J041--Building Automation Services
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 36C24821Q0119
- Agency
- Veterans Integrated Service Network 8 Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 238220 Plumbing, Heating, and Air-Conditioning Contractors
- PSC
- J041 Maint/Repair/Rebuild Of Equipment- Refrigeration, Air Conditioning, And Air Circulating Equipment
- Place of performance
- 10 Casia Street San Juan 00921
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Network Contracting Office-8 is seeking quotes for building automation services at VA facilities in Puerto Rico. Quotes are requested for preventative maintenance and repair of building automation systems controlling HVAC, utilities, and medical equipment. Award will be made based on a comparative evaluation of price and technical acceptability. Quotes are due by December 26, 2020. Questions must be submitted by December 17, 2020.
This procurement has no set-aside designation and is being conducted under NAICS 238220 with a small business size standard of $16.5M and PSC code J041. The period of performance is one base year from January 1, 2020 to December 31, 2021 with four one-year option periods. The place of performance is facilities of the Veterans Affairs Caribbean Health System located in Puerto Rico, including the main medical center in San Juan.
Notice text
2 versions
Update #2 · Latest ·
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the
offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR
ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY
is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not,
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES
SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter
or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to
the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print)
(Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign)
(Signature of Contracting Officer)
0001
12/21/2020
None
36C248
Department of Veterans Affairs
Network Contracting Office 8 (NCO 8)
VA Caribbean HCS (Admin Bldg)
#10 Calle Casia Suite #4M440
San Juan PR 00921-3201
36C248
Department of Veterans Affairs
Network Contracting Office 8 (NCO 8)
VA Caribbean HCS (Admin Bldg)
#10 Calle Casia Suite #4M440
San Juan PR 00921-3201
To all Offerors/Bidders
36C24821Q0119
12-21-2020
X
x
1
Title; PM Building Automation System
1) Please refer to page number two (2) for answers from questions submitted by interested Contractors.
Rafael Rodriguez
Contracting Officer
VA-VHA-2019-3C9E1171
Page 8 of 8
Please provide the quantity of existing VFD s to be included in the contract along with their brand and size in Horse Power
Answer to question 1:
Variable Frequency Drive Inventory Table
Item
Unit
Location
Size
Brand
Serial no.
8
1
AHU 1
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797518
INPUT: 480V 3 Phase 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
2
AHU 1
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797514
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
3
AHU 2
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797506
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
4
AHU 2
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797376
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
5
AHU 3
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797512
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
6
AHU 3
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12807344
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
7
AHU 4
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797511
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
8
AHU 4
Return Fan
SBT Machinery Room
7.5
Johnson Controls
12797387
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
9
AHU 5
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797507
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
10
AHU 5
Return Fan
SBT
Machinery Room
10
Johnson Controls
12797193
INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT
: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
11
AHU 6
Supply Fan
SBT
Machinery Room
50
Johnson Controls
12797173
INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
12
AHU 6
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797436
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
13
AHU 7
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797503
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
14
AHU 7
Return Fan
SBT
Machinery Room
10
Johnson Controls
12797192
INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
15
AHU 8
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797501
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
16
AHU 8
Return Fan
SBT
Machinery Room
5
Johnson Controls
12797194
INPUT: 480V 3 PHASE 50/60HZ 7.6 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 7.6 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
17
AHU 9
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797515
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
18
AHU 9
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797517
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
19
AHU 10
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797509
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
20
AHU 10
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797504
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
21
AHU 11
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797510
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
22
AHU 11
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797370
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
23
AHU 12
Supply Fan
SBT
Machinery Room
40
Johnson Controls
12797505
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
24
AHU 12
Return Fan
SBT
Machinery Room
7.5
Johnson Controls
12797390
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT
: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
25
Cooling
Tower #2
SBT
Machinery Room
50
Johnson Controls
12796894
INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
26
Cooling
Tower #1
SBT Machinery Room
50
Johnson Controls
12796906
INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
27
IEF - 6
SBT
Machinery Room
7.5
Johnson Controls
12797166
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
28
IEF - 5
SBT
Machinery Room
7.5
Johnson Controls
12797179
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
29
IEF - 4
SBT
Machinery Room
3
Johnson Controls
12797196
INPUT: 480V 3 PHASE 50/60HZ 4.8 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 4.8 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
30
IEF - 3
SBT
Machinery Room
7.5
Johnson Controls
12797198
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
31
IEF - 2
SBT
Machinery Room
10
Johnson Controls
12797185
INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
32
IEF - 1
SBT
Machinery Room
7.5
Johnson Controls
12797195
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
33
EF Outside Air
SBT
Machinery Room
15
EMERSON
B4015-21300
FREQUENCY IN/OUT 21 AFLC, VOLTS IN/OUT 460 VAC
34
Hot Water
Pump - 1
SBT
Machinery Room
20
Johnson Controls
12797213
INPUT: 480V 3 PHASE 50/60HZ 27 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 27 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
35
Hot Water
Pump - 2
SBT Machinery Room
20
Johnson Controls
12890581
INTELLIPASS OPTIONS: 3, INPUT: 480VAC 50/60HZ 27A 3PH, OUTPUT: 0-480VAC 0-320HZ 27A 3PH, MAX HP:
20HP @ 480VAC 27A, CONTROL: 24VDC, MAX AMBIENT TEMP: 40 C, ENCLOSURE TYPE: 12, SHORT CIRCUIT
RATINGS: 65KA @ 480Y/277VAC, SCHEMATIC: 285447-1004
36
Cooling Tower
Pump - 1
SBT
Machinery Room
50
DANFOSS
293702Y407
INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT
RASTING: 5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F
37
Cooling Tower
Pump - 2
SBT
Machinery Room
50
DANFOSS
293502Y407
INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT RASTING:
5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F
38
Cooling Tower
Pump -3
SBT
Machinery Room
10
DANFOSS
315804Y407
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10 HP, 14.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
39
Chill Water
Pump - 1
SBT
Machinery Room
60
Johnson Controls
12797090
INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
40
Chill Water
Pump - 2
SBT
Machinery Room
60
Johnson Controls
12797112
INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT:
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
41
AHU 12
Supply Fan
OPA PH
Machinery Room
50
TRANE
755404Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
42
AHU 12
Return Fan
OPA PH
Machinery Room
15
TRANE
757804Y263
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
43
AHU 03
Supply Fan
OPA PH
Machinery Room
50
TRANE
755304Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
44
AHU 03
Return Fan
OPA PH
Machinery Room
15
TRANE
757704Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
45
AHU 04
Supply Fan
OPA PH Machinery Room
40
TRANE
750204Y262
INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
46
AHU 04
Return Fan
OPA PH
Machinery Room
15
TRANE
757904Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
47
AHU - 100
OPA PH
Machinery Room
5
TRANE
751404Y262
INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
48
AHU 14
Supply Fan
OPA PH
Machinery Room
20
TRANE
757204Y262
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
49
AHU 14
Return Fan
OPA PH
Machinery Room
7.5
TRANE
750804Y262
INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
50
AHU - 4A
OPA PH
Machinery Room
3
TRANE
751604Y262
INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
51
AHU 16
Supply Fan
OPA PH
Machinery Room
50
TRANE
755204Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
52
AHU 16
Return Fan
OPA PH
Machinery Room
15
TRANE
757604Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
53
AHU 15
Supply Fan
OPA PH
Machinery Room
20
TRANE
757104Y262
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
54
AHU 15
Return Fan
OPA PH
Machinery Room
5
TRANE
751504Y262
INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
55
AHU 1
Supply Fan
OPA PH
Machinery Room
50
TRANE
755104Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
56
AHU 1
Return Fan
OPA PH
Machinery Room
20
TRANE
757304Y262
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
57
AHU 2
Supply Fan
OPA PH Machinery Room
25
TRANE
756304Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
58
AHU 2
Return Fan
OPA PH
Machinery Room
10
TRANE
751204Y262
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
59
AHU 6
Supply Fan
OPA PH
Machinery Room
40
TRANE
554604Y232
INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
60
AHU 6
Return Fan
OPA PH
Machinery Room
25
TRANE
552104Y232
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
61
AHU 5
Supply Fan
OPA PH
Machinery Room
60
TRANE
534904Y232
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
62
AHU 5
Return Fan
OPA PH
Machinery Room
30
TRANE
542904Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
63
AHU 18
Supply Fan
OPA PH
Machinery Room
25
TRANE
756504Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
64
AHU 18
Return Fan
OPA PH
Machinery Room
7.5
TRANE
751004Y262
INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
65
AHU 17
Supply Fan
OPA PH
Machinery Room
50
TRANE
755504Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
66
AHU 17
Return Fan
OPA PH
Machinery Room
15
TRANE
757504Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
67
AHU 7
Supply Fan
OPA PH
Machinery Room
60
TRANE
758404Y262
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
68
AHU 7
Return Fan
OPA PH
Machinery Room
25
TRANE
756404Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
69
AHU 52
Supply Fan
OPA PH Machinery Room
25
TRANE
756704Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
70
AHU 19
Supply Fan
OPA PH
Machinery Room
25
TRANE
756204Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: 5
KA RMS SYM. AT RATED INPUT V MAX.
71
AHU 19
Return Fan
OPA PH
Machinery Room
10
TRANE
751104Y262
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
72
AHU - 101
OPA PH
Machinery Room
3
TRANE
751704Y262
INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 3.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
73
AHU 8
Supply Fan
OPA PH
Machinery Room
60
TRANE
758504Y262
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
74
AHU 8
Return Fan
OPA PH
Machinery Room
25
TRANE
756604Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
75
AHU 21
Supply Fan
OPA PH
Machinery Room
25
TRANE
003207H422
INPUT: 3, 460 VAC, 60HZ, 34.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 34.0A FLA, POWER: 25HP, 18.5 KW
76
AHU 21
Return Fan
OPA PH
Machinery Room
7.5
TRANE
750904Y262
INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
77
AHU 20
Supply Fan
OPA PH
Machinery Room
25
TRANE
756804Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
78
AHU 20
Return Fan
OPA PH
Machinery Room
5
TRANE
751304Y262
INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
79
Cooling
Tower #1
OPA PH
Machinery Room
30
TRANE
542604Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
80
Cooling
Tower #2
OPA PH
Machinery Room
30
TRANE
543004Y233
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: 5
KA RMS SYM. AT RATED INPUT V MAX.
81
Cooling
Tower #3
OPA PH Machinery Room
30
TRANE
542804Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
82
Cooling
Tower #4
OPA PH
Machinery Room
30
TRANE
542704Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
83
Pump - 11
OPA Basement
Machinery Room
50
TRANE
562004Y082
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: 5
KA RMS SYM. AT RATED INPUT V MAX.
84
AHU 13
Supply Fan
OPA Basement
Machinery Room
10
TRANE
499704Y072
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
85
Pump - 7
OPA Basement
Machinery Room
60
TRANE
562204Y082
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
86
Pump - 8
OPA Basement
Machinery Room
60
TRANE
562104Y082
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
87
Pump - 9
OPA Basement
Machinery Room
20
TRANE
559504Y082
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
88
Pump - 10
OPA Basement
Machinery Room
20
TRANE
559404Y082
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
89
Pump - 18
OPA Basement
Machinery Room
15
TRANE
004007H442
INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW
90
Pump - 17
OPA Basement
Machinery Room
15
TRANE
003907H442
INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW
91
Pump - 16
OPA Basement
Machinery Room
40
TRANE
548804Y072
INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
92
AHU 5
Supply Fan
Admin Bldg. PH
Machinery Room
30
Johnson Controls
2103303731
45 A, 30HP, VOLT 480 VAC
93
AHU 5
Return Fan
Admin Bldg. PH
Machinery Room
10
Johnson Controls
2110102946
15.4 A, 10 HP, VOLT 480 VAC
94
AHU 4
Supply Fan
Admin Bldg. PH Machinery Room
40
Johnson Controls
2110100765
INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 58A
95
AHU 4
Return Fan
Admin Bldg. PH
Machinery Room
10
Johnson Controls
2122400934
15 A, 10 HP, VOLT 480 VAC
96
AHU 3
Supply Fan
Admin Bldg. PH
Machinery Room
40
Johnson Controls
2104002131
INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 58A
97
AHU 3
Return Fan
Admin Bldg. PH
Machinery Room
15
Johnson Controls
2105003602
15 A, 10 HP, VOLT 480 VAC
98
AHU 2
Supply Fan
Admin Bldg. PH
Machinery Room
40
Johnson Controls
2106200645
50 A, 40 HP, VOLT 480 VAC
99
AHU 2
Return Fan
Admin Bldg. PH
Machinery Room
10
Johnson Controls
S/N IS NOT CLEAR
VOLT: 460, AMP: 12.5, 60HZ, PHASE 3
100
AHU 1
Supply Fan
Admin Bldg.
Basement
Machinery Room
40
Johnson Controls
2105200639
INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 58A
101
AHU 1
Return Fan
Admin Bldg.
Basement
Machinery Room
10
Johnson Controls
Â
INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 15.4A
102
Supply Fan 8
Admin Bldg.
Basement
Machinery Room
7.5
ABB
Â
INPUT: 3PH 48 63 HZ, VOLTAGE(U1) 380 480 VAC, CURRENT(L1N) 11.9A
103
AHU - Breezeway
Bldg. 1 Roof
5
TRANE
569902G283
4.0KW(400V), 5.0HP(460), IN: 3X380-480V 50/60HZ 9.1/8.3A, OUT: 3X0-VIN 0-1000HZ 10/8.2A
104
EF - 88
Bldg. 1 Roof
15
DANFOSS
009833H397
11KW / 15HP, IN: 3X380-480V 50/60HZ 22/19A, OUT: 3X0-VIN 0-590HZ 24/21A
105
AHU - S2R
Bldg. 1 Roof
30
TRANE
658304Y144
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
106
AHU
Lineal Accelerator
A 1
CT Scan Bldg.
Roof
7.5
TRANE
861000Y085
INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
107
AHU
Lineal Accelerator
A 1A
CT Scan Bldg.
Roof
7.5
TRANE
789400Y075
INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
108
SF - 3
Bldg. 1
2nd Floor Roof
25
Johnson Controls
2093202587
VOLT: 460, AMPS: 30, 25HP, 60HZ
109
SF - 6
Bldg. 1 2nd Floor Roof
25
Johnson Controls
2093000437
VOLT: 460, AMPS: 30, 25HP, 60HZ
110
AHU - 10
Bldg. 1
2nd Floor Roof
Â
ABB
2154201314
VOLT: 277/480, 3 PHASE, 11.9A, 63HZ
111
SF - 4
Bldg. 1
2nd Floor Roof
25
Johnson Controls
2093000418
VOLT: 460, AMPS: 30, 25HP, 60HZ
112
SF - 5
Bldg. 1
2nd Floor Roof
25
Johnson Controls
2092800522
VOLT: 460, AMPS: 30, 25HP, 60HZ
113
AHU - 1
CLC 1st Floor
Machinery Room
15
TRANE
001329H215
IN: 3X200-240V 50/60HZ, 48.3A, OUT: 3X0-VIN 0.1-1000HZ, 48.3A, 11KW / 15HP
114
AHU - 2
CLC 2nd Floor
Machinery Room
25
TRANE
000529H205
IN: 3X200-240V 50/60HZ, 78.2A, OUT: 3X0-VIN 0.1-1000HZ, 78.2A, 18.5KW / 15HP
115
AHU - 3
CLC 1st Floor
Machinery Room
10
TRANE
000529H215
IN: 3X200-240V 50/60HZ, 32.2A, OUT: 3X0-VIN 0.1-1000HZ, 33A, 7.5KW / 10HP
116
AHU - 4
CLC 1st Floor
Machinery Room
5
TRANE
000429H205
IN: 3X200-240V 50/60HZ, 16.8A, OUT: 3X0-VIN 0.1-1000HZ, 17.6A, 3.7KW / 5HP
117
AHU-
Ambulatory
Surgery
Bldg.1 1st Floor
Roof
10
ABB
51737C0330
3-380 480V, 31A, 48 63HZ,10HP
118
Pump 10
Potable Water
Pump Room
25
TRANE
803204Y415
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
119
Pump 9
Potable Water
Pump Room
25
TRANE
Â
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
120
Pump 8
Potable Water
Pump Room
25
TRANE
Â
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
121
Pump 7
Potable Water
Pump Room
25
TRANE
803104Y415
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
122
Cooling
Tower 1
Main Chiller Plant
75
TRANE
614004Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
123
Cooling
Tower 2
Main Chiller Plant
75
TRANE
613904Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
124
Cooling
Tower 3
Main Chiller Plant
75
TRANE
613804Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
125
Cooling
Tower 4
Main Chiller Plant
75
TRANE
614104Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
126
Cooling
Tower 5
Main Chiller Plant
75
TRANE
613704Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
127
PUMP 1R
Main Chiller Plant
20
DANFOSS
007833H387
15KW/20HP, 50/60HZ, 29/25A
128
PUMP 2R
Main Chiller Plant
20
DANFOSS
295404Y407
15KW/20HP, 50/60HZ, 29/25A
129
PUMP 3R
Main Chiller Plant
20
DANFOSS
295604Y407
15KW/20HP, 50/60HZ, 29/25A
130
PUMP 4R
Main Chiller Plant
20
DANFOSS
295704Y407
15KW/20HP, 50/60HZ, 29/25A
131
PUMP 12R
Main Chiller Plant
150
TRANE
001203H255
110KW/150HP, 50/60HZ,204/183A
132
PUMP 10R
Main Chiller Plant
150
TRANE
001103H255
110KW/150HP, 50/60HZ,204/183A
133
PUMP 11R
Main Chiller Plant
150
TRANE
001003H255
110KW/150HP, 50/60HZ,204/183A
Are any of the VFDs damaged and what s their brand and capacity?
Answer to question 2:
OPA Building
AHU 15 Supply Fan 20 HP Out of service
AHU 53 Supply Fan 10 HP Out of Service
AHU 4 Return Fan 15 HP Out of service
AHU 17 Return Fan 15 HP Out of service
SBT Building
AHU 5 Supply Fan 30 HP Out of service
AHU 10 Supply Fan 40 HP Out of service
AHU 3 Return Fan 7.5 HP Out of service
AHU 1 Return Fan 7.5 HP Out of service
Hot Water Pump 2 15 HP Out of service
Main Building
Pump 7 Millionaires Tanks 25 HP Out of service
Pump 8 Millionaires Tanks 25 HP Out of service
Pump 9 Millionaires Tanks 25 HP Out of service
Pump 10 Millionaires Tanks 25 HP Out of service
Administration Building
AHU 1 Return Fan Out of service
Please provide the quantity of BCUs, UPCMs, MPs, FECs, NAEs, JACEs and Distech Controllers.
Answer to question 3:
Five Network Automation Engines or NAE.
Twenty three Field Equipment Controllers of FEC.
Forty nine FEC expansion cards.
One Java Application Control Engine or JACE.
Eleven Distech controllers 11.
Twenty nine Building Control Units or BCU.
Fifty four Universal Programable Control Modules or UPCMs.
One hundred and ninety-seven Multi-Purpose controllers or MP.
Three hundred and fifty five  MP expansion cards.
Please indicate if there are any of the above-mentioned controllers that are non-operational.
Answer to question 4:
One UPCM is out of service.
Please indicate if there are any of the above-mentioned controllers that are non-operational.
Answer to question 5:
           Yes, the contractor is responsible for any part that need replacement during the contract period.
Please indicate if calibrations will be allowed during normal working hours on all areas of the facilities or if the contractor will have to perform calibrations of sensitive areas during non-normal working hours.
Answer to question 6:
          Contractor will perform all recurring maintenance on scheduled with final customer systematically. Recurring
maintenance or calibrations shall not impact patientcare service. Contractor might need to work irregular
hours, weekends, holydays, etc. according to service department work schedule.
If calibrations are to be performed during other than normal working hours in sensitive areas please indicate which areas are deemed sensitive and how many calibration points can we assume in these areas?
            Answer to question 7:
SPS (20 points)
Operation Rooms (55 points)
Cardio (20 points)
Nuclear Medicine (10 points)
Multipurpose (10 points)
Outpatient Pharmacy (150 points)
Inpatient Pharmacy (20 points)
Laboratory (20 points)
Hemodialysis (24 points)
SICU (20 points)
Is an electrician required for this contract, to work with the VFD s?
                       Answer to question 8:
                                   Yes, a license electrician is required to work with any electrical circuits and VFDs.
Additional question:
           Given that Trane does not sell tracer summit products any more please indicate what will the
contractor need to do if a BCU or an MP581 or a UPCM becomes damaged and if the cost of
the solution will be the responsibility of the contractor.
           Answer:
           The contractor must submit recommendations for alternative solutions in case that parts are no longer
manufactured, cannot be found through retailers, and no equivalent is available as a direct replacement.Â
The government will evaluate the alternatives and will make decisions accordingly. Â
Update #1 ·
This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in Federal Acquisition Regulation (FAR) subpart 12.6, Streamlined Procedures for Evaluation and Solicitation for Commercial Items, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; quotes are being requested, and a written solicitation document will not be issued.
The solicitation number 36C24821Q0119 is issued as a Request for Quotation (RFQ). The incorporated provisions and clauses in this document are those in effect through Federal Acquisition Circular 2021-02, effective on 11-23-2020.
This solicitation will be competed using Tier Evaluation: 1st Tier- SDVOSB, 2nd Tier- VOSB and 3rd Tier- All Other Small Business (SB). The associated North American Industrial Classification System (NAICS) code for this procurement is 238220, with a small business size standard of $16.5 Million. The PSC is J041.
The Department of Veterans Affairs, Network Contracting Office -8 located at VA Caribbean Health System (VACHS), 10 Casia Street, Admin Building Suite 4M440, San Juan, Puerto Rico 00921 is seeking services to provide Preventive Maintenance and Repair for the Building Automation System (BAS) Services.
Detailed specifications and requirements are provided in the attached SCOPE OF WORK (SOW) Instructions to Quoters, Price/Cost Schedule, Clauses and Provisions.
The contract period of performance is expected to be from January 01, 2020 or date of award if later until December 31, 2021 plus four one-year option periods.
Place of Performance/Place of Delivery
Address: VA Caribbean Healthcare System: 10 Casia Street, San Juan, PR 00921
The full text of FAR provisions or clauses may be accessed electronically at https://www.acquisition.gov/browse/index/far
The following solicitation provisions apply to this acquisition:
1. FAR 52.212-1, Instructions to Quoters Commercial Items (Addendum attached)
2. FAR 52.212-3, Offerors Representations and Certifications Commercial Items
(www.sam.gov registration is required to be complete at time of submission of response)
Offerors must complete annual representations and certifications electronically via the System for Award Management (SAM) website located at https://www.sam.gov/SAM/ in accordance with FAR 52.212-3, Offerors Representations and Certifications Commercial Items. If paragraph (j) of the provision is applicable, a written submission is required.
The following contract clauses apply to this acquisition:
1. FAR 52.212-4, Contract Terms and Conditions Commercial Items (OCT 2018) (Addendum attached)
2. FAR 52.212-5, Contract Terms and Conditions Required to Implement Statutes or Executive Orders (OCT 2019)
Award will be based upon a comparative evaluation of quotes in accordance with the Simplified Acquisition Procedures of FAR 13. Comparative evaluation is the side by side pairwise comparison of quotes based on factors resulting in a Contracting Officer decision for the quote most favorable to the Government. Options will be evaluated at time of award.
The award will be made to the response most advantageous to the Government. Responses should contain your best terms, conditions. To facilitate the award process, all quotes must include a statement regarding the terms and conditions herein as follows:
"The terms and conditions in the solicitation are acceptable to be included in the award document without modification, deletion, or addition."
OR
"The terms and conditions in the solicitation are acceptable to be included in the award document with the exception, deletion, or addition of the following:"
Quoters shall list exception(s) and rationale for the exception(s), if any.
Questions submission shall be received not later than 10:00 AM AST on December 17, 2020 at Rafael.Rodriguez2@va.gov.
Submission of your response shall be received not later than 9:00 AM AST on December 26, 2020 at Rafael.Rodriguez2@va.gov.
Due to the COVID 19 pandemic, the Government will not be conducting site visits for this procurement action. This is done to avoid any contact with patients, personnel and visitors.
The quoter shall submit a PDF version of the quote to the Government. Late submissions shall be treated in accordance with the solicitation provision at FAR 52.212-1(f). Omission of any one item MAY result in a quoter package being deemed not technically acceptable.
Any questions or concerns regarding this solicitation should be forwarded in writing via e-mail to the Point of Contact listed below.
Point of Contact
Rafael Rodriguez, Contracting Officer, 787-641-7582 Ext. 34972 and email Rafael.Rodriguez2@va.gov
See attached document A: 36C24821Q0119- SOW
See attached document B: Schedule of Prices
See attached document C: Clauses and Provisions
See attached document D: Wage determination
Attachments
| File | Type | Posted |
|---|---|---|
| 36C24821Q0119_3.docx | DOCX document | |
| SCHEDULE A SOW BAS Services VACHS.pdf | ||
| Attachment D- WAGE DETERMINATION BAS Services PR.pdf | ||
| Attachment B SCHEDULE BAS 1.pdf | ||
| 36C24821Q0119_2.docx | DOCX document | |
| Attachment C Clauses and Provisions BAS Services revi 12 11.pdf |
Notice history
| Notice | Type | Posted |
|---|---|---|
| J041--Building Automation Services Long Term Contract | Award Notice | |
| J041--Building Automation Services | Solicitation | |
| J041--SERVICE: Building Automation Services | Pre-Solicitation |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity