140R3021Q0023 DAVIS DAM ADMIN OFFICE TRANSFORMER

Questions and Answers

Do you have a spec on what breakers they want in the 2 panels.

Breaker specs are in the Salient Characteristics under the respective panel heading.

We need to know they are indoor or outdoor and if they are main breaker or main lug.

The 480V panel is main breaker and NEMA 3R rated and will be outdoors.

The 208V panel is main breaker and NEMA 1 rated and will be indoors.

Other info that would be needed is overhead or underground feed, if indoor is it flush or surface mount?

Both panels will be surface mounted and bottom feed. Salient Characteristics update to reflect the panel feed.