IPC_Parker_Final_Drawings.pdf
PDF 32 MB Posted
- Attached to
- Improving Patient Care Remodel - Parker, AZ
- Solicitation number
- 14-161-SOL-00008
About this file
IPC Remodel Parker Drawings
View the file
Other files
| File | Type | Posted |
|---|---|---|
| IPC_Parker_Final_Drawings.pdf | ||
| IPC_Parker_FINAL_Specifications.pdf | ||
| IPC_Parker _14-00008.pdf | ||
| IPC_Parker_FINAL_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation 14-161-SOL-00008
Attachment 5 mtouchan Typewritten Text mtouchan Rectangle mtouchan Typewritten Text
Typewritten Text mtouchan Rectangle mtouchan Rectangle mtouchan
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle tmcgann Typewritten Text mtouchan Rectangle tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
Rectangle mtouchan Rectangle tmcgann Typewritten Text tmcgann
1 2 3 4
A
B
C
A
B
C
1 2 3 4
REV
ISSUE: OCTOBER 23, 2013 CONSTRUCTION DOCUMENTS
PROJECT NO: 1117.200
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
ES BRANCH CHIEF
ES PROJECT MANAGER
AGENCY REPRESENTATIVE
APPROVED:
CONCURRENCE
TITLE
REVIEWED:
ES ARCHITECT / ENGINEER DATE
DATE
DATE
DATE
SHEET ______ OF ______
PARKER
INDIAN HEALTH CENTER RENOVATIONS
PARKER, AZ
HHSI161201200001I
SHEET TITLE
STRUCTURAL
Turner Structural Eng.
3026 N. Country Club Tucson, AZ 85716 Phone: 323.3422
MECHANICAL
Adams & Associates 4067 East Grant Rd, # 200 Tucson, AZ 85712 Phone: 323.3858
ELECTRICAL
M3 Engineering 2051 W. Sunset Rd, # 101 Tucson, AZ 85704 Phone: 293.1488
261 North Court Avenue Tucson, Arizona 85701
520.795.2705 Fax 520.795.6171
www.bwsarchs.com
CONSULTANTS
2051 W. SUNSET ROAD, SUITE 101
TUCSON, ARIZONA 85704
520.293.1488
M3-PN130091
1 1-7-14 ELECTRICAL CHANGE
FLEXIBLE CONDUIT
MOTOR
ELECTRICAL SYMBOLS
GFCI
J JUNCTION BOX
NEW CONDUIT
0-10V DIMMER SWITCH AS INDICATED ON DRAWINGS
TOGGLE SWITCH TYPE MANUAL MOTOR STARTER
THREE WAY SWITCH, 20 AMP
'DP-001'-1,3,5
NEUT.HOT
DUPLEX RECEPTACLE OUTLET, MOUNTED 18" AFF (U.O.N.)
DUPLEX RECEPTACLE ABOVE 42" COUNTER
GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE 20 AMP
FEED THROUGH TYPE
QUADRAPLEX - TWO DUPLEX RECEPTACLE UNDER A TWO GANG
RING, MOUNTED @ 18" AFF (U.O.N.)
EXTERNALLY OPERATED FUSED DISCONNECT SWITCH, SIZE, FUSE
SIZE, PHASE AND QUANTITY AS INDICATED. NUMBER INDICATES NEMA
TYPE ENCLOSURE, NO NUMBER INDICATES NEMA '1' TYPE ENCLOSURE.
EXTERNALLY OPERATED NON-FUSED DISCONNECT SWITCH, SIZE AND
PHASE AS INDICATED. 'N' INDICATES NEMA TYPE ENCLOSURE. NO
NUMBER INDICATES NEMA '1' TYPE ENCLOSURE.
TELEPHONE/DATA SYSTEM OUTLET. FLUSH 4S DEEP BOX WITH 1
GANG RING & BLANK COVER AND 3/4" C. STUBBED OUT ABOVE
ACCESSIBLE CEILING WITH PLASTIC BUSHING ROUTED TO
NEAREST CABLE TRAY, OR AS NOTED.
CONCEALED CONDUIT - NUMBER OF SLASHES INDICATE NUMBER OF
WIRES (WHEN MORE THAN TWO) PROVIDE GROUND WIRE IN ALL
CONDUITS (SIZE PER NEC 250.122 UNLESS NOTED OTHERWISE);
GROUNDS ARE NOT SHOWN BY SLASHES. SLASHES WHERE SHOWN
ARE FOR CONVENIENCE OF THE CONTRACTOR ONLY; PROVIDE
NUMBER OF CONDUCTORS AS REQUIRED BY CIRCUIT FUNCTION.
HOME RUN TO PANELBOARD. 'DP-001' - INDICATES PANEL DESIGNATION
1,3,5 - INDICATES CIRCUIT BREAKER NO.
SINGLE POLE SWITCH, 20 A OR LOW VOLTAGE TYPE. MAX. HEIGHT = 42" TO
CENTERLINE OR AS NOTED ON DRAWINGS.S
3S
SD
MS
M
ELECTRICAL PANEL
UNDERGROUND CONDUIT
STARTER
30A/3P
(3) 30A FU
3R
30A/3P 3R
DP1
POWER SYMBOLS
WIRING SYMBOLS
LIGHTING FIXTURE DESIGNATION
SWITCH SYMBOLS
SPECIAL SYSTEMS SYMBOLS
AMP AMPACITY
FU
EWC ELECTRIC WATER COOLER
FUSE
#/C
C
AC
AWG
NUMBER OF CONDUCTORS
CONDUIT
AMERICAN WIRE GAUGE
ALTERNATING CURRENT
MANUFACTURER
MOTOR CONTROL CENTER
MFG
MCC
MOTOR CIRCUIT PROTECTOR
MAIN CIRCUIT BREAKER
MOTORM
MCP
MCB
AMERICANS WITH DISABILITIESADA
AIC
AFF
AMPERES INTERRUPTING
CAPACITY
ACT (1990)
ABOVE FINISHED FLOOR
ABBREVIATIONS
A AMPERES
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GROUND
KILOVOLT AMPS
HORSEPOWER
KILOWATTS
KVA
KW
GND
HP
GROUND FAULT INTERRUPTERGFI WATTSW
TRANSFORMER
WEATHERPROOFWP
XFMR
UNINNTERUPTABLE POWER SOURCE
VOLTS
UPS
V
SP
TYP TYPICAL
SPARE
N, NEU NEUTRAL
SHIELDED
RIGID GALVANIZED STEEL
REMARKREM
RGS
SHLD,SH
PR PAIR
NATIONAL ELECTRICAL CODENEC
AFG ABOVE FINISHED GRADE
MAIN LUGS ONLYMLO
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
PH PHASE
PVC POLYVINYL CHLORIDE
SOLID NEUTRALSN
UL UNDERWRITER'S LABORATORIES
UNLESS OTHERWISE NOTEDUON
STRANDED BARE COPPERSDBC
FLEXIBLE METAL CONDUITFMC
ELECTRICAL METALLIC TUBINGEMT
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT
4" SQUARE4S
3a
AFIXTURE TYPE DESIGNATION
CIRCUIT NUMBER
SWITCH REFERENCE
RACEWAY TURNING UP
RACEWAY TURNING DOWN
RACEWAY - (C) CAPPED, (B) BUSHED
LIGHTING FIXTURES ON NORMAL LIGHTING CIRCUIT
WALL MOUNTED LUMINAIRE
RECESSED OR SURFACE DOWNLIGHT
4' STRIP LIGHT
1 x 4 RECESSED FIXTURE
2 x 4 RECESSED FIXTURE
LIGHT FIXTURE SCHEDULE, DEMOLITON NOTES
ELECTRICAL SYMBOLS AND ABBREVIATIONS,
E001
LHB
STROBE LIGHT
HORN/STROBE
SMOKE DETECTOR
MANUAL PULL STATION
CABLE TRAY
TELEVISION ANTENNA OUTLET
SD
F
L
F
FIRE ALARM SYMBOLS
EXISTING TELEPHONE/DATA OUTLET
LIGHTING FIXTURES ON LIFE SAFETY BRANCH
DOWNLIGHT
EXIT LIGHT FIXTURE WITH DIRECTIONAL ARROW(S)
1. THE DRAWINGS INDICATE APPROXIMATE LOCATIONS AND QUANTITY OF ITEMS TO BE REMOVED. THE ELECTRICAL CONTRACTOR SHALL VERIFY QUANTITY AND LOCATION OF ITEMS TO BE REMOVED AS NO ALLOWANCE WILL BE MADE BECAUSE OF THE CONTRACTOR'S UNFAMILIARITY WITH THESE DETAILS.
2. ALL ITEMS SCHEDULED FOR RELOCATION SHALL BE CAREFULLY REMOVED IN REVERSE OF ORIGINAL ASSEMBLY OR PLACEMENT AND BE PROTECTED UNTIL RELOCATED. THE CONTRACTOR SHALL CLEAN, REPAIR AND PROVIDE NEW MATERIALS AND APPURTENANCES AS REQUIRED TO COMPLETE INSTALLATION AND RESTORE TO GOOD WORKING ORDER. ALL RELOCATIONS SHALL BE PERFORMED BY SKILLED WORKMEN IN ACCORDANCE WITH STANDARD PRACTICE OF THE
TRADES INVOLVED.
3. ITEMS SCHEDULED FOR RELOCATION REQUIRING EXTENSION OF CIRCUITRY, SHALL HAVE THEIR WIRE AND CONDUIT EXTENDED TO THE NEW LOCATION.
EXTENDED WIRE AND CONDUIT SHALL BE ROUTED IN SUCH A MANNER SO AS NOT TO INTERFERE WITH THE USE OR ESTHETICS OF ANY AREA IN WHICH IT IS ROUTED. THE CONTRACTOR SHALL BE RESPONSIBLE FOR RELOCATING OR MODIFYING AND RECONNECTING ANY EQUIPMENT ASSOCIATED WITH ITEMS BEING
RELOCATED.
4. CIRCUITS WITH ONLY A PORTION OF THE LOAD REMOVED SHALL HAVE THE ASSOCIATED CIRCUITRY REMOVED ONLY TO A POINT OR IN SUCH MANNER THAT THE REMAINING LOAD IS ACTIVE AND IN FIRST CLASS WORKING ORDER. ASSOCIATED CIRCUITRY IS DEFINED AS ALL WIRE, CONDUIT, JUNCTION BOXES, WIRING DEVICES, FUSES, DISCONNECT SWITCHES, ETC., ASSOCIATED WITH THE ITEM SCHEDULED FOR REMOVAL.
5. ITEMS SCHEDULED FOR REMOVAL WITH CONDUIT IN INACCESSIBLE AREAS SHALL ONLY HAVE THIS CONDUIT EMPTIED AND SEALED OR CAPPED IN A SAFE
MANNER ACCEPTABLE TO THE CONTRACTING OFFICER.
6. WHERE ITEMS SCHEDULED FOR RELOCATION ARE FOUND TO BE IN DAMAGED CONDITION, THE CONTRACTOR SHALL CALL THE ATTENTION OF THE CONTRACTING OFFICER TO SUCH ITEMS AND RECEIVE FURTHER INSTRUCTIONS PRIOR TO REMOVAL. ITEMS DAMAGED DURING RELOCATION SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACTING OFFICER.
7. ALL CUTTING AND PATCHING REQUIRED FOR INSTALLATION OF RACEWAYS OR EQUIPMENT SHALL BE PERFORMED BY A TRADESMAN EXPERIENCED IN THE WORK REQUIRED. ALL FINISHES SHALL MATCH EXISTING ADJACENT SURFACES OR AS INDICATED ON ARCHITECTURAL DRAWINGS.
8. THE CONTRACTOR SHALL COORDINATE THE DEMOLITION OF ELECTRICAL DEVICES SCHEDULED FOR RELOCATION WITH THE DEMOLITION CONTRACTOR.
REMOVAL OF DEVICES SCHEDULED FOR RELOCATION SHALL BE SCHEDULED PRIOR TO DEMOLITION CONTRACTOR ACTIVITIES.
ELECTRICAL DEMOLITION NOTES
NEW/RELOCATED
EXISTING TO BE REMOVED/REPLACED
EXISTING TO REMAIN
DEVICE CONSTRUCION SYMBOLS
NC
NURSE CALL SYMBOLS
NURSE CALL STAFF STATION. PROVIDE 3-GANG BOX, MUD
RING & 3/4" C ABOVE CEILING SPACE. PROVIDE BUSHING ON
END OF CONDUIT. COORDINATE MOUNTING HEIGHT WITH IHS.
NC
EMERGENCY STATION WITH PULL CORD (TOILET). PROVIDE 4"
SQUARE BOX, SINGLE GANG MUD RING AND 3/4" C ABOVE
CEILING SPACE. COORDINATE MOUNTING HEIGHT WITH IHS.
P
CEILING MOUNT ROOM CONTROLLER W/DOME LIGHT.
PROVIDE 2-GANG BOX, MUD RING & 3/4" C TO NEAREST CABLE
TRAY ABOVE CEILING. PROVIDE BUSHING ON END OF
CONDUIT.
S SPEAKER
TELEPHONE TERMINAL BOARD
CR CARD READER (42" U.O.N.) PROVIDE 4S BOX WITH SINGLE GANG
MUD RING AND 3/4" EC W/ PULL STRING TO 6" ABOVE ACCESSIBLE
CEILING. PROVIDE BUSHING AT END OF CONDUIT. COORDINATE
EXACT LOCATION WITH ARCHITECT PRIOR TO ROUGH-IN. PROVIDE
J-BOX ABOVE DOOR AND ROUTE 1/2" EC W/ PULL STRING TO DOOR
LATCH.
NCS EXISTING NURSE CALL CONSOLE STATION
2 x 4 RECESSED FIXTURE
WIRELESS ACCESS POINT. 4S BOX WITH 1 GANG RING MOUNTED
ABOVE CEILING. PROVIDE 3/4" C. WITH PLASTIC BUSHING ROUTED
TO NEAREST CABLE TRAY.
WAP
(E)
NURSE CALL CONSOLE STATION. PROVIDE 3-GANG BOX, MUD
RING & 3/4" C ABOVE CEILING SPACE. COORDINATE
MOUNTING HEIGHT WITH IHS.
NCS
NURSE CALL NOTES:
1. RE-USE EXISTING JERON NURSE CALL
EQUIPMENT AND VERFIY WITH FACILITY
FOR SPARE DEVICES.
2. FACILITY HAS SPARE CALLS TO BE USED.
COORDINATE WITH FACILITY.
3. SPEARS COMMUNICATION IS PREFERRED
VENDOR.
4. TESTING & TRAINING SHALL BE PART OF
THE SCOPE OF WORK.
LIGHT FIXTURE SCHEDULE NOTE: COLOR TEMPERATURE OF NEW LAMPS SHALL MATCH EXISTING CONDITIONS.
Rectangle tmcgann Typewritten Text tmcgann
GFCIGFCIGFCIGFCI
GFCI
GFCI
GFCI
GFCI
GFCI
J
GFCI
+48"
GFCI
+48"
GFCI
+96"
+48"
GFCI
GFCI
GFCI
GFCI
F
J7
J7
SD
NC
F
F
+96"
+42"
+42"
GFCI
+42"
NC
L
+42"+42"+42"+42"+42"
NC
L
+42"
GFCI
+42"
+42"
GFCI
+42"
NC
+42"
GFCI
+42"
+42"
GFCI
+42"
F
NC
NC
F
J
GFI
NCS
+42"
GFCI
+96" +48"
+42" +42"
+42"
+48"
GFCI
+48"
J +42"
+48"
M
S
S
S
S
S
S
S
S
S
S
S
+48"
+48"
+48"
+48"
+48" +48" +48" +48"
+48"
+48"
+48"
+48"
+48"
+48"
P4-36
P4-36 P4-36
P4-36
P4-36
+96"
P4-36 P4-42
P4-42
P4-40
P4-42
P4-36
P4-36
P4-36
P4-42
P4-42 P4-42
P4-42
P4-33
P4-33 P4-33
P4-35
P4-35 P4-35
P4-35
P4B-3
P4-37
P4-37P4-37
P4-37
P4-37
P4-37
P4-26
P4-26
P4-26
P4-26
P4-22 P4-22
P4-22 P4-22
P4-22P4-22
P4-22
P4-23
P4-16
P4-16
P4-16 P4-16 P4-17
P4-17
GFCI
+48"
P4-17 P4-17
P4-17
P4-15 P4-15
P4-13
P4-13
P4-13
GFCI
+48"
P4-13
P4-15P4-15
P4-15 P4-18
P4-14 P4-14P4-14
P4-14
P4-12P4-12 P4-12
P4-12
2 3
P4-29
P4-27 P4-31
P4-25 P4-31
P4-29 P4-25
GFCI
P4-27
P4-40 P4-40
P4-40
P4-6
P4-8 P4-8
P4-8
P4-8
P4-8P4-10
P4-6
P4-10
P4-10
P4-10
P4-6
P4-6P4-6 P4-38
P4-38
P4-38
P4-38
P4-20
P4-20 P4-20
P4-20P4-23
P4-20 P4-20
P4-23
P4-23 P4-23P4-23
P4-23
GFCI
+48"
GFCI
+48"
P4-38
P4-38
GFCI
+48"
P4-24 P4-24
P4-12
PHASE - 2
PHASE - 1
GFCI GFCI
PHASE - 2
PHASE - 1
M
EF-15
VAV 45
M15
VAV 48
M
VAV 44
16 M
M
VAV 42
CAV 78
M
VAV 43
M
M
VAV 40
M
VAV 39
14 VAV 37
M a,b a,b a,b a,b a,b a,b a,b a,b a,b a,b
3 3
3 3 a,b a,b a,b a,b a,b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a b a,b a,b a,b a,b a ba b a b a ba b a b
E1 a ba b a b
E1 a ba b a b
E1 a ba b a b
E1
6 6 6 6 6 6 6 a b a,b a b a b a b a b a b a b a b a b a b aa b a b a b a a,b a,b a,b
E1
E1
E1
E1 a b a b a b a b a b a b a b a b a b a,b 1 a,b a b a b a b
E1 a b a b a b a b a b a b
E1
E1
E3 E2 E2 E2 E2
E2 E2
E2 E2 a b a b a b a b a b a b a b a b
E2
E2
E2
E1
E1
E1
E1 E2
E2 b
(2) F32 T8
(2) 26W
(2) 26W
L4-9L4-9L4-9L4-9L4-9L4-9L4-9L4-9
L4-9L4-9L4-9L4-9
L4-9 L4-9 L4-9 L4-9 L4-9
EL4-1EL4-1
E1
EL4-1
L4-8 L4-8
E2
L4-9
L4-9
L4-9
L4-9
L4-9
L4-9
L4-9
A A A A A
A
A
A
A
A
A
A
A
EL4-1
EL4-1
3A
L4-9
EL4-1
L4-9
A
(TYP)
L4-6
L4-6
L4-6L4-6
L4-6L4-6
L4-6L4-6
L4-6
L4-6
EL4-1
L4-6
L4-6
E2
E2L4-6
L4-6
L4-6
L4-6
L4-6
EL4-1
E2
(2) F32 T8
(TYP)
(2) F32 T8
(TYP)
A
A
A
A
L4-9
L4-9
L4-9
L4-9
EL4-1
L4-8 L4-8
L4-8
E3
L4-8
A L4-9
A L4-9 3A
A L4-9
(2) 13 W
L4-8 L4-8 L4-8
L4-8 L4-8 L4-8
L4-8
L4-8
L4-8
L4-8 L4-8
L4-8 L4-8 L4-8
L4-8
L4-10 L4-10
L4-10
L4-10 L4-10
L4-10 L4-10
L4-10
EL4-1 EL4-1 EL4-1
L4-9
A
L4-9
A
L4-8 L4-8
L4-8
EL4-1 EL4-1 EL4-1
(2) 13 W
(TYP)
EL4-1 EL4-1 EL4-1
EL4-1
EL4-1
L4-10 L4-10
L4-10
L4-10
L4-10 L4-10
E2 E2
L4-10
L4-10
L4-10
L4-8
L4-8L4-8
L4-8
L4-8
L4-8
(2) F32
T8(TYP)
L4-9
E1 E1
L4-6
(L 4-
(L4-10)
E1
E1
E3
(L 4-
6)
(L4-6)
PHASE - 2
PHASE - 1
PHASE - 2
PHASE - 1
E1
E1
E1
E1
E1
E1
E1
E1
1 2 3 4
A
B
C
A
B
C
1 2 3 4
REV
ISSUE: OCTOBER 23, 2013 CONSTRUCTION DOCUMENTS
PROJECT NO: 1117.200
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
ES BRANCH CHIEF
ES PROJECT MANAGER
AGENCY REPRESENTATIVE
APPROVED:
CONCURRENCE
TITLE
REVIEWED:
ES ARCHITECT / ENGINEER DATE
DATE
DATE
DATE
SHEET ______ OF ______
PARKER
INDIAN HEALTH CENTER RENOVATIONS
PARKER, AZ
HHSI161201200001I
SHEET TITLE
STRUCTURAL
Turner Structural Eng.
3026 N. Country Club Tucson, AZ 85716 Phone: 323.3422
MECHANICAL
Adams & Associates 4067 East Grant Rd, # 200 Tucson, AZ 85712 Phone: 323.3858
ELECTRICAL
M3 Engineering 2051 W. Sunset Rd, # 101 Tucson, AZ 85704 Phone: 293.1488
261 North Court Avenue Tucson, Arizona 85701
2051 W. SUNSET ROAD, SUITE 101
TUCSON, ARIZONA 85704
520.293.1488
M3-PN130091
1 1/8"=1'-0"
POWER & SPECIAL SYSTEMS DEMOLITION PLAN 2 1/8"=1'-0"
LIGHTING DEMOLITION PLAN
1. (E) DEVICES/LIGHT FIXTURES LOCATED IN THIS ROOM SHALL REMAIN (U.O.N.)
2. (E) SPEAKER TO REMAIN.
3. (E) SPEAKER TO BE RELOCATED. REFER TO (N) SPECIAL SYSTEMS PLAN, SHEET EY001.
4. (E) DEVICES TO BE RELOCATED. SEE NEW POWER PLAN, SHEET EP001 FOR NEW LOCATION.
5. (E) DEVICE/SWITCH TO REMAIN.
6. (E) LIGHT FIXTURE TO REMAIN.
7. (E) J-BOX FOR CONNECTION OF EXAM LIGHT TO BE REMOVED.
8. ALL ELECTRICAL LOCATED IN THIS ROOM SHALL REMAIN. (U.O.N.)
9. (E) NURSE CALL DEVICE TO REMAIN.
10. (E) LIGHT FIXTURE TO BE RELOCATED. REFER TO (N) LIGHTING PLAN, SHEET EP001 FOR (N) LOCATION.
11. (E) DOOR OPERATOR TO BE REMOVED. (E) CIRCUIT TO REMAIN. REFER TO (N) POWER PLAN, SHEET
EP001 FOR (N) WORK.
12. (E) CIRCUIT TO REMAIN.
13. (E) J-BOX TO BE REMOVED. (E) CIRCUIT TO REMAIN. REFER TO (N) POWER PLAN, SHEET EP001 FOR (N)
WORK.
KEYED NOTES-
ELECTRICAL DEMOLITION PLANS
ED001
LHB1. (E) PANEL 'L4' TO REMAIN.
2. (E) PANEL 'P4 SECTION 1' TO REMAIN.
3. (E) PANEL 'P4 SECTION 2' TO REMAIN.
4. (E) PANEL 'P4A SECTION 1' TO REMAIN.
5. (E) PANEL 'P4A SECTION 2' TO REMAIN.
6. (E) PANEL 'P4B' TO REMAIN.
7. (E) PANEL 'EP4' TO REMAIN.
8. (E) PANEL 'EL4' TO REMAIN.
ELECTRICAL EQUIPMENT KEYED NOTES
1. ALL DEVICES/LIGHT FIXTURES SHOWN AS DASHED SHALL BE REMOVED. (U.O.N.)
2. COORDINATE WITH OWNER FOR DEVICES, ETC. TO BE RETURNED TO THE OWNER.
3. COORDINATE DEMOLITION WITH ARCHITECTURE DEMOLITION PLAN.
4. (34) 'E1' TYPE FIXTURES SHALL BE RE-USED. REFER TO LIGHTING PLAN, SHEET EP001 FOR NEW WORK.
5. (19) 'E2' TYPE FIXTURES SHALL BE RE-USED. REFER TO LIGHTING PLAN, SHEET EP001 FOR NEW WORK.
6. (1) 'E3' TYPE FIXTURE SHALL BE RE-USED. REFER TO LIGHTING PLAN, SHEET EP001 FOR NEW WORK.
GENERAL NOTES
14. REMOVE (E) VAV BOX & ASSOCIATED ELECTRICAL.
15. (E) VAV/CAV BOX & ASSOCIATED ELECTRICAL TO BE RELOCATED. REFER TO (N) POWER
PLAN, SHEET EP001 FOR (N) WORK.
16. (E) VAV BOX/ EXHAUST FAN & ASSOCIATED ELECTRICAL TO REMAIN.
17. (E) NURSE CALL CONSOLE STATION TO BE RELOCATED. REFER TO (N) SPECIAL SYSTEMS
PLAN, SHEET EY001 FOR NEW LOCATION.
Typewritten Text mtouchan Rectangle tmcgann
MED. ROOM
CLEAN UTILITYSCN ROOMEXAM ROOM 16EXAM ROOM 15EXAM ROOM 14EXAM ROOM 13
MSA/FILES
MSA/FILES
AUDIOLOGY
EXAM ROOM 18
INFANT SCREENING
EXAM ROOM 17 -ISO MEDICAL EQUIPMENT QA OFFICE
MED. ROOM TEAM ROOM
RESTROOM
ELECTRICAL
EXAM ROOM 12
EXAM ROOM 11
EXAM ROOM 10
SOILED UTILITY
EXAM ROOM 9
EXAM ROOM 8
VESTIBULE
EXAM ROOM 7- ISO
EXAM ROOM 6 EXAM ROOM 5
EXAM ROOM 4
RESTROOM EXAM ROOM 3
JANITOR
EXAM ROOM 2
EXAM ROOM 1
NURSE STATION
NURSE STATION
TEAM ROOM
CORRIDORCORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
GFCI
GFCI
GFCI
8 GFCI
GF
CI
GFCI
(TYP.)
GFCI
GFCI
GF
CI
(TYP.)
GF
CI
GF
CI
GF
CI
GFCI
GFCI
GFCI
GFCI
GFCI GFCI GFCI GFCI1
+48
GFCI
+48
+48
23 23
13 13
'P4'-23 'P4'-13
22 22 22
'P4'-22
+48
16181618
'P4'-35 35
'P4'-14
14 12
'P4'-8440
'P4'-40
27 25 27 25
+48"
GFCI
'P4'-17
'P4'-15
'P4'-33
+48"
GFCI
'P4'-26
GFCI
'P4'-37
'P4'-38
37 37
38 38
GF
CI
GF
CI
GF
CI
GF
CI
'P4'-6 'P4'-8 'P4'-10 'P4'-36
6 6
8 8
10 10
363636
GFCI
+48
GFCI
+48
GFCI
+48
GFCI
GFCI
J
P4B-3
J
M
M
J
15 15
(TYP)
'P4'-83
'P4'-26
'P4'-16,18,20
'P4'-12
'P4'-25,27,29
'P4'-82
PHASE - 2
PHASE - 1
PHASE - 2
PHASE - 1
M
M
M
M
MM
M
VAV 45
VAV 48
VAV 44
CA
V
14(TYP)
M
T 9
M R
MEF-2
WP 19
P4-69
M R
MEF
-3 WP
M R
M EF-1
WP
M
M
M
M
'P4'-67
VA
V
4D
VAV 4B
VAV 4A
M
EF-1517
MED. ROOM
CLEAN UTILITYSCN ROOMEXAM ROOM 16EXAM ROOM 15EXAM ROOM 14EXAM ROOM 13
MSA/FILES
MSA/FILES
AUDIOLOGY
EXAM ROOM 18
INFANT SCREENING
EXAM ROOM 17 -ISO MEDICAL EQUIPMENT QA OFFICE
MED. ROOM TEAM ROOM
RESTROOM
ELECTRICAL
EXAM ROOM 12
EXAM ROOM 11
EXAM ROOM 10
SOILED UTILITY
EXAM ROOM 9
EXAM ROOM 8
VESTIBULE
EXAM ROOM 7- ISO
EXAM ROOM 6 EXAM ROOM 5
EXAM ROOM 4
RESTROOM EXAM ROOM 3
JANITOR
EXAM ROOM 2
EXAM ROOM 1
NURSE STATION
NURSE STATION
TEAM ROOM
CORRIDORCORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
a,b a b a b a b a bE1 a,b a b a bE1 a,b a b a bE1 a,b a,b a b a b
E1
E2
4 4 4 4
E2
E2 c cR1 R1
R1 c c c
R1
R1
R1 a,b a b a b a,b a b a b a,b a b a b a,b a b a b a,b a b a b a,b a b a b
R2 a b a b a,b a,b a b a b
E1 E1 a,b a b a b
E1 a,b a b a b E1 a b a b E1 a b a b E1 a b a b a,b a b a b a,b a b a b
E1 a,b a b a b a,b
E1 a b a b a b a b a b a b
D$
D$ D$
E2
E2
4 4
E2
E2 E2 E2 E2
D$D$ a,b a b E1 a b a bE1 a,b a b E1 a,b
E3
R1 P
R1
P
R2 a a aDc a a aDc
L1
P P
P P a,b a,b a,b a,b
L2L2
L2L2
CP9 CP9
CP9 CP9
CP9
CP9
a b a
E1 E1
E1
'L4'-8
1 1 1 1 'EL4'-1A
'L4'-9 'L4'-9
A 'L4'-9
A
'EL4'-1
'L4'-9 A
'L4'-9
A
12 12
3A
'L4'-9
A
'L4'-9a
'L4'-9 A
A 'L4'-9
AA
'L4'-9
'L4'-9 A 'L4'-9'L4'-9
AA
A 'L4'-9 'L4'-9
A 'L4'-9
'EL4'-1
'L4'-10
10 A 'L4'-9
A 'L4'-9
A 'L4'-9
A 'L4'-9
A 'L4'-9
'EL4'-1
P
'EL4'-1
WV WV
1010 10
P
WV WV
1 1
1 1
4A
A A'L4'-9 'L4'-9
8 8 a b
3a
R2
'L4'-8
A 'L4'-9
'L4'-8
'L4'-8
'L4'-8
'EL4'-1
10 10 bb a 8 8
PHASE - 2
PHASE - 1
PHASE - 2
PHASE - 1
L1
L1 b a a b b b a b b a b a b a b a a a c
E2
E2
1 2 3 4
A
B
C
A
B
C
1 2 3 4
REV
ISSUE: OCTOBER 23, 2013 CONSTRUCTION DOCUMENTS
PROJECT NO: 1117.200
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
ES BRANCH CHIEF
ES PROJECT MANAGER
AGENCY REPRESENTATIVE
APPROVED:
CONCURRENCE
TITLE
REVIEWED:
ES ARCHITECT / ENGINEER DATE
DATE
DATE
DATE
SHEET ______ OF ______
PARKER
INDIAN HEALTH CENTER RENOVATIONS
PARKER, AZ
HHSI161201200001I
SHEET TITLE
STRUCTURAL
Turner Structural Eng.
3026 N. Country Club Tucson, AZ 85716 Phone: 323.3422
MECHANICAL
Adams & Associates 4067 East Grant Rd, # 200 Tucson, AZ 85712 Phone: 323.3858
ELECTRICAL
M3 Engineering 2051 W. Sunset Rd, # 101 Tucson, AZ 85704 Phone: 293.1488
261 North Court Avenue Tucson, Arizona 85701
2051 W. SUNSET ROAD, SUITE 101
TUCSON, ARIZONA 85704
520.293.1488
M3-PN130091
1 1/8"=1'-0"
NEW POWER PLAN 2 1/8"=1'-0"
NEW LIGHTING PLAN
1. (E) DEVICES/LIGHT FIXTURES LOCATED INSIDE THIS ROOM SHALL REMAIN.
(U.O.N.)
2. INTERCEPT (E) CIRCUIT AND EXTEND CIRCUIT AS INDICATED.
3. PROVIDE J-BOX MOUNTED AS REQUIRED BY BOOTH MANUFACTURER.
CONNECT TO BOOTH PER MANUFACTURER REQUIREMENTS.
4. (E) DEVICE/LIGHT FIXTURE/SWITCH TO REMAIN.
5. DEVICES MOUNTED IN MILLWORK. COORDINATE EXACT MOUNTING
LOCATION WITH MILL WORK PROVIDER PRIOR TO ROUGH IN.
6. CONDUIT SHALL BE ROUTED UNDER FLOOR.
7. (N) RECEPTACLE LOCATED BELOW SINK FOR CONNECTION OF INFRARED
SINK. COORDINATE EXACT MOUNTING LOCATION WITH PLUMBING
CONTRACTOR PRIOR TO ROUGH IN.
8. (N) LOCATION OF (E) DEVICE/LIGHT FIXTURE/SWITCH. EXTEND (E) CIRCUIT TO
NEW LOCATION AS REQUIRED.
9. ALL ELECTRICAL LOCATED IN THIS ROOM TO REMAIN. (U.O.N.)
10. (E) CIRCUIT TO REMAIN.
11. EXTEND (E) CIRCUIT TO (N) LIGHT FIXTURES AS INDICATED.
12. EXTEND (E) LIFE-SAFETY CIRCUIT TO (N) LIGHT FIXTURES AS INDICATED. (E)
LOAD PER AS-BUILT DRAWINGS IS 2,500 VA @ 1.25%. LOAD REMOVED IS 1,163
VA @ 1.25% AND LOAD ADDED IS 853 VA @ 1.25%, THEREFORE THERE IS A
NET LOAD REDUCTION IN EXISTING 277 VOLT, 20 AMPERE CIRCUIT.
13. INTERCEPT (E) DOOR OPERATOR CIRCUIT & EXTEND TO (N) DOOR
OPERATOR. CONNECT TO DOOR OPERATORS PER MANUFACTURER
REQUIREMENTS.
14. PUSH PLATE ACTUATOR PROVIDED BY OTHERS. COORDINATE EXACT
MOUNTING LOCATION WITH DOOR HARDWARE MANUFACTURER AND MAKE
CONNECTION AS REQUIRED.
15. 1" C WITH CONTROL WIRING PER MANUFACTURER REQUIREMENTS.
16. (N) LOCATION OF (E) VAV/CAV BOX. EXTEND (E) CIRCUIT TO (N) LOCATION.
17. (E) VAV BOX/EXHAUST FAN & ASSOCIATED ELECTRICAL TO REMAIN.
18. 120V AC CONTROL RELAY WITH 20 AMPERE CONTACTS IN NEMA-3R
ENCLOSURE FOR CONTROL OF EXHAUST FAN. COIL VOLTAGE TO MATCH
EMCS CONTROL VOLTAGE. RELAY SHALL ENERGIZE VIA EMCS SYSTEM.
19. 1" EC TO EMCS SYSTEM.
KEYED NOTES-
D$
PP-20 POWER PACK, 120/277 VAC; 20 AMPSP
WSD WALL SWITCH DECORATOR SENSOR; 120/277 VAC
WSD-PDT-2P-WALL SWITCH DECORATOR WALL SENSOR, MICROPHONIC & PIR DUAL TECHNOLOGY; 120/277 VAC
CM-PDT-9 CEILING MOUNT SENSOR; MICROPHONIC-DUAL TECHNOLOGY, 12 TO 24 VOLT VDC/VACCP9
OCCUPANCY SENSOR LEGEND
ELECTRICAL PLANS
EP001
LHB
1. ONE POWER PACK IS NEEDED PER CIRCUIT /ZONE TO BE CONTROLLED BY LOW VOLTAGE SENSORS. POWER PACK PLACEMENT ON DRAWINGS IS FOR COUNTING ONLY. FINAL PLACEMENT OF POWER PACK IS UP TO CONTRACTOR. CHECK
COUNTS TO VERIFY THE NUMBER OF POWER PACKS NEEDED TO MAKE A COMPLETE SYSTEM.
2. SENSOR PLACEMENT AND TYPES WERE PLACED WITH CURRENT PROJECT INFORMATION. ADDITIONAL SENSORS AND TYPES OF SENSORS MAY BE REQUIRED TO PROVIDE COMPLETE COVERAGE DEPENDING ON DRAWING CHANGES, EMS/BMS, FINAL PARTITION HEIGHT/PLACEMENT, FURNITURE PLACEMENT, EQUIPMENT HEIGHT/PLACEMENT AND
SHELVING HEIGHT/PLACEMENT.
3. SENSOR MASKING KITS MAY BE REQUIRED TO LIMIT COVERAGE DEPENDING ON REQUIREMENTS.
SENSOR NOTES
ELECTRICAL EQUIPMENT KEYED NOTES
WV DUAL TECHNOLOGY WALL/CEILING SENSOR, 24VDC/VAC
GENERAL NOTES
Typewritten Text mtouchan Rectangle tmcgann
600A, 277/480V, 3Ø, 4W
(E) DISTRIBUTION BOARD 'D5'
1. (E) (4) #500 KCMIL, (1) #3 AWG GRD., 4" TO REMAIN.
2. (E) (3) #2 AWG, (E) FLEX CONDUIT TO BE REMOVED.
3. (E) (2) PARALLEL SETS: (4) #4/0 AWG, #1 AWG GRD., 2-1/2"C EACH
SET TO REMAIN.
4. (E) (4) #4/0 AWG, #6 AWG GRD. TO BE REMOVED.
5. (N) (3) #3/0 AWG, #6 AWG GRD., 2" C.
6. (N) (2) PARALLEL SETS: (4) #4/0 AWG, #2 AWG GRD., 2-1/2"C, EACH
SET.
200/3
450/3
X X
X X
X X X
X
FO
XFMR FAULT CALC
400/3
1 2 3 4
A
B
C
A
B
C
1 2 3 4
REV
ISSUE: OCTOBER 23, 2013 CONSTRUCTION DOCUMENTS
PROJECT NO: 1117.200
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
ES BRANCH CHIEF
ES PROJECT MANAGER
AGENCY REPRESENTATIVE
APPROVED:
CONCURRENCE
TITLE
REVIEWED:
ES ARCHITECT / ENGINEER DATE
DATE
DATE
DATE
SHEET ______ OF ______
PARKER
INDIAN HEALTH CENTER RENOVATIONS
PARKER, AZ
HHSI161201200001I
SHEET TITLE
STRUCTURAL
Turner Structural Eng.
3026 N. Country Club Tucson, AZ 85716 Phone: 323.3422
MECHANICAL
Adams & Associates 4067 East Grant Rd, # 200 Tucson, AZ 85712 Phone: 323.3858
ELECTRICAL
M3 Engineering 2051 W. Sunset Rd, # 101 Tucson, AZ 85704 Phone: 293.1488
261 North Court Avenue Tucson, Arizona 85701
2051 W. SUNSET ROAD, SUITE 101
TUCSON, ARIZONA 85704
520.293.1488
M3-PN130091
PANEL SCHEDULES
EP101
LHB
1 N.T.S.
PARTIAL SINGLE LINE DIAGRAM
Typewritten Text mtouchan Rectangle tmcgann
+42"
+42"3
+42"3
+42"3
+42"3
+42"3
+42" +42" +42" +42" +42"
+42"
+42"
L
L
F
F F
+42"
+42" +42" +42"
+42"
+42"
F
F
MED. ROOM
CLEAN UTILITYSCN ROOMEXAM ROOM 16EXAM ROOM 15EXAM ROOM 14EXAM ROOM 13
MSA/FILES
MSA/FILES
AUDIOLOGY
EXAM ROOM 18
INFANT SCREENING
EXAM ROOM 17 -ISO MEDICAL EQUIPMENT QA OFFICE
MED. ROOM TEAM ROOM
RESTROOM
ELECTRICAL
EXAM ROOM 12
EXAM ROOM 11
EXAM ROOM 10
SOILED UTILITY
EXAM ROOM 9
EXAM ROOM 8
VESTIBULE
EXAM ROOM 7- ISO
EXAM ROOM 6 EXAM ROOM 5
EXAM ROOM 4
RESTROOM EXAM ROOM 3
JANITOR
EXAM ROOM 2
EXAM ROOM 1
NURSE STATION
NURSE STATION
TEAM ROOM
CORRIDORCORRIDOR
CORRIDOR
CORRIDOR
CORRIDOR
NC
NC NC NC NC NC
P
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
NCNCNCNC
NCP
1" EC 1" EC
1 1/4" EC
1" EC 1" EC
1-1/4" EC
F
S S
S
S
S
L
L
S
F
S
S
S
S
S
CR
WAP
WAP
WAP
WAP
NCS
(E)
NCS
NCS
F SD
L
F
FIRE ALARM GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE BOOSTER POWER
SUPPLIES/AMPLIFIERS AS REQUIRED BY MANUFACTURER.
COORDINATE LOCATIONS WITH OWNER. PROVIDE SMOKE
DETECTOR WITHIN 2' OF EACH BOOSTER POWER SUPPLY.
2. SEE SYSTEMS PLANS FOR LOCATIONS AND NUMBER OF
DEVICES.
3. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST
EDITION OF NFPA 72.
4. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2012 IFC & IBC.
5. ALL WORK SHALL BE IN ACCORDANCE WITH THE ARIZONA FIRE
CODE.
6. ALL DEVICES SHALL BE ADA COMPLIANT AND SHALL BE
INSTALLED/MOUNTED IN ACCORDANCE WITH ADA
REQUIREMENTS.
7. THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY, PRIOR TO
BID, THE EXACT LOCATIONS OF EACH EXISTING FIRE ALARM
CONTROL PANEL, AUDIO/VISUAL DEVICES AND ALL FIRE ALARM
SIGNAL CIRCUITS. EXACT ROUTING OF NEW CIRCUITS
CONNECTING TO EXISTING CIRCUITS SHALL BE
PREDETERMINED AND INCLUDED IN THE BID.
8. FIRE ALARM DESIGN IS CONCEPTUAL ONLY. CONTRACTOR
SHALL PROVIDE ADDITIONAL DEVICES REQUIRED TO COMPLY
WITH 2012 INTERNATIONAL FIRE CODE & 2012 BUILDING CODE
AND ANY CODES CALLED OUT ABOVE, AT NO ADDITIONAL COST
TO GOVERNMENT.
9. CONTRACTOR SHALL PROVIDE ADDITIONAL DEVICES IF
REQUIRED BY THE FIRE MARSHALL AT NO ADDITIONAL COST TO
GOVERNMENT.
10. FIRE ALARM IS DESIGNED AS PRIVATE MODE PER USER
PREFERENCE.
NOTES:
1. ALL NEW FIRE ALARM
DEVICES SHALL BE
COMPATIBLE WITH
EXISTING EST FIRE
ALARM CONTROL
PANEL.
2. CLIMATEC IS
PREFERRED
CONTRACTOR.
L FF
1 2 3 4
A
B
C
A
B
C
1 2 3 4
REV
ISSUE: OCTOBER 23, 2013 CONSTRUCTION DOCUMENTS
PROJECT NO: 1117.200
CAD DWG FILE:
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
U. S. DEPARTMENT
OF HEALTH AND
HUMAN SERVICES
ES BRANCH CHIEF
ES PROJECT MANAGER
AGENCY REPRESENTATIVE
APPROVED:
CONCURRENCE
TITLE
REVIEWED:
ES ARCHITECT / ENGINEER DATE
DATE
DATE
DATE
SHEET ______ OF ______
PARKER
INDIAN HEALTH CENTER RENOVATIONS
PARKER, AZ
HHSI161201200001I
SHEET TITLE
STRUCTURAL
Turner Structural Eng.
3026 N. Country Club Tucson, AZ 85716 Phone: 323.3422
MECHANICAL
Adams & Associates 4067 East Grant Rd, # 200 Tucson, AZ 85712 Phone: 323.3858
ELECTRICAL
M3 Engineering 2051 W. Sunset Rd, # 101 Tucson, AZ 85704 Phone: 293.1488
261 North Court Avenue Tucson, Arizona 85701
2051 W. SUNSET ROAD, SUITE 101
TUCSON, ARIZONA 85704
520.293.1488
M3-PN130091
1 1-7-14 ELECTRICAL CHANGE
1 1/8"=1'-0"
NEW SPECIAL SYSTEMS PLAN
1. DEVICES MOUNTED IN MILLWORK. COORDINATE EXACT MOUNTING LOCATION WITH MILLWORK PROVIDER.
2. EXISTING CABLE TRAY ABOVE CEILING TO REMAIN.
3. EXITING DEVICE TO REMAIN.
4. EXISTING SPEAKER TO REMAIN.
5. NEW LOCATION OF EXISTING SPEAKER. EXTEND EXISTING CIRCUIT TO NEW LOCATION AS REQUIRED.
6. CONDUIT ROUTED UNDER THE FLOOR WITHIN THE UNDER FLOOR SPACE.
7. ROUTE CONDUIT TO ABOVE CEILING AND NEAREST CABLE TRAY.
8. EXISTING NURSE CALL DEVICE TO REMAIN.
9. NEW LOCATION OF EXISTING NURSE CONSOLE.. EXTEND EXISTING CIRCUITS TO NEW LOCATION AS REQUIRED.
KEYED NOTES-
NEW SPECIAL SYSTEMS PLAN
EY001
LHB
2 N.T.S.
PARTIAL FIRE ALARM BLOCK DIAGRAM
1. RE-USE EXISTING NURSE CALL EQUIPMENT AND VERFIY WITH FACILITY FOR SPARE DEVICES.
GENERAL NOTE
Rectangle tmcgann Typewritten Text tmcgann
| CVR |
| G1-1 |
| G1-2 |
| D21 |
| D31 |
| A21 |
| A22 REV |
| A23 |
| A24 |
| A31 |
| A32 |
| A51 |
| A61 |
| A62 |
| A71 |
| A101 |
| F21 |
| 13040s1.1 |
| 13040s2.1 |
| 10-23-13.MG0-1 |
| 10-23-13.M0-1 |
| 10-23-13.M0-2 |
| 10-23-13.M1-1 |
| 10-23-13.M1-2 |
| 10-23-13.M2-1 |
| 10-23-13.M3-1 |
| 10-23-13.M4-1 |
| 10-23-13.M5-1 |
| 10-23-13.P0-1 |
| 10-23-13.P1-1 |
| 10-23-13.P2-1 |
| E001 |
| ED001 |
| EP001 |
| EP101 |
| EY001 |
File details come from the government source that posted it. Updated .