Atch_6_Questions_and_Answers_0002.docx

DOCX document 14 KB Posted

Attached to
SCBL Upgrade Maintenance Fire and Security Alarm S Federal contract opportunity
Solicitation number
140P6324Q0014
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document contains Questions and Answers related to a federal contract opportunity for the upgrade of the maintenance, fire, and security alarm system at Scotts Bluff National Monument.

The key details are:

  • The network lines between the buildings appear to already be in place, as noted on page EO1 and drawing 3.
  • If the contractor encounters asbestos during construction, they must stop work and immediately contact the Contracting Officer (CO) and Contracting Officer's Representative (COR).
  • There is attic space above the office area, but no loft in the vehicle bays.
  • Park staff will be responsible for relocating any furniture or items, and contractors should coordinate with them at least 48 hours prior to required access.

The related federal contract opportunity is a Request for Quotes (RFQ) for the Scotts Bluff National Monument Upgrade Maintenance Fire and Security Alarm System, with Solicitation Number 140P6324Q0014, issued by the Department of the Interior National Park Service Midwest Region.

View the file

Other files for this federal contract opportunity

Other files attached to SCBL Upgrade Maintenance Fire and Security Alarm S, newest first.
File Type Posted
Sol_140P6324Q0014_Amd_0002.pdf PDF
Atch_7_Site_Visit_Sign-in_Sheet_0002.pdf PDF
Sol_140P6324Q0014_Amd_0001.pdf PDF
Atch_3_SOW_Drawings-8_pages_0001.pdf PDF
Atch_4_Experience_Questionnaire.xls XLS spreadsheet
Sol_140P6324Q0014.pdf PDF
Atch_5_DOL_Wage_Determination_NE20240079.pdf PDF
Atch_2_SOW_Div_2_thru_49.pdf PDF
Atch_1_SOW_Div_1.pdf PDF
Atch_3_SOW_Drawings.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers:

1. Do the network lines already run between buildings (referring to maintenance and visitor center)?

Yes, see notes on page EO1 and drawing 3 (Data Network Schematic) on sheet E 3

1. Does asbestos abatement need to be part of the scope?

If the contractor comes across asbestos during construction, stop work, and contact the CO and COR immediately.

1. Is there a loft above the shop? Or is the loft in the vehicle bays only?

There is attic space above the office area.

1. Will the owner plan to move furniture, boxes, etc?

Park staff will relocate furniture, boxes, etc. If there is any furniture or items that need to be moved, please communicate with park staff at least 48 hours prior to required access.