USP LEE – UPDATE FIRE ALARM
PROJECT 1C2Y QUESTIONS & ANSWERS
SOLICITATION 15B11718B00000001
QUESTIONS AND ANSWERS
SUBMITTED BY K.C. ELECTRICAL CONSTRUCTION:
1. Is there going to be a separate conduit required between each panel and annunciators needed to be installed for the class A circuit or can we utilize the existing conduit.
Clarification: See below answer the SOW requires this to be code compliant. MXRO
2. Can we use the existing single conduits between panels and annunciators? NFPA 72 is calling for a separate conduit for the separation of the circuits.
Clarification: Per Sow this must be code compliant, a separate conduit is needed
MXRO
3. Can the existing fire alarm panels be used as junction boxes for the new EST-3 fire alarm panels? Provided that all ends cables are labeled and terminal strips are used in the junction panels and a metal plate covers the Lexan window on the old est2 panels.
Clarification: Yes this is acceptable providing the metal plate is secured in a way that prevents tempering MXRO
File details come from the government source that posted it.