1-20052.04 OLD RIVERSIDE PARK Building.pdf
PDF 12 MB Posted
- Attached to
- SURPLUS FIREARMS SALE - FCPD
- Solicitation number
- 26-020
- Issued by
- Cobb County, Georgia
About this file
This document is a comprehensive set of architectural and engineering plans for the Old Riverside Park Building, a prefabricated restroom facility located at 6500 Old Riverside Drive NW, Sandy Springs, Georgia 30328. The project, identified as ORS01 and prepared by ROMTEC, Inc. in collaboration with PSE Consulting Engineers, Inc., includes detailed construction drawings for a single-story concrete masonry unit (CMU) structure measuring approximately 22'-8" by 13'-4" with an 8-foot wall height. The facility is designed to accommodate ADA-compliant unisex and non-ADA restrooms with complete plumbing, electrical, mechanical, and roofing systems. The plan set comprises 51 sheets covering architectural details, structural specifications, foundation plans, roof framing, interior and exterior elevations, door and window schedules, wall finishes, ADA accessibility requirements, and fixture details. Construction is governed by the 2018 International Building Code, with seismic design category D, wind speed of 110 mph, and a 2,500 psf allowable soil bearing capacity.
The structural design utilizes 8-inch reinforced concrete masonry block walls with running bond patterns, grouted solid throughout, supported by reinforced concrete footings with #5 rebar specifications and monolithic slab construction. The roof system features pre-engineered timber trusses with 5:12 pitch, standing seam metal roofing, and glue-laminated beams at eave and ridge connections. The facility includes three restrooms with fixture counts totaling ten lavatories, three water closets, and associated accessories such as grab bars, paper towel dispensers, and soap dispensers. Building utilities consist of a 3,000 psi minimum concrete slab, 5-inch thickness with #4 rebar at 16-inch on-center spacing, cold and hot water supply systems, 4-inch sanitary sewer connection, a 10-gallon electric water heater, mechanical exhaust ventilation with occupancy sensors, and a 100-amp electrical service panel. Interior finishes include epoxy-painted CMU walls, tile cove base in restrooms, concrete flooring with water-based sealer, and 5/8-inch moisture-resistant drywall ceilings. Exterior finishes feature stone veneer and fiber cement board and batt siding over 2-inch rigid insulation, with 6-inch by 8-inch resawn timber posts and trim elements.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
T
IT
L E S
H E E T
R E V
IS
IO
N
S H E E T S
C H E D
UL
E
G0
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
T
IT
L E S
H E E T
R E V
IS
IO
N
S H E E T S
C H E D
UL
E
G0
(541)-496-3541 FAX (541)-496-0803
18240 NORTH BANK ROAD - ROSEBURG, OR 97470
PROJECT I.D. :
PROJECT INFORMATION
CITY / STATE:
SITE ADDRESS:
PROJECT NAME: OLD RIVERSIDE PARK
ORS01
6500 OLD RIVERSIDE DR NW
SAND SPRINGS, GA 30328
SHEET SCHEDULE
SHEET CONTENTS
A5.1 DOOR SCHEDULE
G1 GENERAL NOTES / SYMBOL LEGEND
A1.1 FLOOR PLAN
S7.1 FOUNDATION PLAN
S8.2 STRUCTURAL CMU REBAR LAYOUT
S10.1 ROOF CONNECTION DETAILS
A5.2 DOOR DETAILS
A2.1 EXTERIOR ELEVATION VIEWS
G2 DESIGN CRITERIA AND CODE SUMMARY
A3.1 SECTION VIEWS
S7.2 FOUNDATION DETAILS
S9.1 ROOF FRAMING PLAN
A4.1 WALL FINISH SCHEDULE (INTERIOR/EXTERIOR)
A1.2 ADA CLEARANCES
S7.3 FOUNDATION DETAILS
S8.1 STRUCTURAL CMU PLAN
S8.3 STRUCTURAL CMU DETAILS
E1 ELECTRICAL SCHEDULE
E3 ELECTRICAL RISER DETAILS
P1 PLUMBING SCHEDULE
A1.3 ADA RESTROOM FIXTURE DETAILS
A2.2 EXTERIOR ELEVATION VIEWS
A3.2 SECTION VIEWS
S8.4 STRUCTURAL CMU ELEVATION VIEWS
S8.5 STRUCTURAL CMU ELEVATION VIEWS
P2 PLUMBING PLAN
E2 ELECTRICAL PLAN
E4 ELECTRICAL PANEL SCHEDULE
R1 ROOFING PLAN
R2 ROOFING DETAILS
A4.2 WALL FINISH DETAILS
M1 MECHANICAL PLAN
S10.2 ROOF CONNECTION DETAILS
S10.3 ROOF CONNECTION DETAILS
A1.4 INTERIOR ELEVATIONS VIEWS
R3 ROOFING DETAILS
A5.3 SIGN DETAILS
G0 TITLE PAGE, SHEET & REVISION SCHEDULE
REVISION SCHEDULE
REV. DATE BY DESCRIPTION
1 12/23/2024 ZW
G2, A3.1, S7.1, S7.2, S9.1, S10.4, S10.5, S10.6
A3.3 SECTION VIEWS
A3.4 SECTION VIEWS
A4.3 WALL FINISH DETAILS
A4.4 WALL FINISH DETAILS
S10.4 ROOF CONNECTION DETAILS
S10.5 ROOF CONNECTION DETAILS
S10.6 ROOF CONNECTION DETAILS
Ex. 12/31/2025
1/08/2025
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
G E N E R
A L N
O T E S
S Y M
B O
L L
E G
E N D
G1
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
G E N E R
A L N
O T E S
S Y M
B O
L L
E G
E N D
G1 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
S10.1
DETAIL
NAME
ABBREVIATIONS
NOTE: ARCHITECT/ENGINEER IS NOT RESPONSIBLE FOR ANY SITE DESIGN OR
ENGINEERING AND WILL NOT BE HELD ACCOUNTABLE OR LIABLE FOR ANY
ISSUES RELATED TO THIS SITE. IT IS THE OWNER'S RESPONSIBILITY TO
ACCURATELY LOCATE THIS BUILDING, SET FLOOR AND ADJACENT ELEVATIONS,
DETERMINE SITE IS SUITABLE FOR CONSTRUCTION, VERIFY ALL UTILITIES, ETC.
SYMBOL LEGEND
DETAIL REFERENCE
BUILDING SECTION
SHEET NO.
DETAIL NO.
A3.1
RECYCLE
RECYCLE ALL USED SHIPPING
MATERIALS AND LEFT OVER
BUILDING MATERIALS
A1.4
DETAIL CALLOUT
1. THIS PROJECT SHALL COMPLY WITH ALL CODES AND STANDARDS IDENTIFIED ON SHEET G2. ALL WORK SHALL MEET
OR EXCEED INDUSTRY STANDARDS FOR MATERIALS, WORKMANSHIP, ETC.
2. CONTRACTOR SHALL REVIEW THE DRAWINGS THOROUGHLY BEFORE PROCEEDING WITH ANY WORK. ANY DISCREPANCIES FOUND WITHIN THESE DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF ROMTEC.
CONTRACTOR SHALL NOT PROCEED WITH ANY WORK HE KNOWS TO BE IN CONFLICT WITH OTHER WORK, OR IS NOT
APPROVED BY CODE, UNTIL RESOLVED BY ROMTEC OR THE ENGINEER/ARCHITECT.
3. CONTRACTOR SHALL MAINTAIN GENERAL LIABILITY INSURANCE AND WORKER'S COMP. INSURANCE AS PER SPECIFIC
STATE MINIMUM REQUIREMENTS.
4. FOOTINGS SHALL BE CONSTRUCTED ON UNDISTURBED NATIVE SOIL OR ENGINEER APPROVED FILL. CONTRACTOR TO VERIFY ASSUMED SOIL BEARING CAPACITY NOTED ON SHEET G2. SHOULD SOIL NOT MEET OR EXCEED THE ASSUMED SOIL BEARING CAPACITY, CONTRACTOR TO MODIFY SOIL CONDITIONS TO SATISFY CRITERIA OR NOTIFY THE STRUCTURAL ENGINEER TO REVISE DESIGN PER CONDITIONS ENCOUNTERED. BACKFILL AROUND BUILDING TO PROVIDE SLOPE AWAY FROM BUILDING NOT LESS THAN A 2% SLOPE FOR A MINIMUM DISTANCE OF 10' FROM THE BUILDING, PER 2018 IBC 1804.3.
5. A. CAST-IN-PLACE CONCRETE: 3000 PSI MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS 4" +/- 1" SLUMP, WITH MAX 1" AGGREGATE, AND ALL MATERIALS IN ACCORDANCE WITH ACI 318 STANDARDS. FINE BROOM FINISH INTERIOR SURFACES AND EXTERIOR SLABS. JOINTS REQUIRED IN FLAT WORK, SEE FOUNDATION DETAILS FOR REQUIREMENTS.
B. CMU BLOCKS “MEDIUM WEIGHT DENSITY” ARE MANUFACTURED TO ASTMC90-02 STANDARDS WITH A MIN COMPRESSIVE STRENGTH Fm = 1500 PSI. ALL CMU BLOCKS MUST BE FULLY GROUTED IN 5 FT MAXIMUM LIFTS (EXCEPTION - HIGH LIFT GROUTING FOR 8'-8" WALLS MAYBE USED AS LONG AS CLEANOUT OPENINGS ARE PROVIDED AT THE BOTTOM OF EVERY CELL FOR EACH POUR ABOVE 5 FT). THE MORTAR TO BE USED SHALL BE TYPE S 1800 PSI MORTAR CONFORMING TO ASTM C270. MASONRY (CONCRETE) GROUT: 2500 PSI MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS 9" +/- 1" SLUMP, WITH MAX 1/2" AGGREGATE, AND TESTED IN ACCORDANCE TO MEET ACI 318. FINE OR COURSE GROUT MAY BE USED IN ACCORDANCE WITH 2018 IBC. CONSOLIDATE GROUT AT THE TIME OF PLACEMENT. CONSOLIDATE POURS EXCEEDING 12 IN. IN HEIGHT BY MECHANICAL VIBRATION, AND RECONSOLIDATE BY MECHANICAL VIBRATION AFTER INITIAL WATER LOSS AND SETTLEMENT HAS OCCURRED. CONSOLIDATION AND RECONSOLIDATION ARE NORMALLY ACHIEVED WITH A MECHANICAL VIBRATOR. A LOW VELOCITY VIBRATOR WITH A 3/4 IN. HEAD IS USED.
6. ANCHOR AND MACHINE BOLTS SHALL BE ASTM A307, UNLESS NOTED OTHERWISE BOLTS SHALL BE INSTALLED PER TURN-OF-NUT INSTALLATION METHOD, REQUIRED TURNS FOR PRE-TENSIONING FROM SNUG-TIGHT, U.N.O. IN THIS PLAN SET OR BY ANCHOR BOLT OR FASTENER MANUFACTURER. SCREWS AND MACHINE BOLT CALLOUTS ARE MINIMUM SIZE ALLOWED, ACTUAL SIZE MAY VARY. HOLLOW STRUCTURAL SECTION (HSS) SHALL BE ASTM A500 GRADE B, Fy = 46 ksi.
WIDE FLANGE BEAMS SHALL BE ASTM A992, Fy = 50 ksi. STEEL PLATES & SHAPES SHALL BE ASTM A36, Fy = 36 ksi.
CONCRETE REINFORCING STEEL (REBAR): 60 ksi. (GRADE 60). WOOD FRAMING SHALL BE #2 & BETTER DOUGLAS FIR, UNO.
GLU-LAM BEAMS SHALL BE GRADE 24F-V4.
7. QUESTIONS CONCERNING MATERIALS OR CONSTRUCTION CONTACT ROMTEC TECHNICAL ASSISTANCE AT: 541-496-3541
8. ROMTEC SCOPE SUPPLY AND DESIGN SUBMITTAL (SSDS) IDENTIFY SPECIFIC MODEL, MANUFACTURER & BRAND OF ALL PLUMBING AND ELECTRICAL FIXTURES AND ACCESSORIES. REFER TO THE SSDS FOR SPECIFIC LIST OF ITEMS SUPPLIED BY ROMTEC, ANY ITEMS NOT LISTED IN THE SSDS IS ASSUMED SUPPLIED BY THE INSTALLER.
9. THE OWNER / CONTRACTOR MAY EXERCISE DISCRETION IN SELECTING THE FINAL LOCATION FOR NON-DIMENSIONED
ACCESSORIES AND FIXTURES (E.G., LIGHTS, COMFORT HEATERS, ETC.)
GENERAL NOTES
ELEVATION VIEW
A2.1
VENT NUMBER OR
WINDOW NUMBER - SEE
APPLICABLE SCHEDULE
DOOR NUMBER - SEE
APPLICABLE SCHEDULE
WOOD FILLER WALL - SEE
APPLICABLE SCHEDULE
INTERIOR ELEVATION
REFERENCE
S10.1
DETAIL
NAME
AB ANCHOR BOLT
ACT ADULT CHANGING TABLE
AFF ABOVE FINISHED FLOOR
ATS AUTOMATIC TRANSFER SWITCH
BN BOUNDARY NAIL
BOT BOTTOM
BP BREAKER PANEL
CJ CONTROL JOINT
CL CENTER LINE
CO CLEAN OUT
CMU CONCRETE MASONRY UNIT
db NOMINAL BAR DIAMETER
DD DIAPER DECK
DIA DIAMETER
DISC DISCONNECT
EM ELECTRIC METER
EN END NAIL
EW EACH WAY
FA FREE AIR
FD FLOOR DRAIN
FF FINISHED FLOOR
FG FINISHED GRADE
FN FIELD NAIL
FRP FIBERGLASS REINFORCED PANEL
GB GRAB BAR
GLB GLUE LAMINATED BEAM
HB HOSE BIBB
HD HAND DRYER
HM HOLLOW METAL (DOOR)
HSS HOLLOW STRUCTURAL SECTIONS
HTR HEATER
HYP HYPOTENUSE
I.S. INSTALLER SUPPLIED
KSI KIPS PER SQUARE INCH
L STRUCTURAL STEEL ANGLE
LAV LAVATORY
LF LIGHT FIXTURE
MBP MAIN BREAKER PANEL
MD MAIN DISCONNECT
MIN MINIMUM
MIR MIRROR
MO MASONRY OPENING
MR METAL ROOFING
MS MILD STEEL
ND NAPKIN DISPOSAL
NTS NOT TO SCALE
OC ON CENTER
OCEW ON CENTER EACH WAY
OSB ORIENTED STRAND BOARD
P PHOTO EYE
PCC PORTLAND CEMENT COMPANY
PEN PANEL EDGE NAILING
PL PLATE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PV PHOTO VOLTAIC
R4S ROUGH FOUR SIDES
REQD REQUIRED
RO ROUGH OPENING
S4S SURFACED FOUR SIDES
SCH SCHEDULE
SD SOAP DISPENSER
SIP STRUCTURAL INSULATED PANEL
SJ SAW JOINT
SM SHEET METAL
SN SHEAR NAILING
SS STAINLESS STEEL
TBD TO BE DETERMINED
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
TLT TOILET
TP TOILET PAPER DISPENSER
TS TIMER SWITCH
TSCD TOILET SEAT COVER DISPENSER
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VAPOR BARRIER
VTR VENT THROUGH ROOF
WH WATER HEATER
WWM WOVEN WIRE MESH
W/ WITH
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
D E S
IG
N C
R
IT
E R
IA
C O
D E S
UM
M
A R
Y
G2
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
D E S
IG
N C
R
IT
E R
IA
C O
D E S
UM
M
A R
Y
G2 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
CODES AND STANDARDS
ANALYSIS METHOD: EQUIVALENT STATIC FORCE METHOD
BEARING WALL SYSTEM: SPECIAL REINFORCED MASONRY SHEAR WALL
ACI AMERICAN CONCRETE INSTITUTE, ACI 318, "BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE"
TMS THE MASONRY SOCIETY, TMS 402, "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES"
SPECIAL INSPECTIONS
CONCRETE SPECIAL INSPECTION NOT REQUIRED PER IBC 1705.3
EXCEPTION 2.3 [FOOTINGS]
EXCEPTION 3 [SLAB]
P
P
P
P
C
P
C
C
C(b)/P(c)
P
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR
NR P
NR P
NR P
NR P
P
P
P
P
C(b)/P(c)
P
NR
NR
NR
NR
NR
NR
LEVEL 2 LEVEL 3
R R
NR R
NR R
NR NR
NR NR
INSPECTION TASK
1. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE
FOLLOWING ARE IN COMPLIANCE:
B. PLACEMENT OF PRESTRESSING TENDONS AND ANCHORAGES
TABLE 3 -- MINIMUM VERIFICATION REQUIREMENTS
MINIMUM VERIFICATION REQUIRED FOR QUALITY ASSURANCE (a)
LEVEL 1
ART. 1.5 & 1.6.3
ART. 1.5
TMS 602
ART. 1.4 B
(a) R=REQUIRED, NR=NOT REQUIRED
REFERENCE
FOR CRITERIA
ART. 1.4 BPRIOR TO CONSTRUCTION, VERIFICATION OF f'm AND f'AAC, EXCEPT WHERE
SPECIFICALLY EXEMPT BY THE CODE.
PRIOR TO CONSTRUCTION, VERIFICATION OF COMPLIANCE OF SUBMITTALS
DURING CONSTRUCTION, VERIFICATION OF SLUMP FLOW AND VISUAL
STABILITY INDEX (VSI) WHEN SELF-CONSOLIDATING GROUT IS DELIVERED
TO THE PROJECT SITE.
DURING CONSTRUCTION, VERIFICATION OF f'm AND f'AAC FOR EVERY 5,000 sq. ft. (465 sq.m).
DURING CONSTRUCTION, VERIFICATION OF PORPORTIONS OF MATERIALS
AS DELIVERED TO THE PROJECT SITE FOR PREMIXED OR PREBLENDED
MORTAR, PRESTRESSING GROUT, AND GROUT OTHER THAN
SELF-CONSOLIDATING GROUT.
ART. 1.4 B
TABLE 4 -- MINIMUM SPECIAL INSPECTION REQUIREMENTS
MINIMUM SPECIAL INSPECTION
REQUIRED FOR QUALITY ASSURANCE (a)
LEVEL 1 LEVEL 2 TMS 402LEVEL 3
REFERENCE FOR CRITERIA
ART. 2.4 B & 2.4 H
TMS 602
ART. 2.1 , 2.6 A, & 2.6 CA. PROPORTION OF SITE-PREPARED MORTAR
B. GRADE AND SIZE OF PRESTRESSING TENDONS AND ANCHORAGES
ART. 3.4 & 3.6 AC. GRADE, TYPE AND SIZE OF REINFORCEMENT, CONNECTORS, ANCHOR
BOLTS, AND PRESTRESSING TENDONS AND ANCHORAGES
ART. 3.6 BD. PRESTRESSING TECHNIQUE
ART. 2.1 C.1E. PROPERTIES OF THIN-BED MORTAR FOR AAC MASONRY
ART. 2.1 C.1F. SAMPLE PANEL CONSTRUCTION
2. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
ART. 3.2 D & 3.2 FA. GROUT SPACE
ART. 2.4 & 3.6 SEC. 10.8 & 10.9
C. PLACEMENT OF REINFORCEMENT, CONNECTORS, AND
ANCHOR BOLTS ART. 2.4 & 3.6 SEC. 6.1, 6.3.1,
6.3.6, & 6.3.7
D. PROPORTIONS OF SITE-PREPARED GROUT AND
PRESTRESSING GROUT FOR BONDED TENDONS ART. 2.6 B & 2.4 G.1.b
3. VERIFY COMPLIANCE OF THE FOLLOWING DURING CONSTRUCTION:
ART. 1.5
A. MATERIALS AND PROCEDURES WITH THE APPROVED
SUBMITTALS
ART. 3.3 B
B. PLACEMENT OF MASONRY UNITS AND MORTAR JOINT
CONSTRUCTION
ART. 3.3 FC. SIZE AND LOCATION OF STRUCTURAL MEMBERS
D. TYPE, SIZE AND LOCATION OF ANCHORS, INCLUDING
OTHER DETAILS OF ANCHORAGE OF MASONRY TO
STRUCTURAL MEMBERS, FRAMES OR OTHER
CONSTRUCTION.
SEC. 1.2.1(e),
6.2.1 & 6.3.1
E. WELDING OF REINFORCEMENT SEC. 6.1.6.1.2
F. PREPARATION, CONSTRUCTION, AND PROTECTION OF MASONRY
DURING COLD WEATHER (TEMPERATURE BELOW 40°F(4.4°C)) OR
HOT WEATHER (TEMPERATURE ABOVE 90°F(32.2°C))
ART. 1.8 C & 1.8 D
G. APPLICATION AND MEASUREMENT OF PRESTRESSING
FORCE
H. PLACEMENT OF GROUT AND PRESTRESSING GROUT
FOR BONDED TENDONS IS IN COMPLIANCE
I. PLACEMENT OF AAC MASONRY UNITS AND
CONSTRUCTION OF THIN-BED MORTAR JOINTS
ART. 3.6 B
ART. 3.5 & 3.6 C
ART. 3.3 B.9 & 3.3 F.1.b
4. OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS
ART. 1.4 B.2.a.3,
1.4 B.2.b.3, 1.4
B.2.c.3, 1.4 B.3, & 1.4 B.4
(a) FREQUENCY REFERS TO THE FREQUENCY OF INSPECTION, WHICH MAY BE CONTINUOUS DURING THE LISTED TASK OR PERIODICALLY DURING THE LISTED TASK, AS DEFINED IN THE TABLE.
NR=NOT REQUIRED, P=PERIODIC, C=CONTINUOUS
(b) REQUIRED FOR THE FIRST 5000 SQUARE FEET (465 SQUARE METERS) OF AAC MASONRY.
(c) REQUIRED AFTER THE FIRST 5000 SQUARE FEET (465 SQUARE METERS) OF AAC MASONRY.
SPECIAL INSPECTIONS (TMS 402-16)
R
R
R
R
R
P
P
P
P
C
C
P
P
P
C
C
P
C
C
C
C
C
P
C
P
RISK CATEGORY: II
± 0.18INTERNAL PRESSURE COEFE =
EXPOSURE: C
MPHWIND SPEED = 110
SS:
S1:
SITE CLASS:
SDS:
SD1:
SEISMIC DESIGN CATEGORY:
BASE SHEAR: V = W
R =
SMS:
SM1:
SEISMIC DESIGN DATA:
RISK CATEGORY:
IMPORTANCE FACTOR:
II
1.0
0.203
0.088
D
0.325
0.212
0.216
0.141
C
0.043
DESIGN LOADS
ROOF:
ROOF: DEAD LOAD
WALL DEAD LOAD
IBC SEISMIC DESIGN CATEGORY
DESIGN WIND SPEED (ULTIMATE)
ALLOWABLE SOIL BEARING
EXPOSURE
MPH
PSF
PSF
PSF
PSF
LOADLIVE 20
C
C
WIND DESIGN :
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL MECHANICAL CODE
2020 NATIONAL ELECTRICAL CODE
2018 INTERNATIONAL FIRE CODE
ACCESSIBILITY CODE ADAAG
2015 INTERNATIONAL ENERGY CONSERVATION CODE
OCCUPANCY CLASS.:
CONSTRUCTION:
AREA: ______ FT2
AREA ALLOWABLE: _______FT2
HEIGHT: _ STORY
HEIGHT ALLOWABLE: _ STORY
OCCUPANT LOAD: ___
CODE SUMMARY:
U
VB
1 12-23-2024 ZW
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
F L O
O R
P L A N
A1.1
WALL TYPE SCHEDULE
8" REINFORCED CONCRETE
MASONRY BLOCK WALL WITH
MORTAR JOINTS, GROUTED SOLID
ALL CELLS RUNNING BOND PATTERN.
A
B
C
D1
FLOOR PLAN
SCALE: 1/4" = 1'-0"
A A2.1
C A2.2
B A2.1
D A2.2
B
UI
L D
IN
G
S L A B
7'-0" SLAB 13'-4" BUILDING
6'-0"
TP
TP
TP
WC-1
GB42G
B
G B
WC-1
LV
-1
LV
-1
LV
-1
PTD
PTD
PTD
SD
SD
SD
3" VTR
3" VTR
S-
S P A R
E C
O N D
UI
T
B P
WC-1
GB42G
B
G B
DD
FD-2
FD-1
FD-2
FD-2
ADA UNISEX
ADA UNISEX
UNISEX
WH
HT
H B
-2
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
A D
A C
L E A R
A N C E S
A1.2
30"x36"
A
B
C
D1
ADA RESTROOM FIXTURE CLEAR FLOOR AREA
SCALE: 1/4" = 1'-0"
60"x60"
48"x48"
TP
TP
TP
WC-1
GB42G
B
G B
WC-1
LV
-1
LV
-1
LV
-1
PTD
PTD
PTD
SD
SD
SD
3" VTR
3" VTR
S-
S P A R
E C
O N D
UI
T
B P
WC-1
GB42G
B
G B
DD
FD-2
FD-1
FD-2
FD-2
ADA UNISEX
ADA UNISEX
UNISEX
WH
HT
H B
-2
"x 9"
30"x48"
60"x60"
48"x48"
"x 9"
30"x48"
A1.4
A1.4
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
A D
A R
E S T R
O O
M F
IX
T
UR
E D
E T A
IL
S
A1.3 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
A D
A R
E S T R
O O
M F
IX
T
UR
E D
E T A
IL
S
A1.3 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
F.F. F.F.
A. THE ACCESSIBLE SINK SHALL BE MOUNTED
WITH THE COUNTER OR RIM NO HIGHER THAN
34” ABOVE FINISH FLOOR. KNEE CLEARANCE
THAT IS AT LEAST 27” HIGH, 30” SIDE AND 19”
UNDERNEATH THE SINK SHALL BE PROVIDED.
HOT WATER AND DRAIN SHALL BE INSULATED
OR OTHERWISE CONFIGURED SO AS TO
PROTECT AGAINST CONTACT. THERE SHALL
BE NO SHARP OR ABRASIVE SURFACES
UNDER THE SINK. SECTION 11B- 606.
B. FAUCET CONTROLS AND OPERATING
MECHANISMS SHALL BE OPERABLE WITH
ONE HAND AND SHALL NOT REQUIRE TIGHT
GRASPING, PINCHING OR TWISTING OF THE
WRIST. LEVER OPERATED, PUSH-TYPE AND
ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE. SELF-CLOSING
VALVES ARE ALLOWED IF THE FAUCET REMAINS OPEN FOR AT LEAST 10 SECONDS.
SECTION 11B-606.4.
1 1/4" TO 1 1/2"
NOMINAL
DIAMETER
1 1/2"
WALL
FASTEN TO
CMU WALL W/ (2)
5/16"Ø X 1 3/4"
CONCRETE ANCHORS
INSTALLED GRAB BARS MUST
MEET 250# MINIMUM LOAD &
GRAB BARS SHALL NOT
ROTATE WITHIN THEIR FITTINGS
PER CODE.
GRAB BAR
SCALE: 1 1/2" = 1'-0"2 1
ADA RESTROOM FIXTURE DETAILS
SCALE: 1/4" = 1'-0"
9" M
IN
6"
MAX
7"
M
IN
M
A X
(R
IM
13"
8"
MIN
9"
M
IN
C L E A R
22"
17" MIN
25" MAX
16"
11" MIN
LAVATORY GRAB BARS
SEE DETAIL 2/A1.3
SIDE WALL BACK WALL
F.F. F.F. F.F. F.F.
GB18
GB42
GB36
6"
18" 17"-18"
GB42
40"
REAR
WALL
GB18
GB36
12"
1/
M
IN
10"
LV-1
WC-1WC-1
18"
TO WALL
T O
S E A T
WATER CLOSET
(TOILET)
WC-1
TP TP
/4
32"
1/
DIAPER DECK
DD
F.F. F.F.
T O
B O
T T O
M O
F R
O L
L 7"-9" TO
FRONT
OF TLT
9 3/8"
MIN
TOILET PAPER
DISPENSER
TP
M
A X
PAPER TOWEL
DISPENSER
PTD
M
A X
T O
B
UT
T O
N
SOAP
DISPENSER
SD
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
IN
T E R
IO
R
E L E V
A T
IO
N V
IE
W
S
A1.4
ADA RESTROOM INTERIOR ELEVATION VIEWS
SCALE: 1/4" = 1'-0"
PTD SDDD
LV-1 LV-1
PTD SD
GB18
GB42
GB36
WC-1
TP
GB42
GB18
GB36
TP
WC-1
PTD SD
LV-1
TP
WC-1
LV-1
PTD SD
TP
WC-1
VIEW A VIEW B VIEW C VIEW D
VIEW A VIEW B VIEW C VIEW D
NON ADA RESTROOM INTERIOR ELEVATION VIEWS
SCALE: 1/4" = 1'-0"
COVE BASE
SEE 2/A4.1
LAV GUARD
ADA INSULATION
24"20"
18" 18" 10"
COVE BASE
SEE 2/A4.1
LAV GUARD
ADA INSULATION
24"
WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
URINALS AND WATER CLOSETS SHALL HAVE SMOOTH, HARD,
NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
FEET ABOVE THE FLOOR OR PER LOCAL CODE.
FOR EXTERIOR/INTERIOR FINISH SCHEDULE REFER TO SHEET A4.1
THRU WALL 8X8
INTAKE REGISTER
WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
URINALS AND WATER CLOSETS SHALL HAVE SMOOTH, HARD,
NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS THAN 4
FEET ABOVE THE FLOOR OR PER LOCAL CODE.
FOR EXTERIOR/INTERIOR FINISH SCHEDULE REFER TO SHEET A4.1
THRU WALL 8X8
INTAKE REGISTER
18" 10"18"
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
E X T E R
IO
R
E L E V
A T
IO
N V
IE
W
S
A2.1 B
ELEVATION VIEW
SCALE: 1/4" = 1'-0"
22'-8"
13'-4" 6'-0"
FG FG
STONE VENEER, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
FIBER CEMENT BOARD &
BATT. SIDING, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
3" VTR W/ VENT
BOOT, TYP.
METAL ROOFING
6X8 RESAWN TIMBER
POST, TYP.
STONE VENEER, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
FIBER CEMENT BOARD &
BATT. SIDING, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
3" VTR W/ VENT
BOOT, TYP.
A
ELEVATION VIEW
SCALE: 1/4" = 1'-0"
FG FG
17 1/2"
O.H.
17 1/2"
O.H.
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
E X T E R
IO
R
E L E V
A T
IO
N V
IE
W
S
A2.2 D
ELEVATION VIEW
SCALE: 1/4" = 1'-0"
22'-8"
13'-4"6'-0"
FGFG
STONE VENEER, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
FIBER CEMENT BOARD &
BATT. SIDING, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
3" VTR W/ VENT
BOOT, TYP.
METAL ROOFING
6X8 RESAWN TIMBER
POST, TYP.
3" VTR W/ VENT
BOOT, TYP.
C
ELEVATION VIEW
SCALE: 1/4" = 1'-0"
RESTROOM RESTROOM
UNISEX ISA WITH BRAILLE SIGN
PER ADA & LOCAL CODES
STONE VENEER, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
FIBER CEMENT BOARD &
BATT. SIDING, OVER
INSULATION, OVER 8"X16"
CMU SMOOTH FACE
CONCRETE BLOCK WALL
RESTROOM
UNISEX
(NON-ADA)
6X8 RESAWN TIMBER
ROOF EXTENSION
17 1/2"
O.H.
17 1/2"
O.H.LF-1 LF-1 LF-1
LF-1
WALL MOUNT LIGHT, TYP.
WALL MOUNT LIGHT, TYP.
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
S E C T
IO
N V
IE
W
S
A3.1
SECTION VIEW
SCALE: 1/4" = 1'-0"
22'-8" 5'-0"5'-0"
FG FG
2'-0" 2'-0"
13'-10 " R
OOFING
14'-0 3/16
" FASCIA
2'-0" 2'-0"
2'-0" 2'-0"
1'-6 11/
16"
S7.2
FOUNDATION
DETAIL
S7.3
EDGE OF
CONC. DETAIL
W
A L L
S10.1
EAVE
DETAIL
17 1/2"
O.H.
S7.3
INTERIOR WALL
FOOTING DETAIL
S10.2
INTERIOR WALL
CONNECTION
7'-4 3/8" INT. WALL
ADA UNISEX
7'-4 3/8" INT. WALL 5'-4 3/4"
INT. WALL
ADA UNISEX UNISEX
ROOF SHEATHING
2x6 FASCIA
FLAT 2x4 OUTLOOKERS. NOTCH
GABLE TRUSS TO FIT
INTERIOR
8" X 16" CMU SMOOTH FACE CONCRETE
BLOCK WALL FULLY REINFORCED
RUNNING BOND PATTERN
EXTERIOR
FIBER CEMENT BOARD AND BAT
SIDING AND STONE VENEER W/
INSULATION, OVER 8" X 16" CMU
SMOOTH FACE CONCRETE
BLOCK WALL FULLY REINFORCED
RUNNING BOND PATTERN
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
S E C T
IO
N V
IE
W
S
A3.2
17 1/2"
OH
W
A L L
S10.2
GABLE WALL
CONNECTION
S10.1
GABLE
DETAIL
13'-4"5'-0"
FG
GABLE SHEATHING
2x FASCIA
ROOF SHEATHING
G2 T1 T1 T1 T1 T1 T1 G1
7'-0"
5'-6 1/2" 1'-5 1/2"
SECTION VIEW
SCALE: 1/4" = 1'-0"
S7.2
FOUNDATION
DETAIL
S7.3
EDGE OF
CONC. DETAIL
EXTERIOR
FIBER CEMENT BOARD AND BAT
SIDING AND STONE VENEER W/
INSULATION, OVER 8" X 16" CMU
SMOOTH FACE CONCRETE
BLOCK WALL FULLY REINFORCED
RUNNING BOND PATTERN
S7.3
COLUMN
FOOTING DETAIL
1 12-23-2024 ZW
T1
STANDARD TRUSS
SCALE: 1/4" = 1'-0"
1'-4" TAIL 22'-8" BUILDING
/4 H E E L
1'-4" TAIL
13'-8 11/
16" TO
P CHORD
25'-4"
/1
/1
5 1/8" GLULAM BEAM FASTEN TO
TRUSS W/ USP GHF51600IF
GLULAM FACE MOUNT HANGER
G1
GABLE END TRUSS
SCALE: 1/4" = 1'-0"
1'-4" TAIL 22'-8" BUILDING
/4 H E E L
1'-4" TAIL
13'-8 11/
16" TO
P CHORD
25'-4"
/1
/1
G1
DROPPED GABLE TRUSS
SCALE: 1/4" = 1'-0"
1'-4" TAIL 22'-8" BUILDING
/8
H E E L
1'-4" TAIL
13'-8 11/
16" TO
P CHORD
25'-4"
/1
2X6 POSTS FOR
GLULAM BEAMS
1'-7 15/16"
9'-0 3/16"
/1 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
S E C T
IO
N V
IE
W
S
A3.3
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
S E C T
IO
N V
IE
W
S
A3.4
22'-0 3/8"1'-3" 1'-3"
14'-0 3/16
" FASCIA
13'-10
" SHEATHING
13'-8 1/1 6" T&
G
13'-11
3/8" TO
P CHORD
S10.4
EAVE
DETAIL
S10.4
RIDGE
DETAIL
S10.5
RIDGE
DETAIL
MID PLATE ROMTEC TB-050-5006 (EXTERIOR SIDE) &
RIDGE BRACKET ROMTEC Z3-ORS01 (INTERIOR SIDE).
SECURE TO TRUSS W/ (6) 3/4"Ø x 8" BOLT, (2)
WASHERS & NUT, TYP.
SECURE GLULAM IN SADDLE W/ (2) 3/4"Ø X 7" BOLT,
(2) WASHER, & NUT, TYP.
TOP CHORD PLATE ROMTEC TB-050-5012 (BOTH
SIDES) SECURE WITH (6) 3/4"Ø x 8" BOLT, (2)
WASHERS, & NUT, TYP.
RIDGE PLATE ROMTEC TB-050-5009 (BOTH SIDES)
SECURE WITH (4) 3/4"Ø x 8" BOLT, (2)
WASHERS, & NUT, TYP.
2X6 CEDAR FASCIA
5/8" OSB OVER 2 X 6 T&G
EAVE PLATE ROMTEC TB-050-5002 (EXTERIOR SIDE) &
EAVE BRACKET ROMTEC Z2-ORS01 (INTERIOR SIDE).
SECURE TO TRUSS W/ (12) 3/4"Ø x 8" BOLT, (2)
WASHERS & NUT, TYP.
SECURE GLULAM IN SADDLE W/ (2) 3/4"Ø X 7"
BOLT, (2) WASHER, & NUT, TYP.
6X8 RESAWN TIMBER
COLUMNS, TYP. (4)
BOTTOM CHORD PLATE ROMTEC
TB-000-5005 (BOTH SIDES) SECURE
WITH (7) 3/4"Ø x 8" BOLT, (2)
WASHERS, & NUT, TYP.
TIMBER TRUSS ASSEMBLY (RE-SAWN)
SCALE: 1/4" = 1'-0"
17 11/16"
O.H.
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
W A L L F
IN
IS
H S
C H E D
UL
E
(I N T E R
IO
R
/E X T E R
IO
R
A4.1
WALL FINISH PLAN
SCALE: 1/4" = 1'-0"
CONCRETE FLOOR
3/16" OF ULTRAFLEX 2
THIN-SET (OR EQUAL), TYP.
(INSTALLER SUPPLIED)
1"
SANITARY COVE BASE W/ TILE
WALL & CONCRETE FLOOR
6x6 SANITARY COVE BASE
(6X8 FOR BUY AMERICA)
R3/8"
WALL: TILE & GROUT
(SEE S4.1 FOR DETAILS)
7/16"
3/16"1/4"
NOTE: GROUT TO BE
INSTALLER SUPPLIED (1/8"
GROUT LINES RECOMMENDED)
* AT INSIDE CORNER JOINT
USE SILICONE CAULK TO FINISH
COVE BASE DETAIL
SCALE: 3" = 1'-0"
CMU WALL
SCALE: 3" = 1'-0"
COVE BASE DETAIL
FINISH SCHEDULE
NO. LOCATION FINISH DETAIL
INTERIOR WALL
PRIMED & (2) COATS OF EPOXY PAINT
CMU WALLS FLOOR TO CEILING
(INSTALLER SUPPLIED)
EXTERIOR SIDE
OF CMU
APPLY BLOCK SEALER TO CMU
SURFACES. INSTALLER TO APPLY 2
COATS OF RAIN GUARD BLOK LOK
OR EQUAL PER MANUFACTURE'S
INSTALL INSTRUCTIONS (INSTALLER
SUPPLIED)
EXTERIOR WALL
8" SMOOTH FACE REINFORCED
CONCRETE MASONRY BLOCK WALL
W/ MORTAR JOINTS, GROUTED SOLID
ALL CELLS RUNNING BOND PATTERN.
CEILING
5/8" MOISTURE RESISTANT DRYWALL
TO BE TEXTURED, PRIMED & PAINTED
(INSTALLER SUPPLIED)
FLOOR
CONCRETE WITH A WATER BASED
WET CURE SEALER CURE-N-SEAL OR
EQUAL (INSTALLER SUPPLIED)
COVE BASE IN
RESTROOMS
ONLY
SANITARY TILE COVE BASE
DETAIL 2/A4.1
EXTERIOR SIDING
STONE VENEER WITH
FIBER CEMENT BOARD & BATT SIDING
OVER 2" RIGID INSULATION
3 SEE PAGE A4.2
EXPOSED WOOD
ALL T&G, FASCIA, SUB FASCIA,
TIMBER TRUSSES, TIMBER BEAMS AND
RAFTERS TO BE SEALED WITH
INSTALLER SUPPLIED CLEAR COAT
FINISH APPLIED ONSITE BY INSTALLER
A
B
C
D
INTERIOR WALL TILE (42" HIGH)4
TP
TP
TP
WC-1
GB42G
B
G B
WC-1
LV
-1
LV
-1
LV
-1
PTD
PTD
PTD
SD
SD
SD
3" VTR
3" VTR
S-
S P A R
E C
O N D
UI
T
B P
WC-1
GB42G
B
G B
DD
FD-2
FD-1
FD-2
FD-2
ADA UNISEX
ADA UNISEX
UNISEX
WH
HT
H B
-2
2 3
5 5
4 5
A A2.1
C A2.2
B A2.1
D A2.2
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
W A L L F
IN
IS
H D
E T A
IL
S
A4.2 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
SMOOTH FACE REINFORCED CMU WALL.
INSTALLER TO SEAL CMU PER FINISH
SCHEDULE ON SHEET A4.1 BEFORE
INSTALLING FURRING STRIPS.
26GA FT-000-5145 J-CHANNEL.
VERTICALS @ CORNERS FASTEN TOP &
BOTTOM FASTEN W/ 3/16" X 1 1/4" FLAT
HEAD CONCRETE ANCHORS @ 16" O.C. MAX
W/ RIGID INSULATION
SCALE: 1/2" = 1'-0"
EXTERIOR WALL FURRING DETAIL
1"
2X2 P.T. FURRING IN J-CHANNEL
AROUND DOORS / OTHER OPENINGS
FASTEN W/ 1/4" X 4" GALV. SPLIT
ANCHOR BOLTS @ 16"OC MAX.
A4.3
A4.3
EXTERIOR FINISH STONE VENEER SIDING
W/ 2" INSULATION
SIDING NOTES (SEE )
J-CHANNEL-26GA ROMTEC FT-000-5145 - AT CORNERS,
J-CHANNEL-26GA ROMTEC FT-000-5145 - TOP & BOTTOM OF
SMOOTH FACE CMU WALL AND AROUND OPENINGS. FASTEN
W/ 3/16" X 1 1/4" FLAT HEAD CONCRETE ANCHORS @ 16"
O.C. MAX.
2" RIGID INSULATION (R-13.1), SHALL BE FASTENED TO CMU
W/ 3/16" X 4" FLAT HEAD CONCRETE ANCHORS &
PLASTI-GRIP WASHERS IN THE PATTERN OF TWO ROWS OF
FOUR EVENLY SPACED, USE VENTURE TAPE & SCREWS W/
WASHERS TO FASTEN (2 SHEETS TOGETHER @ SEAMS).
1/2" P.T. PLYWOOD 1'-0" FROM F.F -1/2" PLYWOOD ABOVE
- SHALL BE FASTENED THRU INSULATION TO CMU W/ 3/16" X
4" FLAT HEAD CONCRETE ANCHORS, 12" O.C. PERIMETER &
16" O.C. IN FIELD
#15 BUILDING PAPER - SECURED TO 7/16" OSB SHEATHING
PER MANUFACTURE'S INSTALL INSTRUCTIONS.
METAL LATHE - ATTACH INTO MORTAR BED W/ 3/16" x 4" FLAT HEAD CONCRETE ANCHOR & 3/16" x 1" MIN. WASHER THRU SHEATHING / INSULATION INTO CMU. 16" oc HORZ. 7" oc VERT.
STONE VENEER - INSTALL PER MANUFACTURERS
INSTALLATION INSTRUCTIONS
A4.3
EXTERIOR FINISH FIBER CEMENT
BOARD & BATT SIDING W/ 2" INSULATION
SIDING NOTES (SEE )
J-CHANNEL-26GA ROMTEC FT-000-5145 - AT CORNERS,
J-CHANNEL-26GA ROMTEC FT-000-5145 - TOP & BOTTOM OF
SMOOTH FACE CMU WALL AND AROUND OPENINGS. FASTEN
W/ 3/16" X 1 1/4" FLAT HEAD CONCRETE ANCHORS @ 16"
O.C. MAX.
2" RIGID INSULATION (R-13.1), SHALL BE FASTENED TO CMU
W/ 3/16" X 4" FLAT HEAD CONCRETE ANCHORS &
PLASTI-GRIP WASHERS IN THE PATTERN OF TWO ROWS OF
FOUR EVENLY SPACED, USE VENTURE TAPE & SCREWS W/
WASHERS TO FASTEN (2 SHEETS TOGETHER @ SEAMS).
1/2" P.T. PLYWOOD 1'-0" FROM F.F -1/2" PLYWOOD ABOVE
- SHALL BE FASTENED THRU INSULATION TO CMU W/ 3/16" X
4" FLAT HEAD CONCRETE ANCHORS, 12" O.C. PERIMETER &
16" O.C. IN FIELD
#15 BUILDING PAPER - SECURED TO 7/16" OSB SHEATHING
PER MANUFACTURE'S INSTALL INSTRUCTIONS.
5/16" FIBER CEMENT PANEL SIDING - ATTACH W/ 1"
ROOFING NAIL@ 8" O.C. PERIMETER & @ 16" O.C. FIELD
1x3 FIBER CEMENT BATTS @ 16" O.C. - ATTACH WITH 2"
GALV. FINISH NAILS @ 12" 0.C., COUNTERSINK & FINISH
5/4x4 FIBER CEMENT TRIM - ATTACH WITH 2" GALV.
FINISH NAILS @ 12" 0.C., COUNTERSINK & FINISH
A4.4
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
W A L L F
IN
IS
H D
E T A
IL
S
A4.3
CMU CORNER FINISH DETAIL
SCALE: 3" = 1'-0"
SCRATCH COAT
MORTAR BED
MORTAR JOINT
2" RIGID INSULATION
REFER TO NOTE #2
1/2" PLYWOOD
REFER TO NOTE #3
ATTACH METAL LATH INTO MORTAR
BED W/ 3/16" x 4" FLAT HEAD CONCRETE ANCHOR & 3/16" x 1" MIN.
WASHER THRU SHEATHING / INSULATION
INTO CMU. 16" oc HORZ. 7" oc VERT.
STONE VENEER INSTALL
PER MANUFACTURER
DIRECTION
#15 BUILDING PAPER
REFER TO NOTE #4
J-CHANNEL-26GA
REFER TO NOTE #1
M O
R T A R
J O
IN
T
M O
R T A R
J O
IN
T
BOTTOM OF WALL DETAIL
SCALE: 3" = 1'-0"
SLOPE
1/4"-12" (2%) MIN.
1"
T O
F .G
1/ M
IN
1/2" P.T. PLYWOOD
2" RIGID INSULATION
ATTACH METAL LATH INTO MORTAR
BED W/ 3/16" x 4" FLAT HEAD CONCRETE ANCHOR & 3/16" x 1" MIN.
WASHER THRU SHEATHING / INSULATION
INTO CMU. 16" oc HORZ. 7" oc VERT.
MORTAR JOINT
MORTAR BED
STONE VENEER
#15 BUILDING PAPER
SELF-ADHESIVE, RUBBERIZED
AIR VAPOR BARRIER
WEEP SCREED
SCRATCH COAT
STONE VENEER INSTALL
PER MANUFACTURER
DIRECTION
3"
3" BRICK LEDGE
FOR STONE VENEER
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
W A L L F
IN
IS
H D
E T A
IL
S
A4.4
J-CHANNEL-26GA
REFER TO NOTE #1
#15 BUILDING PAPER
REFER TO NOTE #4
1/2" PLYWOOD
REFER TO NOTE #3
2" RIGID INSULATION
REFER TO NOTE #2
5/16" FIBER CEMENT
PANEL VERTICAL SIDING
REFER TO NOTE #5
5/4x4 TRIM
FIBER,
REFER TO
NOTE #7
VERTICAL FIBER CEMENT 1x3 BATTS
REFER TO NOTE #6
3/8" MIN. FROM PANEL EDGES
2" MIN. FROM CORNERS
CMU CORNER FINISH DETAIL
SCALE: 3" = 1'-0"
M O
R T A R
J O
IN
T
TRANSITION DETAIL
SCALE: 3" = 1'-0"
1/
G A P
WATER SILL
STONE VENEER
MORTAR JOINT
ROMTEC FLASHING
FT-000-5049
STONE 'L' ANCHOR 1/8" THICK
X 1 1/4" WIDE X 2" LENGTH
FASTEN TO CMU W/ SIP LD 4"
SCREW, TYP. (2) PER SILL
ATTACH METAL LATH INTO MORTAR
BED W/ 3/16" x 4" FLAT HEAD CONCRETE ANCHOR & 3/16" x 1" MIN.
WASHER THRU SHEATHING / INSULATION
INTO CMU. 16" oc HORZ. 7" oc VERT.
15# BUILDING PAPER OVER WALL
MEMBRANE
1/2" P.T. PLYWOOD
#15 BUILDING PAPER
5/16" FIBER CEMENT PANEL
1X3 FIBER CEMENT BATTS
(SELF-ADHESIVE, RUBBERIZED
AIR VAPOR BARRIER)
STONE VENEER INSTALL
PER MANUFACTURER
DIRECTION
T O
F .F
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
D O
O R
S C H E D
UL
E
A5.1 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
D O
O R
S C H E D
UL
E
A5.1
DOOR HARDWARE SCHEDULE (QTYS PER DOOR)
GROUP
DO-1
GROUP
DO-2
3 3 EACH HINGE 4.5" x 4.5" S.S. (NRP)
1 1 DOOR CLOSER, (USE THRU BOLT ANCHORING OPTION)
- 1
LEVER LOCKSET,
HAGER - CLASSROOM - (KEY - OUTSIDE / ALWAYS OPEN - INSIDE)
- 1 LATCH GUARD - HAGER
1 -
MORTISE LEVER LOCKSET W/ OCCUPANCY INDICATOR
SCHLAGE LV9056 - (KEY - OUTSIDE / THUMBTURN - INSIDE)
1 1 KICK PLATE, 10" X 34"
1 1 THRESHOLD
1 1 SWEEP
6 6 WIRE DOOR CLIPS
NOTE: ALL DOORS MAY BE OPENED FROM THE INSIDE W/O KEY, SPECIAL KNOWLEDGE,
OR EFFORT. 5# MAX OPENING EFFORT DOOR IS EQUIPPED W/ SINGLE-EFFORT,
NON-GRASP HARDWARE. DOOR COMPLIES WITH ADA REQUIREMENT FOR AN INSIDE LOCK.
KICKPLATE
BOND BEAM EA
SIDE OF DOOR
HEADER
JAMB
THRESHOLD
DOOR CLIP, TYP
24" MIN
EA SIDE
REBAR @ JAMBS
AS PER DETAIL 2/S8.3
ADDITIONAL (1) HORIZONTAL
8'-0" #5 REBAR EXTEND 24"
BEYOND DOOR (BOTH SIDES)
REBAR IN BOND BEAM
AS PER DETAIL 1/S8.2
SHOWN EXTERIOR VIEW:
RIGHT HAND REVERSE BEVEL DOOR
(SWING OUT) LEFT HAND FRAME
FF
3/4" SPACE
A5.2
A5.2
A5.2
S T R
IK
E
9/
/1
/8 C A S E
SCALE: 1/4' = 1'-0"
DOOR DETAILS
SWING OUT
LEFT HAND
RIGHT HAND D0~(REVERSE)K
INTERIOR
1 36"x84"x1 3/4" SL18 F16 1
NO DOORSIZE (WxHxT) SWING - DOOR / FRAMEFRAME
HARD-
WARE REMARKS
DOOR SCHEDULE
GROUP
SWING OUT
LEFT HAND
RIGHT HAND D0~(REVERSE)K
INTERIOR
2 36"x84"x1 3/4" SL18 F16 1
SWING OUT
LEFT HAND
RIGHT HAND D0~(REVERSE)K
INTERIOR
3 36"x84"x1 3/4" SL18 F16 1
SWING OUT
RIGHT HAND
LEFT HAND D0~
K
INTERIOR
(REVERSE)4 36"x84"x1 3/4" SL18 F16 2
KICKPLATE
BOND BEAM EA
SIDE OF DOOR
HEADER
JAMB
THRESHOLD
DOOR CLIP, TYP
24" MIN
EA SIDE
REBAR @ JAMBS
AS PER DETAIL 2/S8.3
ADDITIONAL (1) HORIZONTAL
8'-0" #5 REBAR EXTEND 24"
BEYOND DOOR (BOTH SIDES)
REBAR IN BOND BEAM
AS PER DETAIL 1/S8.2
FF
3/4" SPACE
A5.2
A5.2
A5.2
SHOWN INTERIOR VIEW:
LEFT HAND REVERSE BEVEL DOOR
(SWING OUT) RIGHT HAND FRAME
SCALE: 1/4' = 1'-0"
DOOR DETAILS
SLOPE 1/4":12"
SLAB FLUSH & LEVEL
ONLY AT DOORWAY
HM DOOR W/ CHANNEL
FILLER @ BOT
CONC SLAB & REBAR
AS PER SLAB PLAN
EQEQ
#5 X 12" DOWELS @ 12" O.C.
(AT DOOR LOCATIONS)
(DRILL & DOWEL)
THRESHOLD
DOOR SWEEP
/4
THRESHOLD DETAIL
SCALE: 3" = 1'-0"3
FOR ADDITIONAL SIDING
& WALL FINISH DETAILS
REFER TO SHEET A4.2
7 3/4" x 4"
7'-4"1/4"
1 15/16"
STEEL DOOR
GROUT SOLID
ADDITIONAL
(1) #5 REBAR EXTEND
24" BEYOND DOOR
(WRAP CORNER IF
REQUIRED)
REBAR IN BOND BEAM
AS PER DETAIL 1/S8.2
EXTEND FULL WALL LENGTH
HEADER DETAILS
SCALE: 3" = 1'-0"
N O
T E
A
1/4" 1 15/16"
NOTE A.
SINGLE DOOR 2" JAMB
DOUBLE DOOR 4" JAMB
CAULK
GROUT SOLID
DOOR CLIP; LOCATE
IN MORTAR JOINT
REBAR @ JAMBS AS
PER DETAIL 1/S8.2
AVOID INTERFERENCE
JAMB DETAIL
SCALE: 3" = 1'-0"
1/2" PLYWOOD
15# BLDG. PAPER
FIBER CEMENT 5/16" PANEL
FIBER CEMENT 1 X 3 BATTS
2" RIGID CONTINOUS
INSULATION
WHEN A SIGN IS REQUIRED:
SEE DETAIL 3/A5.3 FOR
SIGN BACKING BOARD
10" O.C. FROM DOOR
OPENING
O
.C
2" X 2" P.T. FURRING
FIBER CEMENT
5/4 X 4 TRIM
CLEAR SEALANT
J-CHANNEL-26GA
ROMTEC FT-000-5145
2" X 2" P.T. FURRING
J-CHANNEL-26GA
ROMTEC FT-000-5145
MIN. 1/4" GAP
FIBER CEMENT
5/4 X 4 TRIM
CLEAR CAULK SEALANT
FIBER CEMENT 5/16" PANEL
FIBER CEMENT 1 X 3 BATTS
1/2" PLYWOOD
15# BLDG. PAPER
2" RIGID CONTINOUS
INSULATION
TILE OVER
GROUT
1/2" 1/2"
TILE OVER
GROUT
www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
D O
O R
D E T A
IL
S
A5.2 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
ADA SIGNS DETAIL
SCALE: 1 1/2" = 1'-0"
NOTES:
A) CHARACTERS ON SIGNS SHALL BE
RAISED 1/32“ INCH MINIMUM AND SHALL
BE 'SANS SERIF' UPPERCASE
CHARACTERS ACCOMPANIED BY GRADE II
BRAILLE (WHERE REQUIRED). RAISED
CHARACTERS SHALL BE A MINIMUM OF
5/8” INCH AND A MAXIMUM OF 2” INCHES
HEIGHT.
B) CONTRACTED GRADE II BRAILLE
SHALL BE USED WHENEVER BRAILLE IS
REQUIRED. DOTS SHALL BE 1/10”TH INCH
ON CENTERS IN EACH CELL WITH A 2/10TH
INCH SPACE BETWEEN CELLS, MEASURED
FROM THE SECOND COLUMN OF DOTS IN
THE FIRST CELL TO THE FIRST COLUMN
OF DOTS IN THE SECOND CELL. DOTS
SHALL BE A RAISED A MINIMUM OF 1/40TH
(0.025) INCH ABOVE THE BACKGROUND.
RESTROOM
1/
"6
8"
/8
M
IN
1/ M
A X
/8
M
IN
NOTE 'A'
NOTE 'B'
F.F. F.F.
RESTROOM
10"
· LOCATIONS & HEIGHT OF SIGN
REQUIREMENTS PER PLANS
SCALE: 1" = 1'-0"
BACKING BOARD - FIELD CUT
7"
8 1/2"
/2
(5/4" X 4" FIBER CEMENT)
· FOR LAP OR SHAKE SIDING ONLY!
FOR OTHER FINISHES SEE 2/A5.2
· ATTACH BACKING BOARD 10" o.c., FROM DOOR OPENING (LATCH
SIDE)
FOR 8"x8" SIGNFOR 6"x9" SIGN
SHOWN
WHEN A SIGN IS REQUIRED
SIGN FASTENERS: WOOD/FIBER CEMENT/STEEL
(4) #10 3/4" PHILLIPS ROUND HEAD SCREW.1
ADA SIGN ELEVATIONS
SCALE: 1/2" = 1'-0"
www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
S
IG
N D
E T A
IL
S
A5.3 www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
FD-2
FD-1
FD-2
FD-2
www.structure1.com Klamath Falls Office
250 Main Klamath Falls, Oregon 97603 Phone: (541) 850-6300 `Fax: (541) 850-6233 info@structure1.com
PSE Consulting Engineers, Inc.
ROMTEC 224-136
9/27/2024
ORS01
S A N D
Y S
P R
IN
G
S G
E O
R G
IA
O L D
R
IV
E R
S
ID
E P
A R
K
ZW
SHEET NO.
DRAWN BY:
DATE:
PROJECT #:
P R
O
JE
C T
S H
E E
T T
IT
LE
REVISIONS:
REV. DATE: BY:
R O
M
TE
C , I
N C
AL
L R
IG
H
TS
R
ES
ER
VE
D
TH
ES
E
PL
AN
S
AN
D D
R
AW
IN
G
S M
AY
N
O T
BE
R
EP
R
O D
U C
ED
, A
D
AP
TE
D
O R
F U
R
TH
ER
D
IS
TR
IB
U
TE
D
, A N
D N
O B
U
IL
D
IN
G S
M
AY
B E
C O
N
ST
R U
C
TE
D F
R O
M T
H
ES
E
PL
AN
S, W
IT
H O
U T
TH
E
W R
IT
TE
N P
ER
M
IS
SI
O N
O F
R O
M
TE
C , I
N C www.romtec.com
(541) 496-3541 FAX (541) 496-0803
JOB CREATED: 12/23/2024 - LAST SAVED BY: zweiser ON 12/23/2024 - LAST PRINTED: 1/8/2025 - LOCATION: O:\Engineering RI\Plan Sets\ORS01-Old Riverside, GA\ORS01-Old Riverside 2047M, GA 240926.dwg
F O
UN
D
A T
IO
N P
L A N
S7.1
FOUNDATION NOTES:
1. FINISH FLOOR SLOPE IS 2% (1/4" PER FT) MAX & 1% (1/8"
PER FT) MIN
2. VERIFY SIDEWALKS W/ OWNER
3. PROVIDE BLOCK-OUTS FOR PLUMBING, MECHANICAL, &
ELECTRICAL AS REQD. CO-ORDINATE W/ SUBS.
4. REBAR MIN. BEND SHALL BE NOT LESS THAN 6db INSIDE
DIA. AS PER TMS 402-16…