EL CENTRO BORDER PATROL
EL CENTRO SECTOR, CA
CHECKPOINT 111 BACK UP GENERATOR
STATEMENT OF WORK
REVISION 1
AUG 30, 2011
CHECKPOINT 111 BACKUP GENERATOR
CHECKPOINT 111
33.360360, -115.645060 10 miles Northwest of NILAND, CA 92257
1. BACKGROUND
Current and proposed conditions at the El Centro Sector Highway 111 Checkpoint are such that a facility backup generator is required in order to continue mission essential operations in the event of a complete power failure. Primary power to the checkpoint is provided by the City of Indio. No secondary power source is in place.
2. SCOPE
The Customs and Border Protection/ Office of Administration, FM&E Border Patrol Facilities and Tactical Infrastructure PMO requires a contractor’s services to furnish and install a back up generator, and open transition Automatic Transfer Switch (ATS) that provides the entire facility 120/230 volt, 60 Hz. single phase – 400 amp electrical service.
The ATS will need to switch to the backup generator within 10 seconds of a complete power failure. ATS needs to switch back to line source and generator needs to perform an automatic shut-down once primary power has been restored. For ease of use and environmental concerns, a natural gas powered generator is preferred but not required. The Generator fuel tank will be sized to provide 100% of the power required to operate the Checkpoint for a minimum of 24 hours. Contractor will be responsible to meet all Federal, State and local code and provide design criteria for fuel storage.
The contractor shall provide all labor, supervision, tools, materials, parts, equipment, transportation, bonding, licenses, permits, certifications and management necessary to carry out and complete, in every detail, the work included in this SOW. Construction services shall include incidental and ancillary components, materials, or equipment accessories customarily required by code, guideline, or industry standard practice to make the work complete and operational – whether or not such incidental or ancillary components are identified, named, or shown in or on any document provided to the contractor.
2.1.General Conditions:
2.1.1. All lengths and dimensions included in this SOW are for reference only. Bidders shall visit the site and determine for themselves the lengths of runs, the gauge of conductor (wire), and the dimensions of the concrete pad to provide the above stated electrical service at Checkpoint 111.
2.1.2. All temporary on-site or off-site facilities and/or other accommodations as well as all indirect management effort and expenses required to deliver the design and construction activities in this technical package.
2.1.3. Submit manufacturer’s certification and cut sheets and/or sales brochures on the items proposed to be furnished. All such products or items must be recommended, by the manufacturer, for the intended use and application.
2.1.4. Environmental protection measures as necessary to prevent pollution of the environment or be cause of a nuisance to operations or personnel in close proximity to the work.
2.1.4.1.This requirement includes the contractor’s providing and maintaining a positive barrier to assure that building personnel will at no time be subject to potential danger from construction activities.
2.1.5. Any need for interruption of the site’s electrical service shall be scheduled and coordinated through Border Patrol and FM&E personnel.
2.1.6. Before requesting acceptance of the work, contractor shall complete final cleaning of all areas affected by new or remodel activities. Cleaning shall be to the extent that there is no remaining evidence that construction took place.
2.2.The contractor shall provide services for and/or furnish and install no less than the following:
2.2.1 Design and Engineer the installation of a new Generator and Automatic Transfer Switch at Checkpoint 111 to integrate with existing Electrical Service. Design and work will conform to NFPA, IBC and NEC requirements.
2.2.2 Provide Submittal’s of Generator, Automatic Transfer Switch and major components of project for BP and FM&E approvals. Provide progress schedule and timeline for design phase and construction.
2.2.3 Design and drawings stamped by registered engineer in the State of California to be reviewed by BP and FM&E for approval. Submit 90% drawing for review and acceptance. Installation will commence when 100% drawings are reviewed and approved by BP & FM&E.
2.2.4 Provide steel reinforced Concrete Pad designed for weight of Generator and auxiliary fuel tank.
2.2.5 Provide and install a shade canopy sized to cover the generator and auxiliary fuel tank area.
2.2.5.1 Frame will be constructed from 2” Diameter Heavy Duty Galvanized Steel Tubing and fittings.
2.2.5.2 Canopy tarp will be constructed from high density woven polyethylene (with a minimum 8oz per square yard with a 14 x 14 mesh count). The tarp will be water proof, mildew resistant, and fire retardant in accordance with NFPA-701 and CPAI-84 fire code requirements.
2.2.5.3 The tarp will be sized and placed on the steel canopy frame in a manner that will provide shade to the backup generator and auxiliary fuel tank area during all daylight hours while still allowing access to the Generator fuel tank and controls.
2.2.5.4 The legs of the canopy frame will be secured to the reinforced concrete pad to prevent any potential shifting caused by local winds.
2.2.5.5 The tarp will have at a minimum a 75% shade rating.
2.2.6 In accordance with CBP Security Policy and Procedure Handbook standards, provide and install an 8’ high perimeter fence around the generator and auxiliary fuel tank site.
2.2.6.1 The fabric height will be 7’ and have twisted and barbed selvage at the top and bottom.
Install a 1’ top guard for a total fence height of 8’.
2.2.6.2 Fencing will be fabricated with 9-guage steel wire mesh material with mesh openings not larger than 2” per side.
2.2.6.3 Provide type I tension wire, class 4 coating, in accordance with ASTMA 824. Provide 7 gauge coil spring tension wire for top and bottom wire. All fencing will be installed on the outside of the support posts.
2.2.6.4 A clear zone will be established no less then 20 feet from any structure or object inside of the fence and 10 feet from any structure or object outside the fence. The use of residential grade is not permitted.
2.2.6.5 Install a chain link fence double door with metal frame that utilizes a standard lockset (deadbolt only) keyed individually and to a Border Patrol master. The door will be sized appropriately to allow for removal and repair of the generator.
2.2.7 Provide all excavation and backfill for installation and revisions to electrical conduit and wire.
2.2.8 Strategically place new Automatic Transfer Switch next to existing Utility Service.
2.2.9 Provide As built drawings in PDF format:
2.2.8.1 Electronic on CDROM to include drawings and specifications
2.2.8.2 Printed copies of drawings (11” X 17”)
2.2.8.3 Printed copies of drawings to scale (24” X 36”)
2.2.10 Provide Testing and Close out Documents to include O&M manuals and operator training.
2.2.11 Provide Installation and Materials warrant documents.
3. PERIOD OF PERFORMANCE
3.1 Period of performance is after receipt of order 90 days to complete.
4. WARRANTY
4.1 Contractor / business partner must warranty material, workmanship and functionality for a period of 12 months. Warranty to begin on the date the project is completed and accepted by USBP.
5. SPECIAL REQUIREMENTS
5.1 No overtime related cost will be paid by the Government
5.2 Security Clearance/Screening is required for 100% of Contractor workers and supervisors accessing the Station to service this contract.
5.3 Clearance is based upon a favorable local/state/national criminal history and immigration status records check. Vendor must submit names of prospective representatives (to include social security number, date of birth, and driver’s license info) no less than 48 hours in advance of commencement of work on the premises.
5.4 The CBP, El Centro Sector Security Officer will notify vendors, Contracting Officer, and Contracting Officer’s Technical Representative whether or not an employee has been cleared.
6. ATTACHMENTS
6.1 CBP Security Policy and Procedures Handbook Fence requirements.
6.2 Checkpoint 111 General Construction Specifications.
End of Statement of Work
Location of Backup Generator w/ aux fuel, Concrete pad, canopy.
Conduit from BU Generator to Checkpoint main power panel. Panel is located on a vertical board approximately 75 feet north of modular building.
Connection point to Checkpoint main power panel
Modular Bldg
Cano
Perimeter fence around the generator area