140R3023Q0010_-_Attachment_1_-_Specifications.pdf

PDF 65 KB Posted

Attached to
YAO Electrical Components Federal contract opportunity
Solicitation number
140R3023Q0010
Issued by
Department of the Interior Bureau of Reclamation

About this file

This document specifies requirements for a federal contract solicitation to provide Yuma Square D Motor Control Centers. The solicitation is for electrical components including an 800 amp 480/277V motor control center with a 65kA withstand rating, combination Altistart 48 soft starter, Power Logic PM8000 power meter, thermal magnetic circuit breakers, 240VAC transformer, and distribution panelboard. The power meter will monitor current, voltage, frequency, power factors, harmonic distortion, and provide data recording, communication via Modbus and Ethernet, and remote display. The solicitation was issued by the Department of the Interior Bureau of Reclamation for the identified electrical components to support their Yuma facility needs.

View the file

Other files for this federal contract opportunity

Other files attached to YAO Electrical Components, newest first.
File Type Posted
Attachment_1_-_Specifications_Sheet_5_18_23_0003.pdf PDF
Sol_140R3023Q0010_Amd_0003.pdf PDF
Sol_140R3023Q0010_Amd_0002.pdf PDF
Attachment_3_-_Statement_of_Work_Square_D_MCCs_0001.pdf PDF
Attachment_1_-_MCC_Specifications_Sheet_0001.pdf PDF
Attachment_4_-_Provisions_0001.pdf PDF
Sol_140R3023Q0010_Amd_0001.pdf PDF
Sol_140R3023Q0010.pdf PDF
140R3023Q0010_-_Attachment_2_-Clauses_and_Provisions.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

140R3023Q0010 Attachment 1 – Specifications

Yuma 242 MCC Equipment – Spec Sheet

1. Square D Model 6 MCC (Motor Control Center) by Schneider

a. 800 amps MJ 480/277V 3 pole main 65kAIC with 2X‐10X instantaneous setting

b. 65kA withstand rating

c. Incoming section fed from bottom

d. Outgoing motor feeders and power feeders from bottom

e. Incoming section at left

f. Hardwire control

g. 600 VAC

h. NEMA Type 3R with IR viewing windows

i. Provide Nameplates

j. Provide mimic bus in phone lic plate

k. Double barrel main lugs and lugs for the soft starter, 600MCM for the main and 500MCM for the starter

l. Modules for MCC

i. Combination Altistart 48 Soft Start (bypass included)

1. 400 type

2. C59 series starter frame

ii. Power Logic Power meter

1. PM870 (type)

2. PM8M2222 (I/O device)

3. CT included for the device

iii. 3 Thermal‐Magnetic Case Circuit breaker

1. 2 ‐ 60 amp & 1 20 amp (150 amp frame)

2. 480 VAC

3. HG, stand alone rated at (35kA)

iv. 240VAC Fusible Single Phase Transformer

1. 15 kVA

v. Distribution Panel board

1. 1‐phase Type NQ bolt on

2. 18 spaces

3. 4 ‐ 240 VAC 30 amp breakers (2EA 2‐Pole 240V)

4. 6 – 120 VAC 20 amp breakers (10EA 1‐pole 120V)

m. Infrared (IR) Window

2. PowerLogic PM8000 ‐ PM8244 DIN

a. Rail mount meter and remote display

b. Type of Measurements

i. Current

ii. Voltage

iii. Frequency

iv. Active and reactive power total

v. Apparent power total

vi. Power factor total

vii. Active and reactive power per phase, rms

140R3023Q0010 Attachment 1 – Specifications

viii. Apparent power per phase, rms

ix. Power factor per phase, rms

c. Remote LCD display

d. Info Displayed

i. Voltage

ii. Current

iii. Frequency

iv. Power

v. Energy consumption

vi. Harmonic distortion

e. Data Recording

i. Sequence of event recording

ii. Event logs

iii. Min/max of instantaneous values

iv. Harmonics logs

v. Alarm logs

vi. GPS synchronisation

vii. Waveform logs

viii. Data logs

ix. Time stamping

x. Trending/forecasting

xi. Sag and swell logs

f. Communication Port Protocol

i. Modbus RTU 115 kbauds ‐ 2‐wire

ii. ION 115 kbauds ‐ 2‐wire

iii. DNP3

iv. IEC 61850

v. Modbus TCP/IP

vi. Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s

vii. RSTP 801.1d 2004