B09_Attachment_5_corrected_0001.pdf

PDF 71 KB Posted

Attached to
Fire Systems Maintenance, Death Valley, California Federal contract opportunity
Solicitation number
140P8122Q0064
Issued by
Department of the Interior National Park Service Pacific West Region

About this file

This document contains an attachment outlining deficiencies and required repairs at various buildings within Death Valley National Park, along with a related federal contract opportunity notice. The attachment lists twenty building locations in need of fire sprinkler system inspections, testing, and repairs such as replacing sprinkler heads, adding sprinkler coverage in new areas, rebuilding air actuation valves, installing missing escutcheons, and testing backflows. It also specifies required five year inspections at several buildings. The related federal contract opportunity is a solicitation from the Department of the Interior National Park Service Pacific West Region seeking bids for fire systems inspection, testing and maintenance services within Death Valley National Park. The response is needed to address deficiencies across multiple park buildings as detailed in the attachment.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Systems Maintenance, Death Valley, California, newest first.
File Type Posted
B09_Cow_Creek_Area_Map_0002.pdf PDF
Sol_140P8122Q0064_Amd_0002.pdf PDF
Sol_140P8122Q0064_Amd_0001.pdf PDF
B03_Wage_Determination_20155669.pdf PDF
B08_Attachment_10.pdf PDF
B08_Attachments_1_through_3.pdf PDF
Sol_140P8122Q0064.pdf PDF
B08_Price_Schedule.pdf PDF
B08_Attachment_8.pdf PDF
B08_Attachment_7.pdf PDF
B08_Attachment_13.pdf PDF
B08_Attachment_12.pdf PDF
B08_Attachment_11.pdf PDF
B08_Attachment_6.pdf PDF
B08_Attachment_5.pdf PDF
A04_Scope_of_Services.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ATTACHMENT 5

BUILDING

DESCRIPTION

Trade Shop

Curatorial bldg

Visitors center

HQ

Annex

Gas house

Cookhouse

Stables

Ranger Station warehouse

MAINT. ADMIN

AUTO SHOP

International Hall

Salt Pan vista dorm west

Salt Pan vista dorm east

BUILDING NUMBER DEFICIENCY SCOPE OF WORK

REPAIRS BY BUILDING NUMBER ‐ DEATH VALLEY NATIONAL PARK ‐ 2022 STRUCTURAL FIRE

PV353 5 year inspection needed perform 5 year inspection

PV354 5 year inspection needed perform 5 year inspection

CC348 5 year inspection needed perform 5 year inspection

CC350 5 year inspection needed perform 5 year inspection

CC62 5 year inspection needed perform 5 year inspection

CC316 5 year inspection needed and backflow needs to be tested perform 5 year inspection and test backflow

SC11 3 loaded 200 deg brass uprights in stables. Wasp nest. Unprotected area in Stables storage. A room was placed in with ceiling that has not coverage replace loaded heads, add sprinklers to ceiling in storage room

SP351 5 white concealed escutcheon need replaced for either damage of paint.

replace escutcheons

SC6 FDC caps missing install FDC caps

SC2 Dry heads are older then 10 years and need replaced or tested, Castle garage loaded heads (wasp nest) 3 155 deg brass HSW SR, Loaded head Castle Courtyard patio Dry Pen 155 deg brass SR,Painted head annex entryway at bridge 155 deg HSW brass SR replace 4 dry heads and send off for testing. replace painted heads and loaded heads.

SC5 System was out of service. Air is bypassing past diaphragm of Air Actuation valve. Needs rebuilt, System was out of service to keep compressor from cycling. Was cycling every 15 mins,Entire riser is open to the exterior of the building in the elimates, FDC ends do not replace air actuation, replace FDC, clean out birds nest in bell.

FC270 Loaded head Mens room 155 QR wh pen, MDR room missing escutcheon wh,Missing escutcheon main visitors center near water fountains. 3 missing escutcheons HSW in theater 3 missing escutcheon in front of screen in theater. Missing escutcheon left of replaced loaded heads and install missing escutchoens and perform 5 year inspection

FC271 PIV does not have a break away lock on it,HQ mail room missing escutcheon and loaded head 155 QR WH pen,South entryway missing escutcheon,Bullpen east door painted head 155 QR WH pen. 5 year inspection needed add lock to PIV, replace painted heads and install missing escutcheons and perfrom 5 year inspection

CC54 No coverage under roll up garage doors (2) 5 year inspection needed. Backflow needs tested

Add heads for garage doors, perform 5 year inspection and test backflow

CC345 Reading room and hall near mechanical room painted head (2) 155 SR Chrome pen, Outside dark room/ lab painted head 155 SR chrome,Painted head workroom 155 SR chrome. 5 year inspection needed replace 4 sprinkler heads and perform 5 year inspection