Submittal 25 - For Construction Drawings_.pdf

PDF 9 MB Posted

Attached to
Camp James A Garfield Dining Facility Conversion Federal contract opportunity
Solicitation number
W91364-22-R-0003
Issued by
Department of the Army Ohio Army National Guard

About this file

This federal contract opportunity notice solicits bids for a dining facility conversion project at Camp James A Garfield Joint Military Training Center in Ravenna, Ohio. The scope of work includes mechanical, electrical, and plumbing work to convert an existing classroom building into a fully functional dining facility. Additional requirements include connecting sanitary sewer and water lines, installing an oil water separator, and incorporating antiterrorism measures per DOD standards. The project magnitude ranges from $85,000 to $150,000. A site visit will be held on August 25, 2022 at 11:00 AM. The solicitation number is W91364-22-R-0003 and was issued by the Department of the Army Ohio Army National Guard. The NAICS code is 236220 and the small business size standard is $39.5 million. Bids will be evaluated based on criteria in the attached documentation.

View the file

Other files for this federal contract opportunity

Other files attached to Camp James A Garfield Dining Facility Conversion, newest first.
File Type Posted
DFAC Conversion Drawings.pdf PDF
W91364-22-R-0003 CJAG DFAC Conversion_sign in sheet.pdf PDF
CJAG Dining Facility Conversion Project Q and A.docx DOCX document
889 Representations Form.pdf PDF
W91364-22-R-0003 CJAG DFAC Conversion .pdf PDF
Instructions and Evaluation Criteria.docx DOCX document
3922010_CJAG Bldg 1019 DFAC Conversion SOW_final__.pdf PDF
RFI-000.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E1

C A

M P

J A

M E

S

A

G

A R

F I E

L D

J O

I N

T

M

I L

I T

A R

Y

T

R A

I N

I N

G

C

E N

T E

R

N

E W

T O

N

F

A L

L S

O

H

D F

I

B

U I L

D I N

G

S

T

A

E

OF

O

H

AutoCAD SHX Text

TYPE

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

LAMP(S)

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text A

AutoCAD SHX Text D

AutoCAD SHX Text %%uLIGHT FIXTURE SCHEDULE

AutoCAD SHX Text

(UNLESS NOTED OTHERWISE EQUALS WILL BE ACCEPTED)

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text %%uLEGEND

AutoCAD SHX Text S

AutoCAD SHX Text

%%UGENERAL ELECTRICAL NOTES

AutoCAD SHX Text

1. FURNISH ALL MATERIALS AND LABOR NECESSARY TO PROVIDE COMPLETE AND FURNISH ALL MATERIALS AND LABOR NECESSARY TO PROVIDE COMPLETE AND PROPERLY OPERATING ELECTRICAL SYSTEMS. FURNISH ALL MATERIALS AND LABOR NECESSARY TO DEMONSTRATE TO THE OWNER AND TO THE ENGINEER THAT ALL SYSTEMS ARE OPERATING PROPERLY AND AS SPECIFIED. WARRANTY ALL WORK AND ALL MATERIALS, EQUIPMENT AND DEVICES FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. 2. WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF: WORK SHALL CONFORM TO THE LATEST ADOPTED EDITION OF: A. ANSI/NFPA 70 (NATIONAL ELECTRICAL CODE) B. NECA STANDARD OF INSTALLATION C. INTERNATIONAL BUILDING CODE D. NFPA 101 (LIFE SAFETY CODE) E. IECC (INTERNATIONAL ENERGY CONSERVATION CODE) F. ALL FEDERAL, STATE AND LOCAL CODES AND ORDINANCES G. LOCAL UTILITY COMPANY REGULATIONS 3. ALL MATERIALS, EQUIPMENT AND DEVICES SHALL BE NEW AND AS A MINIMUM ALL MATERIALS, EQUIPMENT AND DEVICES SHALL BE NEW AND AS A MINIMUM MEET THE REQUIREMENTS OF U.L. WHERE U.L. STANDARDS ARE ESTABLISHED FOR THOSE ITEMS, AND THE REQUIREMENTS OF NFPA 70. ALL ITEMS SHALL BE CLASSIFIED BY U.L. AS SUITABLE FOR THE PURPOSE USED. 4. COORDINATE LOCATION OF ELECTRICAL DEVICES AND ELECTRICAL WORK WITH COORDINATE LOCATION OF ELECTRICAL DEVICES AND ELECTRICAL WORK WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. 5. PROVIDE THE INTERCONNECTING POWER WIRING AND CONDUIT, CONTROL PROVIDE THE INTERCONNECTING POWER WIRING AND CONDUIT, CONTROL WIRING RATED 120 VOLTS (NOMINAL) AND CONDUIT, AND THE ELECTRICAL POWER CIRCUITS FOR ALL EQUIPMENT PROVIDED BY OTHER TRADES. 6. COORDINATE WITH AND OBTAIN PERMITS AND INSPECTIONS FROM THE COORDINATE WITH AND OBTAIN PERMITS AND INSPECTIONS FROM THE AUTHORITY HAVING JURISDICTION, AND INCLUDE ALL FEES IN BID. 7. PROVIDE A LAMINATED PLASTIC NAMEPLATE FOR EACH MAJOR ITEM OF PROVIDE A LAMINATED PLASTIC NAMEPLATE FOR EACH MAJOR ITEM OF ELECTRICAL EQUIPMENT (E.G. PANELBOARDS, DISCONNECT SWITCHES, TRANSFORMERS, ETC.). ATTACH WITH SCREWS, BOLTS OR RIVETS. 8. PROVIDE ALL PANELS WITH TYPED DIRECTORIES SHOWING AS-BUILT CONDITIONS PROVIDE ALL PANELS WITH TYPED DIRECTORIES SHOWING AS-BUILT CONDITIONS AND LABEL ALL CIRCUITS. 9. THE NEUTRAL AND GROUND BUS SHALL BE BONDED TOGETHER AT THE SERVICE THE NEUTRAL AND GROUND BUS SHALL BE BONDED TOGETHER AT THE SERVICE EQUIPMENT AND AT ANY DOWNSTREAM TRANSFORMERS WHICH CONSTITUTE A SEPARATELY DERIVED SYSTEM. THE GROUNDING CONDUCTOR SHALL BE BONDED TO THE GROUNDING ELECTRODE SYSTEM, WHICH SHALL BE COMPRISED OF A 3/4" X 10' DRIVEN GROUND ROD, METALLIC PIPING,BUILDING STEEL, ETC. ALL SUBPANELS SHALL HAVE INSULATED ISOLATED NEUTRALS PER N.E.C. ARTICLE 250. 10. ALL 120V CIRCUITS SHALL BE COMPRISED OF AN UNGROUNDED CONDUCTOR ALL 120V CIRCUITS SHALL BE COMPRISED OF AN UNGROUNDED CONDUCTOR AND AN INSULATED NEUTRAL. THERE WILL BE NO SHARING OF NEUTRALS. 11. ALL WIRING SHALL BE COPPER, 600 VOLT, WITH THHN/THWN INSULATION ALL WIRING SHALL BE COPPER, 600 VOLT, WITH THHN/THWN INSULATION INSTALLED IN CONDUIT UNLESS NOTED OTHERWISE. MINIMUM CONDUCTOR SIZE SHALL BE #12 AWG FOR POWER AND LIGHTING CIRCUITS AND #16 AWG FOR CONTROL CIRCUITS UNLESS NOTED OTHERWISE. 12. UNLESS NOTED OTHERWISE, CONDUITS SHALL BE: UNLESS NOTED OTHERWISE, CONDUITS SHALL BE: A. ELECTRICAL METALLIC TUBING (EMT) FOR INTERIOR LOCATIONS. B. SCHEDULE 40 PLASTIC CONDUIT (PVC) FOR EXTERIOR LOCATIONS. C. RIGID GALVANIZED STEEL (RGS) CONDUIT WHERE EXPOSED TO PHYSICAL DAMAGE. 13. ALL CONDUIT ABOVE CEILING SHALL BE SUPPORTED FROM BUILDING ALL CONDUIT ABOVE CEILING SHALL BE SUPPORTED FROM BUILDING STRUCTURAL MEMBERS OR CONCRETE DECKING, NOT FROM CEILING GRID OR GRID HANGER WIRES. 14. PROVIDE ALL MOUNTING BRACKETS, HANGERS, CLIPS, ETC. AS NECESSARY TO PROVIDE ALL MOUNTING BRACKETS, HANGERS, CLIPS, ETC. AS NECESSARY TO MOUNT AND SECURE LIGHT FIXTURES IN LOCATIONS SHOWN AND AS RECOMMENDED BY THE MANUFACTURER FOR THE APPLICATION INTENDED. 15. WHERE CONDUIT PENETRATES FIRE RATED BARRIERS (WALLS, FLOORS AND WHERE CONDUIT PENETRATES FIRE RATED BARRIERS (WALLS, FLOORS AND CEILINGS), SEAL THE OPENING AROUND THE CONDUIT WITH U.L. LISTED FIRE STOPPING MATERIAL TO MAINTAIN THE FIRE RATING OF THE BARRIER. 16. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK WHERE POSSIBLE; COORDINATE ALL PENETRATIONS WITH ARCHITECT. 17. MAKE ARRANGEMENTS WITH THE POWER COMPANY TO OBTAIN PERMANENT MAKE ARRANGEMENTS WITH THE POWER COMPANY TO OBTAIN PERMANENT ELECTRICAL SERVICE TO THE PROJECT. PROVIDE SERVICE ENTRANCE AND PROVISIONS FOR METERING IN ACCORDANCE WITH THE POWER COMPANY'S REQUIREMENTS. INCLUDE ALL FEES IN BID. 18. MAKE ARRANGEMENTS WITH THE POWER COMPANY AND PROVIDE TEMPORARY MAKE ARRANGEMENTS WITH THE POWER COMPANY AND PROVIDE TEMPORARY ELECTRICAL SERVICE TO THE PROJECT FOR CONSTRUCTION POWER. INCLUDE ALL FEES IN BID. 19. PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH IBC 2015. SUBMIT SHOP PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH IBC 2015. SUBMIT SHOP DRAWINGS FOR APPROVAL. 20. WIRE ALL EMERGENCY/EXIT LIGHTING AHEAD OF ANY SWITCHING. WIRE ALL EMERGENCY/EXIT LIGHTING AHEAD OF ANY SWITCHING. 21. ALL MATERIALS LOCATED WITHIN THE RETURN AIR PLENUM SHALL BE PLENUM ALL MATERIALS LOCATED WITHIN THE RETURN AIR PLENUM SHALL BE PLENUM RATED.

AutoCAD SHX Text

EMERGENCY LIGHTING UNIT WITH NUMBER OF HEADS INDICATED.

AutoCAD SHX Text

208/120V, POWER PANEL

AutoCAD SHX Text

TELEPHONE BACKBOARD

AutoCAD SHX Text

GROUNDING CONNECTION/DEVICE.

AutoCAD SHX Text

KEYED NOTE IDENTIFIER

AutoCAD SHX Text DUAL TECHNOLOGY VACANCY SENSOR, CEILING MOUNTED, LINE VOLTAGE (LEVITON O2C DUAL RELAY SERIES OR EQUAL).

AutoCAD SHX Text BRANCH CIRCUIT, ARROW INDICATES HOMERUN, CROSS LINES INDICATE NUMBER OF CONDUCTORS, GROUNDING CONDUCTOR IS NOT SHOWN BUT SHALL BE PROVIDED IN ALL CIRCUITS (2#12, 1#12G, 1/2"C UNLESS NOTED OTHERWISE).

AutoCAD SHX Text COMBINATION TV/TELEPHONE/COMPUTER OUTLET, 4"x4"x1 1/2" BOX WITH SINGLE GANG EXTENSION RING (18" A.F.F., 3/4" CONDUIT UNLESS NOTED OTHERWISE).

AutoCAD SHX Text DISCONNECT SWITCH, UNLESS NOTED OTHERWISE RATING SHALL BE 240V, 30 AMP/2 POLE/NEMA 1/NON FUSED (30/2/1/NF). 20AF - INDICATES 20 AMP FUSE. (FUSES SHALL BE DUAL ELEMENT, TIME DELAY, CURRENT LIMITING).

AutoCAD SHX Text

ELECTRIC MOTOR (PROVIDED UNDER MECHANICAL - WIRED UNDER ELECTRICAL).

AutoCAD SHX Text DUPLEX RECEPTACLE OUTLET, 20 AMP, 125V AC, 2 POLE, 3 WIRE, GROUNDING (18" A.F.F. UNLESS NOTED OTHERWISE). SUBSCRIPT: WR - LISTED WEATHER RESISTANT RECEPTACLE WITH "EXTRA DUTY" WEATHERPROOF WHILE IN USE COVER.

AutoCAD SHX Text

DUPLEX RECEPTACLE OUTLET, GROUND FAULT CIRCUIT INTERRUPTER (GFCI).

AutoCAD SHX Text ENCLOSED LED FIXTURE, LETTER INDICATES TYPE, APPROXIMATE DIMENSIONS AS INDICATED.

AutoCAD SHX Text

OPEN LED FIXTURE, LETTER INDICATES TYPE.

AutoCAD SHX Text

WALL MOUNTED FIXTURE, LETTER INDICATES TYPE.

AutoCAD SHX Text

LED

AutoCAD SHX Text 2-1.5W

AutoCAD SHX Text

LED EXIT/EMERG. LIGHTING COMBO UNIT, PLASTIC

AutoCAD SHX Text

HOUSING, WHITE FINISH, INTEGRAL BATTERY

AutoCAD SHX Text

AND CHARGER, MOUNT 1' BELOW CEILING BUT

AutoCAD SHX Text

NO HIGHER THAN 12' A.F.F.

AutoCAD SHX Text

LITHONIA-

AutoCAD SHX Text

LHQM SERIES

AutoCAD SHX Text R

AutoCAD SHX Text

LED

AutoCAD SHX Text 2-51.5W

AutoCAD SHX Text

LED EXIT/EMERG. LIGHTING COMBO UNIT, PLASTIC

AutoCAD SHX Text

HOUSING, WHITE FINISH, INTEGRAL BATTERY

AutoCAD SHX Text

AND CHARGER, MOUNT 1' BELOW CEILING BUT

AutoCAD SHX Text

NO HIGHER THAN 12' A.F.F., PROVIDE WITH

AutoCAD SHX Text

SURE-LITE SEL255D

AutoCAD SHX Text

INTEGRAL HIGH OUTPUT BATTERY CAPABLE OF

AutoCAD SHX Text

POWERING 2 REMOTE FIXTURES FOR 90

AutoCAD SHX Text

MINUTES, WHERE INDICATED WITH "R" ON

AutoCAD SHX Text

DRAWINGS.

AutoCAD SHX Text

INDICATED ON PLANS. REFER TO EXTERIOR

AutoCAD SHX Text

1.25W - POWERED FROM EMERGENCY LIGHT AS

AutoCAD SHX Text

ELEVATIONS FOR MOUNTING HEIGHTS.

AutoCAD SHX Text

OUTDOOR 2 HEAD CYLINDER, BLACK FINISH, 3.6V,

AutoCAD SHX Text 3.6V

AutoCAD SHX Text

2-1.25W LED

AutoCAD SHX Text

WEATHER PROOF.

AutoCAD SHX Text

EMERGENCY LIGHTING UNIT, PLASTIC HOUSING,

AutoCAD SHX Text

WHITE FINISH, INTEGRAL BATTERY AND

AutoCAD SHX Text

CHARGER, MOUNT 1' BELOW CEILING BUT NO

AutoCAD SHX Text

HIGHER THAN 12' A.F.F.

AutoCAD SHX Text 2-1.5W

AutoCAD SHX Text

LED

AutoCAD SHX Text

LITHONIA-ELM2

AutoCAD SHX Text

SERIES

AutoCAD SHX Text 24W

AutoCAD SHX Text 4000K

AutoCAD SHX Text

RAB

AutoCAD SHX Text

BRISKXL 24N/PCU

AutoCAD SHX Text

LED WALL PACK, DARK BRONZE, WITH PHOTO CELL.

AutoCAD SHX Text

2856 LUMENS

AutoCAD SHX Text 4000K

AutoCAD SHX Text

23W LED

AutoCAD SHX Text C

AutoCAD SHX Text

2150 LUMENS

AutoCAD SHX Text

48" STRIP 2-1/2" WIDE.

AutoCAD SHX Text

METALUX 24FP4735C

AutoCAD SHX Text 3500K

AutoCAD SHX Text

40.4W LED

AutoCAD SHX Text

4990 LUMENS

AutoCAD SHX Text

2' X 4' LED RECESSED FLAT PANEL FIXTURE.

AutoCAD SHX Text B

AutoCAD SHX Text

58.8W LED

AutoCAD SHX Text 3500K

AutoCAD SHX Text

2' X 4' LED RECESSED FLAT PANEL TYPE FIXTURE.

AutoCAD SHX Text

6602 LUMENS

AutoCAD SHX Text SWITCH, 20 AMP, 120-277V, AC (48" A.F.F. UNLESS NOTED OTHERWISE) SUBSCRIPT: NONE - SINGLE POLE 3 - 3 WAY 4 - 4 WAY M - MOTOR RATED (120V, 1P, 30A UNLESS NOTED OTHERWISE) VS - DUAL TECHNOLOGY VACANCY SENSOR (MANUAL ON, AUTO OFF- LEVITON "DECORA" OR EQUAL)

AutoCAD SHX Text

METALUX 24FP4735C

AutoCAD SHX Text

METALUX

AutoCAD SHX Text

25LSTP2040DD-120V

AutoCAD SHX Text

SURE-LITE SRP25D

AutoCAD SHX Text WHERE OUTLETS ARE MOUNTED IN A FIRE RATED WALL, PROVIDE A 90 DEGREE BEND OUT OF WALL

AutoCAD SHX Text

SEE FLOOR PLANS FOR NUMBER AND LOCATIONS OF OUTLETS.

AutoCAD SHX Text TO ALLOW ACCESS. WHERE OUTLETS WILL NOT BE MOUNTED ON A FLOOR TO CEILING WALL, RUN CONDUIT

AutoCAD SHX Text OUTLET. STUB UP 1-3/4" EMT ABOVE DROP CEILING FROM EACH COMBINATION TELEPHONE/COMPUTER OUTLET.

AutoCAD SHX Text

SERVICE STUB-UP. COORDINATE

AutoCAD SHX Text

WITH PHONE COMPANY.

AutoCAD SHX Text

ENAMEL PAINT.

AutoCAD SHX Text

WATER BASE GRAY

AutoCAD SHX Text

PAINT WITH 2 COATS OF

AutoCAD SHX Text 4'x8'x3/4" PLYWOOD, AutoCAD SHX Text

TELEPHONE BACKBOARD,

AutoCAD SHX Text

TO NEAREST WALL AND STUB UP ABOVE DROP CEILING.

AutoCAD SHX Text 2.

AutoCAD SHX Text

1" SERVICE CONDUIT TO TELEPHONE

AutoCAD SHX Text

%%UNOTE

AutoCAD SHX Text 1.

AutoCAD SHX Text

%%UTELEPHONE RISER

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

SURFACE MOUNT

AutoCAD SHX Text

ON BACKBOARD 5' A.F.F.

AutoCAD SHX Text

#6 TW

AutoCAD SHX Text

TO BLDG.

AutoCAD SHX Text

SERVICE

AutoCAD SHX Text

GROUND

AutoCAD SHX Text 120V

AutoCAD SHX Text

CKT

AutoCAD SHX Text

COMBINATION TELEPHONE/COMPUTER

AutoCAD SHX Text

OUTLET (TYPICAL).

AutoCAD SHX Text 1-3/4"C

AutoCAD SHX Text

SEE NOTE)

AutoCAD SHX Text

(TYPICAL-

AutoCAD SHX Text

2"C TO PROPERTY LINE FOR TELE.

AutoCAD SHX Text

(COORDINATE EXACT LOCATION

AutoCAD SHX Text

WITH TELEPHONE COMPANY)

AutoCAD SHX Text

TELEPHONE STUB-UP

AutoCAD SHX Text

10 PORT INTERSYSTEM

AutoCAD SHX Text

GROUND BAR

AutoCAD SHX Text

DUPLEX RECEPTACLE OUTLET, GFCI, MOUNT 6" ABOVE COUNTER.

AutoCAD SHX Text SPECIAL RECEPTACLE OUTLET, RATING AND CONFIGURATION TO MATCH EQUIPMENT PROVIDED UNLESS NOTED OTHERWISE

AutoCAD SHX Text

QUADRAPLEX RECEPTACLE OUTLET (TWO DUPLEX RECEPTACLES MOUNTED IN COMMON BOX)

AutoCAD SHX Text

LIGHTING PLAN

AutoCAD SHX Text

RAD

AutoCAD SHX Text 09/29/2017

AutoCAD SHX Text 07/12/2018

AutoCAD SHX Text

ACT

AutoCAD SHX Text 07/19/2018

AutoCAD SHX Text 11/21/2018

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text 3544G

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text DRAWING No.

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

FAX 843-745-0436

AutoCAD SHX Text

CHARLESTON, SOUTH CAROLINA 29415

AutoCAD SHX Text

WWW.KCONINC.COM

AutoCAD SHX Text

PHONE 843-745-0434

AutoCAD SHX Text

TOLL 1-800-394-5266

AutoCAD SHX Text

POST OFFICE BOX 70904

AutoCAD SHX Text THESE DRAWINGS AND DESIGNS THEREON ARE THE PROPERTY OF K-CON, INC. AND MAY NOT BE USED IN WHOLE OR INPART WITH OUT THE WRITTEN CONSENT OF K-CON, INC. AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

REV 1

AutoCAD SHX Text

ORIG

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text DRAWING Tlt.

AutoCAD SHX Text JOB No.

AutoCAD SHX Text

(843) 849-6878

AutoCAD SHX Text

MT. PLEASANT, SC 29465

AutoCAD SHX Text

P.O. BOX 2132

AutoCAD SHX Text

EPIC JOB NO. 18112

AutoCAD SHX Text

COPYRIGHT 2018 THIS DOCUMENT IS THE PROPERTY OF

AutoCAD SHX Text

EPIC ENGINEERING, INC. ANY UNAUTHORIZED REPRODUCTION

AutoCAD SHX Text

OR USE IS PROHIBITED AND SUBJECT TO LEGAL PROSECUTION

AutoCAD SHX Text c

AutoCAD SHX Text 7/19/2019

AutoCAD SHX Text 02/07/2019

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

CHECKED BY:

DATE:

E2

A

M E

S

A

G

A R

F I E

L D

J O

I N

T

M

I L

I T

A R

Y

T

R A

I N

I N

G

C

E N

T E

R

N

E W

T O

N

F

A L

L S

O

H

D F

B

U I L

D I N

G

A

R

AutoCAD SHX Text R

AutoCAD SHX Text R

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text B

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

VS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A-5

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text C

AutoCAD SHX Text A-3

AutoCAD SHX Text A-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Supply Room

AutoCAD SHX Text Office C

AutoCAD SHX Text Office B

AutoCAD SHX Text Office A

AutoCAD SHX Text Comm Room

AutoCAD SHX Text Men

AutoCAD SHX Text Women

AutoCAD SHX Text Entrance Lobby

AutoCAD SHX Text Janitor/ Mechanical

AutoCAD SHX Text Corridor

AutoCAD SHX Text Kitchen

AutoCAD SHX Text Multipurpose Area A

AutoCAD SHX Text Multipurpose Area B

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text D

AutoCAD SHX Text

LIGHTING PLAN

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text %%uLIGHTING PLAN

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

KEYED NOTES

AutoCAD SHX Text

(THIS SHEET ONLY)

AutoCAD SHX Text MOUNT FIXTURE AT 8'-6"A.F.F. IN CORRIDOR (ENSURE FIXTURE IS ALSO MOUNTED AT LEAST 1 FOOT BELOW CEILING).

AutoCAD SHX Text

AutoCAD SHX Text

RAD

AutoCAD SHX Text 09/29/2017

AutoCAD SHX Text 07/12/2018

AutoCAD SHX Text

ACT

AutoCAD SHX Text 07/19/2018

AutoCAD SHX Text 11/21/2018

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text 3544G

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text DRAWING No.

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

FAX 843-745-0436

AutoCAD SHX Text

CHARLESTON, SOUTH CAROLINA 29415

AutoCAD SHX Text

WWW.KCONINC.COM

AutoCAD SHX Text

PHONE 843-745-0434

AutoCAD SHX Text

TOLL 1-800-394-5266

AutoCAD SHX Text

POST OFFICE BOX 70904

AutoCAD SHX Text THESE DRAWINGS AND DESIGNS THEREON ARE THE PROPERTY OF K-CON, INC. AND MAY NOT BE USED IN WHOLE OR INPART WITH OUT THE WRITTEN CONSENT OF K-CON, INC. AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

REV 1

AutoCAD SHX Text

ORIG

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text DRAWING Tlt.

AutoCAD SHX Text JOB No.

AutoCAD SHX Text

(843) 849-6878

AutoCAD SHX Text

MT. PLEASANT, SC 29465

AutoCAD SHX Text

P.O. BOX 2132

AutoCAD SHX Text

EPIC JOB NO. 18112

AutoCAD SHX Text

COPYRIGHT 2018 THIS DOCUMENT IS THE PROPERTY OF

AutoCAD SHX Text

EPIC ENGINEERING, INC. ANY UNAUTHORIZED REPRODUCTION

AutoCAD SHX Text

OR USE IS PROHIBITED AND SUBJECT TO LEGAL PROSECUTION

AutoCAD SHX Text c

AutoCAD SHX Text 7/19/2019

AutoCAD SHX Text 02/07/2019

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

CHECKED BY:

E3

A

M E

S

A

G

A R

F I E

L D

J O

I N

T

M

I L

I T

A R

Y

T

R A

I N

I N

G

C

E N

T E

R

N

E W

T O

N

F

A L

L S

O

H

D F

B

U I L

D I N

G

A

T

PANEL A

AutoCAD SHX Text

AutoCAD SHX Text

FACP

AutoCAD SHX Text

WR

AutoCAD SHX Text A-18

AutoCAD SHX Text A-24

AutoCAD SHX Text M

AutoCAD SHX Text A-21

AutoCAD SHX Text A-13

AutoCAD SHX Text A-6

AutoCAD SHX Text A-8

AutoCAD SHX Text A-10

AutoCAD SHX Text A-14

AutoCAD SHX Text A-12

AutoCAD SHX Text A-2

AutoCAD SHX Text A-4

AutoCAD SHX Text

%%UCU-1

AutoCAD SHX Text

%%UPAC-2

AutoCAD SHX Text

%%UPAC-1

AutoCAD SHX Text

%%UF-1

AutoCAD SHX Text

WH-1

AutoCAD SHX Text A-52

AutoCAD SHX Text A-51

AutoCAD SHX Text

AutoCAD SHX Text

WR

AutoCAD SHX Text

WR

AutoCAD SHX Text A-16

AutoCAD SHX Text M

AutoCAD SHX Text A-7

AutoCAD SHX Text A-9

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text Supply Room

AutoCAD SHX Text Office C

AutoCAD SHX Text Office B

AutoCAD SHX Text Office A

AutoCAD SHX Text Comm Room

AutoCAD SHX Text Men

AutoCAD SHX Text Women

AutoCAD SHX Text Entrance Lobby

AutoCAD SHX Text Janitor/ Mechanical

AutoCAD SHX Text Corridor

AutoCAD SHX Text Kitchen

AutoCAD SHX Text Multipurpose Area A

AutoCAD SHX Text Multipurpose Area B

AutoCAD SHX Text

TELEPHONE BACKBOARD

AutoCAD SHX Text A-20

AutoCAD SHX Text A-32

AutoCAD SHX Text

HANDHOLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A-22

AutoCAD SHX Text

AutoCAD SHX Text A-26

AutoCAD SHX Text A-28

AutoCAD SHX Text A-34

AutoCAD SHX Text A-23

AutoCAD SHX Text A-30

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text M

AutoCAD SHX Text

POWER PLAN

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text %%uPOWER PLAN

AutoCAD SHX Text 1/4"=1'-0"

AutoCAD SHX Text

KEYED NOTES

AutoCAD SHX Text

(THIS SHEET ONLY)

AutoCAD SHX Text 1/12 HP, 120V EXHAUST FAN. PROVIDE WITH SWITCH DISCONNECT. 2#8, 1#10G, 3/4"C 60A/2P/NF NEMA 3R DISCONNECT SWITCH PROVIDE 4' HIGH 1/2" THICK PLYWOOD BACKBOARDS ON WALLS OF I.T. ROOM AS SHOWN MOUNTED 4' A.F.F. RECEPTACLES IN I.T. ROOM SHALL BE ORANGE IN COLOR. PROVIDE 12" WIDE CABLE TRAY WALL TO WALL AT 12" OFF OF BACK WALL FOR DATA CABLES. MOUNT AT HEIGHT AS DIRECTED. 2#10, 1#10G, 1/2"C PROVIDE 30A, 120V, RECEPTACLES FOR I.T. EQUIPMENT. 2x1, 3"C FIBER OPTIC DUCTBANK 24"BFG WITH 12 STRAND SINGLE MODE FIBER. RUN FIBER TO COMM ROOM AND TERMINATE INSIDE CABINET. 48" DATA CABINET WITH FIBER LIGHT INTERFACE UNIT AND RJ-45 TERMINATION PANEL INSIDE CABINET. CONTRACTOR SHALL PROVIDE ALL TERMINATIONS AND TESTING OF CABLES PER SPECIFICATIONS. FIBER HANDHOLE FURNISHED AND INSTALLED UNDER THIS CONTRACT. 2#6, 1#10G, 3/4"C PROVIDE ONE 1/2" CONDUIT BETWEEN MECH ROOM AND COMM ROOM. 3#6, 1#10G, 1"C 60A/3P/NF NEMA 3R DISCONNECT SWITCH

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

(THIS SHEET ONLY)

AutoCAD SHX Text

1. COORDINATE LOCATIONS OF RECEPTACLES AND COORDINATE LOCATIONS OF RECEPTACLES AND OTHER WALL MOUNTED DEVICES WITH THE ARCHITECTURAL WALL ELEVATIONS AND FINISHES. 2. COORDINATE LOCATIONS OF MECHANICAL COORDINATE LOCATIONS OF MECHANICAL EQUIPMENT WITH MC. ALL DISCONNECTS AND ELECTRICAL EQUIPMENT SHALL BE MOUNTED IN AN ACCESSIBLE LOCATION WITH PROPER WORKING SPACE CLEARANCES PER THE NEC. 3. COORDINATE LOCATIONS OF RECEPTACLES IN I.T. COORDINATE LOCATIONS OF RECEPTACLES IN I.T. ROOM WITH OWNER'S I.T. EQUIPMENT AND REQUIREMENTS.

AutoCAD SHX Text

RAD

AutoCAD SHX Text 09/29/2017

AutoCAD SHX Text 07/12/2018

AutoCAD SHX Text

ACT

AutoCAD SHX Text 07/19/2018

AutoCAD SHX Text 11/21/2018

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text 3544G

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text DRAWING No.

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

FAX 843-745-0436

AutoCAD SHX Text

CHARLESTON, SOUTH CAROLINA 29415

AutoCAD SHX Text

WWW.KCONINC.COM

AutoCAD SHX Text

PHONE 843-745-0434

AutoCAD SHX Text

TOLL 1-800-394-5266

AutoCAD SHX Text

POST OFFICE BOX 70904

AutoCAD SHX Text THESE DRAWINGS AND DESIGNS THEREON ARE THE PROPERTY OF K-CON, INC. AND MAY NOT BE USED IN WHOLE OR INPART WITH OUT THE WRITTEN CONSENT OF K-CON, INC. AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

REV 1

AutoCAD SHX Text

ORIG

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text DRAWING Tlt.

AutoCAD SHX Text JOB No.

AutoCAD SHX Text

(843) 849-6878

AutoCAD SHX Text

MT. PLEASANT, SC 29465

AutoCAD SHX Text

P.O. BOX 2132

AutoCAD SHX Text

EPIC JOB NO. 18112

AutoCAD SHX Text

COPYRIGHT 2018 THIS DOCUMENT IS THE PROPERTY OF

AutoCAD SHX Text

EPIC ENGINEERING, INC. ANY UNAUTHORIZED REPRODUCTION

AutoCAD SHX Text

OR USE IS PROHIBITED AND SUBJECT TO LEGAL PROSECUTION

AutoCAD SHX Text c

AutoCAD SHX Text 7/19/2019

AutoCAD SHX Text 02/07/2019

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

M E

S

A

G

A R

F I E

L D

J O

I N

T

M

I L

I T

A R

Y

T

R A

I N

I N

G

C

E N

T E

R

N

E W

T O

N

F

A L

L S

O

H

D F

B

U I L

D I N

G

A

E4

G

AutoCAD SHX Text G

AutoCAD SHX Text

#4 AWG

AutoCAD SHX Text

BARE COPPER

AutoCAD SHX Text

STEEL COLUMN

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text

FOOTING

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

EXOTHERMIC WELD TO COLUMN WEB

AutoCAD SHX Text

1 1/2" PVC CONDUIT "KICK PIPE" 4"

AutoCAD SHX Text

ABOVE AND 4" BELOW FLOOR SLAB

AutoCAD SHX Text

EXOTHERMIC WELD - CABLE TO CABLE

AutoCAD SHX Text

2'-0" ABOVE FINISHED FLOOR

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text

%%UAT BUILDING STEEL

AutoCAD SHX Text

%%UTYPICAL GROUNDING CONNECTION

AutoCAD SHX Text

FOUNDATION REBAR

AutoCAD SHX Text

GROUND ROD

AutoCAD SHX Text

10' CU. CLAD

AutoCAD SHX Text

#4 AWG

AutoCAD SHX Text

TO SERVICE

AutoCAD SHX Text

DISCONNECT

AutoCAD SHX Text

#4 AWG

AutoCAD SHX Text

BARE COPPER

AutoCAD SHX Text

#4 AWG

AutoCAD SHX Text

BARE COPPER

AutoCAD SHX Text

CU.

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text %%uPOWER RISER DIAGRAM

AutoCAD SHX Text

NONE

AutoCAD SHX Text

UNDERGROUND WATER

AutoCAD SHX Text

METALLIC/COPPER

AutoCAD SHX Text

#4 AWG CU.

AutoCAD SHX Text

EXOTHERMIC WELD

AutoCAD SHX Text

CONNECTION

AutoCAD SHX Text

PROVIDE SUPPLEMENTAL

AutoCAD SHX Text

GROUNDING ELECTRODE IF

AutoCAD SHX Text

MEASURED EARTH RESISTANCE

AutoCAD SHX Text

IS MORE THAN 25 OHMS

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

ABOVE GROUND

AutoCAD SHX Text

GAS PIPING

AutoCAD SHX Text

(BONDED TO

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

GROUND)

AutoCAD SHX Text

DIELECTRIC

AutoCAD SHX Text

ISOLATOR

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text

UNDERGROUND

AutoCAD SHX Text

GAS PIPING

AutoCAD SHX Text

(NOT BONDED

AutoCAD SHX Text

TO GROUND)

AutoCAD SHX Text

LEVEL

AutoCAD SHX Text

PIPING

AutoCAD SHX Text TO POWER COMPANY'S SERVICE POINT, COORDINATE LOCATION AND DETAILS WITH POWER COMPANY

AutoCAD SHX Text 4#3/O, 2 1/2"C

AutoCAD SHX Text

PANEL "A" 208/120V, 3 ,4W, 225A

AutoCAD SHX Text

4-POINT GROUND BLOCK

AutoCAD SHX Text

TO SERVE AS INTERSYSTEM

AutoCAD SHX Text

BONDING GROUND BAR.

AutoCAD SHX Text

AutoCAD SHX Text GROUND IN ACCORDANCE WITH NEC, ART. 250 TO BLDG. STEEL & 3/4" x 10' CU. CLAD GROUND ROD.

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text N

AutoCAD SHX Text

NOTE 9 SHEET E1

AutoCAD SHX Text

AMP MAINS

AutoCAD SHX Text

AutoCAD SHX Text

AMP MAIN BKR

AutoCAD SHX Text

SURFACE

AutoCAD SHX Text X

AutoCAD SHX Text

PANEL SHALL BE PROVIDED WITH SEPARATE GROUND BUS.

AutoCAD SHX Text

TOTAL CONNECTED LOAD KVA

AutoCAD SHX Text

ALL BREAKERS SHALL HAVE A MINIMUM INTERRUPTING RATING OF AMPS.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

CKT

AutoCAD SHX Text No.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PANEL

AutoCAD SHX Text

V, PH, W, 60 HZ

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

POLE

AutoCAD SHX Text

AMP

AutoCAD SHX Text

BREAKERS

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KVA

AutoCAD SHX Text

POLE

AutoCAD SHX Text

AMP

AutoCAD SHX Text

BREAKERS

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

LOAD

AutoCAD SHX Text

CKT

AutoCAD SHX Text No.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208/120

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text 10,000 *

AutoCAD SHX Text

COORIDOR/KIT LTG

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.9

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

CU-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 5.44

AutoCAD SHX Text

OFFICE/R.R. LTG

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.8

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MULTIPURPOSE LTG

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1.41

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text

WATER COOLER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.65

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

KITCHEN

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FACP

AutoCAD SHX Text

SPARE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2.0

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IT ROOM (CABINET)

AutoCAD SHX Text

EF-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.3

AutoCAD SHX Text 2.0

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IT ROOM (MECH. WALL)

AutoCAD SHX Text

TELE. BKBD.

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

EXTERIOR RECP

AutoCAD SHX Text

FURNACE 1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1.7

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text

RECEPTACLES

AutoCAD SHX Text 1.8

AutoCAD SHX Text 1.6

AutoCAD SHX Text 1.0

AutoCAD SHX Text 1.6

AutoCAD SHX Text 1.8

AutoCAD SHX Text 1.6

AutoCAD SHX Text 1.0

AutoCAD SHX Text

PAC-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 13.0

AutoCAD SHX Text 16.6

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

PAC-2

AutoCAD SHX Text

* VERIFY AIC RATING WITH TRANSFORMER FAULT CURRENT ** PROVIDE CIRCUIT BREAKER WITH LOCK-ON CLIP AND PAINTED RED *** PROVIDE GFI TYPE CIRCUIT BREAKER.

AutoCAD SHX Text 0.4

AutoCAD SHX Text 0.4

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

IT ROOM RECEPTACLE

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

IT ROOM RECEPTACLE

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IT ROOM RECEPTACLE

AutoCAD SHX Text 0.2

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

IT ROOM RECEPTACLE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

200A (MAIN)

AutoCAD SHX Text 0.1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WH-1

AutoCAD SHX Text

RAD

AutoCAD SHX Text 09/29/2017

AutoCAD SHX Text 07/12/2018

AutoCAD SHX Text

ACT

AutoCAD SHX Text 07/19/2018

AutoCAD SHX Text 11/21/2018

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text 3544G

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text DRAWING No.

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

FAX 843-745-0436

AutoCAD SHX Text

CHARLESTON, SOUTH CAROLINA 29415

AutoCAD SHX Text

WWW.KCONINC.COM

AutoCAD SHX Text

PHONE 843-745-0434

AutoCAD SHX Text

TOLL 1-800-394-5266

AutoCAD SHX Text

POST OFFICE BOX 70904

AutoCAD SHX Text THESE DRAWINGS AND DESIGNS THEREON ARE THE PROPERTY OF K-CON, INC. AND MAY NOT BE USED IN WHOLE OR INPART WITH OUT THE WRITTEN CONSENT OF K-CON, INC. AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

REV 1

AutoCAD SHX Text

ORIG

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text DRAWING Tlt.

AutoCAD SHX Text JOB No.

AutoCAD SHX Text

(843) 849-6878

AutoCAD SHX Text

MT. PLEASANT, SC 29465

AutoCAD SHX Text

P.O. BOX 2132

AutoCAD SHX Text

EPIC JOB NO. 18112

AutoCAD SHX Text

COPYRIGHT 2018 THIS DOCUMENT IS THE PROPERTY OF

AutoCAD SHX Text

EPIC ENGINEERING, INC. ANY UNAUTHORIZED REPRODUCTION

AutoCAD SHX Text

OR USE IS PROHIBITED AND SUBJECT TO LEGAL PROSECUTION

AutoCAD SHX Text c

AutoCAD SHX Text 7/19/2019

AutoCAD SHX Text 02/07/2019

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

PANEL SCHEDULES

M1

A

M E

S

A

G

A R

F I E

L D

J O

I N

T

M

I L

I T

A R

Y

T

R A

I N

I N

G

C

E N

T E

R

N

E W

T O

N

F

A L

L S

O

H

D F

B

U I L

D I N

G

A

T

LOUVER SCHEDULE

AutoCAD SHX Text

(IN W.G.)

AutoCAD SHX Text

PRESSURE

AutoCAD SHX Text 0.150

AutoCAD SHX Text

DROP

AutoCAD SHX Text

INTAKE/EXHAUST

AutoCAD SHX Text L-1

AutoCAD SHX Text

MARK

AutoCAD SHX Text 24x12

AutoCAD SHX Text 0.41

AutoCAD SHX Text

AutoCAD SHX Text

TYPE

AutoCAD SHX Text (W x H)

AutoCAD SHX Text

FACE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

VELOCITY

AutoCAD SHX Text

(SQFT)

AutoCAD SHX Text

AREA

AutoCAD SHX Text

FREE

AutoCAD SHX Text

(FPM)

AutoCAD SHX Text

AIR

AutoCAD SHX Text

GREENHECK MODEL FDS-602

AutoCAD SHX Text

AND MODEL NO.

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text 0.01

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

(OZ./SQFT)

AutoCAD SHX Text

PENETRATION

AutoCAD SHX Text

WATER

AutoCAD SHX Text

AIR DEVICE SCHEDULE

AutoCAD SHX Text

MARK

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

TYPE

AutoCAD SHX Text 8"

AutoCAD SHX Text 24x24

AutoCAD SHX Text 10"

AutoCAD SHX Text 24x24

AutoCAD SHX Text

NECK

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

SIZE

AutoCAD SHX Text

FACE

AutoCAD SHX Text

AND MODEL NO.

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

AutoCAD SHX Text

4-WAY

AutoCAD SHX Text

4-WAY

AutoCAD SHX Text

AutoCAD SHX Text

PATTERN

AutoCAD SHX Text

AIR -

AutoCAD SHX Text

MAX.

AutoCAD SHX Text

NC

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

RG

AutoCAD SHX Text 24x12

AutoCAD SHX Text 22x10

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2,3,4,5

AutoCAD SHX Text

NAILOR MODEL 51FP-L

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text

NAILOR MODEL ARNSA-08-L

AutoCAD SHX Text

NAILOR MODEL ARNSA-10-L

AutoCAD SHX Text C

AutoCAD SHX Text 12"

AutoCAD SHX Text 24x24

AutoCAD SHX Text

4-WAY

AutoCAD SHX Text

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text

NAILOR MODEL ARNSA-12-L

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

RG1

AutoCAD SHX Text 24x24

AutoCAD SHX Text 22x22

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2,3,4

AutoCAD SHX Text

NAILOR MODEL 51PR-L

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text

A/### A.F.F. A.F.G. AHU CD DN. HP O.A. REFRIG. RG TYP.

AutoCAD SHX Text

%%ULEGEND

AutoCAD SHX Text

SUPPLY AIR (S.A.)

AutoCAD SHX Text

RETURN AIR (R.A.)

AutoCAD SHX Text

EXHAUST AIR (E.A.)

AutoCAD SHX Text

MANUAL VOLUME DAMPER (VD)

AutoCAD SHX Text

THERMOSTAT

AutoCAD SHX Text

SMOKE DETECTOR

AutoCAD SHX Text

MOTORIZED DAMPER ACTUATOR

AutoCAD SHX Text

TURNING VANE

AutoCAD SHX Text

AIR DEVICE MARK/CFM

AutoCAD SHX Text

ABOVE FINISH FLOOR

AutoCAD SHX Text

ABOVE FINISH GRADE

AutoCAD SHX Text

AIR HANDLING UNIT

AutoCAD SHX Text

CONDENSATE

AutoCAD SHX Text

DOWN

AutoCAD SHX Text

HEAT PUMP

AutoCAD SHX Text

OUTSIDE AIR

AutoCAD SHX Text

REFRIGERANT

AutoCAD SHX Text

RETURN AIR GRILL

AutoCAD SHX Text

TYPICAL

AutoCAD SHX Text S

AutoCAD SHX Text T

AutoCAD SHX Text M

AutoCAD SHX Text NOTES 1. PROVIDE ALL MATERIALS AND LABOR FOR COMPLETE AND PROPERLY FUNCTIONING PROVIDE ALL MATERIALS AND LABOR FOR COMPLETE AND PROPERLY FUNCTIONING MECHANICAL SYSTEMS. WARRANTY ALL WORK AND ALL MATERIALS, EQUIPMENT AND DEVICES FOR A PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. 2. WORK SHALL CONFORM TO OR MEET THE REQUIREMENTS OF THE MOST CURRENT WORK SHALL CONFORM TO OR MEET THE REQUIREMENTS OF THE MOST CURRENT EDITION OF: A: INTERNATIONAL MECHANICAL CODE - 2015 B: SMACNA C: ASHRAE D: ALL FEDERAL, STATE AND LOCAL CODES AND ORDINANCES WHICH APPLY TO THIS WORK. 3. DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO BE SCALED DRAWINGS ARE DIAGRAMMATIC IN NATURE AND ARE NOT INTENDED TO BE SCALED FOR DIMENSIONS. 4. ALL MATERIALS, EQUIPMENT AND DEVICES SHALL MEET THE REQUIREMENTS OF UL ALL MATERIALS, EQUIPMENT AND DEVICES SHALL MEET THE REQUIREMENTS OF UL WHERE UL STANDARDS ARE ESTABLISHED FOR THOSE ITEMS. ALL ITEMS SHALL BE CLASSIFIED BY UL AS SUITABLE FOR THE PURPOSE USED. 5. ALL ITEMS SHALL BE NEW AND ALL MATERIALS/EQUIPMENT/DEVICES SHALL BE ALL ITEMS SHALL BE NEW AND ALL MATERIALS/EQUIPMENT/DEVICES SHALL BE CURRENT PRODUCTS BY MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH PRODUCTS. 6. COORDINATE LOCATION OF MECHANICAL WORK WITH OTHER TRADES TO AVOID COORDINATE LOCATION OF MECHANICAL WORK WITH OTHER TRADES TO AVOID CONFLICTS AND INTERFERENCES. 7. INSTALL ALL EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER'S INSTALL ALL EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER'S WRITTEN, PRINTED INSTRUCTIONS AND RECOMMENDATIONS. 8. PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTIONS AND ACCEPTANCE PROVIDE OWNER WITH CERTIFICATES OF FINAL INSPECTIONS AND ACCEPTANCE FROM AUTHORITY HAVING JURISDICTION. 9. MAKE CONNECTIONS FROM MECHANICAL EQUIPMENT TO DUCTWORK USING FLEXIBLE MAKE CONNECTIONS FROM MECHANICAL EQUIPMENT TO DUCTWORK USING FLEXIBLE DUCT CONNECTIONS. 10. ALL EQUIPMENT, PIPE AND DUCTWORK ABOVE CEILING SHALL BE SUPPORTED FROM ALL EQUIPMENT, PIPE AND DUCTWORK ABOVE CEILING SHALL BE SUPPORTED FROM BUILDING STRUCTURE ABOVE. 11. DUCT SIZES INDICATED ARE NET FREE INSIDE DIMENSIONS OF RECTANGULAR METAL DUCT SIZES INDICATED ARE NET FREE INSIDE DIMENSIONS OF RECTANGULAR METAL DUCT. AT CONTRACTOR'S OPTION, EQUIVALENT SIZE ROUND DUCT MAY BE USED. 12. PROVIDE FLOAT SWITCH IN ALL SECONDARY DRAIN PANS TO SHUT OFF UNITS PROVIDE FLOAT SWITCH IN ALL SECONDARY DRAIN PANS TO SHUT OFF UNITS WHEN DRAINS BECOME OBSTRUCTED. 13. FURNISH AND INSTALL ALL MANUAL DAMPERS INDICATED ON DRAWINGS OR FURNISH AND INSTALL ALL MANUAL DAMPERS INDICATED ON DRAWINGS OR NECESSARY TO PROPERLY DISTRIBUTE AND BALANCE AIR. ALL INACCESSIBLE VOLUME DAMPERS SHALL BE PROVIDED WITH REMOTE CONCEALED DAMPER REGULATORS. 14. BALANCE SYSTEM TO AIR FLOWS SHOWN ON FLOOR PLAN. PROVIDE TEST AND BALANCE SYSTEM TO AIR FLOWS SHOWN ON FLOOR PLAN. PROVIDE TEST AND BALANCE REPORT TO ENGINEER FOR APPROVAL. 15. WHERE PIPES PENETRATE FIRE RATED WALLS, FLOORS OR CEILING, SEAL OPENING WHERE PIPES PENETRATE FIRE RATED WALLS, FLOORS OR CEILING, SEAL OPENING AROUND PIPES WITH U.L. LISTED FIRE STOPPING MATERIAL TO MAINTAIN THE FIRE RATING OF THE WALL, FLOOR OR CEILING IN ACCORDANCE WITH U.L. LISTED DESIGN. SUBMIT U.L. DESIGN FOR FIRE RATED PENETRATIONS SEALS TO ARCHITECT/ENGINEER FOR APPROVAL PRIOR TO START OF WORK. 16. ALL BUILDING PENETRATIONS SHALL BE COORDINATED WITH ARCHITECT. SEE ALL BUILDING PENETRATIONS SHALL BE COORDINATED WITH ARCHITECT. SEE ARCHITECTURAL DRAWINGS FOR PENETRATION DETAILS. 17. PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH IBC 2015. SUBMIT SHOP PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH IBC 2015. SUBMIT SHOP DRAWINGS FOR APPROVAL. 18. ALL CONDENSATE PIPING SHALL BE INSULATED WITH 3/4"-THICK CLOSED CELL ALL CONDENSATE PIPING SHALL BE INSULATED WITH 3/4"-THICK CLOSED CELL EPDM ELASTOMERIC THERMAL INSULATION AS MANUFACTURED BY AEROCEL. ALL REFRIGERANT PIPING SHALL BE INSULATED WITH 1 1/2" THICK CLOSED CELL EPDM ELASTOMERIC THERMAL INSULATION AS MANUFACTURED BY AEROCEL. 19. ALL DUCTWORK SHALL BE INSULATED WITH 3"-THICK FIBERGLASS DUCTWRAP WITH ALL DUCTWORK SHALL BE INSULATED WITH 3"-THICK FIBERGLASS DUCTWRAP WITH FOIL FACE (OWENS CORNING TYPE 75 OR APPROVED EQUAL). 20. ALL DUCTWORK SHALL BE GALVANIZED STEEL. ALL JOINTS AND SEAMS SHALL BE ALL DUCTWORK SHALL BE GALVANIZED STEEL. ALL JOINTS AND SEAMS SHALL BE CLEANED, COATED AND SEALED WITH MASTIC OR MASTIC TAPE PRIOR TO APPLYING THE EXTERNAL INSULATION. 21. ALL MATERIALS LOCATED WITHIN THE RETURN AIR PLENUM SHALL BE PLENUM ALL MATERIALS LOCATED WITHIN THE RETURN AIR PLENUM SHALL BE PLENUM RATED. 22. ALL S.A. AND R.A. GALVANIZED EXTERIOR DUCTWORK SHALL BE INSULTED WITH ALL S.A. AND R.A. GALVANIZED EXTERIOR DUCTWORK SHALL BE INSULTED WITH 2"-THICK CLOSED CELL RUBBER (TYP).

AutoCAD SHX Text NOTES: 1. PROVIDE WITH OPPOSED BLADE DAMPER. PROVIDE WITH OPPOSED BLADE DAMPER. 2. PROVIDE WITH ALUMINUM CONSTRUCTION AND STANDARD FINISH. PROVIDE WITH ALUMINUM CONSTRUCTION AND STANDARD FINISH. 3. PROVIDE NAILOR OR APPROVED EQUAL BY HART & COOLEY, PRICE, METALAIRE OR TITUS. PROVIDE NAILOR OR APPROVED EQUAL BY HART & COOLEY, PRICE, METALAIRE OR TITUS. 4. PROVIDE SQUARE TO ROUND TRANSITION AS NECESSARY. PROVIDE SQUARE TO ROUND TRANSITION AS NECESSARY. 5. PROVIDE TO ACCEPT 20x20x1 PLEATED FILTERS. CONTRACTOR SHALL PROVIDE INITIAL FILTERS.PROVIDE TO ACCEPT 20x20x1 PLEATED FILTERS. CONTRACTOR SHALL PROVIDE INITIAL FILTERS.

AutoCAD SHX Text NOTES: 1. PROVIDE WITH A BIRDSCREEN. PROVIDE WITH A BIRDSCREEN. 2. PROVIDE WITH ALUMINUM CONSTRUCTION AND STANDARD FINISH. PROVIDE WITH ALUMINUM CONSTRUCTION AND STANDARD FINISH. 3. COLOR BY ARCHITECT. PROVIDE SELECTION OPTIONS. COLOR BY ARCHITECT. PROVIDE SELECTION OPTIONS. 4. PROVIDE NAILOR OR EQUAL BY POTTORFF, RUSKIN, UNITED AIR, NCA, CSI, OR AMERICAN WARMING AND VENTILATING.PROVIDE NAILOR OR EQUAL BY POTTORFF, RUSKIN, UNITED AIR, NCA, CSI, OR AMERICAN WARMING AND VENTILATING.

AutoCAD SHX Text

GREENHECK

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

MODEL NO.

AutoCAD SHX Text

EF-1

AutoCAD SHX Text

IN-LINE

AutoCAD SHX Text

EXHAUST

AutoCAD SHX Text

AutoCAD SHX Text 0.250

AutoCAD SHX Text

DIRECT

AutoCAD SHX Text 1/12

AutoCAD SHX Text 120/1/60

AutoCAD SHX Text

SONES (MAXIMUM)

AutoCAD SHX Text

MOTOR - HP (WATTS)

AutoCAD SHX Text ELECTRICAL - V/%%C/Hz

AutoCAD SHX Text

DRIVE

AutoCAD SHX Text

AIR QUANTITY - CFM

AutoCAD SHX Text

EXT. S.P. - IN. W.G.

AutoCAD SHX Text

FAN TYPE

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FAN SCHEDULE

AutoCAD SHX Text 1,2,3

AutoCAD SHX Text NOTES: 1. PROVIDE A UNIT MOUNTED PROVIDE A UNIT MOUNTED DISCONNECT SWITCH, WHITE PLASTIC GRILLE, FAN MOUNTED SPEED CONTROLLER, BACKDRAFT DAMPER, WALL CAP AND GEMINI ISOLATOR KIT. 2. CONTROL WITH OCCUPANCY CONTROL WITH OCCUPANCY SENSORS. ONE IN EACH TOILET. 3. PROVIDE COOK OR APPROVED PROVIDE COOK OR APPROVED EQUAL BY GREENHECK OR TWIN CITY.

AutoCAD SHX Text

SQ-85-D

AutoCAD SHX Text 7.4

AutoCAD SHX Text

GAS FIRED FURNACE WITH COOLING COIL SCHEDULE

AutoCAD SHX Text

FURNACE

AutoCAD SHX Text

FAN

AutoCAD SHX Text

INPUT - MBTUH

AutoCAD SHX Text

OUTSIDE AIR - CFM

AutoCAD SHX Text ELECTRICAL - V/%%C/Hz

AutoCAD SHX Text

EXT S.P. - IN. W.G.

AutoCAD SHX Text

SUPPLY AIR - CFM

AutoCAD SHX Text

BLOWER MOTOR - HP (MIN.)

AutoCAD SHX Text

HEATING

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

MODEL NO.

AutoCAD SHX Text

MARK

AutoCAD SHX Text

MARK

AutoCAD SHX Text

COILS

AutoCAD SHX Text

AIR CONDITIONER

AutoCAD SHX Text

PRESSURE DROP - IN. W.G.

AutoCAD SHX Text

SENSIBLE CAPACITY - MBTUH

AutoCAD SHX Text

TOTAL CAPACITY - MBTUH

AutoCAD SHX Text

MATCHED COILS

AutoCAD SHX Text

MAX. OVER CURRENT PROT. (AMPS)

AutoCAD SHX Text

POWER CONNECTION

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

FLUE SIZE - OUTLET

AutoCAD SHX Text

FLUE SIZE - INLET

AutoCAD SHX Text

CONDENSING UNIT

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

SYSTEM SEER

AutoCAD SHX Text

MANUFACTURER (SEE NOTE 5)

AutoCAD SHX Text

CONDENSING UNIT MODEL NO.

AutoCAD SHX Text AMBIENT AIR TEMP. - %%DF db

AutoCAD SHX Text

PROT. RTG. RECMD. (AMPS)

AutoCAD SHX Text

COMPR. RLA/FAN MOTOR FLA

AutoCAD SHX Text

MINIMUM CIRCUIT AMPACITY

AutoCAD SHX Text

APPROXIMATE WEIGHT - LB.

AutoCAD SHX Text ELECTRICAL - V/%%C/Hz

AutoCAD SHX Text

COMPRESSORS - NO.

AutoCAD SHX Text F-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 120/1/60

AutoCAD SHX Text 0.5

AutoCAD SHX Text 0.75

AutoCAD SHX Text

TRANE

AutoCAD SHX Text

AutoCAD SHX Text 120/1/60

AutoCAD SHX Text 2"

AutoCAD SHX Text 3"

AutoCAD SHX Text C-1

AutoCAD SHX Text

CU-1

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 0.4

AutoCAD SHX Text

4PXCDU60BS3HAA

AutoCAD SHX Text

TUC1D120A9601A

AutoCAD SHX Text

AutoCAD SHX Text 208/1/60

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 25.1/1.05

AutoCAD SHX Text

AutoCAD SHX Text 1-7

AutoCAD SHX Text 4A7A3060D1000P

AutoCAD SHX Text

AMERICAN STANDARD

AutoCAD SHX Text

AutoCAD SHX Text

PAC-1

AutoCAD SHX Text

MARK

AutoCAD SHX Text

FAN

AutoCAD SHX Text

OUTSIDE AIR - CFM

AutoCAD SHX Text

TOTAL CAPACITY - MBTUH

AutoCAD SHX Text

SENSIBLE CAPACITY - MBTUH

AutoCAD SHX Text

BLOWER MOTOR - HP (MIN.)

AutoCAD SHX Text

EXT. S.P. - IN W.G.

AutoCAD SHX Text

SUPPLY AIR - CFM

AutoCAD SHX Text

PACKAGE GAS AIR CONDITIONER SCHEDULE

AutoCAD SHX Text

HEATING

AutoCAD SHX Text

CONDENSING

AutoCAD SHX Text

COMPR. RLA/FAN MOTOR FLA

AutoCAD SHX Text

COMPRESSORS - NO.

AutoCAD SHX Text AMBIENT AIR TEMP. - %%dF db

AutoCAD SHX Text ENT. AIR TEMP. - %%dF db/wb

AutoCAD SHX Text

OUTPUT - MBTUH

AutoCAD SHX Text

INPUT - MBTUH

AutoCAD SHX Text

MANUFACTURER

AutoCAD SHX Text

MINIMUM CIRCUIT AMPACITY

AutoCAD SHX Text

APPROXIMATE WEIGHT - LB.

AutoCAD SHX Text

PROT. RTG. RECMD. (AMPS)

AutoCAD SHX Text ELECTRICAL V/%%c/Hz

AutoCAD SHX Text

COP - HIGH TEMP. HEATING AT ARI

AutoCAD SHX Text

EER/SEER AT ARI

AutoCAD SHX Text

NOTES

AutoCAD SHX Text

MODEL NO.

AutoCAD SHX Text

COOLING

AutoCAD SHX Text 1,2,3,4,5,6,7

AutoCAD SHX Text

YSC090H3EHA

AutoCAD SHX Text 11.2/12.7

AutoCAD SHX Text

AutoCAD SHX Text

AMERICAN STANDARD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208/3/60

AutoCAD SHX Text

AutoCAD SHX Text 25.0/3.3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 80/67

AutoCAD SHX Text

AutoCAD SHX Text 71.8

AutoCAD SHX Text 2.03

AutoCAD SHX Text 0.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text NOTES: 1. EXTERNAL STATIC PRESSURE IS FOR DUCTWORK SYSTEM ONLY. EXTERNAL STATIC PRESSURE IS FOR DUCTWORK SYSTEM ONLY. FILTERS, COILS AND CASING LOSSES ARE INTERNAL. 2. DIRECT DRIVEN BLOWERS SHALL BE PROVIDED WITH 3-SPEED DIRECT DRIVEN BLOWERS SHALL BE PROVIDED WITH 3-SPEED MOTORS. BELT DRIVEN BLOWERS SHALL BE PROVIDED WITH A SECOND DRIVE SET (PULLEY AND SHEAVES) IF NECESSARY TO BALANCE THE SYSTEM WITH ACTUAL FIELD CONDITIONS. 3. PROVIDE WITH 1" PLEATED, 30% EFFICIENT THROWAWAY PROVIDE WITH 1" PLEATED, 30% EFFICIENT THROWAWAY FILTERS. FILTERS SHALL BE REPLACEABLE WITHOUT THE NEED FOR ANY TOOLS. 4. PROVIDE A 7-DAY PROGRAMMABLE THERMOSTAT. PROVIDE A 7-DAY PROGRAMMABLE THERMOSTAT. 5. PROVIDE TRANE OR EQUAL BY CARRIER, LENNOX, OR YORK. PROVIDE TRANE OR EQUAL BY CARRIER, LENNOX, OR YORK. 6. PROVIDE WITH LOW AMBIENT CONTROL. PROVIDE WITH LOW AMBIENT CONTROL. 7. PROVIDE WITH COSATRON SERIES 2000 AIR PURIFICATION PROVIDE WITH COSATRON SERIES 2000 AIR PURIFICATION FILTER, * KW RATING AT THE SPECIFIED VOLTAGE.

AutoCAD SHX Text

PAC-2

AutoCAD SHX Text 1,2,3,4,5,6,7

AutoCAD SHX Text

YSC120H3EHA

AutoCAD SHX Text 11.3/-

AutoCAD SHX Text

AutoCAD SHX Text

AMERICAN STANDARD

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 208/3/60

AutoCAD SHX Text

AutoCAD SHX Text 19.6/3.3

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 80/67

AutoCAD SHX Text

AutoCAD SHX Text 93.0

AutoCAD SHX Text 2.75

AutoCAD SHX Text 0.5

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text 14"

AutoCAD SHX Text 24x24

AutoCAD SHX Text

4-WAY

AutoCAD SHX Text

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text

NAILOR MODEL ARNS-14-L

AutoCAD SHX Text NOTES: 1. EXTERNAL STATIC PRESSURE IS FOR DUCTWORK SYSTEM ONLY. EXTERNAL STATIC PRESSURE IS FOR DUCTWORK SYSTEM ONLY. FILTERS, COILS AND CASING LOSSES AREA INTERNAL. 2. DIRECT DRIVEN BLOWERS SHALL BE PROVIDED WITH 3-SPEED DIRECT DRIVEN BLOWERS SHALL BE PROVIDED WITH 3-SPEED MOTORS. BELT DRIVEN BLOWERS SHALL BE PROVIDED WITH A SECOND DRIVE SET (PULLEYS AND SHEAVES) NECESSARY TO BALANCE THE SYSTEM WITH ACTUAL FIELD CONDITIONS. 3. PROVIDE WITH 1" PLEATED, 30% EFFICIENT THROWAWAY FILTERS. PROVIDE WITH 1" PLEATED, 30% EFFICIENT THROWAWAY FILTERS. FILTERS SHALL BE REPLACEABLE WITHOUT THE NEED FOR ANY TOOLS. 4. PROVIDE AIR HANDLING UNIT WITH A SINGLE POINT ELECTRICAL PROVIDE AIR HANDLING UNIT WITH A SINGLE POINT ELECTRICAL CONNECTION. 5. PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT BY HONEYWELL, PROVIDE 7-DAY PROGRAMMABLE THERMOSTAT BY HONEYWELL, MODEL # RTH7600D OR APPROVED EQUAL. 6. PROVIDE CARRIER OR EQUAL BY TRANE, LENOX OR YORK. PROVIDE CARRIER OR EQUAL BY TRANE, LENOX OR YORK. 7. PROVIDE WITH LP CONVERSION KIT AND RETAIN NATURAL GAS PROVIDE WITH LP CONVERSION KIT AND RETAIN NATURAL GAS ORIFICES. TURN OVER ORIFICES TO OWNER FOR FUTURE COME BACK TO NATURAL GAS. ** VERIFY TDH VS. TUH WITH MANUFACTURER TO ENSURE REQUIRED VERIFY TDH VS. TUH WITH MANUFACTURER TO ENSURE REQUIRED CLEARANCES AND ACCESS IS MAINTAINED.

AutoCAD SHX Text

RETURN

AutoCAD SHX Text

RG2

AutoCAD SHX Text 24x24

AutoCAD SHX Text 12x12

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 2,3,4

AutoCAD SHX Text

NAILOR MODEL 51PR-L

AutoCAD SHX Text

CEILING

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text E

AutoCAD SHX Text

SUPPLY

AutoCAD SHX Text

CEILING

AutoCAD SHX Text 8"

AutoCAD SHX Text 12x12

AutoCAD SHX Text

FOR T-BAR LAY-IN CEILINGS

AutoCAD SHX Text

NAILOR MODEL ARNSA-08-L

AutoCAD SHX Text

4-WAY

AutoCAD SHX Text

AutoCAD SHX Text 1,2,3,4

AutoCAD SHX Text

NOTES, LEGEND, SCHEDULES

AutoCAD SHX Text

RAD

AutoCAD SHX Text 09/29/2017

AutoCAD SHX Text 07/12/2018

AutoCAD SHX Text

ACT

AutoCAD SHX Text 07/19/2018

AutoCAD SHX Text 11/21/2018

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text 3544G

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text DRAWING No.

AutoCAD SHX Text

TITLE

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

FAX 843-745-0436

AutoCAD SHX Text

CHARLESTON, SOUTH CAROLINA 29415

AutoCAD SHX Text

WWW.KCONINC.COM

AutoCAD SHX Text

PHONE 843-745-0434

AutoCAD SHX Text

TOLL 1-800-394-5266

AutoCAD SHX Text

POST OFFICE BOX 70904

AutoCAD SHX Text THESE DRAWINGS AND DESIGNS THEREON ARE THE PROPERTY OF K-CON, INC. AND MAY NOT BE USED IN WHOLE OR INPART WITH OUT THE WRITTEN CONSENT OF K-CON, INC. AND ANY INFRINGEMENT WILL BE SUBJECT TO LEGAL ACTION

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

REV 1

AutoCAD SHX Text

ORIG

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text DRAWING Tlt.

AutoCAD SHX Text JOB No.

AutoCAD SHX Text

(843) 849-6878

AutoCAD SHX Text

MT. PLEASANT, SC 29465

AutoCAD SHX Text

P.O. BOX 2132

AutoCAD SHX Text

EPIC JOB NO. 18112

AutoCAD SHX Text

COPYRIGHT 2018 THIS DOCUMENT IS THE PROPERTY OF

AutoCAD SHX Text

EPIC ENGINEERING, INC. ANY UNAUTHORIZED REPRODUCTION

AutoCAD SHX Text

OR USE IS PROHIBITED AND SUBJECT TO LEGAL PROSECUTION

AutoCAD SHX Text c

AutoCAD SHX Text 7/19/2019

AutoCAD SHX Text 02/07/2019

AutoCAD SHX Text

RAD

AutoCAD SHX Text

ACT

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

REV 2

AutoCAD SHX Text

CHECKED BY:

M2

A

M E

S

A

G

A R

F I E

L D

J O

I N

T

M

I L

I T

A R

Y

T

R A

I N

I N

G

C

E N

T E

R

N

E W

T O

N

F

A L

L S

O

H

D F

B

U I L

D I N

G

A

T

PLANTERS. CONDENSATE DRAIN LINE SHALL BE FIELD SHIFTED AS REQUIRED.

AutoCAD SHX Text

COORDINATE TO ENSURE THE CONDENSATE DRAIN FIELD IS LOCATED WITHIN

AutoCAD SHX Text

3" AFG

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text %%uCONDENSATE DRAIN FIELD DETAIL

AutoCAD SHX Text

CONDENSATE DRAIN FROM AHU

AutoCAD SHX Text

4" SAND

AutoCAD SHX Text

%%UNOTES:

AutoCAD SHX Text 1.

AutoCAD SHX Text

STUD WALL OF

AutoCAD SHX Text

BUILDING

AutoCAD SHX Text 2' DEEP x 6" WIDE

AutoCAD SHX Text

TRENCH

AutoCAD SHX Text

3" CORRUGATED DRAIN PIPE

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text

30' LONG COIL WITH HOLES

AutoCAD SHX Text

12" GRAVEL

AutoCAD SHX Text

8" BACKFILL

AutoCAD SHX Text

UNDISTURBED

AutoCAD SHX Text

GROUND

AutoCAD SHX Text

SEAL AT WALL

AutoCAD SHX Text

PENETRATION

AutoCAD SHX Text

PROVIDE SEISMIC RESTRAINTS IN ACCORDANCE WITH IBC 2015 AS MANUFACTURED BY LOOS

AutoCAD SHX Text

& CO.INC, OR APPROVED EQUAL. ACTUAL BRACKETS, ATTACHMENTS TO STRUCTURE AND

AutoCAD SHX Text EQUIPMENT VARY WITH ACTUAL MANUFACTURER PROVIDED. SUBMIT SHOP DRAWINGS FOR APPROVAL.

AutoCAD SHX Text 1.

AutoCAD SHX Text

UNIVERSAL RESTRAINT…