140R3023Q0010_-_Attachment_1_-_Specifications.pdf
PDF 65 KB Posted
- Attached to
- YAO Electrical Components Federal contract opportunity
- Solicitation number
- 140R3023Q0010
About this file
This document specifies requirements for a federal contract solicitation to provide Yuma Square D Motor Control Centers. The solicitation is for electrical components including an 800 amp 480/277V motor control center with a 65kA withstand rating, combination Altistart 48 soft starter, Power Logic PM8000 power meter, thermal magnetic circuit breakers, 240VAC transformer, and distribution panelboard. The power meter will monitor current, voltage, frequency, power factors, harmonic distortion, and provide data recording, communication via Modbus and Ethernet, and remote display. The solicitation was issued by the Department of the Interior Bureau of Reclamation for the identified electrical components to support their Yuma facility needs.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment_1_-_Specifications_Sheet_5_18_23_0003.pdf | ||
| Sol_140R3023Q0010_Amd_0003.pdf | ||
| Sol_140R3023Q0010_Amd_0002.pdf | ||
| Attachment_3_-_Statement_of_Work_Square_D_MCCs_0001.pdf | ||
| Attachment_1_-_MCC_Specifications_Sheet_0001.pdf | ||
| Attachment_4_-_Provisions_0001.pdf | ||
| Sol_140R3023Q0010_Amd_0001.pdf | ||
| Sol_140R3023Q0010.pdf | ||
| 140R3023Q0010_-_Attachment_2_-Clauses_and_Provisions.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140R3023Q0010 Attachment 1 – Specifications
Yuma 242 MCC Equipment – Spec Sheet
1. Square D Model 6 MCC (Motor Control Center) by Schneider
a. 800 amps MJ 480/277V 3 pole main 65kAIC with 2X‐10X instantaneous setting
b. 65kA withstand rating
c. Incoming section fed from bottom
d. Outgoing motor feeders and power feeders from bottom
e. Incoming section at left
f. Hardwire control
g. 600 VAC
h. NEMA Type 3R with IR viewing windows
i. Provide Nameplates
j. Provide mimic bus in phone lic plate
k. Double barrel main lugs and lugs for the soft starter, 600MCM for the main and 500MCM for the starter
l. Modules for MCC
i. Combination Altistart 48 Soft Start (bypass included)
1. 400 type
2. C59 series starter frame
ii. Power Logic Power meter
1. PM870 (type)
2. PM8M2222 (I/O device)
3. CT included for the device
iii. 3 Thermal‐Magnetic Case Circuit breaker
1. 2 ‐ 60 amp & 1 20 amp (150 amp frame)
2. 480 VAC
3. HG, stand alone rated at (35kA)
iv. 240VAC Fusible Single Phase Transformer
1. 15 kVA
v. Distribution Panel board
1. 1‐phase Type NQ bolt on
2. 18 spaces
3. 4 ‐ 240 VAC 30 amp breakers (2EA 2‐Pole 240V)
4. 6 – 120 VAC 20 amp breakers (10EA 1‐pole 120V)
m. Infrared (IR) Window
2. PowerLogic PM8000 ‐ PM8244 DIN
a. Rail mount meter and remote display
b. Type of Measurements
i. Current
ii. Voltage
iii. Frequency
iv. Active and reactive power total
v. Apparent power total
vi. Power factor total
vii. Active and reactive power per phase, rms
140R3023Q0010 Attachment 1 – Specifications
viii. Apparent power per phase, rms
ix. Power factor per phase, rms
c. Remote LCD display
d. Info Displayed
i. Voltage
ii. Current
iii. Frequency
iv. Power
v. Energy consumption
vi. Harmonic distortion
e. Data Recording
i. Sequence of event recording
ii. Event logs
iii. Min/max of instantaneous values
iv. Harmonics logs
v. Alarm logs
vi. GPS synchronisation
vii. Waveform logs
viii. Data logs
ix. Time stamping
x. Trending/forecasting
xi. Sag and swell logs
f. Communication Port Protocol
i. Modbus RTU 115 kbauds ‐ 2‐wire
ii. ION 115 kbauds ‐ 2‐wire
iii. DNP3
iv. IEC 61850
v. Modbus TCP/IP
vi. Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s
vii. RSTP 801.1d 2004