOND FLOOR ELECTRICAL PLAN
1. COORDINATE RELOCATION OF SECURITY CAMERA WITH GDRTA PERSONNEL.
2. PROVIDE E-STOPS AND 24 POLE CONTACTOR PANEL TO SHUTDOWN ALL SERVER ROOM
ELECTRICAL AND HVAC EQUIPMENT AND CLOSE THE FIRE DAMPER OF CRAC-1. CIRCUITS
SHALL BE RE-ROUTED THROUGH CONTACTOR PANEL. FOR BIDDING PURPOSES, USE (12) 20A
CIRCUITS. COORDINATE ACTUAL QUANTITY IN FIELD WITH GDRTA.
3. DEMOLISH 3-TON CRAC.REMOVE FEED TO CRAC BACK TO PANEL EMB:16,18,20. MARK
EXISTING 35A BREAKER AS SPARE.
A. MINIMUM ACCEPTABLE CONDUIT SIZE IS ¾” ABOVE GRADE AND 1” UNDERGROUND.
B. CONDUCTORS SHALL BE THHN/THWN-2 COPPER. MINIMUM SIZE IS #12 AWG UON.
C. MATCH AIC RATINGS AND ALL OTHER CHARACTERISTICS OF EXISTING DEVICES IN MCC’S,
PANELBOARDS, SWITCHBOARDS, ETC. WHEN ADDING DEVICES TO THE EXISTING GEAR.
D. FIRE SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS.
R E
V D
R C
H K
D A
T E
D
E S
C R
IP
T
IO
N
A
F B
W L
/0 /2
Is su e d f o r
B id s a n d
P e rm itt in
ACCU-1
NF-ACCU-1
EMB: 37,39,41
KEY PLAN
V
A N
G U
A R
D B
L V
D
M
IA
M
IS
B
U R
G
O H
P H
O N
E
-0
T im e
D at e
SHEET:
F ile
R E
V
IS
IO
N
I N
F O
R M
A T
IO
N
D ra w in g
D is c ip lin e
S or t:
GENNERAL NOTES:
KEY NOTES:
PLAN NORTH
E
R D
S T
MAIN ST
/8
/2
:5
:0
A
M
A u to d e s k D o c s /3
G re a te r D a y to n R
T A
S e rv e r
R o o m
/3 G
D R
T A
S R
E
V
.r v t
W S
P R
O O
F E
L E
C T
R
IC
A L
P L
A N
EH1-102
G R
E A
T E
R D
A Y
T O
N R
E G
IO
N
A L
T R
A N
S
IT
A U
T H
O R
IT
Y
W R
IG
H
T S
T O
P P
L A
Z A
S
M
A
IN
S T
R E
E T
D
A Y
T O
N
O H
FILE NO: 3761614
S E
R V
E R
R O
O M
C O
O L
IN
G S
Y S
T E
M
E H
-1
W S
P R
O O
F E
L E
C T
R
IC
A L P
L A
N
.5
SCALE: 1/4" = 1'-0"
EH1-102
1 WSP ROOF ELECTRICAL PLAN
1. DEMOLISH CONDENSING UNIT (CU). REMOVE CONDUCTORS TO UNIT BACK TO PANEL
EMB:37,39,41. RE-USE EXISTING 25A BREAKER FOR NEW ACCU-1 UNIT. RE-USE EXISTING
CONDUITS WHERE POSSIBLE. CONTRACTOR SHALL REMOVE EXISTING SUPPORT RAILS AND
PATCH ALL AFFECTED ROOF AREAS IN ACCORDANCE WITH ROOFING MANUFACTURER’S
REQUIREMENTS TO MAINTAIN THE EXISTING ROOF WARRANTY. CONTRACTOR SHALL
COORDINATE WITH ROOFING SYSTEM PROVIDER PRIOR TO PERFORMING ANY WORK.
2. DISCONNECT SWITCH FOR NEW MECHANICAL EQUIPMENT. COORDINATE THE EXACT
LOCATION WITH THE MECHANICA EQUIPMENT SUBMITTAL. THE MAXIMUM LENGTH OF FLEXIBLE
CONDUIT FROM THE DISCONNECT SWITCH TO THE EQUIPMENT SHALL BE 6 FEET.
A. MINIMUM ACCEPTABLE CONDUIT SIZE IS ¾” ABOVE GRADE AND 1” UNDERGROUND.
B. CONDUCTORS SHALL BE THHN/THWN-2 COPPER. MINIMUM SIZE IS #12 AWG UON.
C. MATCH AIC RATINGS AND ALL OTHER CHARACTERISTICS OF EXISTING DEVICES IN MCC’S,
PANELBOARDS, SWITCHBOARDS, ETC. WHEN ADDING DEVICES TO THE EXISTING GEAR.
D. FIRE SEAL ALL CONDUIT PENETRATIONS OF FIRE RATED WALLS.
R E
V D
R C
H K
D A
T E
D
E S
C R
IP
T
IO
N
A
F B
W L
/0 /2
Is su e d f o r
B id s a n d
P e rm itt in
| G-001 - COVER SHEET |
| MG1-001 - MECHANICAL GENERAL NOTES AND LEGEND |
| MD1-101 - WSP SECOND FLOOR PLAN - DEMOLITION |
| MD1-102 - WSP ROOF PLAN - DEMOLITION |
| MH1-101 - WSP SECOND FLOOR PLAN |
| MH1-102 - WSP ROOF PLAN |
| MH3-001 - WSP SECTIONS |
| MH4-001 - WSP ENLARGED PLANS |
| MH5-001 - DETAILS |
| MH8-001 - CONTROL DIAGRAMS |
| EG1-001 - ELECTRICAL LEGEND |
| EG1-002 - WSP SCHEDULES & ELECTRICAL ONE-LINE |
| EH1-101 - WSP SECOND FLOOR ELECTRICAL PLAN |
| EH1-102 - WSP ROOF ELECTRICAL PLAN |