This is an Electrical Plan (E-1) for a USDA-ARS facility located in Prosser, Washington (Job No. U55850-02), drawn at a scale of 1/2" = 1'-0" and dated 07-23-2025.
The plan depicts electrical infrastructure including two 42/64 space 225-ampere, three-phase interior flush-mount sub-panels (Sub-Panel A and Sub-Panel B) with main breakers not to exceed 72 inches above finished floor. The layout specifies multiple 15-ampere, 120-volt circuits for three snorkels with associated override switches for hoods 1 and 2, each with dedicated control switches (EF-4, EF-5, EF-6). Heat tape receptacles are mounted under floor with roof-mounted receptacles providing 8-foot coiled whips for eight circuits. Additional equipment shown includes furnace plugs, GFCI outlets distributed throughout the facility, a fume hood connection, varío max cube organic air intake unit, vacuum pump, water chiller, and a 20-ampere 120-volt autosampler. Standard electrical symbols indicate junction boxes, switches, and GFCI protection points at various locations marked with numeric and alphanumeric designations (+42" denotes 42 inches above floor level). The plan is prepared by JHP and includes SMW as the design firm reference.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Electrical drawings Question Answers.docx | DOCX document | |
| ARS_Prosser_BentonPUD_DevLtr.pdf | ||
| ARS_Prosser_Utilities_B300.pdf | ||
| USDA - ARS - REVISED PANEL SCHEDULE_7.23.25.pdf | ||
| Wage Rates.pdf | ||
| LPTA Evaluation Criteria for a Service Contract 1232SA26Q0125.docx | DOCX document | |
| 1153441_ PGIRU- Bryla_ Prosser Mod. Building Elect. FY26- SOW.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
#2&4B
#1&3A
WP
GFCI
#5B
#29A #5A
GFCI
#7A
#9A
#35A +42"
#22A GFCI#13B
#20A
#11B
#9B
#23A
+42"
+42"
+42"
J
J
J
#42A #15A
J J J+42" +42"
#8B #7B
#10B
+42" +42" +42" +42"
+42" +42" +42"
+42"
+42"
+42"
+42"
+42"
#19B
#16B
#14B
#15B #12B #17B
#24A
#25A
S S S
S
J JJ
#1&3B
+42"
+42"
+42"
WP
GFCI
#18B#26A
J
J
SWITCH TO CONTROL
EF-6 FOR SNORKEL 3
EF-6
EF-5
EF-4
SWITCH TO CONTROL
EF-5 FOR SNORKEL 2
SWITCH TO CONTROL
EF-4 FOR SNORKEL 1
15AMP, 120V
SNORKEL 3
OVERRIDE SWITCH
FOR HOODS 1 & 2
EF-3
EF-3
#36B
WIRED IN TANDEM
W/ AUTOSAMPLER
& ICP-MS
WATER CHILLER:
#6&8A - 42" AFF
*VERIFY FEMALE
PLUG ON SITE*
ICP-MS
#28,30A - 42" AFF
WALL SOCKET: IEC60309
VACUUM PUMP:
#24&26B - 42" AFF
*VERIFY FEMALE
PLUG ON SITE*
15 AMP, 120V
SNORKEL 1
15 AMP, 120V
MOUNT ON
ROOF BOTTOM
SNORKEL 2
EF-4
#35B EF-5
#42B
EF-6
#23B
SPS 4 AUTOSAMPLER:
#25&27B - 30A, 240V - 42" AFF
AC ADAPTER OUTPUT/AUTO
SAMPLER INPUT
*VERIFY FEMALE PLUG ON SITE*
VARIO MAX CUBE ORGANIC
ELEMENTAL ANALYZER (CNS):
#28B - 42" AFF
*VERIFY FEMALE PLUG ON SITE*
J
FURNACE PLUG #1:
#30&32B - 30A, 240V - 42" AFF
(POWER PLUG CEE)
*VERIFY FEMALE PLUG ON
SITE*
FURNACE PLUG #2:
#39&41B - 42" AFF
W/ SNAP IN COUPLING
*VERIFY FEMALE PLUG
ON SITE*J
20 AMP, 120V
- (TYP OF 4)
20 AMP, 120V
- (TYP OF 4)
WMU-1 WMU-2
42/64 SPACE 225A 3Ø INTERIOR FLUSH
MOUNT "SUB-PANEL A" ELECTRICAL PANEL;
MAIN BREAK TO BE MAX. 72" A.F.F.
42/64 SPACE 225A 3Ø INTERIOR FLUSH
MOUNT "SUB-PANEL B" ELECTRICAL PANEL;
MAIN BREAK TO BE MAX. 72" A.F.F.
HEAT TAPE
RECEPTACLE MOUNT
UNDER FLOOR
HEAT TAPE
RECEPTACLE MOUNT
UNDER FLOOR
MOUNT ON ROOF BOTTOM
AND PROVIDE 8' WHIP COILED
FOR EACH CIRCUIT
- (TYP OF 8)
FUME HOOD
- N.I.C. HEAT TAPE
RECEPTACLE MOUNT
UNDER FLOOR
WH-1
+42"
GFCI
+42"
GFCI
J
JJ
J
JJ
J
J
J
#13A #36A
#11A #12A
#17A #18A
+42"
D
AT
E:
D R
AW
N
B Y:
SC
AL
E:
JO
B
N O
LO
C
AT
IO
N
R
EV
IS
IO
N
1. 2. 3. 4.
E-1
ELECTRICAL PLAN
U5
-02
US
DA
- A
RS
PR
OS
SE
R, W A
JH
P
1/2
1' -0"
PR
OS
SE
R, W A
-23
-20
AutoCAD SHX Text
WH
AutoCAD SHX Text
RP
AutoCAD SHX Text
4 TON 15 KW
AutoCAD SHX Text
4 TON 15 KW
AutoCAD SHX Text
ABCU-1272-5988 A
AutoCAD SHX Text
ABCU-1272-5989 B
AutoCAD SHX Text
ABCU-1272-5990 C
http://www.sustainablemodular.com/ AutoCAD SHX Text www.sustainablemodular.com
| Sheets and Views |
| E-1 ELECTRICAL PLAN |
File details come from the government source that posted it. Updated .