Cove Recreation Site Host Cabana Solicitation No 140L2621Q0040

QUESTIONS AND ANSWERS:

1.

QUESTION: In lieu of the Poligon Model REK 20x34; Will it be suitable if we have one of our subs, design & fabricate the Cabana based on the spec requirement details?

ANSWER: YES, It is acceptable to have a like structure designed and fabricated by a local engineering and fabricating facility. Please note all the structural and architectural elements must meet or exceed the criteria for the specified pre-engineered model provided as the basis of design including but not limited to, material shapes and sizes, fasteners and connections and coatings. The qualified engineer must also provide stamped and signed plans for the structure and the foundation as required in the construction specifications and drawings. Contractor must provide additional time for submittal review by the Government since it would not be a pre-engineered structure and the Government will require full submittal to verify all criteria of the structure and foundation have been met.

DESIGN AMENDMENTS

1. The cabana minimum eave height shall be changed from 13 feet to 13 feet – 6 inches minimum clearance. Please replace Sheet 2 construction drawings, construction specifications table of contents, page 010000-1 and page 130470-2 with REVISION 1 showing the change from 13 feet to 13 feet – 6 inches for minimum clearance eave height. Revision 1 pages are attached.

TABLE OF CONTENTS

APRIL 2021

Cove Recreation Host Site Cabana

TABLE OF CONTENTS

SPECIFICATIONS

DIVISION 01 – GENERAL REQUIREMENTS

010000 – GENERAL REQUIRMENTS

DIVISION 03 – CONCRETE

033000 – CAST-IN-PLACE CONCRETE

DIVISION 13 – SPECIAL CONSTRUCTION

130470 – PRE-ENGINEERED SHELTERS

DIVISION 32 – EXTERIOR IMPROVEMENTS

312000 – EARTHMOVING

END OF SECTION

REVISION 1 07/22/2021

REVISION 1 07/22/2021

APRIL 2021

Cove Recreation Host Site Cabana

GENERAL REQUIREMENTS

010000 - 1

SECTION 010000 - GENERAL REQUIREMENTS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of Contract, including General and Supplementary Conditions apply to this Section.

1.2 SECTION 011000 - SUMMARY OF WORK

A. Project Description:

1. The Project consists of the following: Installation of one (1) new 20 foot x 34 foot Gable Roof Rectangular Shelter with a eave height of 13 feet - 6 inches and one (1) 20 foot x 36 foot x 6 inch reinforced concrete slab.

B. Contractor Use of Premises:

1. General: During the construction period the Contractor shall have use of the premises for construction operations, including use of the site. The Contractor’s use of the premises is limited by the Government’s ongoing operations.

1.3 SECTION 012000 - PROJECT MANAGEMENT AND COORDINATION

A. Pre-Construction Conference:

1. The Government will schedule a pre-construction conference and organizational meeting at the Project site or other convenient location after award. Conduct the meeting to review responsibilities and personnel assignments.

2. Attendees: The Government, and their consultants, the Contractor and its superintendent, major subcontractors, manufacturers, suppliers and other concerned parties shall each be represented at the conference by persons familiar with and authorized to conclude matters relating to the Work.

3. Agenda: Discuss items of significance that could affect progress.

4. The Contractor shall submit a work schedule at this time.

B. Coordination Meetings:

1. Conduct Project coordination meetings at regularly scheduled times convenient for all parties involved. Project coordination meetings are in addition to specific meetings held

APRIL 2021

Cove Recreation Host Site Cabana

PRE-ENGINEERED SHELTERS

130470-3

1.7 WARRANTY

A. Roof Requirements: Furnish a written warranty from the manufacturer certifying the metal roofing for a period of at least 20 years against any manufacturing defects that will adversely affect the performance of the roof and that the metal roof shall resist damage by wind, including gusts, up to 90 miles per hour.

PART 2 - PRODUCTS

2.1 MATERIALS

A. Pre-Engineered Shelters: Prefabricated steel structure, Model REK 20x34 with 13 foot - 6 inch eave for the individual shelter as manufactured by Poligon, 4240 136th Ave Holland, MI

49424 Phone 616.888.3500, or approved equal, with the following salient features.

1. Structural framing: Structural steel tube minimum ASTM A500 grade B or cold-formed box sections minimum ASTM A570b grade 55. “I” beams, tapered columns, open channels, or wood products shall not be accepted.

2. Fasteners: ASTM A325 high strength bolts and A563 high strength nuts, ASTM A36 anchor bolts, self-drilling screws, rivets.

3. Metal roofing: 24-gauge galvalume factory finished with Kynar 500 paint system.

Standing seam panels shall be 12 to 16 inch wide. Seams shall run with the pitch of the roof for proper drainage. Color shall be selected from manufacturer’s standard color options to match existing cabana structures at the site, as approved by the

Contracting Officer.

4. Metal roofing trim shall match the color of the roof and shall be formed from 24 gauge painted galvalume steel as follows.

a. Panel end caps shall be pre-bent to a “U” shape to fit over ridge end of roof panels.

The inside of the “U” shall match the roof color.

b. Metal ridge caps shall be preformed with a single central bend to match the roof pitch. They shall be hemmed on the sides.

c. Roof peak cap shall be supplied on all structures that do not include a cupola.

d. “J” channel shall be shaped like a “J” with colored metal on the outside wrapped around 20 gauge galvanized steel core. “J” channel shall be applied all along the eave to strength and straighten the eave. Both colored metal and galvanized core shall have 7/16” weep holes 6” on center.

e. Eave splice channels shall be provided to fit behind “J” channel butt joints to create strength at the joint and maintain a straight eave line.

f. Special “J” channel corner trim shall be provided which fits over the main “J” channel to simplify final detailing of corners.

2.2 FABRICATION

A. All base plates, stiffener plates, U-clips, and end plates shall be factory welded into place and bolt connection holes shall be factory cut.

16'- 4"

REF

13'- 0"

CLEAR

FINISH GRADE.

MOUNTING VARIES

BASED ON ENGINEERING

REQUIREMENTS.

20'

34'

N A

TI

O

N A

L

SY

ST

EM

O F

PU

BL

IC

L

A N

D S

U .S

. D

EP

A

RT

M

EN

T O

F

TH

E

IN

TE

RI

O R

BU

RE

A U

O F

LA

N

D M

A N

A G

EM

EN

T

SCALE:

A

SHELTER ELEVATION

N.T.S.

GENERAL NOTES:

DESIGN LOADS

1. DESIGN IS IN ACCORDANCE WITH THE MOST CURRENT EDITION OF THE

INTERNATIONAL BUILDING CODE.

2. GROUND SNOW LOADS, Pg = 40 PSF

3. LIVE LOADS - LATERAL:

WIND - 90 MPH, EXPOSURE C

SEISMIC - SS=102% OF g

S1=33% OF g

FOUNDATION

1. ALLOWABLE BEARING PRESSURE IS 1,500 PSF.

2. MINIMUM DEPTH OF FOOTING IS 36".

3. MINIMUM FOOTING DIAMETER IS 24".

4. DO NOT PLACE FOUNDATION ON FROZEN GROUND.

5. A FOUNDATION DESIGN MUST BE PROVIDED BY THE SHELTER

MANUFACTURER PRIOR TO THE PROJECT START DATE. THE

FOUNDATION DESIGN ON THIS SHEET IS PROVIDED FOR REFERENCE

ONLY AND MAY BE MODIFIED. MANUFACTURER MUST SIGN AND STAMP

DRAWINGS

CONCRETE

1. CONCRETE DESIGN CONFORMS TO AMERICAN CONCRETE INSTITUTE

BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI

318).

2. MINIMUM COMPRESSIVE STRENGTH: f'c = 4,000 PSI

3. STEEL REINFORCEMENT YIELD STRENGTH: fy = 60,000 PSI.

4. SPLICES FOR STEEL REINFORCEMENT IN CONCRETE SHALL BE

CONTACT LAP SPLICES. MINIMUM LAP SPLICE LENGTH FOR #5 BAR

SHALL BE 30".

5. MINIMUM CONCRETE COVER FOR REINFORCEMENT SHALL BE AS

FOLLOWS:

CONCRETE CAST AGAINST EARTH - 3"

CONCRETE EXPOSED TO EARTH OR WEATHER, #5 AND SMALL - 1

2"

STEEL

1. ALL FABRICATED STEEL SHALL CONFORM TO ASTM A36. STRUCTURAL

TUBING SHALL CONFORM TO ASTM A500, GRADE B.

2. ALL WELDS SHALL CONFORM TO AWS D1.1. WELDS SHALL BE MADE

USING E70XX ELECTRODES AND SHALL BE A MINIMUM OF

16", UNLESS

OTHERWISE NOTED.

3. ALL STRUCTURAL STEEL TO BE EMBEDDED IN CONCRETE SHALL BE

CLEAN AND FREE OF PAINT, OIL, OR DIRT.

4. ANCHOR BOLTS SHALL CONFORM TO ASTM A307.

ROOF

1. 24 GA STANDING SEAM METAL ROOF.

2. COLOR SHALL BE SELECTED BASED ON CLOSEST STANDARD OPTION

AVAILABLE TO MATCH EXITING STRUCTURES

PAINT

1. POWDER COATED FINISH, COLOR TO MATCH EXISTING CABANA

STRUCTURES AT SITE

SCALE:

B

SHELTER FRAME PLAN

N.T.S.

SCALE:

C

SHELTER ISOMETRIC FRAME VIEW

N.T.S.

SCALE:

D

SHELTER FRAME ELEVATION

N.T.S.

NOTE: DIMENSIONS ARE NOMINAL

ACTUAL DIMENSIONS MAY VARY FROM THOSE SHOWN

AND ARE DEPENDENT ON DESIGN AND CODE

C O

N

ST

R U

C

TI

O N

S

ET

5/

/2

RE

V

IN

CR

EA

SE

D

EA

VE

H

EI

GH

T

7/2 2/2

AutoCAD SHX Text

CHK'D BY:

AutoCAD SHX Text

DESIGN OFFICE:

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

PROJECT NO:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

SHEET

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

OF

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

MARK

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DATE

AutoCAD SHX Text

UNITED STATES DEPARTMENT OF THE INTERIOR

AutoCAD SHX Text

BUREAU OF LAND MANAGEMENT

AutoCAD SHX Text

COVE RECREATION SITE HOST CABANA

AutoCAD SHX Text

SHELTER DETAILS

AutoCAD SHX Text

BOISE

AutoCAD SHX Text

IDAHO

AutoCAD SHX Text

MMP

AutoCAD SHX Text

MMP

AutoCAD SHX Text

APRIL 2021

AutoCAD SHX Text

AutoCAD SHX Text

Site Tour Sign In
Amendment 1
Amendment 1
3 pages Cove Rec Site Host Cabana Specifications Rev 1
Cove Rec Host Cabana Construction Drawings Sheet 2 Rev1

File details come from the government source that posted it. Updated .