UNITED STATES DEPARTMENT OF JUSTICE
FEDERAL BUREAU OF PRISONS
FCC VICTORVILLE
13777 AIR EXPRESSWAY BLVD.
VICTORVILLE CALIFORNIA, 92394
STATEMENT OF WORK 2018 ANNUAL ELECTRICAL INSPECTION
PART I - GENERAL INFORMATION
A. INTRODUCTION
Annual electrical inspection per Facilities Manual P.S. 4200.12
B. SCOPE
The following electrical equipment shall be tested according to manufacturer’s recommended procedures.
1. Seventy Two (72) MV Switches
2. Twenty Four (24) High Voltage Distribution Sections
3. Thirteen (13) High Voltage Switches
4. Utility Switchgear FCI1, with Four (4) protective relays
5. Utility Switchgear FCI2, with Four (4) protective relays
6. Utility Switchgear USP, with Four (4) protective relays
7. Four (4) protective relays
8. Protective Relays
9. Two (2) 951 Basler relays located in FCI2 & USP
10. Four (4) GPS Basler relays located in FCI2 & USP
11. Four (4) 87G Basler relays located in FCI2 & USP
12. Eight (8) 851 Basler relays located in FCI2 & USP
13. Twenty (20)DT3000 Eaton relays located in FCI2 & USP
14. Thirty Three (33) Oil Filled Transformers
15. Two (2) Dry Type Transformer
16. Two (2) Load Banks
17. Thirty Eight (39) High Voltage Circuit Breakers
(See Attachments)
PART II - WORK REQUIREMENTS
A. Switchgear and Switchboard Assemblies
1. Visual and Mechanical Inspection.
· Inspect for physical damage and proper installation.
· Inspect for proper alignment, anchorage and grounding.
· Inspect for proper identification of protective devices and switches.
· Physically test all mechanical interlocks to assure proper operation.
· Check tightness of accessible bolted bus connections.
· Clean switchboard interior compartments.
· Inspect insulators for evidence of physical damage or contaminated surfaces.
· Check key interlock systems for safe operation and proper key distribution. If applicable.
· Perform visual and mechanical inspection on all instrument transformers.
· Inspect control power transformers for physical damage, cracked insulation, broken leads, tightness of connections, defective wiring, and overall general condition.
· Verify correct functioning of instrument and control power transformer draw out disconnecting and grounding contacts and interlocks.
2. Electrical Tests
· Measure insulation resistance of each bus section phase-to-phase and phase-to ground.
B. Medium/High Voltage Load Interrupter Fusible Switch
1. Visual and Mechanical Inspection.
Inspect the switch and enclosure for cleanliness, condition of louvers and filters, corrosion and paint conditions.
Inspect the switch, bus, cable terminations and fuse holders for evidence of defects in insulation integrity, such as cracking, tracking, corona and overheating.
Inspect the switch contacts and arc chutes. Check for smooth movement, proper alignment and flicker blade operation per manufacturer’s procedures.
Verify that any mechanical and key interlock schemes function as intended.
Verify equipment ground connection.
Verify proper operation of space heaters.
Clean the cabinet floor and walls by vacuuming and wiping the walls.
Clean and lubricate the operating mechanism and blade contact surfaces per manufacturer’s guidelines.
Clean the switch, bus and support insulators by vacuuming and wiping. Some components may be cleaned with a manufacture approved electrical solvent.
2. Electrical Tests
Measure contact resistance for each phase.
Measure insulation resistance at the appropriate test value, each pole to ground, between phases and across open contacts of each phase.
C. Protective Relays
1. Visual and Mechanical Inspection.
Inspect relays for physical damage and proper installation.
Tighten case connections. Inspect cover for correct gasket seal. Inspect shorting hardware, connection paddles, and/or knife switches. Verify target reset.
Clean cover glass and relay components as required.
Check relay components for proper operation and alignment, as applicable.
Verify relays were set in accordance with coordination study supplied by owner.
Verify proper identification of protective relays.
2. Electrical Tests
Perform the following tests at the settings specified by client:
Pickup parameters on each operating element of the relay.
Timing tests conducted to verify proper delay of each element.
Pickup target and seal-in units.
Special tests as required checking operation of restraint, directional and other elements, per manufacturer's instructions.
Perform functional test to ensure relay trips the associated breaker or auxiliary device, as applicable.
Perform insulation resistance test on each electrical circuit to frame. Insulation resistance tests shall not be performed on solid-state protective relays.
C. Liquid Transformers
1. Visual and Mechanical Inspection.
Inspect the tank, radiators, control cabinets, fans and auxiliary devices for corrosion and paint condition.
Inspect the outside of the tank, radiators, sample valves, gauges and pad area for signs of fluid leaks.
Inspect the bushings, cable terminations and control wiring for evidence of defects in insulation integrity, such as cracking, wear, tracking corona or overheating.
Verify proper operation of temperature indicators, alarms and fan controls.
Check and record the nitrogen blanket pressure, liquid temperature, maximum temperature and liquid level.
Inspect mechanical pressure relief device to verify it has not operated.
Verify equipment, arrester, and neutral grounds if applicable.
2. Electrical Tests
Measure insulation resistance at the appropriate test value, each winding high to low and ground, low to high and ground, and high and low to ground.
Perform a Transformer turns ratio test on all three phase and compare results to values calculated from nameplate data.
Draw a fluid sample for general lab analysis.
Perform an insulation power factor test.
Perform a winding resistance test.
All service will be conducted in accordance with manufacturer’s specifications.
A comprehensive engineering report to include findings, equipment specific test data, and recommendations will be completed and submitted to the Facilities Manager within 30 days of completion of the inspection.
All work will be conducted Tuesday thru Friday, 7:00am-4:00 pm All 12 contract personnel entering the facility will be required to pass a NCIC background check, conducted by FCC Victorville. Because of time restraints of the job a minimum of 12 contractors will be required.
Facilities Manager: D.Dittemore, Cost Center Manager
Consolidated Equipment List
| Oil Filled Transformers | Switchgear | High Voltage Distribution Gear | |||||||
| Manufacturer: Cooper Power | Manufacturer: Cutler-Hammer | Manufacturer: Cutler-Hammer | |||||||
| Model# 000D3A64K24A | Model# 1A33845G16 | Model# VCP-WSWGR | |||||||
| Qty: 6 | Qty: 38 | Qty: 28 Sections | |||||||
| Model# 000J2P11K36A | Model# 1A33841G16 | ||||||||
| Qty: 3 | Qty: 54 | Model# 150VCP-W500 | |||||||
| Model# V45M28F30LS42 | Model# VACCLAD-W | Qty: 38 Circuit Breakers | |||||||
| Qty: 2 | Qty: 2 | ||||||||
| Model# 000L9P12K83A | Relay | ||||||||
| Qty: 1 | Model# G5N1H0 | ||||||||
| Model# 000J2P12K05A | Qty: 8 | ||||||||
| Qty: 5 | Model# BE1GPS100 E4N1H0 | ||||||||
| Model# 00A0A65W67S | Qty: 4 | ||||||||
| Qty: 3 | Model# BE1-851 |
Model# 0076YA6SW01S Qty: 1
| Qty: 1 | Model# E4NH0N | ||||
| Model# 000A1P11W88A | High Voltage Switches | Qty: 1 | |||
| Qty: 3 | Manufacturer: Scott Engineering | ||||
| Model# 000E0P07W42A | Model# 140436-0 | Differential Relay |
| Qty: 1 | Qty: 5 | Model# BE1-87G | |||
| Model# 0034WA64W75S | Model# 140437-0 Qty: 4 | ||||
| Qty: 2 | Qty: 6 | ||||
| Model# 00A9P13W21A | Manufacturer: RSE-Sierra | ||||
| Qty: 1 | Manufacturer: S&C | Serial# 11886-1 | |||
| Model# 000D3A65K07A | Model# PMH-9 | Qty: 10 Sections | |||
| Qty: 1 | Qty: 1 | ||||
| Model# 000J2P10K03A | Vacuum Circuit Interrupter | ||||
| Qty: 6 | Manufacturer: Power Con | Qty: 2 | |||
| Model# 000J2P11K04A | Model# PIF A 62-09 |
Qty: 2 Fused Switches
| Model# 000J2P09K02A | Dry Type Transformers | Qty: 6 | |
| Qty: 1 | Manufacturer: Hammond Power | ||
| Model# 000A1912W89A | Model# 159302 | ||
| Qty: 1 | Qty: 2 |
Model# 000A1P13W90A
| Qty: 1 | Manufacturer: Cooper Power | |
| Model# 000A1P11W87A | Model# MSN 02060 |
Qty: 3
| Manufacturer: Cutler-Hammer | ||
| Load Bank | Model# MSN 01946 |
Manufacturer: ALCAD Model# SLRF 120-25 Qty: 3 Sections
Site #1
FCI 2 B UNIT
ASSET # T-H3-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL# 000D3A64K24A
SERIAL# CP0237003098
ASSET# SWGEAR-H3-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL# SM01A996G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A996G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A996G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A996G04
Site #2
FCI 2 D UNIT
ASSET# T-H2-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000D3A64K24A
SERIAL#CP0237003099
ASSET# SWGEAR-H2-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A995G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A995G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A995G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
SERIAL#SM01A995G04
Site #3
FCI 2 F UNIT
ASSET# T-H1-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000D3A64K24A
SERIAL#CP0237003100
ASSET# SWGEAR-H1-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A994G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A994G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A994G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
SERIAL#SM01A994G04
Site #4
FCI 2 FOOD SERVICE
ASSET# T-FS-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000D3A64K24A
SERIAL#CP0126002262
ASSET# SWGEAR-FS-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A992G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A992G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A992G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
SERIAL#SM01A992G04
Site #5
FCI 2 UNICOR
ASSET# T-UF-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000D3A64K24A
SERIAL#CP0126002261
ASSET# SWGEAR-UF-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A991G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A991G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A991G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
SERIAL#SM01A991G04
Site #6
FCI 2 VOCATIONAL TRAINING
ASSET# T-VT-01-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000J2P11K36A
SERIAL#CP0137019338
ASSET# SWGEAR-VT-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A988G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A988G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A988G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
SERIAL#SM01A988G04
Site #7
FCI 2 SPECIAL HOUSING
ASSET# T-SH-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000D3A64K24A
SERIAL#CP0137019334
ASSET# SWGEAR-SH-01-VIX (4 section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33845G16
SERIAL#SM01A993G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A993G02
DESCRIPTION: SWITCHGEAR (section 3)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A993G03
DESCRIPTION: SWITCHGEAR (section 4)
MANUFACTURER: CUTLER HAMMER
SERIAL#SM01A993G04
Site #8
FCI 2 ADMINISTRATION
ASSET# T-AO-02-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000J2P11K36A
SERIAL#CP0137019342
ASSET# T-AO-03-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000J2P11K36A
SERIAL#CP0137019341
ASSET# SWGEAR-AO-01-VIX
DESCRIPTION: SWITCHGEAR (1 Section)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A986G01
ASSET# SWGEAR-AO-02-VIX
DESCRIPTION: SWITCHGEAR (1 Section)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A968G01
Site #9
FPC CENTRAL ADMIN BUILDING
ASSET# T-CA-02-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#V45M28F30LS42
SERIAL#CP0137019339
ASSET# T-CA-03-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#V45M28F30LS42
SERIAL#CP0137019340
ASSET# SWGEAR-CA-01-VIX
DESCRIPTION: SWITCHGEAR (1 Section)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A989G01
ASSET# SWGEAR-CA-02-VIX
DESCRIPTION: SWITCHGEAR (1 Section)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A998G01
Site #10
FCI 2 POWERHOUSE LOAD BANK
ASSET# T-UP-03-VIX
DESCRIPTION: TRANSFORMER (DRY TYPE)
MANUFACTURER: HAMMOND POWER
MODEL#159302
SERIAL#DB02F23
ASSET# SWGEAR-UP-02-VIX
DESCRIPTION: SWITCHGEAR (1 Section)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM02A465G01
ASSET# LDBNK-UP-01-VIX
DESCRIPTION: LOAD BANK
MANUFACTURER: ALCAD
MODEL#SLRF 120-25
SERIAL#282
Site #11
FCI 2 POWERHOUSE
ASSET# T-UP-01-VIX
DESCRIPTION: TRANSFORMER (DRY TYPE)
MANUFACTURER: CUTLER HAMMER
MODEL#MSN 02060
SERIAL#D S05007001
ASSET# SWGEAR-UP-03-VIX (2 Section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A990G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A990G02
ASSET# HVLTDISP-UP-01-VIX (14 Sections)
DESCRIPTION: HIGH VOLTAGE DISTRIBUTION
MANUFACTURER: CUTLER HAMMER
MODEL#VCP-WSWGR
SERIAL#29949
DESCRIPTION: HIGH VOLTAGE BREAKERS (18 Breakers)
MANUFACTURER: CUTLER HAMMER
MODEL# 150VCP-W500
SERIAL#01097695, 01097543, 01097609, 01097556, 01097698, 01097696,
01107780, 01097796, 01107795, 01107805, 01107807, 01107801, 01097612, 02050538, 02050548, 01107794, 01107792, 01107803
DESCRIPTION: HIGH VOLTAGE RELAYS
MANUFACTURER: CUTLER HAMMER
MODEL# G5N1H0
SERIAL#H00215985, H00215986, H00215987, H00215988, H00215989
MODEL# BE1GPS100 E4N1H0
SERIAL#H00215990 (REV F), H00215991 (REV F)
DESCRIPTION: DIFFERENTIAL RELAY
MODEL# BE1-87G
SERIAL#H00214739, H00214740
Site #12
UNICOR PBW
ASSET# T-
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000L9P12K83A
SERIAL#CP0650014514
Site #14
FCI 1 OUTSIDE POWERHOUSE
ASSET# HVLS GL-CP-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
MODEL# 140437-0
SERIAL#101
ASSET# T-CP-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A0A65W67S
SERIAL#986000615
ASSET# ET-CP-VIX (2 Section)
DESCRIPTION: EMERGENCY TRANSFORMER
MANUFACTURER: COOPER POWER
MODEL#0076YA6SW01S
SERIAL#986000635
Site #15
FCI 1 POWERHOUSE
ASSET# HVLTDISP-CP-01-VIX (10 Sections)
DESCRIPTION: HIGH VOLTAGE DISTRIBUTION
MANUFACTURER:RSE-SIERRA
MODEL#
SERIAL#11886-1
Site #16
WATERTOWER #1
ASSET# HVLS-WT1-VIX
DESCRIPTION: HIGH VOLTAGE DISTRIBUTION
MANUFACTURER: SCOTT ENGINEERING
MODEL#140436-0
SERIAL#206
ASSET# T-WT-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000E0P07W42A
SERIAL#9937017574
Site #17
EDISON YARD
ASSET# (3 Sections)
DESCRIPTION: FCI 2 SWITCHGEAR
MANUFACTURER: CUTLER HAMMER
MODEL#VACCLAD-W
SERIAL#72YE790
DESCRIPTION: CIRCUIT BREAKER
MANUFACTURER: CUTLER HAMMER
MODEL#150VCP-W500
SERIAL#01107793
ASSET# (3 Sections)
DESCRIPTION: USP SWITCHGEAR
MANUFACTURER: CUTLER HAMMER
MODEL#VACCLAD-W
SERIAL#72YE612
DESCRIPTION: CIRCUIT BREAKER
MANUFACTURER: CUTLER HAMMER
MODEL#150VCP-W500
SERIAL#01107787
ASSET# (4Sections)
DESCRIPTION: FCI 1SWITCHGEAR
MANUFACTURER: RSE-SIERRA
MODEL#
SERIAL#13344-1
Site #20
FPC FOOD SERVICE
ASSET# T-CC3-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#0034WA64W75S
SERIAL#986000670
ASSET# HVLS CC3-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
MODEL#140436-0
SERIAL#204
Site #21
FPC HOUSING UNIT
ASSET# T-A4-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#00A9P13W21A
SERIAL#986000742
ASSET# HVLS A4-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
MODEL#140436-0
SERIAL#205
Site #22
USP OUTSIDE POWERHOUSE
ASSET# T-M1-04-VIX
DESCRIPTION: TRANSFORMER (DRY TYPE) (2 Section)
MANUFACTURER: HAMMOND POWER
MODEL#159302
Site #23
USP OUTSIDE POWERHOUSE
ASSET# T-M1-01-VIX
DESCRIPTION: TRANSFORMER (DRY TYPE) (4 Section)
MANUFACTURER: CUTLER HAMMER
MODEL#MSN 01946
SERIAL#D S04154001
ASSET# SWGEAR-M1-02-VIX (2 Section) DESCRIPTION: SWITCHGEAR (section 1)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A443G01
DESCRIPTION: SWITCHGEAR (section 2)
MANUFACTURER: CUTLER HAMMER
MODEL#1A33841G16
SERIAL#SM01A443G02
ASSET# HVLTDISP-M1-01-VIX (14 Sections)
DESCRIPTION: HIGH VOLTAGE DISTRIBUTION
MANUFACTURER: CUTLER HAMMER
MODEL#VCP-WSWGR
SERIAL#29570
DESCRIPTION: HIGH VOLTAGE BREAKERS (18 Breakers)
MANUFACTURER: CUTLER HAMMER
MODEL# 150VCP-W500
SERIAL#01087368, 01087301, 01087358, 01087299, 01087266, 01076785, 01087302, 01087300, 01087372, 01087311, 01087320, 01076791, 01087370, 01076753, 01076767, 01076783, 01076794, 01076788
DESCRIPTION: HIGH VOLTAGE RELAYS
MANUFACTURER: CUTLER HAMMER
MODEL#E4NH0N
SERIAL#H00204645
MODEL#G5N1H0
SERIAL#H00207322, H00207323, H00207324
MODEL#BE1GPS100 E4N1H0
SERIAL#H00204012 (REV F), H00204013 (REV F)
Site #23
USP OUTSIDE POWERHOUSE
(CONT)
DESCRIPTION: HIGH VOLTAGE RELAY
MANUFACTURER: CUTLER HAMMER
MODEL#BE1-851
SERIAL#E00797748
DESCRIPTION: DIFFERENTIAL RELAY
MANUFACTURER: CUTLER HAMMER
MODEL#BE1-87G
SERIAL#H00214126, H00214127
Site #36
FCI 1 ADMINISTRATION
ASSET# T-B-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P12W89A
SERIAL#989002768
ASSET# HVLS BCD-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
MODEL#140437-0
SERIAL#102
Site #37
FCI 1 HEALTH SERVICES
ASSET# T-K-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P11W88A
SERIAL#989002712
ASSET# HVLS-K-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
SERIAL#106
Site #38
FCI 1 RECREATION
ASSET# T-O-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P11W88A
SERIAL#989002711
ASSET# HVLS-O-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
MODEL#140436-0
SERIAL#202
ASSET# T-P-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A0A65W67S
SERIAL#986000614
Site #39
FCI 1 FOOD SERVICE
ASSET# T-S-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A0A65W67S
SERIAL#986000613
ASSET# HVLS-S-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
MODEL#140436-0
SERIAL#203
Site #40
FCI 1 FACILITIES
ASSET# T-V-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P13W90A
SERIAL#989002821
ASSET# HVLS-V-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: S&C ELECTRIC
MODEL#MANUAL PMH-9
SERIAL#051483
Site #41
FCI 1 UNIT E
ASSET# T-A3-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P11W87A
SERIAL#989002934
ASSET# HVLS-A3-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
SERIAL#105
Site #42
FCI 1 UNIT C
ASSET# T-A2-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P11W87A
SERIAL#989002933
ASSET# HVLS-A2-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
SERIAL#104
Site #43
FCI 1UNIT A
ASSET# T-A1-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: COOPER POWER
MODEL#000A1P11W87A
SERIAL#989002932
ASSET# HVLS-A1-VIX
DESCRIPTION: HIGH VOLTAGE SWITCH
MANUFACTURER: SCOTT ENGINEERING
SERIAL#103
Site #44
FCI 1 BLDG 1123
ASSET# T-1123-01-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: CUTLER HAMMER
MODEL#VGAE497CDK
SERIAL#10JC519460002
Site #45
FCI 1 BLDG 1119
ASSET# T-1119-01-VIX
DESCRIPTION: TRANSFORMER (OIL FILLED)
MANUFACTURER: CUTLER HAMMER
MODEL#VGAE497CDK
SERIAL#10JC519460001