Amd006_0006.pdf

PDF 112 KB Posted

Attached to
SARA HVAC CONTROLS Federal contract opportunity
Solicitation number
140P4324Q0025
Issued by
Department of the Interior National Park Service Northeast Region

About this file

This document is an Amendment 006 to a Request for Information (RFI) for the SARA HVAC Controls contract, Solicitation Number 140P4324Q0025. The RFI discusses the facility's requirement to shut down all HVAC equipment when the fire alarm is triggered, including furnaces, air handlers, and exhaust fans. The existing fire alarm system is a non-addressable Honeywell panel, and some of the fire alarm components have been decommissioned or the cabling has been cut, making it potentially unusable. The government response indicates that the HVAC shutdown by the fire alarm system was not required by code for this project, and that using the future building management system (BMS) to shut down fans would be acceptable. The contract opportunity is for SARA HVAC Controls, issued by the Department of the Interior National Park Service Northeast Region.

View the file

Other files for this federal contract opportunity

Other files attached to SARA HVAC CONTROLS, newest first.
File Type Posted
Sol_140P4324Q0025_Amd_0006.pdf PDF
IMG_03_0005.jpg JPG image
IMG_06_0005.jpg JPG image
Sol_140P4324Q0025_Amd_0005.pdf PDF
IMG_04_0005.jpg JPG image
IMG_07_0005.jpg JPG image
IMG_02_0005.jpg JPG image
IMG_01_0005.jpg JPG image
IMG_05_0005.jpg JPG image
Amd005_0005.pdf PDF
Amd004_0004.pdf PDF
Sol_140P4324Q0025_Amd_0004.pdf PDF
Amd003_0003.pdf PDF
Sol_140P4324Q0025_Amd_0003.pdf PDF
Sol_140P4324Q0025_Amd_0002.pdf PDF
Amd002_0002.pdf PDF
B09-Attachment-3_1990_Plans_0001.pdf PDF
B09-Attachment-4_2019_Plans_0001.pdf PDF
Sol_140P4324Q0025_Amd_0001.pdf PDF
B09-Attachment-2_1974_Plans_0001.pdf PDF
B09-140P4324Q0025-Amd001_0001.pdf PDF
B09-Attachment-1_1960_Plans_0001.pdf PDF
B09-Attachment-1b_1960_Plans_0001.pdf PDF
WD-2015-4143-Rev26-12_26_23.pdf PDF
Sol_140P4324Q0025.pdf PDF
HVAC-CONTROLS-SOW.pdf PDF
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SARA HVAC Controls, 140P4324Q0025

Amendment 006

RFI# (18)

18. Our understanding is the facility would like to shut down all HVAC equipment when a fire alarm is triggered. This includes the furnaces, air handlers and exhaust fans.

• The existing fire alarm system is a non-addressable Honeywell panel. We were unable to locate documentation.

• We noted that some of the existing fire alarm components have been decommissioned and we noted that some fire alarm cabling had been cut so it may not be reusable.

There was a discussion about having the (future) building management system shut down the HVAC equipment.

Is this allowed or does it violate NFPA codes?

Government Response: The HVAC shutdown by the fire alarm system was not required for this project by code. Therefore, using the future BMS to shut down fans (or not) would be perfectly acceptable.