QUESTIONS AND ANSWERS_0001.pdf
PDF 406 KB Posted
- Attached to
- INSTALL FIRE SUPPRESSION SYSTEM IN VC Federal contract opportunity
- Solicitation number
- 140P5220R0025
About this file
This document contains questions and answers related to a federal solicitation to install a fire suppression system at the Abraham Lincoln Birthplace National Historical Park. The solicitation is seeking a general contractor to be responsible for coordinating all work, including fire alarm and suppression installation supervised by a NICET Level II certified individual on-site at all times. Ductile iron pipe is required with restrained joints for the fire service connection from the water main. Testing will include a hydrostatic test at 200psi and new flow tests due to the age of previous tests. Coordination drawings will be provided by the general contractor. No design submission to the state of Kentucky is necessary as this is a project on federal property.
The related federal contract opportunity is solicitation number 140P5220R0025 from the Department of the Interior National Park Service Southeast Region to install a fire suppression system at the Abraham Lincoln Birthplace National Historical Park for $500,000 to $1,000,000. The general contractor will be responsible for all coordination and work must meet specifications for approval.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B11 - Site Visit Docs_0001.pdf | ||
| Sol_140P5220R0025_Amd_0001.pdf | ||
| B03 - DOL Wage Determination.pdf | ||
| Sol_140P5220R0025.pdf | ||
| A06 - Drawings.pdf | ||
| Provisions and Clauses - UCF1.docx | DOCX document | |
| Past Performance Worksheet.doc | DOC document | |
| Proposal Submission Package.docx | DOCX document | |
| A06 - Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABLI Install Fire Suppression System In V.C.
REVIEWER: SP
DATE REVIEWED: 08/16/2020
NO. Section Contractor Question RESPONSE
Spec Section 211313/1.6B
This is an unusual requirement. We do a lot of government work and have been allowed to submit documentation for our installer to be qualified as a competent person. Will this suffice?
If it has to be a NICET Level II, is that for Sprinkler design?
As stated during the Pre-Bid Visit, during any Fire Alarm, Fire Suppression Work is being conducted a NICET Level ll must be on site.All fire protection installation work shall be supervised by a NICET Level II or higher certified individual.
NICET Level II certified supervisor shall be on-site any time work is on-going. This can be found in Section 211313-2/1.6B
2 1.6D
Is the sprinkler subcontractor responsible for this or GC? The Government contract will be with the General Contractor, therfore the General Contractor will be responsible for all Work
3 1.9A 1.a
Does the PE or NICET Level III or higher perform the hydrostatic test?
The Contractor and the NICET Level ll is responsible for all testing. The Contracting Officer Represetative must be present at all testing as a witness. See Divisions 02 through 49 Sections for specific test and inspection requirements.
4 2.2A
Is schedule 10 black pipe allowed? See Specification Section 211313 3.15 Piping Schedule
5 2.5
Is grooved end BFP’s acceptable? End Connections are specified as to be Flanged, however Grooved ends on the BFP's is acceptable. See Specifications 211313-6 2.4/5
6 2.7B
This section addresses alarm valves. Is the intent to install this?
With the installation of the BFP there will be 3 check valves that will have to be accounted for with pressure loss
See Riser detail on FP002 for riser requirments, Alarm check valve would not be required.
7 2.9C
Is this to be included in our price or can we provide capped openings for future flushing connections?
Capped openings for future flushing connections would be acceptable.
8 2.11 B-C
Which is preferred? Electric Alarm Bell is indicated to be used in the Riser Detail on FP002 and on E100 on the fire alarm plans
9 3.2 Does this section apply to this project? Since hose stations are not being installed this does not apply.
10 3.8
Does this section apply to this project? Since a stand pipe is not being installed this does not apply
Spec Section 312500/2.1
Would you provide a manufacturer name for these products? Selected Contractor will need to meet Specification Requirements and submit to Contracting Officer for Approval.
Spec Section 331000/2.2B
Is C-900 pipe allowed? All Pipe should be DIP C-900 is not allowed
13 2.2C If DIP, is slip joint acceptable? No all pipe should be Restrained Joint.
14 2.7
Since we are cutting the water main to install a cap and valve would it not be acceptable to install a mechanical joint tee and valve for the fire service?
Installation of a mechanical joint tee and valve for the fire service is acceptable. Cap should still be installed
15 3.7
Code requires 200 psi minimum. Not sure what the static pressure is onsite
The hydrostatic testing of all the system piping will be at 200psi regardless of onsite static pressure. The contractor will need to do new flow tests since the last ones are over 12 months old.
After the constrcution is completed the contractor should perform a flow and pressure test to verify flow and pressure.
16 Spec Section 210510
Will other trades provide drawings in CAD for us to use in the coordination drawings?
The Genaral Contractor who has the contract with the Federal Government will be responsible for coordination with trades
17 Will the Sprinkler Design need to be submitted to The State of Kentucky for review and permit?
No- This project is on Federal Property
DSC-49
Revised December 2003 1 of 1