36C24821Q0119_3.docx
DOCX document 48 KB Posted
- Attached to
- J041--Building Automation Services Federal contract opportunity
- Solicitation number
- 36C24821Q0119
About this file
This solicitation requests quotes for building automation system preventive maintenance and repair services. The Department of Veterans Affairs Network Contracting Office 8 seeks to provide services for the Building Automation System at the VA Caribbean Health System facilities in Puerto Rico. The small business set-aside contract would have a one-year base period of performance from January 2020 to December 2021 plus four one-year option periods. Quotes are due by December 26, 2020 with the award based on a best value determination. The solicitation applies FAR provisions for commercial item acquisitions and includes the statement of work, price schedule, clauses and provisions, and wage determination as attachments.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SCHEDULE A SOW BAS Services VACHS.pdf | ||
| Attachment D- WAGE DETERMINATION BAS Services PR.pdf | ||
| Attachment B SCHEDULE BAS 1.pdf | ||
| 36C24821Q0119_2.docx | DOCX document | |
| Attachment C Clauses and Provisions BAS Services revi 12 11.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Contract Opportunity Amendment to a Previous Combined Solicitation
PRODUCT SERVICE CODE
SUBJECT
CONTRACTING OFFICE'S
ZIP-CODE
SOLICITATION NUMBER
BASE NOTICE TYPE
RESPONSE DATE/TIME/ZONE
ARCHIVE
DAYS AFTER THE RESPONSE DATE
RECOVERY ACT FUNDS
SET-ASIDE
NAICS CODE
CONTRACTING OFFICE
ADDRESS
POINT OF CONTACT
(POC Information Automatically Filled from User Profile Unless Entered)
DESCRIPTION
See Attachment
AGENCY'S URL
URL DESCRIPTION
AGENCY CONTACT'S EMAIL
ADDRESS
EMAIL DESCRIPTION
ADDRESS
POSTAL CODE
COUNTRY
ADDITIONAL INFORMATION
GENERAL INFORMATION
PLACE OF PERFORMANCE
* = Required Field Contract Opportunity Amendment to a Previous Combined Solicitation J041 Building Automation Services 00921-3201 36C24821Q0119 12-26-2020
10AM
EASTERN TIME, NEW YORK, USA
N 238220 Department of Veterans Affairs Network Contracting Office 8 (NCO 8) VA Caribbean HCS (Admin Bldg) #10 Calle Casia Suite #4M440 San Juan PR 00921-3201 Rafael Rodriguez 10 Casia Street San Juan
00921 Puerto Rico Rafael.Rodriguez2@va.gov COs e-mail
5. PROJECT NUMBER (if applicable)
CODE
7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER
3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO.
1. CONTRACT ID CODE
FACILITY CODE
CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office.
is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER
16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30
PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer) 12/21/2020 None 36C248 Department of Veterans Affairs Network Contracting Office 8 (NCO 8) VA Caribbean HCS (Admin Bldg) #10 Calle Casia Suite #4M440 San Juan PR 00921-3201 36C248 Department of Veterans Affairs Network Contracting Office 8 (NCO 8) VA Caribbean HCS (Admin Bldg) #10 Calle Casia Suite #4M440 San Juan PR 00921-3201 To all Offerors/Bidders
36C24821Q0119 12-21-2020
X x Title; PM Building Automation System
1) Please refer to page number two (2) for answers from questions submitted by interested Contractors.
Rafael Rodriguez Contracting Officer
VA-VHA-2019-3C9E1171
1. Please provide the quantity of existing VFD’s to be included in the contract along with their brand and size in Horse Power Answer to question 1:
Variable Frequency Drive Inventory Table
| Item |
| Unit |
| Location |
| Size |
| Brand |
| Serial no. |
| 8 |
| 1 |
| AHU 1 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797518 |
| INPUT: 480V 3 Phase 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 2 |
| AHU 1 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797514 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 3 |
| AHU 2 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797506 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 4 |
| AHU 2 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797376 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 5 |
| AHU 3 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797512 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 6 |
| AHU 3 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12807344 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 7 |
| AHU 4 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797511 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 8 |
| AHU 4 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797387 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 9 |
| AHU 5 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797507 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 10 |
| AHU 5 |
Return Fan
SBT
Machinery Room
| 10 |
| Johnson Controls |
| 12797193 |
| INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT |
: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 11 |
| AHU 6 |
Supply Fan
SBT
Machinery Room
| 50 |
| Johnson Controls |
| 12797173 |
| INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 12 |
| AHU 6 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797436 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 13 |
| AHU 7 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797503 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 14 |
| AHU 7 |
Return Fan
SBT
Machinery Room
| 10 |
| Johnson Controls |
| 12797192 |
| INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 15 |
| AHU 8 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797501 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 16 |
| AHU 8 |
Return Fan
SBT
Machinery Room
| 5 |
| Johnson Controls |
| 12797194 |
| INPUT: 480V 3 PHASE 50/60HZ 7.6 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 7.6 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 17 |
| AHU 9 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797515 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 18 |
| AHU 9 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797517 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 19 |
| AHU 10 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797509 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 20 |
| AHU 10 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797504 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 21 |
| AHU 11 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797510 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 22 |
| AHU 11 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797370 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 23 |
| AHU 12 |
Supply Fan
SBT
Machinery Room
| 40 |
| Johnson Controls |
| 12797505 |
| INPUT: 480V 3 PHASE 50/60HZ 52 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 52 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 24 |
| AHU 12 |
Return Fan
SBT
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797390 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT |
: 40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 25 |
| Cooling |
Tower #2
SBT
Machinery Room
| 50 |
| Johnson Controls |
| 12796894 |
| INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 26 |
| Cooling |
Tower #1
SBT
Machinery Room
| 50 |
| Johnson Controls |
| 12796906 |
| INPUT: 480V 3 PHASE 50/60HZ 65 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 65 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 27 |
| IEF - 6 |
| SBT |
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797166 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 28 |
| IEF - 5 |
| SBT |
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797179 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 29 |
| IEF - 4 |
| SBT |
Machinery Room
| 3 |
| Johnson Controls |
| 12797196 |
| INPUT: 480V 3 PHASE 50/60HZ 4.8 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 4.8 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 30 |
| IEF - 3 |
| SBT |
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797198 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 31 |
| IEF - 2 |
| SBT |
Machinery Room
| 10 |
| Johnson Controls |
| 12797185 |
| INPUT: 480V 3 PHASE 50/60HZ 14 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 14 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 32 |
| IEF - 1 |
| SBT |
Machinery Room
| 7.5 |
| Johnson Controls |
| 12797195 |
| INPUT: 480V 3 PHASE 50/60HZ 11 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 11 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 33 |
| EF Outside Air |
| SBT |
Machinery Room
| 15 |
| EMERSON |
| B4015-21300 |
| FREQUENCY IN/OUT 21 AFLC, VOLTS IN/OUT 460 VAC |
| 34 |
| Hot Water |
Pump - 1
SBT
Machinery Room
| 20 |
| Johnson Controls |
| 12797213 |
| INPUT: 480V 3 PHASE 50/60HZ 27 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 27 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 35 |
| Hot Water |
Pump - 2
SBT
Machinery Room
| 20 |
| Johnson Controls |
| 12890581 |
| INTELLIPASS OPTIONS: 3, INPUT: 480VAC 50/60HZ 27A 3PH, OUTPUT: 0-480VAC 0-320HZ 27A 3PH, MAX HP: |
20HP @ 480VAC 27A, CONTROL: 24VDC, MAX AMBIENT TEMP: 40 C, ENCLOSURE TYPE: 12, SHORT CIRCUIT
RATINGS: 65KA @ 480Y/277VAC, SCHEMATIC: 285447-1004
| 36 |
| Cooling Tower |
Pump - 1
SBT
Machinery Room
| 50 |
| DANFOSS |
| 293702Y407 |
| INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT |
RASTING: 5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F
| 37 |
| Cooling Tower |
Pump - 2
SBT
Machinery Room
| 50 |
| DANFOSS |
| 293502Y407 |
| INPUT: 3, 460 VAC, 60HZ, 65 A, OUTPUT: 3, 0-460 VAC, 0-60HZ, 65A, POWER 50 HP, 37 KW, SHORT CIRCUIT RASTING: |
5KA RMS SYM. AT RATED INPUT V MAX., MAX. AMBIENT: 40 C/ 104 F, MIN AMBIENT: -10C / 14F
| 38 |
| Cooling Tower |
Pump -3
SBT
Machinery Room
| 10 |
| DANFOSS |
| 315804Y407 |
| INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10 HP, 14.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 39 |
| Chill Water |
Pump - 1
SBT
Machinery Room
| 60 |
| Johnson Controls |
| 12797090 |
| INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 40 |
| Chill Water |
Pump - 2
SBT
Machinery Room
| 60 |
| Johnson Controls |
| 12797112 |
| INPUT: 480V 3 PHASE 50/60HZ 77 A RMS OUTPUT: 0 TO 480V 3 PHASE 1 TO 320 HZ 77 A RMS MAX AMBIENT: |
40 DEG. C OVERLOAD: 1.10 ENCLOSURE: NEMA TYPE 12W / INTELLIPASS MANUFACTURE BY EATON ELECTRICAL
| 41 |
| AHU 12 |
Supply Fan
OPA PH
Machinery Room
| 50 |
| TRANE |
| 755404Y262 |
| INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 42 |
| AHU 12 |
Return Fan
OPA PH
Machinery Room
| 15 |
| TRANE |
| 757804Y263 |
| INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 43 |
| AHU 03 |
Supply Fan
OPA PH
Machinery Room
| 50 |
| TRANE |
| 755304Y262 |
| INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 44 |
| AHU 03 |
Return Fan
OPA PH
Machinery Room
| 15 |
| TRANE |
| 757704Y262 |
| INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 45 |
| AHU 04 |
Supply Fan
OPA PH
Machinery Room
| 40 |
| TRANE |
| 750204Y262 |
| INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 46 |
| AHU 04 |
Return Fan
OPA PH
Machinery Room
| 15 |
| TRANE |
| 757904Y262 |
| INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 47 |
| AHU - 100 |
| OPA PH |
Machinery Room
| 5 |
| TRANE |
| 751404Y262 |
| INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 48 |
| AHU 14 |
Supply Fan
OPA PH
Machinery Room
| 20 |
| TRANE |
| 757204Y262 |
| INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 49 |
| AHU 14 |
Return Fan
OPA PH
Machinery Room
| 7.5 |
| TRANE |
| 750804Y262 |
| INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 50 |
| AHU - 4A |
| OPA PH |
Machinery Room
| 3 |
| TRANE |
| 751604Y262 |
| INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 51 |
| AHU 16 |
Supply Fan
OPA PH
Machinery Room
| 50 |
| TRANE |
| 755204Y262 |
| INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 52 |
| AHU 16 |
Return Fan
OPA PH
Machinery Room
| 15 |
| TRANE |
| 757604Y262 |
| INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 53 |
| AHU 15 |
Supply Fan
OPA PH
Machinery Room
| 20 |
| TRANE |
| 757104Y262 |
| INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 54 |
| AHU 15 |
Return Fan
OPA PH
Machinery Room
| 5 |
| TRANE |
| 751504Y262 |
| INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 55 |
| AHU 1 |
Supply Fan
OPA PH
Machinery Room
| 50 |
| TRANE |
| 755104Y262 |
| INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 56 |
| AHU 1 |
Return Fan
OPA PH
Machinery Room
| 20 |
| TRANE |
| 757304Y262 |
| INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 57 |
| AHU 2 |
Supply Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756304Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 58 |
| AHU 2 |
Return Fan
OPA PH
Machinery Room
| 10 |
| TRANE |
| 751204Y262 |
| INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 59 |
| AHU 6 |
Supply Fan
OPA PH
Machinery Room
| 40 |
| TRANE |
| 554604Y232 |
| INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 60 |
| AHU 6 |
Return Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 552104Y232 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 61 |
| AHU 5 |
Supply Fan
OPA PH
Machinery Room
| 60 |
| TRANE |
| 534904Y232 |
| INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 62 |
| AHU 5 |
Return Fan
OPA PH
Machinery Room
| 30 |
| TRANE |
| 542904Y232 |
| INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 63 |
| AHU 18 |
Supply Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756504Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 64 |
| AHU 18 |
Return Fan
OPA PH
Machinery Room
| 7.5 |
| TRANE |
| 751004Y262 |
| INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 65 |
| AHU 17 |
Supply Fan
OPA PH
Machinery Room
| 50 |
| TRANE |
| 755504Y262 |
| INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 66 |
| AHU 17 |
Return Fan
OPA PH
Machinery Room
| 15 |
| TRANE |
| 757504Y262 |
| INPUT POWER: 480 VAC, 21.3 A, 3, 60HZ, MOTOR: 460 VAC, 15.00 HP, 21.0 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 67 |
| AHU 7 |
Supply Fan
OPA PH
Machinery Room
| 60 |
| TRANE |
| 758404Y262 |
| INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 68 |
| AHU 7 |
Return Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756404Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 69 |
| AHU 52 |
Supply Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756704Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 70 |
| AHU 19 |
Supply Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756204Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: 5 |
KA RMS SYM. AT RATED INPUT V MAX.
| 71 |
| AHU 19 |
Return Fan
OPA PH
Machinery Room
| 10 |
| TRANE |
| 751104Y262 |
| INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 72 |
| AHU - 101 |
| OPA PH |
Machinery Room
| 3 |
| TRANE |
| 751704Y262 |
| INPUT POWER: 480 VAC, 5.1 A, 3, 60HZ, MOTOR: 460 VAC, 3.00 HP, 5.1 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 73 |
| AHU 8 |
Supply Fan
OPA PH
Machinery Room
| 60 |
| TRANE |
| 758504Y262 |
| INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 74 |
| AHU 8 |
Return Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756604Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 75 |
| AHU 21 |
Supply Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 003207H422 |
| INPUT: 3, 460 VAC, 60HZ, 34.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 34.0A FLA, POWER: 25HP, 18.5 KW |
| 76 |
| AHU 21 |
Return Fan
OPA PH
Machinery Room
| 7.5 |
| TRANE |
| 750904Y262 |
| INPUT POWER: 480 VAC, 11.3 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 11.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 77 |
| AHU 20 |
Supply Fan
OPA PH
Machinery Room
| 25 |
| TRANE |
| 756804Y262 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 78 |
| AHU 20 |
Return Fan
OPA PH
Machinery Room
| 5 |
| TRANE |
| 751304Y262 |
| INPUT POWER: 480 VAC, 7.9 A, 3, 60HZ, MOTOR: 460 VAC, 5.00 HP, 7.9 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 79 |
| Cooling |
Tower #1
OPA PH
Machinery Room
| 30 |
| TRANE |
| 542604Y232 |
| INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 80 |
| Cooling |
Tower #2
OPA PH
Machinery Room
| 30 |
| TRANE |
| 543004Y233 |
| INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: 5 |
KA RMS SYM. AT RATED INPUT V MAX.
| 81 |
| Cooling |
Tower #3
OPA PH
Machinery Room
| 30 |
| TRANE |
| 542804Y232 |
| INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 82 |
| Cooling |
Tower #4
OPA PH
Machinery Room
| 30 |
| TRANE |
| 542704Y232 |
| INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 83 |
| Pump - 11 |
| OPA Basement |
Machinery Room
| 50 |
| TRANE |
| 562004Y082 |
| INPUT POWER: 480 VAC, 65.6 A, 3, 60HZ, MOTOR: 460 VAC, 50.00 HP, 65.0 A, 3, 60HZ, SHORT CIRCUIT RATING: 5 |
KA RMS SYM. AT RATED INPUT V MAX.
| 84 |
| AHU 13 |
Supply Fan OPA Basement Machinery Room
| 10 |
| TRANE |
| 499704Y072 |
| INPUT POWER: 480 VAC, 14.3 A, 3, 60HZ, MOTOR: 460 VAC, 10.00 HP, 14.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 85 |
| Pump - 7 |
| OPA Basement |
Machinery Room
| 60 |
| TRANE |
| 562204Y082 |
| INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 86 |
| Pump - 8 |
| OPA Basement |
Machinery Room
| 60 |
| TRANE |
| 562104Y082 |
| INPUT POWER: 480 VAC, 77.6 A, 3, 60HZ, MOTOR: 460 VAC, 60.00 HP, 77.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 87 |
| Pump - 9 |
| OPA Basement |
Machinery Room
| 20 |
| TRANE |
| 559504Y082 |
| INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 88 |
| Pump - 10 |
| OPA Basement |
Machinery Room
| 20 |
| TRANE |
| 559404Y082 |
| INPUT POWER: 480 VAC, 27.3 A, 3, 60HZ, MOTOR: 460 VAC, 20.00 HP, 27.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 89 |
| Pump - 18 |
| OPA Basement |
Machinery Room
| 15 |
| TRANE |
| 004007H442 |
| INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW |
| 90 |
| Pump - 17 |
| OPA Basement |
Machinery Room
| 15 |
| TRANE |
| 003907H442 |
| INPUT: 3, 460 VAC, 60HZ, 21.0A FLA, OUTPUT: 3, 3-460 VAC, 0-60 HZ, 21.0A FLA, POWER: 15HP, 18.5 KW |
| 91 |
| Pump - 16 |
| OPA Basement |
Machinery Room
| 40 |
| TRANE |
| 548804Y072 |
| INPUT POWER: 480 VAC, 52.6 A, 3, 60HZ, MOTOR: 460 VAC, 40.00 HP, 52.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 92 |
| AHU 5 |
Supply Fan Admin Bldg. PH Machinery Room
| 30 |
| Johnson Controls |
| 2103303731 |
| 45 A, 30HP, VOLT 480 VAC |
| 93 |
| AHU 5 |
Return Fan Admin Bldg. PH Machinery Room
| 10 |
| Johnson Controls |
| 2110102946 |
| 15.4 A, 10 HP, VOLT 480 VAC |
| 94 |
| AHU 4 |
Supply Fan Admin Bldg. PH Machinery Room
| 40 |
| Johnson Controls |
| 2110100765 |
| INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 58A |
| 95 |
| AHU 4 |
Return Fan Admin Bldg. PH Machinery Room
| 10 |
| Johnson Controls |
| 2122400934 |
| 15 A, 10 HP, VOLT 480 VAC |
| 96 |
| AHU 3 |
Supply Fan Admin Bldg. PH Machinery Room
| 40 |
| Johnson Controls |
| 2104002131 |
| INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 58A |
| 97 |
| AHU 3 |
Return Fan Admin Bldg. PH Machinery Room
| 15 |
| Johnson Controls |
| 2105003602 |
| 15 A, 10 HP, VOLT 480 VAC |
| 98 |
| AHU 2 |
Supply Fan Admin Bldg. PH Machinery Room
| 40 |
| Johnson Controls |
| 2106200645 |
| 50 A, 40 HP, VOLT 480 VAC |
| 99 |
| AHU 2 |
Return Fan Admin Bldg. PH Machinery Room
| 10 |
| Johnson Controls |
| S/N IS NOT CLEAR |
| VOLT: 460, AMP: 12.5, 60HZ, PHASE 3 |
| 100 |
| AHU 1 |
Supply Fan Admin Bldg.
Basement Machinery Room
| 40 |
| Johnson Controls |
| 2105200639 |
| INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 58A |
| 101 |
| AHU 1 |
Return Fan Admin Bldg.
Basement Machinery Room
| 10 |
| Johnson Controls |
INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 15.4A
| 102 |
| Supply Fan 8 |
| Admin Bldg. |
Basement Machinery Room
| 7.5 |
| ABB |
INPUT: 3PH 48…63 HZ, VOLTAGE(U1) 380…480 VAC, CURRENT(L1N) 11.9A
| 103 |
| AHU - Breezeway |
| Bldg. 1 Roof |
| 5 |
| TRANE |
| 569902G283 |
| 4.0KW(400V), 5.0HP(460), IN: 3X380-480V 50/60HZ 9.1/8.3A, OUT: 3X0-VIN 0-1000HZ 10/8.2A |
| 104 |
| EF - 88 |
| Bldg. 1 Roof |
| 15 |
| DANFOSS |
| 009833H397 |
| 11KW / 15HP, IN: 3X380-480V 50/60HZ 22/19A, OUT: 3X0-VIN 0-590HZ 24/21A |
| 105 |
| AHU - S2R |
| Bldg. 1 Roof |
| 30 |
| TRANE |
| 658304Y144 |
| INPUT POWER: 480 VAC, 40.6 A, 3, 60HZ, MOTOR: 460 VAC, 30.00 HP, 40.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 106 |
| AHU |
Lineal Accelerator A 1 CT Scan Bldg.
Roof
| 7.5 |
| TRANE |
| 861000Y085 |
| INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 107 |
| AHU |
Lineal Accelerator A 1A CT Scan Bldg.
Roof
| 7.5 |
| TRANE |
| 789400Y075 |
| INPUT POWER: 480 VAC, 10.6 A, 3, 60HZ, MOTOR: 460 VAC, 7.5.00 HP, 10.6 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 108 |
| SF - 3 |
| Bldg. 1 |
2nd Floor Roof
| 25 |
| Johnson Controls |
| 2093202587 |
| VOLT: 460, AMPS: 30, 25HP, 60HZ |
| 109 |
| SF - 6 |
| Bldg. 1 |
2nd Floor Roof
| 25 |
| Johnson Controls |
| 2093000437 |
| VOLT: 460, AMPS: 30, 25HP, 60HZ |
| 110 |
| AHU - 10 |
| Bldg. 1 |
2nd Floor Roof
| ABB |
| 2154201314 |
| VOLT: 277/480, 3 PHASE, 11.9A, 63HZ |
| 111 |
| SF - 4 |
| Bldg. 1 |
2nd Floor Roof
| 25 |
| Johnson Controls |
| 2093000418 |
| VOLT: 460, AMPS: 30, 25HP, 60HZ |
| 112 |
| SF - 5 |
| Bldg. 1 |
2nd Floor Roof
| 25 |
| Johnson Controls |
| 2092800522 |
| VOLT: 460, AMPS: 30, 25HP, 60HZ |
| 113 |
| AHU - 1 |
| CLC 1st Floor |
Machinery Room
| 15 |
| TRANE |
| 001329H215 |
| IN: 3X200-240V 50/60HZ, 48.3A, OUT: 3X0-VIN 0.1-1000HZ, 48.3A, 11KW / 15HP |
| 114 |
| AHU - 2 |
| CLC 2nd Floor |
Machinery Room
| 25 |
| TRANE |
| 000529H205 |
| IN: 3X200-240V 50/60HZ, 78.2A, OUT: 3X0-VIN 0.1-1000HZ, 78.2A, 18.5KW / 15HP |
| 115 |
| AHU - 3 |
| CLC 1st Floor |
Machinery Room
| 10 |
| TRANE |
| 000529H215 |
| IN: 3X200-240V 50/60HZ, 32.2A, OUT: 3X0-VIN 0.1-1000HZ, 33A, 7.5KW / 10HP |
| 116 |
| AHU - 4 |
| CLC 1st Floor |
Machinery Room
| 5 |
| TRANE |
| 000429H205 |
| IN: 3X200-240V 50/60HZ, 16.8A, OUT: 3X0-VIN 0.1-1000HZ, 17.6A, 3.7KW / 5HP |
| 117 |
| AHU- |
Ambulatory Surgery Bldg.1 1st Floor Roof
| 10 |
| ABB |
| 51737C0330 |
| 3-380…480V, 31A, 48…63HZ,10HP |
| 118 |
| Pump 10 |
| Potable Water |
Pump Room
| 25 |
| TRANE |
| 803204Y415 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 119 |
| Pump 9 |
| Potable Water |
Pump Room
| 25 |
| TRANE |
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
| 120 |
| Pump 8 |
| Potable Water |
Pump Room
| 25 |
| TRANE |
INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING:
5KA RMS SYM. AT RATED INPUT V MAX.
| 121 |
| Pump 7 |
| Potable Water |
Pump Room
| 25 |
| TRANE |
| 803104Y415 |
| INPUT POWER: 480 VAC, 34.3 A, 3, 60HZ, MOTOR: 460 VAC, 25.00 HP, 34.3 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 122 |
| Cooling |
Tower 1
| Main Chiller Plant |
| 75 |
| TRANE |
| 614004Y111 |
| INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 123 |
| Cooling |
Tower 2
| Main Chiller Plant |
| 75 |
| TRANE |
| 613904Y111 |
| INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 124 |
| Cooling |
Tower 3
| Main Chiller Plant |
| 75 |
| TRANE |
| 613804Y111 |
| INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 125 |
| Cooling |
Tower 4
| Main Chiller Plant |
| 75 |
| TRANE |
| 614104Y111 |
| INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 126 |
| Cooling |
Tower 5
| Main Chiller Plant |
| 75 |
| TRANE |
| 613704Y111 |
| INPUT POWER: 480 VAC, 96.8 A, 3, 60HZ, MOTOR: 460 VAC, 75.00 HP, 96.8 A, 3, 60HZ, SHORT CIRCUIT RATING: |
5KA RMS SYM. AT RATED INPUT V MAX.
| 127 |
| PUMP 1R |
| Main Chiller Plant |
| 20 |
| DANFOSS |
| 007833H387 |
| 15KW/20HP, 50/60HZ, 29/25A |
| 128 |
| PUMP 2R |
| Main Chiller Plant |
| 20 |
| DANFOSS |
| 295404Y407 |
| 15KW/20HP, 50/60HZ, 29/25A |
| 129 |
| PUMP 3R |
| Main Chiller Plant |
| 20 |
| DANFOSS |
| 295604Y407 |
| 15KW/20HP, 50/60HZ, 29/25A |
| 130 |
| PUMP 4R |
| Main Chiller Plant |
| 20 |
| DANFOSS |
| 295704Y407 |
| 15KW/20HP, 50/60HZ, 29/25A |
| 131 |
| PUMP 12R |
| Main Chiller Plant |
| 150 |
| TRANE |
| 001203H255 |
| 110KW/150HP, 50/60HZ,204/183A |
| 132 |
| PUMP 10R |
| Main Chiller Plant |
| 150 |
| TRANE |
| 001103H255 |
| 110KW/150HP, 50/60HZ,204/183A |
| 133 |
| PUMP 11R |
| Main Chiller Plant |
| 150 |
| TRANE |
| 001003H255 |
| 110KW/150HP, 50/60HZ,204/183A |
1. Are any of the VFDs damaged and what’s their brand and capacity?
Answer to question 2:
1. OPA Building
0. AHU 15 Supply Fan 20 HP Out of service
0. AHU 53 Supply Fan 10 HP Out of Service
0. AHU 4 Return Fan 15 HP Out of service
0. AHU 17 Return Fan 15 HP Out of service
1. SBT Building
1. AHU 5 Supply Fan 30 HP Out of service
1. AHU 10 Supply Fan 40 HP Out of service
1. AHU 3 Return Fan 7.5 HP Out of service
1. AHU 1 Return Fan 7.5 HP Out of service
1. Hot Water Pump 2 15 HP Out of service
1. Main Building
2. Pump 7 Millionaires Tanks 25 HP Out of service
2. Pump 8 Millionaires Tanks 25 HP Out of service
2. Pump 9 Millionaires Tanks 25 HP Out of service
2. Pump 10 Millionaires Tanks 25 HP Out of service
1. Administration Building
3. AHU 1 Return Fan Out of service
1. Please provide the quantity of BCUs, UPCMs, MPs, FECs, NAEs, JACEs and Distech Controllers.
Answer to question 3:
1. Five Network Automation Engines or NAE.
1. Twenty three Field Equipment Controllers of FEC.
1. Forty nine FEC expansion cards.
1. One Java Application Control Engine or JACE.
1. Eleven Distech controllers 11.
1. Twenty nine Building Control Units or BCU.
1. Fifty four Universal Programable Control Modules or UPCMs.
1. One hundred and ninety-seven Multi-Purpose controllers or MP.
1. Three hundred and fifty five MP expansion cards.
1. Please indicate if there are any of the above-mentioned controllers that are non-operational.
Answer to question 4:
1. One UPCM is out of service.
1. Please indicate if there are any of the above-mentioned controllers that are non-operational.
Answer to question 5:
Yes, the contractor is responsible for any part that need replacement during the contract period.
1. Please indicate if calibrations will be allowed during normal working hours on all areas of the facilities or if the contractor will have to perform calibrations of sensitive areas during non-normal working hours.
Answer to question 6:
Contractor will perform all recurring maintenance on scheduled with final customer systematically. Recurring maintenance or calibrations shall not impact patientcare service. Contractor might need to work irregular hours, weekends, holydays, etc. according to service department work schedule.
1. If calibrations are to be performed during other than normal working hours in sensitive areas please indicate which areas are deemed sensitive and how many calibration points can we assume in these areas?
Answer to question 7:
1. SPS (20 points)
1. Operation Rooms (55 points)
1. Cardio (20 points)
1. Nuclear Medicine (10 points)
1. Multipurpose (10 points)
1. Outpatient Pharmacy (150 points)
1. Inpatient Pharmacy (20 points)
1. Laboratory (20 points)
1. Hemodialysis (24 points)
1. SICU (20 points)
1. Is an electrician required for this contract, to work with the VFD’s?
Answer to question 8:
Yes, a license electrician is required to work with any electrical circuits and VFDs.
Additional question:
Given that Trane does not sell tracer summit products any more please indicate what will the contractor need to do if a BCU or an MP581 or a UPCM becomes damaged and if the cost of the solution will be the responsibility of the contractor.
Answer:
The contractor must submit recommendations for alternative solutions in case that parts are no longer manufactured, cannot be found through retailers, and no equivalent is available as a direct replacement.
The government will evaluate the alternatives and will make decisions accordingly.
File details come from the government source that posted it. Updated .