36C24821Q0119_3.docx

DOCX document 48 KB Posted

Attached to
J041--Building Automation Services Federal contract opportunity
Solicitation number
36C24821Q0119
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This solicitation requests quotes for building automation system preventive maintenance and repair services. The Department of Veterans Affairs Network Contracting Office 8 seeks to provide services for the Building Automation System at the VA Caribbean Health System facilities in Puerto Rico. The small business set-aside contract would have a one-year base period of performance from January 2020 to December 2021 plus four one-year option periods. Quotes are due by December 26, 2020 with the award based on a best value determination. The solicitation applies FAR provisions for commercial item acquisitions and includes the statement of work, price schedule, clauses and provisions, and wage determination as attachments.

View the file

Other files for this federal contract opportunity

Other files attached to J041--Building Automation Services, newest first.
File Type Posted
SCHEDULE A SOW BAS Services VACHS.pdf PDF
Attachment D- WAGE DETERMINATION BAS Services PR.pdf PDF
Attachment B SCHEDULE BAS 1.pdf PDF
36C24821Q0119_2.docx DOCX document
Attachment C Clauses and Provisions BAS Services revi 12 11.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Contract Opportunity Amendment to a Previous Combined Solicitation

PRODUCT SERVICE CODE

SUBJECT

CONTRACTING OFFICE'S

ZIP-CODE

SOLICITATION NUMBER

BASE NOTICE TYPE

RESPONSE DATE/TIME/ZONE

ARCHIVE

DAYS AFTER THE RESPONSE DATE

RECOVERY ACT FUNDS

SET-ASIDE

NAICS CODE

CONTRACTING OFFICE

ADDRESS

POINT OF CONTACT

(POC Information Automatically Filled from User Profile Unless Entered)

DESCRIPTION

See Attachment

AGENCY'S URL

URL DESCRIPTION

AGENCY CONTACT'S EMAIL

ADDRESS

EMAIL DESCRIPTION

ADDRESS

POSTAL CODE

COUNTRY

ADDITIONAL INFORMATION

GENERAL INFORMATION

PLACE OF PERFORMANCE

* = Required Field Contract Opportunity Amendment to a Previous Combined Solicitation J041 Building Automation Services 00921-3201 36C24821Q0119 12-26-2020

10AM

EASTERN TIME, NEW YORK, USA

N 238220 Department of Veterans Affairs Network Contracting Office 8 (NCO 8) VA Caribbean HCS (Admin Bldg) #10 Calle Casia Suite #4M440 San Juan PR 00921-3201 Rafael Rodriguez 10 Casia Street San Juan

00921 Puerto Rico Rafael.Rodriguez2@va.gov COs e-mail

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer) 12/21/2020 None 36C248 Department of Veterans Affairs Network Contracting Office 8 (NCO 8) VA Caribbean HCS (Admin Bldg) #10 Calle Casia Suite #4M440 San Juan PR 00921-3201 36C248 Department of Veterans Affairs Network Contracting Office 8 (NCO 8) VA Caribbean HCS (Admin Bldg) #10 Calle Casia Suite #4M440 San Juan PR 00921-3201 To all Offerors/Bidders

36C24821Q0119 12-21-2020

X x Title; PM Building Automation System

1) Please refer to page number two (2) for answers from questions submitted by interested Contractors.

Rafael Rodriguez Contracting Officer

VA-VHA-2019-3C9E1171

1. Please provide the quantity of existing VFD’s to be included in the contract along with their brand and size in Horse Power Answer to question 1:

Variable Frequency Drive Inventory Table

Item
Unit
Location
Size
Brand
Serial no.
8
1
AHU 1

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797518
INPUT: 480V 3 Phase 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

2
AHU 1

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797514
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

3
AHU 2

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797506
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

4
AHU 2

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797376
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

5
AHU 3

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797512
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

6
AHU 3

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12807344
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

7
AHU 4

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797511
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

8
AHU 4

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797387
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

9
AHU 5

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797507
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

10
AHU 5

Return Fan

SBT

Machinery Room

10
Johnson Controls
12797193
INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT

: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

11
AHU 6

Supply Fan

SBT

Machinery Room

50
Johnson Controls
12797173
INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

12
AHU 6

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797436
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

13
AHU 7

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797503
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

14
AHU 7

Return Fan

SBT

Machinery Room

10
Johnson Controls
12797192
INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

15
AHU 8

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797501
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

16
AHU 8

Return Fan

SBT

Machinery Room

5
Johnson Controls
12797194
INPUT: 480V 3 PHASE 50/60HZ 7.6 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 7.6 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

17
AHU 9

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797515
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

18
AHU 9

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797517
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

19
AHU 10

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797509
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

20
AHU 10

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797504
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

21
AHU 11

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797510
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

22
AHU 11

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797370
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

23
AHU 12

Supply Fan

SBT

Machinery Room

40
Johnson Controls
12797505
INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

24
AHU 12

Return Fan

SBT

Machinery Room

7.5
Johnson Controls
12797390
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT

: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

25
Cooling

Tower #2

SBT

Machinery Room

50
Johnson Controls
12796894
INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

26
Cooling

Tower #1

SBT

Machinery Room

50
Johnson Controls
12796906
INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

27
IEF - 6
SBT

Machinery Room

7.5
Johnson Controls
12797166
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

28
IEF - 5
SBT

Machinery Room

7.5
Johnson Controls
12797179
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

29
IEF - 4
SBT

Machinery Room

3
Johnson Controls
12797196
INPUT: 480V 3 PHASE 50/60HZ 4.8 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 4.8 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

30
IEF - 3
SBT

Machinery Room

7.5
Johnson Controls
12797198
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

31
IEF - 2
SBT

Machinery Room

10
Johnson Controls
12797185
INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

32
IEF - 1
SBT

Machinery Room

7.5
Johnson Controls
12797195
INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

33
EF Outside Air
SBT

Machinery Room

15
EMERSON
B4015-21300
FREQUENCY IN/OUT 21 AFLC, VOLTS IN/OUT 460 VAC
34
Hot Water

Pump - 1

SBT

Machinery Room

20
Johnson Controls
12797213
INPUT: 480V 3 PHASE 50/60HZ 27 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 27 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

35
Hot Water

Pump - 2

SBT

Machinery Room

20
Johnson Controls
12890581
INTELLIPASS OPTIONS: 3, INPUT: 480VAC 50/60HZ 27A 3PH, OUTPUT: 0-480VAC 0-320HZ 27A 3PH, MAX HP:

20HP @ 480VAC 27A, CONTROL: 24VDC, MAX AMBIENT TEMP: 40 C, ENCLOSURE TYPE: 12, SHORT CIRCUIT

RATINGS: 65KA @ 480Y/277VAC, SCHEMATIC: 285447-1004

36
Cooling Tower

Pump - 1

SBT

Machinery Room

50
DANFOSS
293702Y407
INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT

RASTING: 5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F

37
Cooling Tower

Pump - 2

SBT

Machinery Room

50
DANFOSS
293502Y407
INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT RASTING:

5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F

38
Cooling Tower

Pump -3

SBT

Machinery Room

10
DANFOSS
315804Y407
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10 HP, 14.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

39
Chill Water

Pump - 1

SBT

Machinery Room

60
Johnson Controls
12797090
INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

40
Chill Water

Pump - 2

SBT

Machinery Room

60
Johnson Controls
12797112
INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT:

40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL

41
AHU 12

Supply Fan

OPA PH

Machinery Room

50
TRANE
755404Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

42
AHU 12

Return Fan

OPA PH

Machinery Room

15
TRANE
757804Y263
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

43
AHU 03

Supply Fan

OPA PH

Machinery Room

50
TRANE
755304Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

44
AHU 03

Return Fan

OPA PH

Machinery Room

15
TRANE
757704Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

45
AHU 04

Supply Fan

OPA PH

Machinery Room

40
TRANE
750204Y262
INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

46
AHU 04

Return Fan

OPA PH

Machinery Room

15
TRANE
757904Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

47
AHU - 100
OPA PH

Machinery Room

5
TRANE
751404Y262
INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

48
AHU 14

Supply Fan

OPA PH

Machinery Room

20
TRANE
757204Y262
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

49
AHU 14

Return Fan

OPA PH

Machinery Room

7.5
TRANE
750804Y262
INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

50
AHU - 4A
OPA PH

Machinery Room

3
TRANE
751604Y262
INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

51
AHU 16

Supply Fan

OPA PH

Machinery Room

50
TRANE
755204Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

52
AHU 16

Return Fan

OPA PH

Machinery Room

15
TRANE
757604Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

53
AHU 15

Supply Fan

OPA PH

Machinery Room

20
TRANE
757104Y262
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

54
AHU 15

Return Fan

OPA PH

Machinery Room

5
TRANE
751504Y262
INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

55
AHU 1

Supply Fan

OPA PH

Machinery Room

50
TRANE
755104Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

56
AHU 1

Return Fan

OPA PH

Machinery Room

20
TRANE
757304Y262
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

57
AHU 2

Supply Fan

OPA PH

Machinery Room

25
TRANE
756304Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

58
AHU 2

Return Fan

OPA PH

Machinery Room

10
TRANE
751204Y262
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

59
AHU 6

Supply Fan

OPA PH

Machinery Room

40
TRANE
554604Y232
INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

60
AHU 6

Return Fan

OPA PH

Machinery Room

25
TRANE
552104Y232
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

61
AHU 5

Supply Fan

OPA PH

Machinery Room

60
TRANE
534904Y232
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

62
AHU 5

Return Fan

OPA PH

Machinery Room

30
TRANE
542904Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

63
AHU 18

Supply Fan

OPA PH

Machinery Room

25
TRANE
756504Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

64
AHU 18

Return Fan

OPA PH

Machinery Room

7.5
TRANE
751004Y262
INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

65
AHU 17

Supply Fan

OPA PH

Machinery Room

50
TRANE
755504Y262
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

66
AHU 17

Return Fan

OPA PH

Machinery Room

15
TRANE
757504Y262
INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

67
AHU 7

Supply Fan

OPA PH

Machinery Room

60
TRANE
758404Y262
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

68
AHU 7

Return Fan

OPA PH

Machinery Room

25
TRANE
756404Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

69
AHU 52

Supply Fan

OPA PH

Machinery Room

25
TRANE
756704Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

70
AHU 19

Supply Fan

OPA PH

Machinery Room

25
TRANE
756204Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: 5

KA RMS SYM. AT RATED INPUT V MAX.

71
AHU 19

Return Fan

OPA PH

Machinery Room

10
TRANE
751104Y262
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

72
AHU - 101
OPA PH

Machinery Room

3
TRANE
751704Y262
INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 3.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

73
AHU 8

Supply Fan

OPA PH

Machinery Room

60
TRANE
758504Y262
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

74
AHU 8

Return Fan

OPA PH

Machinery Room

25
TRANE
756604Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

75
AHU 21

Supply Fan

OPA PH

Machinery Room

25
TRANE
003207H422
INPUT: 3, 460 VAC, 60HZ, 34.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 34.0A FLA, POWER: 25HP, 18.5 KW
76
AHU 21

Return Fan

OPA PH

Machinery Room

7.5
TRANE
750904Y262
INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

77
AHU 20

Supply Fan

OPA PH

Machinery Room

25
TRANE
756804Y262
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

78
AHU 20

Return Fan

OPA PH

Machinery Room

5
TRANE
751304Y262
INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

79
Cooling

Tower #1

OPA PH

Machinery Room

30
TRANE
542604Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

80
Cooling

Tower #2

OPA PH

Machinery Room

30
TRANE
543004Y233
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: 5

KA RMS SYM. AT RATED INPUT V MAX.

81
Cooling

Tower #3

OPA PH

Machinery Room

30
TRANE
542804Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

82
Cooling

Tower #4

OPA PH

Machinery Room

30
TRANE
542704Y232
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

83
Pump - 11
OPA Basement

Machinery Room

50
TRANE
562004Y082
INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: 5

KA RMS SYM. AT RATED INPUT V MAX.

84
AHU 13

Supply Fan OPA Basement Machinery Room

10
TRANE
499704Y072
INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

85
Pump - 7
OPA Basement

Machinery Room

60
TRANE
562204Y082
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

86
Pump - 8
OPA Basement

Machinery Room

60
TRANE
562104Y082
INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

87
Pump - 9
OPA Basement

Machinery Room

20
TRANE
559504Y082
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

88
Pump - 10
OPA Basement

Machinery Room

20
TRANE
559404Y082
INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

89
Pump - 18
OPA Basement

Machinery Room

15
TRANE
004007H442
INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW
90
Pump - 17
OPA Basement

Machinery Room

15
TRANE
003907H442
INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW
91
Pump - 16
OPA Basement

Machinery Room

40
TRANE
548804Y072
INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

92
AHU 5

Supply Fan Admin Bldg. PH Machinery Room

30
Johnson Controls
2103303731
45 A, 30HP, VOLT 480 VAC
93
AHU 5

Return Fan Admin Bldg. PH Machinery Room

10
Johnson Controls
2110102946
15.4 A, 10 HP, VOLT 480 VAC
94
AHU 4

Supply Fan Admin Bldg. PH Machinery Room

40
Johnson Controls
2110100765
INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 58A
95
AHU 4

Return Fan Admin Bldg. PH Machinery Room

10
Johnson Controls
2122400934
15 A, 10 HP, VOLT 480 VAC
96
AHU 3

Supply Fan Admin Bldg. PH Machinery Room

40
Johnson Controls
2104002131
INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 58A
97
AHU 3

Return Fan Admin Bldg. PH Machinery Room

15
Johnson Controls
2105003602
15 A, 10 HP, VOLT 480 VAC
98
AHU 2

Supply Fan Admin Bldg. PH Machinery Room

40
Johnson Controls
2106200645
50 A, 40 HP, VOLT 480 VAC
99
AHU 2

Return Fan Admin Bldg. PH Machinery Room

10
Johnson Controls
S/N IS NOT CLEAR
VOLT: 460, AMP: 12.5, 60HZ, PHASE 3
100
AHU 1

Supply Fan Admin Bldg.

Basement Machinery Room

40
Johnson Controls
2105200639
INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 58A
101
AHU 1

Return Fan Admin Bldg.

Basement Machinery Room

10
Johnson Controls

INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 15.4A

102
Supply Fan 8
Admin Bldg.

Basement Machinery Room

7.5
ABB

INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 11.9A

103
AHU - Breezeway
Bldg. 1 Roof
5
TRANE
569902G283
4.0KW(400V), 5.0HP(460), IN: 3X380-480V 50/60HZ 9.1/8.3A, OUT: 3X0-VIN 0-1000HZ 10/8.2A
104
EF - 88
Bldg. 1 Roof
15
DANFOSS
009833H397
11KW / 15HP, IN: 3X380-480V 50/60HZ 22/19A, OUT: 3X0-VIN 0-590HZ 24/21A
105
AHU - S2R
Bldg. 1 Roof
30
TRANE
658304Y144
INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

106
AHU

Lineal Accelerator A 1 CT Scan Bldg.

Roof

7.5
TRANE
861000Y085
INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

107
AHU

Lineal Accelerator A 1A CT Scan Bldg.

Roof

7.5
TRANE
789400Y075
INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

108
SF - 3
Bldg. 1

2nd Floor Roof

25
Johnson Controls
2093202587
VOLT: 460, AMPS: 30, 25HP, 60HZ
109
SF - 6
Bldg. 1

2nd Floor Roof

25
Johnson Controls
2093000437
VOLT: 460, AMPS: 30, 25HP, 60HZ
110
AHU - 10
Bldg. 1

2nd Floor Roof

ABB
2154201314
VOLT: 277/480, 3 PHASE, 11.9A, 63HZ
111
SF - 4
Bldg. 1

2nd Floor Roof

25
Johnson Controls
2093000418
VOLT: 460, AMPS: 30, 25HP, 60HZ
112
SF - 5
Bldg. 1

2nd Floor Roof

25
Johnson Controls
2092800522
VOLT: 460, AMPS: 30, 25HP, 60HZ
113
AHU - 1
CLC 1st Floor

Machinery Room

15
TRANE
001329H215
IN: 3X200-240V 50/60HZ, 48.3A, OUT: 3X0-VIN 0.1-1000HZ, 48.3A, 11KW / 15HP
114
AHU - 2
CLC 2nd Floor

Machinery Room

25
TRANE
000529H205
IN: 3X200-240V 50/60HZ, 78.2A, OUT: 3X0-VIN 0.1-1000HZ, 78.2A, 18.5KW / 15HP
115
AHU - 3
CLC 1st Floor

Machinery Room

10
TRANE
000529H215
IN: 3X200-240V 50/60HZ, 32.2A, OUT: 3X0-VIN 0.1-1000HZ, 33A, 7.5KW / 10HP
116
AHU - 4
CLC 1st Floor

Machinery Room

5
TRANE
000429H205
IN: 3X200-240V 50/60HZ, 16.8A, OUT: 3X0-VIN 0.1-1000HZ, 17.6A, 3.7KW / 5HP
117
AHU-

Ambulatory Surgery Bldg.1 1st Floor Roof

10
ABB
51737C0330
3-380…480V, 31A, 48…63HZ,10HP
118
Pump 10
Potable Water

Pump Room

25
TRANE
803204Y415
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

119
Pump 9
Potable Water

Pump Room

25
TRANE

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

120
Pump 8
Potable Water

Pump Room

25
TRANE

INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

121
Pump 7
Potable Water

Pump Room

25
TRANE
803104Y415
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

122
Cooling

Tower 1

Main Chiller Plant
75
TRANE
614004Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

123
Cooling

Tower 2

Main Chiller Plant
75
TRANE
613904Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

124
Cooling

Tower 3

Main Chiller Plant
75
TRANE
613804Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

125
Cooling

Tower 4

Main Chiller Plant
75
TRANE
614104Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

126
Cooling

Tower 5

Main Chiller Plant
75
TRANE
613704Y111
INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING:

5KA RMS SYM. AT RATED INPUT V MAX.

127
PUMP 1R
Main Chiller Plant
20
DANFOSS
007833H387
15KW/20HP, 50/60HZ, 29/25A
128
PUMP 2R
Main Chiller Plant
20
DANFOSS
295404Y407
15KW/20HP, 50/60HZ, 29/25A
129
PUMP 3R
Main Chiller Plant
20
DANFOSS
295604Y407
15KW/20HP, 50/60HZ, 29/25A
130
PUMP 4R
Main Chiller Plant
20
DANFOSS
295704Y407
15KW/20HP, 50/60HZ, 29/25A
131
PUMP 12R
Main Chiller Plant
150
TRANE
001203H255
110KW/150HP, 50/60HZ,204/183A
132
PUMP 10R
Main Chiller Plant
150
TRANE
001103H255
110KW/150HP, 50/60HZ,204/183A
133
PUMP 11R
Main Chiller Plant
150
TRANE
001003H255
110KW/150HP, 50/60HZ,204/183A

1. Are any of the VFDs damaged and what’s their brand and capacity?

Answer to question 2:

1. OPA Building

0. AHU 15 Supply Fan 20 HP Out of service

0. AHU 53 Supply Fan 10 HP Out of Service

0. AHU 4 Return Fan 15 HP Out of service

0. AHU 17 Return Fan 15 HP Out of service

1. SBT Building

1. AHU 5 Supply Fan 30 HP Out of service

1. AHU 10 Supply Fan 40 HP Out of service

1. AHU 3 Return Fan 7.5 HP Out of service

1. AHU 1 Return Fan 7.5 HP Out of service

1. Hot Water Pump 2 15 HP Out of service

1. Main Building

2. Pump 7 Millionaires Tanks 25 HP Out of service

2. Pump 8 Millionaires Tanks 25 HP Out of service

2. Pump 9 Millionaires Tanks 25 HP Out of service

2. Pump 10 Millionaires Tanks 25 HP Out of service

1. Administration Building

3. AHU 1 Return Fan Out of service

1. Please provide the quantity of BCUs, UPCMs, MPs, FECs, NAEs, JACEs and Distech Controllers.

Answer to question 3:

1. Five Network Automation Engines or NAE.

1. Twenty three Field Equipment Controllers of FEC.

1. Forty nine FEC expansion cards.

1. One Java Application Control Engine or JACE.

1. Eleven Distech controllers 11.

1. Twenty nine Building Control Units or BCU.

1. Fifty four Universal Programable Control Modules or UPCMs.

1. One hundred and ninety-seven Multi-Purpose controllers or MP.

1. Three hundred and fifty five MP expansion cards.

1. Please indicate if there are any of the above-mentioned controllers that are non-operational.

Answer to question 4:

1. One UPCM is out of service.

1. Please indicate if there are any of the above-mentioned controllers that are non-operational.

Answer to question 5:

Yes, the contractor is responsible for any part that need replacement during the contract period.

1. Please indicate if calibrations will be allowed during normal working hours on all areas of the facilities or if the contractor will have to perform calibrations of sensitive areas during non-normal working hours.

Answer to question 6:

Contractor will perform all recurring maintenance on scheduled with final customer systematically. Recurring maintenance or calibrations shall not impact patientcare service. Contractor might need to work irregular hours, weekends, holydays, etc. according to service department work schedule.

1. If calibrations are to be performed during other than normal working hours in sensitive areas please indicate which areas are deemed sensitive and how many calibration points can we assume in these areas?

Answer to question 7:

1. SPS (20 points)

1. Operation Rooms (55 points)

1. Cardio (20 points)

1. Nuclear Medicine (10 points)

1. Multipurpose (10 points)

1. Outpatient Pharmacy (150 points)

1. Inpatient Pharmacy (20 points)

1. Laboratory (20 points)

1. Hemodialysis (24 points)

1. SICU (20 points)

1. Is an electrician required for this contract, to work with the VFD’s?

Answer to question 8:

Yes, a license electrician is required to work with any electrical circuits and VFDs.

Additional question:

Given that Trane does not sell tracer summit products any more please indicate what will the contractor need to do if a BCU or an MP581 or a UPCM becomes damaged and if the cost of the solution will be the responsibility of the contractor.

Answer:

The contractor must submit recommendations for alternative solutions in case that parts are no longer manufactured, cannot be found through retailers, and no equivalent is available as a direct replacement.

The government will evaluate the alternatives and will make decisions accordingly.

File details come from the government source that posted it. Updated .