DISTINCT UPGRADE
GENERAL
1. THE FOLLOWING DATA WAS USED IN THE DESIGN OF THE floor decks:
DEAD LOAD = 150pcf for concrete, and 490 pcf for all structural steel
SDL = 10 PSF
FLOOR LIVE LOAD = 50 PSF
CONSTRUCTION LOAD = 25 PSF
COMPOSITE BEAM OR STEEL FRAMED STRUCTURES
1. THE CONTRACTOR'S ATTENTION IS DRAWN TO THE FACT THAT UNDER THE DEAD LOAD OF THE WET CONCRETE THE BEAMS AND METAL DECK WILL DEFLECT.
THE DEPTH OF CONCRETE SHOWN ON THE DRAWINGS IS THE MINIMUM REQUIRED. THE CONTRACTOR SHALL MAKE ALLOWANCES FOR ANY ADDITIONAL
CONCRETE THAT WILL BE REQUIRED DUE TO THE ABOVE DESCRIBED DEFLECTION.
2. FRAMED FLOOR SLABS SHALL BE POURED IN STRIPS PERPENDICULAR TO THE STEEL GIRDERS. THE CONTRACTOR SHALL SUBMIT TO PEC 1 WEEK PRIOR TO POUR THE LOCATIONS OF ALL CONSTRUCTION JOINTS AND THE SEQUENCING OF POURS PRIOR TO PROCEEDING.
3. THE SYMBOL (N) ADJACENT TO A BEAM OR PORTION OF A BEAM INDICATES THE NUMBER OF 3/4 INCH DIAMETER HEADED STUDS TO BE WELDED TO THE TOP OF THE BEAM OR PORTION OF THE BEAM. STUDS SHALL EXTEND 3 INCHES ABOVE THE DECK AFTER INSTALLATION. THE NUMBER OF STUDS HAS BEEN DETERMINED BY ASSUMING THE SHAPE OF THE METAL DECK CAUSES NO REDUCTION IN THE SHEAR CAPACITY OF THE STUDS. IF REQUIRED, THE TOTAL NUMBER OF STUDS, N, SHALL BE INCREASED IN ACCORDANCE WITH SECTION I5 OF THE AISC SPECIFICATIONS. THAT IS, IF THE STUD-ALLOWABLE-LOAD-REDUCTION-FACTOR, N (FORMULAS (I5-1) AND/OR (I5-2) OF THE AISC SPECIFICATION), IS LESS THAN 1.0, THE NUMBER OF STUDS SHALL BE INCREASED BY MULTIPLYING THE NUMBER OF STUDS BY THE RECIPROCAL OF THE FACTOR, N.
4. STUDS SHALL BE BEND-TESTED BY BEING BENT 30 DEGREES FROM THE ORIGINAL AXIS. TWO SUCCESIVE STUDS ON EACH BEAM OR GIRDER SHALL BE WELDED AND WITHSTAND THE BEND TEST WITHOUT WELD OR STUD FAILURE BEFORE PROCEEDING WITH FURTHER INSTALLATION
STRUCTURAL AND MISCELLANEOUS STEEL
1. STRUCTURAL STEEL FOR COLUMNS AND BEAMS SHALL BE NEW DOMESTIC STEEL CONFORMING TO ASTM A992 FOR WIDE FLANGE SHAPES, AND A36 FOR
CHANNELS, ANGLES, BARS AND ANY OTHER MISCELLANEOUS SECTIONS, INCLUDING PLATES UNLESS NOTED OTHERWISE. MEMBERS AND CONNECTIONS SHALL BE DESIGNED, FABRICATED, AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE AISC SPECIFICATIONS.
2. UNLESS OTHERWISE NOTED, ALL BOLTS SHALL BE A490-N BOLTS.
3. ALL SHOP CONNECTIONS SHALL BE WELDED, UNLESS NOTED OTHERWISE.
4. ALL WELDED CONNECTIONS SHALL BE DONE WITH E70XX ELECTRODES. SHOP AND FIELD WELDS SHALL BE MADE BY APPROVED CERTIFIED WELDERS AND SHALL CONFORM TO THE AMERICAN WELDING SOCIETY CODE FOR BUILDINGS AWS D1.1. WELDS SHALL DEVELOP THE FULL STRENGTH OF MATERIALS BEING
WELDED UNLESS OTHERWISE NOTED.
5. ALL BUTT WELDS SHALL BE FULL PENETRATION BUTT WELDS IN ACCORDANCE WITH THE STRUCTURAL WELDING CODE (ANSI/AWS D1.1). THESE WELDS SHALL BE MADE ONLY BY OPERATORS QUALIFIED BY PRESCRIBED TESTS IN THE STRUCTURAL WELDING CODE IN BUILDING CONSTRUCTION OF THE AMERICAN WELDING SOCIETY. ACCEPTANCE TO BE SUBJECT TO THE INSPECTION AND REVIEW OF AN INDEPENDENT INSPECTION AGENCY.
6. WELDING SEQUENCE AND TECHNIQUE SHALL BE SUCH THAT DISTORTION OF STEEL MEMBERS IS MINIMIZED AND UNDUE DISTORTION IS AVOIDED.
7. ALL WELDS EXPOSED TO WEATHERING AFTER FINAL CONSTRUCTION SHALL BE GROUND SMOOTH AFTER WELDING.
8. HOT DIP GALVANIZE ALL STRUCTURAL STEEL EXPOSED TO THE WEATHER.
9. ALL FULL PENETRATION WELDS SHALL BE TESTED PER SPECIFICATIONS.
10. ALL STRUCTURAL STEEL SHALL BE AS FOLLOWS:
BEAMS AND GIRDERS: ASTM A-992, FY = 50 KSI
11. CONNECTIONS DETAILED BY THE FABRICATOR SHALL MEET THE FOLLOWING REQUIREMENTS:
UNLESS OTHERWISE NOTED ALL CONNECTIONS DESIGNED BY THE FABRICATOR SHALL BE DESIGNED IN ACCORDANCE WITH THE "AISC MANUAL OF STEEL CONSTRUCTION, ALLOWABLE STRESS DESIGN", 13TH EDITION AND THE "AISC MANUAL OF STEEL CONSTRUCTION, VOLUME II, CONNECTIONS" USING THE ASD 13TH EDITION PROVISIONS CONTAINED THEREIN. THE USE OF "SNUG TIGHT" BOLTED CONNECTIONS IS NOT PERMITTED. BOLTS SHALL BE SLIP CRITICAL OR
BEARING. BOLTED CONNECTIONS SHALL HAVE NO LESS THAN TWO BOLTS.
METAL DECKING
1. ALL METAL DECKING SHALL BE DESIGNED, FABRICATED AND ERECTED IN ACCORDANCE WITH THE LATEST EDITION OF THE "SPECIFICATION OF THE STEEL DECK
INSTITUTE."
2. UNLESS NOTED OTHERWISE, ALL FLOORS SHALL CONSIST OF 1.5 INCH DEEP X 20 GAGE COMPOSITE DECK WITH 2.5 INCHES OF CONRETE FILL FOR A TOTAL SLAB THICKNESS OF 4 INCHES. FLOOR DECKING SHALL BE FASTENED TO SUPPORTS WITH 5/8 INCH DIAMETER PUDDLE WELDS AT 12 INCHES ON CENTER AT SUPPORTS, AND PERIMETER AND SPACING AS SPECIFIED BY MANUFACTURER AT SIDE BEAMS.PROVIDE 6X6-W1.4XW1.4 WIRE MESH REINFORCEMENT PLACED
1 INCH BELOW TOP OF SLAB
3. THE 1.5 INCH DEEP X 20 GAGE METAL DECK MUST HAVE AN AVERAGE MINIMUM RIB WIDTH OF 6 INCHES. AS A MINIMUN THE METAL DECK MUST HAVE THE
FOLLOWING PROPERTIES
a. FY = 40KSI
b. I = 0.20 IN4 / FT
c. S = 0.24 IN3 / FT
4. GALVANAZING FOR ALL DECKING SHALL CONFORM TO THE REQUIREMENTS OF ASTM A525 CLASS G90
5. DECK SHALL BE CONTINUOUS OVER 3 OR MORE SUPPORTS SO AS NOT TO REQUIRE ANY INTERMEDIATE SHORING TO SUPPORT CONSTRUCTION LOADS AND
WET CONCRETE, UNLESS NOTED OTHERWISE
CONNECTION UPGRADE NOTES
1. REMOVE BEAM AND ALL EXISTING COMPONENTS PRIOR TO INSTALLATION OF RETROFIT
2. WHERE PLATES, TABS, WELDS NEED TO BE CUT, GRIND AND REMOVE ALL RESIDUE TO PROVIDE A CLEAN SURFACE FOR INSTALLATION OF NEW RETROFIT
COMPONENTS
3. SUBMIT INSTALLATION PLAN SHOWING SEQUENCE OF CONSTRUCTION FOR APPROVAL BY ENGINEER OF RECORD
SHEET NUMBER
LosAngeles
DRAWN CHECKED APPROVED
Mark Date
Appr. Description
Revisions
2550NorthHollywoodWay,Suite500 Burbank,CA91505-5026
Tel:818-240-1919Fax:818-240-4966 www.kcse.com
DATE ISSUED
JOBNO. FILENAME:
SHEET TITLE
PROJECT
Albuquerque 2501YaleBlvd.,S.E.,Suite304 Albuquerque,NM87106-4358
Tel:505-291-4489Fax:505-298-7436
S001-ARA0660-17.DWGARA 0660.17
EH LT KM
STRUCTURAL
UPGRADES FOR
DISTINCT KESTREL
REACTION
STRUCTURE
11/1/2013
10/31/2013 AM
STRUCTURAL UPGRADES
ORIGINAL STRUCTURE
STRUCTURAL UPGRADES BY:
PROTECTION ENGINEERING
CONSULTANTS
14144 TRAUTWEIN ROAD
AUSTIN, TX 78737
GENERAL NOTES
S-0.0
EXISTING COLUMN
FLANGE PLATES FOR
BEAM CONNECTING TO
WEB (SEE BEAM TO WEB
CONNECTION)
8"
2" GR. 50
CONTINUITY PLATE
COVER PLATE TO
BEAM FLANGES
1"
BEAM
CJP
BEAM TO COLUMN, FLANGE
PLAN VIEW
SHEAR TABS NOT SHOWN FOR CLARITY
SHEAR PLATE TO
COLUMN FLANGES
WELD TOP AND
BOTTOM OF PLATE
ACROSS THICKNESS
1"
EXISTING COLUMN
PLATE TO COLUMN WEB
AND FLANGES (TYP)
1/2"
SHEAR PLATE TO
BEAM WEB
1/2"
BEAM
4"
2" GR. 50 COVER
PLATE TOP AND
BOTTOM
2" GR. 50 COVER
PLATE TOP AND
BOTTOM
1-1/4" A36
EACH SIDE (2)
2" GR. 50 FLANGE PLATE
TOP AND BOTTOM (2)
BEAM TO COLUMN, WEB
PLAN VIEW BEAM TO
COLUMN WEB
1-1/4" A36 EACH SIDE
OF BEAM WEB (2)
BEAM
EXISTING COLUMN
SHEAR PLATE TO
COLUMN WEB AND
FLANGE PLATES
2" GR. 50 CONTINUITY
PLATE EXTERIOR SIDE
ONLY TOP AND BOTTOM
(2). SEE BEAM TO FLANGE
CONNECTION DETAIL
SHEAR PLATE TO
BEAM WEB
1"
2" GR. 50 COVER PLATE
TOP AND BOTTOM. SNUG
FIT AGAINST COLUMN WEB
AND FLANGES. CHAMFER
AS NEEDED.
1"
2" GR. 50 CONTINUITY
PLATE EXTERIOR SIDE
ONLY TOP AND BOTTOM
(2). SEE BEAM TO FLANGE
CONNECTION DETAIL
EXISTING COLUMN
SHEAR TABS NOT SHOWN FOR CLARITY
2" GR. 50 CONTINUITY
PLATE EXTERIOR SIDE
ONLY TOP AND BOTTOM
(2). SEE BEAM TO FLANGE
CONNECTION DETAIL
CJP
COVER PLATE TO
COLUMN FLANGES
1"
COVER PLATE TO
BEAM FLANGES
1"
4"
4"
0" 6" 1' 2'3"
M
I N
SHEET NUMBER
LosAngeles
DRAWN CHECKED APPROVED
Mark Date
Appr. Description
Revisions
2550NorthHollywoodWay,Suite500 Burbank,CA91505-5026
Tel:818-240-1919Fax:818-240-4966 www.kcse.com
DATE ISSUED
JOBNO. FILENAME:
SHEET TITLE
PROJECT
Albuquerque 2501YaleBlvd.,S.E.,Suite304 Albuquerque,NM87106-4358
Tel:505-291-4489Fax:505-298-7436
S001-ARA0660-17.DWGARA 0660.17
EH LT KM
STRUCTURAL
UPGRADES FOR
DISTINCT KESTREL
REACTION
STRUCTURE
11/1/2013
10/31/2013 AM
STRUCTURAL UPGRADES
ORIGINAL STRUCTURE
STRUCTURAL UPGRADES BY:
PROTECTION ENGINEERING
CONSULTANTS
14144 TRAUTWEIN ROAD
AUSTIN, TX 78737
CONNECTION DETAILS
S-0.1
28'-6"
3'-0" 3'-0"22'-6"
W
X
E
M B
E D
D E
D
B
E A
M
W24X192
(EMBEDDED BEAM)
W
X
E
M B
E D
D E
D
B
E A
M
W24X192
(EMBEDDED BEAM)
W
X
T
Y
P
L
O
C
4'-0"X1'-6"
FOOTING BELOW
MAT FOUNDATION
(4 LOC)
3'-6" THICK MAT FOUNDATION W/ #9 @
12" O.C., EACH WAY, TOP AND BOTTOM
W
X
W
X
W14X257 (10)
W14X257 (10)
W12X19 (20)
W12X19 (20)
22'-6"
I N
C
M
P O
S I T
E
D E
C K
S
E
T
E S
M
P O
S I T
E
D E
C K
S
T
E S
M
P O
S I T
E
D E
C K
S
T
E S
0" 6" 1' 2' 4' 0" 6" 1' 2' 4'
SHEET NUMBER
LosAngeles
DRAWN CHECKED APPROVED
Mark Date
Appr. Description
Revisions
2550NorthHollywoodWay,Suite500 Burbank,CA91505-5026
Tel:818-240-1919Fax:818-240-4966 www.kcse.com
DATE ISSUED
JOBNO. FILENAME:
SHEET TITLE
PROJECT
Albuquerque 2501YaleBlvd.,S.E.,Suite304 Albuquerque,NM87106-4358
Tel:505-291-4489Fax:505-298-7436
S001-ARA0660-17.DWGARA 0660.17
EH LT KM
STRUCTURAL
UPGRADES FOR
DISTINCT KESTREL
REACTION
STRUCTURE
11/1/2013
10/31/2013 AM
STRUCTURAL UPGRADES
ORIGINAL STRUCTURE
STRUCTURAL UPGRADES BY:
PROTECTION ENGINEERING
CONSULTANTS
14144 TRAUTWEIN ROAD
AUSTIN, TX 78737
FRAMING PLANS
S-1.0
W24X192
W
X
W
X
3'-0" 22'-6" 3'-0"
W24X192
W
X
W
X
NEW
W12X19
W14X257 (10)
21'-3"3'-0"
W12X19
NEW
W12X19
3'-0"
4" COMPOSITE DECK.
SEE NOTES
4" COMPOSITE DECK.
SEE NOTES
4" COMPOSITE DECK.
SEE NOTES
4" COMPOSITE DECK.
SEE NOTES
EXISTING CONCRETE
SLAB
EXISTING W14X283
COLUMN
EXISTING W14X283
COLUMN
EXISTING W14X283
COLUMN
EXISTING W14X283
COLUMN
EXISTING CONCRETE
SLAB
NEW
W12X19
0" 6" 1' 2' 4'
0" 6" 1' 2' 4'
W14X257 (10)
COLUMN
BEYOND
COLUMN
BEYOND
#9 @12"
O.C E.W.
#4 STIRRUPS
@12" O.C E.W.
COLUMN FOOTING
(BEYOND)
COLUMN FOOTING
(BEYOND)
0" 6" 1' 2'
3"
SHEET NUMBER
LosAngeles
DRAWN CHECKED APPROVED
Mark Date
Appr. Description
Revisions
2550NorthHollywoodWay,Suite500 Burbank,CA91505-5026
Tel:818-240-1919Fax:818-240-4966 www.kcse.com
DATE ISSUED
JOBNO. FILENAME:
SHEET TITLE
PROJECT
Albuquerque 2501YaleBlvd.,S.E.,Suite304 Albuquerque,NM87106-4358
Tel:505-291-4489Fax:505-298-7436
S001-ARA0660-17.DWGARA 0660.17
EH LT KM
STRUCTURAL
UPGRADES FOR
DISTINCT KESTREL
REACTION
STRUCTURE
11/1/2013
10/31/2013 AM
STRUCTURAL UPGRADES
ORIGINAL STRUCTURE
STRUCTURAL UPGRADES BY:
PROTECTION ENGINEERING
CONSULTANTS
14144 TRAUTWEIN ROAD
AUSTIN, TX 78737
ELEVATIONS
S-1.1
BEAM CONNECTION SCHEDULE
BEAM FRAMING ANGLE BOLTS PER LEG
ELEVATION
NOTE 4
NOTES:
10"
2"
6"
2 1/4"
1 1/2"
4"
10"
2"
3/16
3-12
6"
3/16
3-12
3 1/2"3 1/2"
2 1/4" 2 1/4"
A-A SINGLE STUD ORIENTATION B-B SINGLE STUD ORIENTATION
0" 6" 1' 2' 4'
SHEET NUMBER
LosAngeles
DRAWN CHECKED APPROVED
Mark Date
Appr. Description
Revisions
2550NorthHollywoodWay,Suite500 Burbank,CA91505-5026
Tel:818-240-1919Fax:818-240-4966 www.kcse.com
DATE ISSUED
JOBNO. FILENAME:
SHEET TITLE
PROJECT
Albuquerque 2501YaleBlvd.,S.E.,Suite304 Albuquerque,NM87106-4358
Tel:505-291-4489Fax:505-298-7436
S001-ARA0660-17.DWGARA 0660.17
EH LT KM
STRUCTURAL
UPGRADES FOR
DISTINCT KESTREL
REACTION
STRUCTURE
11/1/2013
10/31/2013 AM
STRUCTURAL UPGRADES
ORIGINAL STRUCTURE
STRUCTURAL UPGRADES BY:
PROTECTION ENGINEERING
CONSULTANTS
14144 TRAUTWEIN ROAD
AUSTIN, TX 78737
FLOOR FRAMING
DETAILS
S-3.0