J041--Building Automation Services

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
36C24821Q0119
Agency
Veterans Integrated Service Network 8 Veterans Health Administration, Department of Veterans Affairs
Responses due
Set-aside
No set-aside

Opportunity facts

NAICS code
238220 Plumbing, Heating, and Air-Conditioning Contractors
PSC
J041 Maint/Repair/Rebuild Of Equipment- Refrigeration, Air Conditioning, And Air Circulating Equipment
Place of performance
10 Casia Street San Juan 00921

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Network Contracting Office-8 is seeking quotes for building automation services at VA facilities in Puerto Rico. Quotes are requested for preventative maintenance and repair of building automation systems controlling HVAC, utilities, and medical equipment. Award will be made based on a comparative evaluation of price and technical acceptability. Quotes are due by December 26, 2020. Questions must be submitted by December 17, 2020.

This procurement has no set-aside designation and is being conducted under NAICS 238220 with a small business size standard of $16.5M and PSC code J041. The period of performance is one base year from January 1, 2020 to December 31, 2021 with four one-year option periods. The place of performance is facilities of the Veterans Affairs Caribbean Health System located in Puerto Rico, including the main medical center in San Juan.

Notice text

2 versions

Update #2 · Latest ·

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the

offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR

ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY

is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not,

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES

SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter

or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to

the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print)

(Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign)

(Signature of Contracting Officer)

0001

12/21/2020

None

36C248

Department of Veterans Affairs

Network Contracting Office 8 (NCO 8)

VA Caribbean HCS (Admin Bldg)

#10 Calle Casia Suite #4M440

San Juan PR 00921-3201

36C248

Department of Veterans Affairs

Network Contracting Office 8 (NCO 8)

VA Caribbean HCS (Admin Bldg)

#10 Calle Casia Suite #4M440

San Juan PR 00921-3201

To all Offerors/Bidders

36C24821Q0119

12-21-2020

X

x

1

Title; PM Building Automation System

1) Please refer to page number two (2) for answers from questions submitted by interested Contractors.

Rafael Rodriguez

Contracting Officer

VA-VHA-2019-3C9E1171

Page 8 of 8

Please provide the quantity of existing VFD s to be included in the contract along with their brand and size in Horse Power

Answer to question 1:

Variable Frequency Drive Inventory Table

Item

Unit

Location

Size

Brand

Serial no.

8

1

AHU 1

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797518

INPUT: 480V 3 Phase 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

2

AHU 1

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797514

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

3

AHU 2

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797506

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

4

AHU 2

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797376

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

5

AHU 3

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797512

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

6

AHU 3

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12807344

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

7

AHU 4

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797511

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

8

AHU 4

Return Fan

SBT Machinery Room

7.5

Johnson Controls

12797387

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

9

AHU 5

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797507

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

10

AHU 5

Return Fan

SBT

Machinery Room

10

Johnson Controls

12797193

INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT

: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

11

AHU 6

Supply Fan

SBT

Machinery Room

50

Johnson Controls

12797173

INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

12

AHU 6

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797436

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

13

AHU 7

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797503

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

14

AHU 7

Return Fan

SBT

Machinery Room

10

Johnson Controls

12797192

INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

15

AHU 8

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797501

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

16

AHU 8

Return Fan

SBT

Machinery Room

5

Johnson Controls

12797194

INPUT: 480V 3 PHASE 50/60HZ 7.6 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 7.6 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

17

AHU 9

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797515

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

18

AHU 9

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797517

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

19

AHU 10

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797509

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

20

AHU 10

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797504

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

21

AHU 11

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797510

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

22

AHU 11

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797370

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

23

AHU 12

Supply Fan

SBT

Machinery Room

40

Johnson Controls

12797505

INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

24

AHU 12

Return Fan

SBT

Machinery Room

7.5

Johnson Controls

12797390

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT

: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

25

Cooling

Tower #2

SBT

Machinery Room

50

Johnson Controls

12796894

INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

26

Cooling

Tower #1

SBT Machinery Room

50

Johnson Controls

12796906

INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

27

IEF - 6

SBT

Machinery Room

7.5

Johnson Controls

12797166

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

28

IEF - 5

SBT

Machinery Room

7.5

Johnson Controls

12797179

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

29

IEF - 4

SBT

Machinery Room

3

Johnson Controls

12797196

INPUT: 480V 3 PHASE 50/60HZ 4.8 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 4.8 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

30

IEF - 3

SBT

Machinery Room

7.5

Johnson Controls

12797198

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

31

IEF - 2

SBT

Machinery Room

10

Johnson Controls

12797185

INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

32

IEF - 1

SBT

Machinery Room

7.5

Johnson Controls

12797195

INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

33

EF Outside Air

SBT

Machinery Room

15

EMERSON

B4015-21300

FREQUENCY IN/OUT 21 AFLC, VOLTS IN/OUT 460 VAC

34

Hot Water

Pump - 1

SBT

Machinery Room

20

Johnson Controls

12797213

INPUT: 480V 3 PHASE 50/60HZ 27 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 27 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

35

Hot Water

Pump - 2

SBT Machinery Room

20

Johnson Controls

12890581

INTELLIPASS OPTIONS: 3, INPUT: 480VAC 50/60HZ 27A 3PH, OUTPUT: 0-480VAC 0-320HZ 27A 3PH, MAX HP:

20HP @ 480VAC 27A, CONTROL: 24VDC, MAX AMBIENT TEMP: 40 C, ENCLOSURE TYPE: 12, SHORT CIRCUIT

RATINGS: 65KA @ 480Y/277VAC, SCHEMATIC: 285447-1004

36

Cooling Tower

Pump - 1

SBT

Machinery Room

50

DANFOSS

293702Y407

INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT

RASTING: 5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F

37

Cooling Tower

Pump - 2

SBT

Machinery Room

50

DANFOSS

293502Y407

INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT RASTING:

5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F

38

Cooling Tower

Pump -3

SBT

Machinery Room

10

DANFOSS

315804Y407

INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10 HP, 14.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

39

Chill Water

Pump - 1

SBT

Machinery Room

60

Johnson Controls

12797090

INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

40

Chill Water

Pump - 2

SBT

Machinery Room

60

Johnson Controls

12797112

INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

41

AHU 12

Supply Fan

OPA PH

Machinery Room

50

TRANE

755404Y262

INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

42

AHU 12

Return Fan

OPA PH

Machinery Room

15

TRANE

757804Y263

INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

43

AHU 03

Supply Fan

OPA PH

Machinery Room

50

TRANE

755304Y262

INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

44

AHU 03

Return Fan

OPA PH

Machinery Room

15

TRANE

757704Y262

INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

45

AHU 04

Supply Fan

OPA PH Machinery Room

40

TRANE

750204Y262

INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

46

AHU 04

Return Fan

OPA PH

Machinery Room

15

TRANE

757904Y262

INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

47

AHU - 100

OPA PH

Machinery Room

5

TRANE

751404Y262

INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

48

AHU 14

Supply Fan

OPA PH

Machinery Room

20

TRANE

757204Y262

INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

49

AHU 14

Return Fan

OPA PH

Machinery Room

7.5

TRANE

750804Y262

INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

50

AHU - 4A

OPA PH

Machinery Room

3

TRANE

751604Y262

INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

51

AHU 16

Supply Fan

OPA PH

Machinery Room

50

TRANE

755204Y262

INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

52

AHU 16

Return Fan

OPA PH

Machinery Room

15

TRANE

757604Y262

INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

53

AHU 15

Supply Fan

OPA PH

Machinery Room

20

TRANE

757104Y262

INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

54

AHU 15

Return Fan

OPA PH

Machinery Room

5

TRANE

751504Y262

INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

55

AHU 1

Supply Fan

OPA PH

Machinery Room

50

TRANE

755104Y262

INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

56

AHU 1

Return Fan

OPA PH

Machinery Room

20

TRANE

757304Y262

INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

57

AHU 2

Supply Fan

OPA PH Machinery Room

25

TRANE

756304Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

58

AHU 2

Return Fan

OPA PH

Machinery Room

10

TRANE

751204Y262

INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

59

AHU 6

Supply Fan

OPA PH

Machinery Room

40

TRANE

554604Y232

INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

60

AHU 6

Return Fan

OPA PH

Machinery Room

25

TRANE

552104Y232

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

61

AHU 5

Supply Fan

OPA PH

Machinery Room

60

TRANE

534904Y232

INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

62

AHU 5

Return Fan

OPA PH

Machinery Room

30

TRANE

542904Y232

INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

63

AHU 18

Supply Fan

OPA PH

Machinery Room

25

TRANE

756504Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

64

AHU 18

Return Fan

OPA PH

Machinery Room

7.5

TRANE

751004Y262

INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

65

AHU 17

Supply Fan

OPA PH

Machinery Room

50

TRANE

755504Y262

INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

66

AHU 17

Return Fan

OPA PH

Machinery Room

15

TRANE

757504Y262

INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

67

AHU 7

Supply Fan

OPA PH

Machinery Room

60

TRANE

758404Y262

INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

68

AHU 7

Return Fan

OPA PH

Machinery Room

25

TRANE

756404Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

69

AHU 52

Supply Fan

OPA PH Machinery Room

25

TRANE

756704Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

70

AHU 19

Supply Fan

OPA PH

Machinery Room

25

TRANE

756204Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: 5

KA RMS SYM. AT RATED INPUT V MAX.

71

AHU 19

Return Fan

OPA PH

Machinery Room

10

TRANE

751104Y262

INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

72

AHU - 101

OPA PH

Machinery Room

3

TRANE

751704Y262

INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 3.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

73

AHU 8

Supply Fan

OPA PH

Machinery Room

60

TRANE

758504Y262

INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

74

AHU 8

Return Fan

OPA PH

Machinery Room

25

TRANE

756604Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

75

AHU 21

Supply Fan

OPA PH

Machinery Room

25

TRANE

003207H422

INPUT: 3, 460 VAC, 60HZ, 34.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 34.0A FLA, POWER: 25HP, 18.5 KW

76

AHU 21

Return Fan

OPA PH

Machinery Room

7.5

TRANE

750904Y262

INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

77

AHU 20

Supply Fan

OPA PH

Machinery Room

25

TRANE

756804Y262

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

78

AHU 20

Return Fan

OPA PH

Machinery Room

5

TRANE

751304Y262

INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

79

Cooling

Tower #1

OPA PH

Machinery Room

30

TRANE

542604Y232

INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

80

Cooling

Tower #2

OPA PH

Machinery Room

30

TRANE

543004Y233

INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: 5

KA RMS SYM. AT RATED INPUT V MAX.

81

Cooling

Tower #3

OPA PH Machinery Room

30

TRANE

542804Y232

INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

82

Cooling

Tower #4

OPA PH

Machinery Room

30

TRANE

542704Y232

INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

83

Pump - 11

OPA Basement

Machinery Room

50

TRANE

562004Y082

INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: 5

KA RMS SYM. AT RATED INPUT V MAX.

84

AHU 13

Supply Fan

OPA Basement

Machinery Room

10

TRANE

499704Y072

INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

85

Pump - 7

OPA Basement

Machinery Room

60

TRANE

562204Y082

INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

86

Pump - 8

OPA Basement

Machinery Room

60

TRANE

562104Y082

INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

87

Pump - 9

OPA Basement

Machinery Room

20

TRANE

559504Y082

INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

88

Pump - 10

OPA Basement

Machinery Room

20

TRANE

559404Y082

INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

89

Pump - 18

OPA Basement

Machinery Room

15

TRANE

004007H442

INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW

90

Pump - 17

OPA Basement

Machinery Room

15

TRANE

003907H442

INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW

91

Pump - 16

OPA Basement

Machinery Room

40

TRANE

548804Y072

INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

92

AHU 5

Supply Fan

Admin Bldg. PH

Machinery Room

30

Johnson Controls

2103303731

45 A, 30HP, VOLT 480 VAC

93

AHU 5

Return Fan

Admin Bldg. PH

Machinery Room

10

Johnson Controls

2110102946

15.4 A, 10 HP, VOLT 480 VAC

94

AHU 4

Supply Fan

Admin Bldg. PH Machinery Room

40

Johnson Controls

2110100765

INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 58A

95

AHU 4

Return Fan

Admin Bldg. PH

Machinery Room

10

Johnson Controls

2122400934

15 A, 10 HP, VOLT 480 VAC

96

AHU 3

Supply Fan

Admin Bldg. PH

Machinery Room

40

Johnson Controls

2104002131

INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 58A

97

AHU 3

Return Fan

Admin Bldg. PH

Machinery Room

15

Johnson Controls

2105003602

15 A, 10 HP, VOLT 480 VAC

98

AHU 2

Supply Fan

Admin Bldg. PH

Machinery Room

40

Johnson Controls

2106200645

50 A, 40 HP, VOLT 480 VAC

99

AHU 2

Return Fan

Admin Bldg. PH

Machinery Room

10

Johnson Controls

S/N IS NOT CLEAR

VOLT: 460, AMP: 12.5, 60HZ, PHASE 3

100

AHU 1

Supply Fan

Admin Bldg.

Basement

Machinery Room

40

Johnson Controls

2105200639

INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 58A

101

AHU 1

Return Fan

Admin Bldg.

Basement

Machinery Room

10

Johnson Controls

Â

INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 15.4A

102

Supply Fan 8

Admin Bldg.

Basement

Machinery Room

7.5

ABB

Â

INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 11.9A

103

AHU - Breezeway

Bldg. 1 Roof

5

TRANE

569902G283

4.0KW(400V), 5.0HP(460), IN: 3X380-480V 50/60HZ 9.1/8.3A, OUT: 3X0-VIN 0-1000HZ 10/8.2A

104

EF - 88

Bldg. 1 Roof

15

DANFOSS

009833H397

11KW / 15HP, IN: 3X380-480V 50/60HZ 22/19A, OUT: 3X0-VIN 0-590HZ 24/21A

105

AHU - S2R

Bldg. 1 Roof

30

TRANE

658304Y144

INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

106

AHU

Lineal Accelerator

A 1

CT Scan Bldg.

Roof

7.5

TRANE

861000Y085

INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

107

AHU

Lineal Accelerator

A 1A

CT Scan Bldg.

Roof

7.5

TRANE

789400Y075

INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

108

SF - 3

Bldg. 1

2nd Floor Roof

25

Johnson Controls

2093202587

VOLT: 460, AMPS: 30, 25HP, 60HZ

109

SF - 6

Bldg. 1 2nd Floor Roof

25

Johnson Controls

2093000437

VOLT: 460, AMPS: 30, 25HP, 60HZ

110

AHU - 10

Bldg. 1

2nd Floor Roof

Â

ABB

2154201314

VOLT: 277/480, 3 PHASE, 11.9A, 63HZ

111

SF - 4

Bldg. 1

2nd Floor Roof

25

Johnson Controls

2093000418

VOLT: 460, AMPS: 30, 25HP, 60HZ

112

SF - 5

Bldg. 1

2nd Floor Roof

25

Johnson Controls

2092800522

VOLT: 460, AMPS: 30, 25HP, 60HZ

113

AHU - 1

CLC 1st Floor

Machinery Room

15

TRANE

001329H215

IN: 3X200-240V 50/60HZ, 48.3A, OUT: 3X0-VIN 0.1-1000HZ, 48.3A, 11KW / 15HP

114

AHU - 2

CLC 2nd Floor

Machinery Room

25

TRANE

000529H205

IN: 3X200-240V 50/60HZ, 78.2A, OUT: 3X0-VIN 0.1-1000HZ, 78.2A, 18.5KW / 15HP

115

AHU - 3

CLC 1st Floor

Machinery Room

10

TRANE

000529H215

IN: 3X200-240V 50/60HZ, 32.2A, OUT: 3X0-VIN 0.1-1000HZ, 33A, 7.5KW / 10HP

116

AHU - 4

CLC 1st Floor

Machinery Room

5

TRANE

000429H205

IN: 3X200-240V 50/60HZ, 16.8A, OUT: 3X0-VIN 0.1-1000HZ, 17.6A, 3.7KW / 5HP

117

AHU-

Ambulatory

Surgery

Bldg.1 1st Floor

Roof

10

ABB

51737C0330

3-380 480V, 31A, 48 63HZ,10HP

118

Pump 10

Potable Water

Pump Room

25

TRANE

803204Y415

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

119

Pump 9

Potable Water

Pump Room

25

TRANE

Â

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

120

Pump 8

Potable Water

Pump Room

25

TRANE

Â

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

121

Pump 7

Potable Water

Pump Room

25

TRANE

803104Y415

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

122

Cooling

Tower 1

Main Chiller Plant

75

TRANE

614004Y111

INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

123

Cooling

Tower 2

Main Chiller Plant

75

TRANE

613904Y111

INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

124

Cooling

Tower 3

Main Chiller Plant

75

TRANE

613804Y111

INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

125

Cooling

Tower 4

Main Chiller Plant

75

TRANE

614104Y111

INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

126

Cooling

Tower 5

Main Chiller Plant

75

TRANE

613704Y111

INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

127

PUMP 1R

Main Chiller Plant

20

DANFOSS

007833H387

15KW/20HP, 50/60HZ, 29/25A

128

PUMP 2R

Main Chiller Plant

20

DANFOSS

295404Y407

15KW/20HP, 50/60HZ, 29/25A

129

PUMP 3R

Main Chiller Plant

20

DANFOSS

295604Y407

15KW/20HP, 50/60HZ, 29/25A

130

PUMP 4R

Main Chiller Plant

20

DANFOSS

295704Y407

15KW/20HP, 50/60HZ, 29/25A

131

PUMP 12R

Main Chiller Plant

150

TRANE

001203H255

110KW/150HP, 50/60HZ,204/183A

132

PUMP 10R

Main Chiller Plant

150

TRANE

001103H255

110KW/150HP, 50/60HZ,204/183A

133

PUMP 11R

Main Chiller Plant

150

TRANE

001003H255

110KW/150HP, 50/60HZ,204/183A

Are any of the VFDs damaged and what s their brand and capacity?

Answer to question 2:

OPA Building

AHU 15 Supply Fan 20 HP Out of service

AHU 53 Supply Fan 10 HP Out of Service

AHU 4 Return Fan 15 HP Out of service

AHU 17 Return Fan 15 HP Out of service

SBT Building

AHU 5 Supply Fan 30 HP Out of service

AHU 10 Supply Fan 40 HP Out of service

AHU 3 Return Fan 7.5 HP Out of service

AHU 1 Return Fan 7.5 HP Out of service

Hot Water Pump 2 15 HP Out of service

Main Building

Pump 7 Millionaires Tanks 25 HP Out of service

Pump 8 Millionaires Tanks 25 HP Out of service

Pump 9 Millionaires Tanks 25 HP Out of service

Pump 10 Millionaires Tanks 25 HP Out of service

Administration Building

AHU 1 Return Fan Out of service

Please provide the quantity of BCUs, UPCMs, MPs, FECs, NAEs, JACEs and Distech Controllers.

Answer to question 3:

Five Network Automation Engines or NAE.

Twenty three Field Equipment Controllers of FEC.

Forty nine FEC expansion cards.

One Java Application Control Engine or JACE.

Eleven Distech controllers 11.

Twenty nine Building Control Units or BCU.

Fifty four Universal Programable Control Modules or UPCMs.

One hundred and ninety-seven Multi-Purpose controllers or MP.

Three hundred and fifty five  MP expansion cards.

Please indicate if there are any of the above-mentioned controllers that are non-operational.

Answer to question 4:

One UPCM is out of service.

Please indicate if there are any of the above-mentioned controllers that are non-operational.

Answer to question 5:

           Yes, the contractor is responsible for any part that need replacement during the contract period.

Please indicate if calibrations will be allowed during normal working hours on all areas of the facilities or if the contractor will have to perform calibrations of sensitive areas during non-normal working hours.

Answer to question 6:

          Contractor will perform all recurring maintenance on scheduled with final customer systematically. Recurring

maintenance or calibrations shall not impact patientcare service. Contractor might need to work irregular

hours, weekends, holydays, etc. according to service department work schedule.

If calibrations are to be performed during other than normal working hours in sensitive areas please indicate which areas are deemed sensitive and how many calibration points can we assume in these areas?

            Answer to question 7:

SPS (20 points)

Operation Rooms (55 points)

Cardio (20 points)

Nuclear Medicine (10 points)

Multipurpose (10 points)

Outpatient Pharmacy (150 points)

Inpatient Pharmacy (20 points)

Laboratory (20 points)

Hemodialysis (24 points)

SICU (20 points)

Is an electrician required for this contract, to work with the VFD s?

                       Answer to question 8:

                                   Yes, a license electrician is required to work with any electrical circuits and VFDs.

Additional question:

           Given that Trane does not sell tracer summit products any more please indicate what will the

contractor need to do if a BCU or an MP581 or a UPCM becomes damaged and if the cost of

the solution will be the responsibility of the contractor.

           Answer:

           The contractor must submit recommendations for alternative solutions in case that parts are no longer

manufactured, cannot be found through retailers, and no equivalent is available as a direct replacement.Â

The government will evaluate the alternatives and will make decisions accordingly. Â

Update #1 ·

This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Items, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation document will not be issued.

The solicitation number 36C24821Q0119 is issued as a Request for Quotation (RFQ). The incorporated provisions and clauses in this document are those in effect through Federal Acquisition Circular 2021-02, effective on 11-23-2020.

This solicitation will be competed using Tier Evaluation: 1st Tier- SDVOSB, 2nd Tier- VOSB and 3rd Tier- All Other Small Business (SB). The associated North American Industrial Classification System (NAICS) code for this procurement is 238220, with a small business size standard of $16.5 Million. The PSC is J041.

The Department of Veterans Affairs, Network Contracting Office -8 located at VA Caribbean Health System (VACHS), 10 Casia Street, Admin Building Suite 4M440, San Juan, Puerto Rico 00921 is seeking services to provide Preventive Maintenance and Repair for the Building Automation System (BAS) Services.

Detailed specifications and requirements are provided in the attached SCOPE OF WORK (SOW) Instructions to Quoters, Price/Cost Schedule, Clauses and Provisions.

The contract period of performance is expected to be from January 01, 2020 or date of award if later until December 31, 2021 plus four one-year option periods.

Place of Performance/Place of Delivery

Address: VA Caribbean Healthcare System: 10 Casia Street, San Juan, PR 00921

The full text of FAR provisions or clauses may be accessed electronically at https://www.acquisition.gov/browse/index/far

The following solicitation provisions apply to this acquisition:

1. FAR 52.212-1, Instructions to Quoters Commercial Items (Addendum attached)

2. FAR 52.212-3, Offerors Representations and Certifications Commercial Items

(www.sam.gov registration is required to be complete at time of submission of response)

Offerors must complete annual representations and certifications electronically via the System for Award Management (SAM) website located at https://www.sam.gov/SAM/ in accordance with FAR 52.212-3, Offerors Representations and Certifications Commercial Items. If paragraph (j) of the provision is applicable, a written submission is required.

The following contract clauses apply to this acquisition:

1. FAR 52.212-4, Contract Terms and Conditions Commercial Items (OCT 2018) (Addendum attached)

2. FAR 52.212-5, Contract Terms and Conditions Required to Implement Statutes or Executive Orders (OCT 2019)

Award will be based upon a comparative evaluation of quotes in accordance with the Simplified Acquisition Procedures of FAR 13. Comparative evaluation is the side by side pairwise comparison of quotes based on factors resulting in a Contracting Officer decision for the quote most favorable to the Government. Options will be evaluated at time of award.

The award will be made to the response most advantageous to the Government. Responses should contain your best terms, conditions. To facilitate the award process, all quotes must include a statement regarding the terms and conditions herein as follows:

"The terms and conditions in the solicitation are acceptable to be included in the award document without modification, deletion, or addition."

OR

"The terms and conditions in the solicitation are acceptable to be included in the award document with the exception, deletion, or addition of the following:"

Quoters shall list exception(s) and rationale for the exception(s), if any.

Questions submission shall be received not later than 10:00 AM AST on December 17, 2020 at Rafael.Rodriguez2@va.gov.

Submission of your response shall be received not later than 9:00 AM AST on December 26, 2020 at Rafael.Rodriguez2@va.gov.

Due to the COVID 19 pandemic, the Government will not be conducting site visits for this procurement action. This is done to avoid any contact with patients, personnel and visitors.

The quoter shall submit a PDF version of the quote to the Government. Late submissions shall be treated in accordance with the solicitation provision at FAR 52.212-1(f). Omission of any one item MAY result in a quoter package being deemed not technically acceptable.

Any questions or concerns regarding this solicitation should be forwarded in writing via e-mail to the Point of Contact listed below.

Point of Contact

Rafael Rodriguez, Contracting Officer, 787-641-7582 Ext. 34972 and email Rafael.Rodriguez2@va.gov

See attached document A: 36C24821Q0119- SOW

See attached document B: Schedule of Prices

See attached document C: Clauses and Provisions

See attached document D: Wage determination

Attachments

Files attached to this notice, newest first
File Type Posted
36C24821Q0119_3.docx DOCX document
SCHEDULE A SOW BAS Services VACHS.pdf PDF
Attachment D- WAGE DETERMINATION BAS Services PR.pdf PDF
Attachment B SCHEDULE BAS 1.pdf PDF
36C24821Q0119_2.docx DOCX document
Attachment C Clauses and Provisions BAS Services revi 12 11.pdf PDF

Notice history

Notices posted for this opportunity, newest first
Notice Type Posted
J041--Building Automation Services Long Term Contract Award Award Notice