Questions_and_Answers_0001.pdf
PDF 224 KB Posted
- Attached to
- DEVA FIRE SUPPRESSION ITM REPAIRS Federal contract opportunity
- Solicitation number
- 140P8121Q0096
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P8121Q0096_Amd_0002.pdf | ||
| Sol_140P8121Q0096_Amd_0001.pdf | ||
| Reference_Manual_58_Structural_Fire_Management.pdf | ||
| 7_DEVA_315287_-_Commercial_Sprinkler_Systems_List_for_ITM.pdf | ||
| 5_DEVA_315287_Structural_Fire_-_Repair_Scope_by_building_number.pdf | ||
| 2_DEVA_315287_Structural_Fire_-_Cow_Creek_Housing_Map.pdf | ||
| 1_DEVA_315287_Structural_Fire_-_CC_Overview_Map.pdf | ||
| Sol_140P8121Q0096.pdf | ||
| A04_Statement_of_Work.pdf | ||
| 11_DEVA_315287_AS1A_AS2A_FS1A_RFP1_forms_from_2020_reduced.pdf | ||
| 8_DEVA_315287_-_Residential_Sprinkler_Systems_List_for_ITM.pdf | ||
| B03_SCA_Minimum_Wage_Determination.pdf | ||
| 6_DEVA_315287_-_Fire_Alarm_Systems_List_for_ITM.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RFQ# 140P8121Q0096
Q&A 08/10/2021
| See | Map | for | Color | Code | references | on | Heads, |
| yellow | = | 3 | bedroom | Generally | 5‐6 | Heads | |
| purple | = | 2 | bedroom | Generally | 4‐5 | Heads | |
| green | = | 1 | bedroom | Generally | 3‐4 | Heads | |
| pink | = | studio | 2‐3 | Heads |
CCQ1 Canyon View Ct (2 BR house), Replace CCQ1 Sprinkler Heads and Gauges:
Need to know the following: Needs to match the existing FD approved fire sprinkler heads and we need to know if we will have to adjust the existing pipe length for the sprinkler head size.
Make, Model & Temperature of sprinkler heads? No Idea, system is old we have no infomation
Standard or Quick response? Standard Pendent or Upright? Pendent Color? White Quantity of fire sprinkler heads needed? 1,051 is too many for 2 bedroom house. That is a square footage reference, see info above for head numbers per the map CCQ329 Skyline Rd (2 BR house), Replace CCQ329 Riser.
Need to know the following:
Size of riser? 2" Make, Model & Temperature of sprinkler heads to be replaced? No Idea, system is old we have no infomation Standard or Quick response?Standard Pendent or Upright? Pendent Color? White Quantity of fire sprinkler heads needed? 1,557 is too many for 2 bedroom house. That is a square footage reference, see info above for head numbers per the map CCQ343 Nevares (4‐plex apartment), Replace CCQ343 Riser.
Need to know the following:
Size of riser? 2" Make, Model & Temperature of sprinkler heads to be replaced? No Idea, system is old we have no infomation Standard or Quick response?Standard Pendent or Upright? Pendent Color? White Quantity of fire sprinkler heads needed? 2,940 is too many Same as above
CCQ343 Nevares (4‐plex apartment), Replace CCQ343 Riser Size of Flow Switch: 1”, 2”, 4” ? 2" Size of Bell: 6” or 10”? 6 Bell powered by 120 or 24 volt? 120
CCQ334 Coyote Loop (3 BR house), Replace CCQ334 Riser Need to know the following:
Size of riser? 2" Make, Model & Temperature of sprinkler head to be replaced? No Idea Standard or Quick response? Standard Pendent or Upright?Pendent Color?White Quantity of fire sprinkler heads needed? Same as above Size of Flow Switch: 1”, 2”, 4” ? 2" Size of Bell: 6” or 10”? 6"
08/10/2021
Bell powered by 120 or 24 volt? 120 CCQ341 Coyote Loop (3 BR house), Replace CCQ341 ITV Need to know the following:
Size of ITV? No Idea Make, Model & Temperature of sprinkler heads to be replaced? No Idea Standard or Quick response?Standard Pendent or Upright?Pendent Color?White Quantity of fire sprinkler heads needed? Same as above
CCQ342 Coyote Loop (3 BR house), Replace CCQ342 ITV and Exterior Control Valve Need to know the following:
Size of ITV and Exterior Control Valve? NO Idea water is 2 inch coming in from the street Make, Model & Temperature of sprinkler heads to be replaced? No idea Standard or Quick response?Standard Pendent or Upright?Pendent Color?White Quantity of fire sprinkler heads needed? Same as above Water was turned off to system, do you want us to air test the system before we put water back into the system? Potential water damage if not air tested. Water was turned off but I dont think it was drained. If it was drained from system yes.
Are we to troubleshoot system for leaks? Yes CCQ336 Coyote Loop (duplex ‐ 2 BR apartments), Replace CCQ336 ITV Need to know the following:
Size of ITV? No Idea Make, Model & Temperature of sprinkler heads to be replaced?No Idea Standard or Quick response? Standard Pendent or Upright?Pendant Color?White Quantity of fire sprinkler heads needed? Same as Above
CCQ337 Coyote Loop (duplex ‐ 2 BR apartments), Replace CCQ337 ITV Need to know the following:
Size of ITV? No Idea, 2 inch coming from street Make, Model & Temperature of sprinkler heads to be replaced?No Idea Standard or Quick response? Standard Pendent or Upright?Pendent?
Color?White Quantity of fire sprinkler heads needed? Same as above Water was turned off to system, do you want us to air test the system before we put water back into the system? Potential water damage if not air tested.
Are we to troubleshoot system for leaks? Same as above
CCQ338 Coyote Loop (duplex ‐ 2 BR apartments), Replace CCQ338 ITV Need to know the following:
Size of ITV? Same as above Make, Model & Temperature of sprinkler heads to be replaced?Same as above Standard or Quick response?Same as above Pendent or Upright?Same as above Color?Same as above Quantity of fire sprinkler heads needed? Same as above
CCQ331 Skyline Rd (duplex ‐ 2 BR apartments), Replace CCQ331 Riser
08/10/2021 Need to know the following:
Size of riser? 2" Make, Model & Temperature of sprinkler head to be replaced?Same as above Standard or Quick response?Same as above Pendent or Upright?Same as above Color?Same as above Quantity of fire sprinkler heads needed?Same as above Are we to replace rusted fittings? How many? If that is part of the repairs listed on inspections from year before, Yes they need to be replaced, and Not sure of Quantity.
Size of Flow Switch: 1”, 2”, 4” ? 2" Size of Bell: 6” or 10”?6" Bell powered by 120 or 24 volt? 120
FC270 Furnace Creek Visitor Center, Need to know the following:
2 SSM/SSV Smoke detector replacements only? Yes Cyclic Maintenance is referring to the Annual fire alarm inspection? Yes Confirming that the batteries do not need to be replaced. Correct
FC271 Furnace Creek Visitor Center, Need to know the following:
Replace (2) OS&Y Valve Seals: Size, Make and Model of the OS&Y Yes and Im not sure Cyclic Maintenance is referring to the Annual fire alarm inspection? Yes
SPQ333 Dunes View Dr (duplex ‐ 2 BR apartments), Install SPQ333 ITV Only need to replace ITV? Size? Not sure
SPQ332 Dunes View Dr (duplex ‐ 2 BR apartments), Install SPQ332 ITV Only need to replace ITV? Size?Not sure
CC316 Maintenance Admin Bldg, Replace CC316 OS&Y Tamper Switch Need to know the following:
CCQ359 Skyline (one‐bedroom triplex), Replace CCQ359 Sprinkler Heads and Gauges
Need to know the following:
Make, Model & Temperature of sprinkler heads to be replaced? Not sure
Standard or Quick response? Same as above
Pendent or Upright?Same as above
Color?Same as above
Quantity of fire sprinkler heads needed? 2421 is too many Same as above CCQ357 Old Ghost Duplex: 2 bedroom units, Replace CCQ357 Sprinkler Heads and Gauges
Need to know the following:
Make, Model & Temperature of sprinkler heads to be replaced? Same as above
Standard or Quick response? Same as above
Pendent or Upright? Same as above
Color? Same as above
Quantity of fire sprinkler heads needed? 3050 is too many Same as above CCQ358 Old Ghost Duplex: 2 bedroom units, Replace CCQ358 Sprinkler Heads and Gauges
Need to know the following:
Make, Model & Temperature of sprinkler heads to be replaced? Same as above
Standard or Quick response? Same as above
Pendent or Upright? Same as above
Color? Same as above
Quantity of fire sprinkler heads needed? 3050 is too many Same as above PV353 Salt Pan Vista Dormitory (West), Replace PV353 Sprinkler Heads and Gauges
08/10/2021
Need to know the following:
Make, Model & Temperature of sprinkler heads to be replaced? Same as above Standard or Quick response? Same as above Pendent or Upright? Same as above Color? Same as above Quantity? 3144 is too many. Same as above
PV354 Salt Pan Vista Dormitory (East), Replace PV354 Sprinkler Heads and Gauges Need to know the following:
Make, Model & Temperature of sprinkler heads to be replaced? Same as above Standard or Quick response?Same as above Pendent or Upright?Same as above Color?Same as above Quantity? 3144 is too many. Same as above