Atch_5_Questions_and_Answers_0004.pdf

PDF 74 KB Posted

Attached to
MORU INSTALL FIRE SUPPRESSION SYSTEM QTS #51 Federal contract opportunity
Solicitation number
140P6324Q0037
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document contains Questions and Answers related to a federal contract opportunity for the design and installation of a Fire Suppression System at Housing Quarters #51 at Mount Rushmore National Monument. The contract requires the system to comply with either NFPA 13D (for one- or two-family dwellings) or NFPA 13R (for residential occupancies up to four stories), and the contractor can choose which standard to use. The current water supply at the site is barely sufficient for a 13D system with two sprinkler heads, and would not support a 13R system with four heads. The contractor will be required to provide a design submittal that works in the most cost-effective way while still complying with either 13D or 13R.

View the file

Other files for this federal contract opportunity

Other files attached to MORU INSTALL FIRE SUPPRESSION SYSTEM QTS #51, newest first.
File Type Posted
Sol_140P6324Q0037_Amd_0004.pdf PDF
Sol_140P6324Q0037_Amd_0003.pdf PDF
Atch_5_Questions_and_Answers_0002.pdf PDF
Sol_140P6324Q0037_Amd_0002.pdf PDF
Sol_140P6324Q0037_Amd_0001.pdf PDF
Atch_5_Questions_and_Answers_0001.pdf PDF
Atch_6_Site_Visit_-_Sign-in_Sheet_0001.pdf PDF
Atch_4_DOL_Wage_Determination_SD20240029.pdf PDF
Atch_1_SOW.pdf PDF
Atch_2_Floor_Plan.pdf PDF
Sol_140P6324Q0037.pdf PDF
Atch_3_Experience_Questionnaire.xls XLS spreadsheet
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers:

16. In response to amendments 1 and 2, stating the design standard is NFPA 13R and not NFPA 13D:

(a) Per NFPA 13D (one- or two-family dwellings, manufactured homes or townhouses):

Two sprinklers heads are required to be calculated. System components do not have to be listed for fire sprinkler use. A fire department connection is not required.

(b) Per NFPA 13R (residential occupancies up to and including four stories):

Four sprinkler heads are required to be calculated. System components must be listed for fire sprinkler use. A fire department connection is required.

• The contractor can use either 13D or 13R. The offeror will still be required to provide the design submittal that will work in the most cost-effective way and still comply with either 13D or 13R for review.

17. Unit 46 was designed and installed per NFPA 13D. The current water supply was barely enough to calculate two sprinkler heads – a +3.3 psi of overage. If two more heads are added to the hydraulic calculation, the current water supply will not be enough to supply the fire sprinkler system.

• The fire suppression system will match unit 46, (installed across the street from 51).