BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
GENERAL NOTES
C-100
ABBREVIATIONSLEGENDGENERAL NOTES
THUNDERBOLT ROAD
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
EXISTING
CONDITIONS
C-101
GRAPHIC SCALE
( IN FEET )
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
DEMOLITION PLAN
C-102
GRAPHIC SCALE
VIOLATORS WILL
BE FINED MIN. $150
PARKING
STATE PERMIT
RESERVED
REQUIRED
VIOLATORS WILL
BE FINED MIN. $150
PARKING
STATE PERMIT
RESERVED
REQUIRED
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
LAYOUT PLAN
C-103
GRAPHIC SCALE
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
SEDIMENT AND
EROSION CONTROL
C-104
GRAPHIC SCALE
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
GRADING AND
DRAINAGE PLAN
C-105
GRAPHIC SCALE
GEOTEXTILE SILT FENCE DETAIL
INLET PROTECTION DETAIL
HANDICAP RAMP
BITUMINOUS CONCRETE PAVING
PRECAST CONCRETE CURB
CONCRETE SIDEWALK DETAIL
DETECTABLE WARNINGS DETAIL
CROSSWALK AND STOP BAR DETAIL
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
DETAILS
C-501
TYPICAL PIPE TRENCH DETAIL
PLAN
SECTION THRU DETENTION/RETENTION SYSTEMS
TYPE 'C' CATCH BASIN DETAIL
MANHOLE FRAME AND COVER
REINFORCED PRECAST CONCRETE MANHOLE
NTS
TYPICAL COMM DUCT CONCRETE ENCASEMENT
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
DETAILS
C-502
ACCESSIBLE SIGN DETAIL
STOP SIGN DETAIL
SIGN POST DETAIL-BREAKAWAY TYPE I INSTALLATION
PLAN VIEW
TYPICAL BOLLARD DETAIL
ELEVATION -BOLLARD MOUNTING DETAIL
PAVED AREA SIGN MOUNTING
UTILITY BOLLARD
VIOLATORS WILL
BE FINED MIN. $150
PARKING
STATE PERMIT
RESERVED
REQUIRED
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
DETAILS
C-503
DIVERSION MANHOLE-1
OUTLET CONTROL STRUCTURE-1
STABILIZED CONSTRUCTION ENTRANCE2
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
DETAILS
C-503
DESCRIPTIONABBREVIATIONS
ELECTRICAL ABBREVIATIONS
ELECTRICAL LEGEND
SYMBOL
DESCRIPTION
ELECTRICAL GENERAL NOTES
1. UNLESS OTHERWISE INDICATED, FURNISH AND INSTALL A COMPLETE AND OPERATIONAL
ELECTRICAL SYSTEM INCLUDING ALL NECESSARY MATERIAL, LABOR, AND EQUIPMENT.
2. ELECTRICAL PLANS AND DETAILS SHOW THE GENERAL LOCATION AND ARRANGEMENT OF THE
ELECTRICAL SYSTEM. THEY ARE DIAGRAMMATIC AND DO NOT SHOW ALL CONDUIT BODIES,
CONNECTORS, BENDS, FITTINGS, HANGERS, AND ADDITIONAL PULL AND JUNCTION BOXES WHICH
THE CONTRACTOR MUST PROVIDE TO COMPLETE THE ELECTRICAL SYSTEM.
3. ALL EQUIPMENT AND MATERIAL SHALL BE LABELED AND LISTED, AND INSTALLED IN ACCORDANCE
WITH THEIR LISTING.
4. THE CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS AND ARRANGE FOR ALL REQUIRED
INSPECTIONS IN ACCORDANCE WITH STATE GOVERNING AUTHORITIES.
5. ALL WORK SHALL BE DONE WITH LICENSED WORKMEN IN ACCORDANCE WITH STATE GOVERNING
AUTHORITIES.
6. THE DEFINITION OF ELECTRICAL TERMS USED SHALL BE AS DEFINED IN THE 2014 EDITION OF THE
NATIONAL ELECTRIC CODE (NEC).
7. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRIC CODE (NEC)
ANSI/NFPA 70 2017 EDITION.
8. THE TERM "INDICATED" SHALL MEAN "AS SHOWN ON CONTRACT DOCUMENTS (SPECIFICATIONS, DRAWINGS, AND RELATED ATTACHMENTS)".
9. ELECTRICAL PLANS AND DETAILS DO NOT SHOW ALL INTERFERENCE'S AND CONDITIONS, VISIBLE
AND/OR HIDDEN, THAT MAY EXIST; THUS REQUIRING THE CONTRACTOR TO INSPECT AND SURVEY
THE SPACE BEFORE PERFORMING THE WORK.
10. COORDINATE ELECTRICAL WORK WITH OWNER.
11. COORDINATE ELECTRICAL WORK WITH OTHER DIVISIONS OF THIS PROJECT.
12. BEFORE SELECTING MATERIAL AND EQUIPMENT, AND PROCEEDING WITH WORK, INSPECT AREAS
WHERE MATERIAL AND EQUIPMENT ARE TO BE INSTALLED TO INSURE SUITABILITY, AND CHECK
NEEDED SPACE FOR PLACEMENT, CLEARANCES AND INTERCONNECTIONS.
13. BEFORE CUTTING OR DRILLING INTO BUILDING ELEMENTS INSPECT AND LAYOUT WORK TO AVOID
DAMAGING STRUCTURAL ELEMENTS AND BUILDING UTILITIES.
A AMPERES
AWG AMERICAN WIRE GAUGE
C CONDUIT
CU COPPER
DWG DRAWING
G GROUND
LED LIGHT EMITTING DIODE
MTD MOUNTED
NEC NATIONAL ELECTRIC CODE
NECA NATIONAL ELECTRICAL CONTRACTORS ASSOC.
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOC.
N.T.S. NOT TO SCALE
P POLE
PS PHOTO SENSOR
PVC POLYVINYL CHLORIDE
SL SIGHT LIGHTING
UL UNDERWRITER'S LABORATORY
U.O.N. UNLESS OTHERWISE NOTED
V VOLTS
W WATTS
% PERCENT
# NUMBER
' FEET
" INCHES
WARNING TAPE
SCHEDULE 40 PVC
U.O.N. REFER TO
PLANS FOR SIZES
M
I N
M
A X
12" MIN.
BACKFILL WITH SUITABLE
MATERIAL COMPACTED
TO 95% MAXIMUM
DENSITY (ASTM D 1557)
COMPACTED SAND
BEDDING
NOTES:
1. THE CLEAN FILL SHALL PASS THROUGH A 3/8" MESH SCREEN AND SHALL NOT
CONTAIN SHARP STONES. OTHER BACKFILL SHALL NOT CONTAIN ASHES,
CINDERS, SHELLS, FROZEN MATERIAL, LOOSE DEBRIS OR STONES LARGER
THAN 2" IN MAXIMUM DIMENSION. THE TRENCH SHALL BE BACKFILLED
IMMEDIATELY FOLLOWING PLACEMENT OF OTHER CONDUITS.
2. WHERE EXISTING UTILITIES ARE LIKELY TO BE ENCOUNTERED, CONTRACTOR
SHALL HAND DIG AND PROTECT EXISTING UTILITIES.
FINISHED GRADE
SURFACE MTD PANELBOARD
BRANCH CIRCUIT POWER WIRING
POLE MOUNTED LED LIGHTING FIXTURE
DETAIL CALLOUT. NUMBER ON TOP REPRESENTS DETAIL NUMBER
AND BELOW REPRESENTS DRAWING SHEET
E-001
N.T.S.
CONDUIT INSTALLATION IN GRASS/LANDSCAPE
3" CLR
FINISH GRADE
2' DIAMETER
4-#7 VERTICALS AT 2'-0" DIA 4-#6
VERTICALS AT 1'-6" DIA
#3 CLOSED TIES @ 12" O.C.
90° HOOKS
OR
CLASS A
SPLICE
12" O.C.
1" PVC CONDUIT (TYPICAL).
CONFIGURE CONDUITS FOR OPTIMAL
ALIGNMENT
COUPLING (TYPICAL)
3-#3 CLOSED TIES @ 3" O.C. (TOP)
1"-45° CHAMFER ALONG TOP
GROUT VOID BETWEEN BASE FLANGE AND TOP OF
CONCRETE. HAND FINISH. PROVIDE 3/8"Ø WEEPHOLE
THROUGH GROUT AT BASE OF POLE.
PROJECT ANCHOR BOLTS PER MANUFACTURER
DATA. PROVIDE DOUBLE NUTS AND WASHERS FOR
LEVELING UNIT (ONE ABOVE AND ONE BELOW BASE
FLANGE).
BUSH CONDUITS
GROUND LUG. CONNECT
GROUND CONDUCTOR TO
POLE BASE
BASE COVER.
POLE
FOR ANCHOR BOLT PATTERN, LENGTH AND
SIZE CONSULT MANUFACTURER DATA (MIN.
3/4" X 18" LENGTH GALV.) (ANCHOR BOLTS
SHALL OCCUR WITHIN REBAR CAGE)
1-1/4" GALVANIZED STEEL CONDUIT (TYPICAL)
6"
EDGE OF
SIDEWALK/CURB
TO NEXT FIXTURE. SEE DRAWING C0.6 FOR, WIRE
SIZE AND CONDUIT ROUTING
NOTES:
1. DESIGN PER 2012 CT CODE. EPA OF FIXTURE 1.01 X 2 = 2.02.
24'-0" POLE + 1'-0" EXPOSURE.
2. COORDINATE ANCHOR BOLT SIZE, QUANITITY AND LOCATION
WITH MANUFACTURER. (ANCHOR BOLTS SHALL HAVE A
MINIMUM YIELD STRENGTH OF 50,000 PSI.)
3. CONCRETE FOR FOOTINGS SHOWN ON THIS SHEET, SHALL BE
NORMAL WEIGHT CONCRETE WITH A MINIMUM SPECIFIED 28
DAY COMPRESSIVE STRENGTH OF f'c= 4000psi. REINFORCING
SHALL MEET ASTM A615 GR 60 KSI. GROUT SHALL HAVE A
MINIMAL SPECIFIED 28 DAY COMPRESSIVE STRENGTH OF
5,000 PSI AND SHALL BE NON-METALLIC.
4. FIELD LOCATE ALL BASE LOCATIONS FOR APPROVAL BY
ARCHITECT PRIOR TO INSTALLATION. NOTIFY ARCHITECT OF
ANY CONFLICTS.
5. PROVIDE HAND-RUBBED FINISH ON ALL EXPOSED SURFACES
OF FOOTINGS.
6. FOOTINGS ARE SIZED FOR SPECIFIED POLES AND FIXTURES
SHOWN IN LIGHT FIXTURE SCHEDULE (THIS SHEET). IF POLES
OR FIXTURES BEING PROVIDED ARE DIFFERENT THAN
SPECIFIED, NOTIFY ENGINEER AS FOOTING SIZES MAY NEED
TO BE MODIFIED TO COMPLY WITH THE SUBSTITUTED
POLES/FIXTURES.
HAND RUBBED FINISH
PROVIDE BREAKAWAY FUSE WITH FUSE
HOLDER. SIZE BASED ON FIXTURE TYPES.
12" MIN.
12" MAX
24" MIN
FINISHED GRADE
6"
12"
NOTES:
COMPACTED
BEDDING COURSE
COMPACTED
GRANULAR FILL
WARNING TAPE
1. THE CLEAN FILL SHALL PASS THROUGH A 3/8" MESH SCREEN AND SHALL NOT CONTAIN SHARP STONES. OTHER BACKFILL
SHALL NOT CONTAIN ASHES, CINDERS, SHELLS, FROZEN MATERIAL, LOOSE DEBRIS OR STONES LARGER THAN 2" IN MAXIMUM
DIMENSION. THE TRENCH SHALL BE BACKFILLED IMMEDIATELY FOLLOWING PLACEMENT OF THE CONDUITS.
2. WHERE EXISTING UTILITIES ARE LIKELY TO BE ENCOUNTERED, CONTRACTOR SHALL HAND DIG AND
PROTECT EXISTING UTILITIES.
SCHEDULE 40 PVC U.O.N. SEE
PLANS & RISER DIAGRAM FOR
SIZES AND QUANTITIES.
SAWCUT BITUMINOUS SIDEWALK TO
MATCH NEW WORK
E-001
N.T.S.
CONDUIT INSTALLATION IN BITUMINOUS
C-501
E-001
N.T.S.
ELECTRICAL LIGHT POLE BASE DETAIL
12"
XXX
X
SEE CIVIL DETAILS FOR
PAVEMENT SECTION
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION VOLTAGE LAMPS REMARKS
NOTES:
1. ALL NECESSARY MOUNTING HARDWARE SHALL BE PROVIDED.
SL-A
LED AREA / FLOOD LUMINAIRE, TYPE IV MEDIUM (ASYMMETRIC), 4000K, 53W LED, BRONZE WITH DIRECT ARM
MOUNT AND PROGRAMMABLE MULTI-LEVEL SENSOR AND REMOTE ON A 24', 5" Ø STRAIGHT STEEL POLE. BUG
RATING TO BE EQUAL OR BELOW B2 U0 G2. EFFICIENCY TO BE EQUAL OR ABOVE 130 LUMENS PER WATT. MAX
EPA OF 0.75 (OR ADJUST POLE CAPACITY). 10 YEAR WARRANTY.
120V
53W LED
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
ELECTRICAL COVER
SHEET
E-001
EXIST. PANEL LPB-A
EXIST. PANEL GPC
ELEC/MECH
ROOM
CONDUIT IN TRENCH
(GRASS/LANDSCAPE) TYP.
CONDUIT IN TRENCH
(BITUMINOUS) TYP.
SL-A
SL-A
SL-A
SL-A
SL-A
SL-A
SL-A
SL-A
E-001
E-001
E
E
E E E E E E E E
E
E
E
E
E
E
E
E
EEE
E
E E
BRADLEY
AIR
NATIONAL
GUARD
BASE
AS NOTED
7-27-18
CEKT132211
BUILDING 24 PARKING
LOT
7-27-18
7-27-18
2321 Whitney Avenue - Hamden Center II - Hamden CT 06518
Ph: 203 239 4200 Fax: 203 234 7376 www.teamdtc.com
ELECTRICAL SITE
PLAN
E-101
#ELECTRICAL KEY NOTES
1. PROVIDE 20A-1P CIRCUIT BREAKERs IN PANELBOARD 'LPB-A' TO POWER SITE LIGHTING FIXTURES.
2. PROVIDE 2#10,#10G IN A 1" C FOR SITE LIGHTING FIXTURES.
ELECTRICAL GENERAL NOTES
1. ALL WORK SHOWN ON DRAWING IS MINOR CONSTRUCTION.
2. THE UTILITIES SHOWN ARE APPROXIMATE. CONTRACTOR TO COORDINATE IN FIELD FOR EXACT
LOCATION OF ALL NEW AND EXISTING UTILITIES.
3. LIGHTING FEEDER SHALL ENTER AT BRICK PORTION OF BUILDING EXTERIOR THROUGH EXTERIOR
WALL OF THE BOILER ROOM. PROVIDE RIGID GALVANIZED STEEL WHERE CONDUIT IS EXPOSED
TO OUTDOORS.