NIFC 215-GBK Access Control Amendment-02 140L3719R0009
Drawing Changes:
Sheet E101:
1. Change Plan Note 19 to read: PROVIDE JUNCTION BOX AND CONDUIT TO EXISTING
FIRE ALARM CONTROL PANLE. INTERLOCK ELECTRIFIED DOOR HARDWARE WITH
FIRE ALARM RELAY IN DOOR HARDWARE POWER SUPPLY TO DISABLE
ELECTROMECHANICAL LOCK DURING FIRE ALARM. ALL WORK ON FIRE ALARM
SYSTEM SHALL COMPLY WITH NFPA 72. NICET-CERTIFIED FIRE ALARM
CONTRACTOR SHALL COMPLETE FINAL CONNECTION AND PROGRAMMING AT
EXISTING FIRE ALARM PANEL.
2. Add Plan Note 22 and callout to floorplan near callout 19 on south side of plan. Plan note 22 shall read: INSTALL CONDUIT TO EXISTING J-BOX TO EAST AND THEN NORTH TO
EXISTING PANEL ‘B’. INSTALL CONDUIT NEAR CEILING. EXTEND DEDICATED
CIRCUIT TO NEW DELAYED EGRESS POWER SUPPLY PANEL. COORDINATE WITH
COR FOR NEW POWER SUPPLY LOCATION. See attached Sketch-1.
Specification Changes:
Section 087111 – DOOR HARDWARE (DESCRIPTIVE SPECIFICATION)
1. Replace section in its entirety with attached revised section.