2. Minimum specs b81 aaon.docx

DOCX document 23 KB Posted

Attached to
AAON HVAC UNIT
Solicitation number
N00167CJD001NSWC
Issued by

About this file

This document is a Minimum Specifications sheet for a brand name AAON packaged rooftop unit replacement. The Naval Sea Systems Command (NSWCCD Code 102) requires one new AAON Model RNA-025 heat pump unit with supplemental electric heat to replace an existing unit (Serial # BNWR03515) in Building 81. The unit must feature 2-inch double-wall construction with thermal break, direct drive plenum supply fans, stainless steel double-sloped drain pan, and one set of 4-inch pleated MERV 8 filters with condenser coil guards for protection.

Electrical specifications require 460V/3Ph/60Hz power with a Minimum Circuit Ampacity of 216A and Maximum Overcurrent Protection of 225A, utilizing R-454B refrigerant and a variable capacity primary compressor with 2-step secondary compressor. The unit must include an air-source heat pump with modulating hot gas reheat, VCCX CAV controller, economizer, clogged filter switch, phase and brownout protection, non-fused disconnect switch, factory-wired 115V convenience outlet, and remote safety terminals for field-provided smoke detectors. The contractor must provide a minimum 1-year limited parts and labor warranty and 5-year parts-only warranty for the compressor. The price shall be inclusive of all freight, with the contractor responsible only for equipment supply; excluded items include BAS integration, smoke detectors, airflow monitoring, vibration isolation rails, mounting hardware, structural steel, wiring, rigging, installation, and final commissioning.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Minimum Specifications AAON Package Rooftop Unit

THIS IS A BRAND NAME REQUIREMENT

General The Contractor shall provide one (1) new packaged rooftop unit, AAON Model RNA-025 or equivalent updated model, to replace the existing unit (Serial # BNWR03515).

The unit shall be a heat pump with supplemental electric heat.

Make and Model Requirements

Make: AAON Model: RNA-025

Physical and Construction Requirements Construction: 2-inch double-wall construction with a thermal break Supply Fan: Direct drive plenum supply fans Drain Pan: Stainless steel, double-sloped Filters: One (1) set of 4-inch pleated MERV 8 filters Coil Protection: Condenser coil guards

Electrical and Performance Requirements Power: 460V/3Ph/60Hz Electrical Rating: 10KAIC Circuit Sizing: Minimum Circuit Ampacity (MCA) of 216A and Maximum Overcurrent Protection (MOCP) of 225A Refrigerant: R-454B DX coil Compressor: Variable capacity primary compressor with a 2-step secondary compressor Heating/Cooling:

Air-Source Heat Pump Modulating Hot Gas Reheat Supplemental Electric Heating Controls & Safeties:

Economizer Clogged Filter Switch Phase and Brownout Protection Non-Fused Disconnect Switch Factory-wired 115V Convenience Outlet VCCX CAV Unit Controller Remote safety terminals for field-provided and installed smoke detectors

Warranty The equipment shall include a minimum 1-year limited parts and labor warranty.

The equipment shall include a minimum 5-year parts-only warranty for the compressor.

Scope of Supply Included: The price shall be inclusive of all freight.

Not Included (To be performed by others): The following items are explicitly excluded from the material supply:

* BAS (Building Automation System) integration.

* Smoke detectors (the unit must provide terminals for connection).

* Airflow monitoring station.

* Vibration isolation rails.

* Mounting hardware, structural steel, and curb fill.

* All power and low-voltage wiring.

* Rigging, installation, and final commissioning.