B09_Attachment_5_corrected_0001.pdf
PDF 71 KB Posted
- Attached to
- Fire Systems Maintenance, Death Valley, California Federal contract opportunity
- Solicitation number
- 140P8122Q0064
About this file
This document contains an attachment outlining deficiencies and required repairs at various buildings within Death Valley National Park, along with a related federal contract opportunity notice. The attachment lists twenty building locations in need of fire sprinkler system inspections, testing, and repairs such as replacing sprinkler heads, adding sprinkler coverage in new areas, rebuilding air actuation valves, installing missing escutcheons, and testing backflows. It also specifies required five year inspections at several buildings. The related federal contract opportunity is a solicitation from the Department of the Interior National Park Service Pacific West Region seeking bids for fire systems inspection, testing and maintenance services within Death Valley National Park. The response is needed to address deficiencies across multiple park buildings as detailed in the attachment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B09_Cow_Creek_Area_Map_0002.pdf | ||
| Sol_140P8122Q0064_Amd_0002.pdf | ||
| Sol_140P8122Q0064_Amd_0001.pdf | ||
| B03_Wage_Determination_20155669.pdf | ||
| B08_Attachment_10.pdf | ||
| B08_Attachments_1_through_3.pdf | ||
| Sol_140P8122Q0064.pdf | ||
| B08_Price_Schedule.pdf | ||
| B08_Attachment_8.pdf | ||
| B08_Attachment_7.pdf | ||
| B08_Attachment_13.pdf | ||
| B08_Attachment_12.pdf | ||
| B08_Attachment_11.pdf | ||
| B08_Attachment_6.pdf | ||
| B08_Attachment_5.pdf | ||
| A04_Scope_of_Services.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT 5
BUILDING
DESCRIPTION
Trade Shop
Curatorial bldg
Visitors center
HQ
Annex
Gas house
Cookhouse
Stables
Ranger Station warehouse
MAINT. ADMIN
AUTO SHOP
International Hall
Salt Pan vista dorm west
Salt Pan vista dorm east
BUILDING NUMBER DEFICIENCY SCOPE OF WORK
REPAIRS BY BUILDING NUMBER ‐ DEATH VALLEY NATIONAL PARK ‐ 2022 STRUCTURAL FIRE
PV353 5 year inspection needed perform 5 year inspection
PV354 5 year inspection needed perform 5 year inspection
CC348 5 year inspection needed perform 5 year inspection
CC350 5 year inspection needed perform 5 year inspection
CC62 5 year inspection needed perform 5 year inspection
CC316 5 year inspection needed and backflow needs to be tested perform 5 year inspection and test backflow
SC11 3 loaded 200 deg brass uprights in stables. Wasp nest. Unprotected area in Stables storage. A room was placed in with ceiling that has not coverage replace loaded heads, add sprinklers to ceiling in storage room
SP351 5 white concealed escutcheon need replaced for either damage of paint.
replace escutcheons
SC6 FDC caps missing install FDC caps
SC2 Dry heads are older then 10 years and need replaced or tested, Castle garage loaded heads (wasp nest) 3 155 deg brass HSW SR, Loaded head Castle Courtyard patio Dry Pen 155 deg brass SR,Painted head annex entryway at bridge 155 deg HSW brass SR replace 4 dry heads and send off for testing. replace painted heads and loaded heads.
SC5 System was out of service. Air is bypassing past diaphragm of Air Actuation valve. Needs rebuilt, System was out of service to keep compressor from cycling. Was cycling every 15 mins,Entire riser is open to the exterior of the building in the elimates, FDC ends do not replace air actuation, replace FDC, clean out birds nest in bell.
FC270 Loaded head Mens room 155 QR wh pen, MDR room missing escutcheon wh,Missing escutcheon main visitors center near water fountains. 3 missing escutcheons HSW in theater 3 missing escutcheon in front of screen in theater. Missing escutcheon left of replaced loaded heads and install missing escutchoens and perform 5 year inspection
FC271 PIV does not have a break away lock on it,HQ mail room missing escutcheon and loaded head 155 QR WH pen,South entryway missing escutcheon,Bullpen east door painted head 155 QR WH pen. 5 year inspection needed add lock to PIV, replace painted heads and install missing escutcheons and perfrom 5 year inspection
CC54 No coverage under roll up garage doors (2) 5 year inspection needed. Backflow needs tested
Add heads for garage doors, perform 5 year inspection and test backflow
CC345 Reading room and hall near mechanical room painted head (2) 155 SR Chrome pen, Outside dark room/ lab painted head 155 SR chrome,Painted head workroom 155 SR chrome. 5 year inspection needed replace 4 sprinkler heads and perform 5 year inspection