07/24/2017
16670450
Smith Seckman Reid, Inc.
2650 Thousand Oaks BLVD. - Suite 3200 Memphis, Tennessee 38118 Phone: (901) 683 3900 Fax: (901) 683-3990
COVER SHEET
Smith Seckman Reid, Inc.
2650 Thousand Oaks BLVD. - Suite 3200 Memphis, Tennessee 38118 Phone: (901) 683 3900 Fax: (901) 683-3990
CONSTRUCTION PLANS FOR
164th AIRLIFT WING MEMPHIS, TENNESSEE
GENERAL DESCRIPTION OF PROJECT:
REPAIR MUNITIONS STORAGE
PROJECT NO. PYKL132003
CONTRACT NUMBER: W912L7-14-D-0002
DELIVERY ORDER NUMBER: 0004
JULY 24, 2017
BASE MAP: NTS
REPAIR MUNITIONS
STORAGE
PYKL132003
COVER SHEET.DWG
SHEET INDEX
COVER SHEET---
PARTIAL ELECTRICAL DEMOLITION SITE PLANED1.10
E1.10
SHEET DESCRIPTIONSHEET NO.
PROJECT
LOCATION
PARTIAL ELECTRICAL SITE PLAN
E5.01 ELECTRICAL DETAILS
EXISTING CONDITIONS & DEMOLITION PLANC101
SITE LAYOUT & GRADING PLANC102
STRUCTURAL GENERAL NOTES, PLAN & SECTIONSS0.1
GENERAL NOTESC100
ISSUED FOR
CONSTRUCTION
GENERAL NOTES
DESIGN CRITERIA
DESIGN PER INTERNATIONAL BUILDING CODE (2012), UNLESS NOTED OTHERWISE
DEAD LOADS:
MUNITIONS BUILDING: 48 KIPS (PER MANUF.)
LIVE LOADS:
FLOORS: 200 PSF
WIND LOADS (ASCE 7-10):
BASIC WIND SPEED (Vult): 115 MPH
BASIC WIND SPEED (Vasd): 89 MPH
RISK CATEGORY: II
WIND EXPOSURE CATEGORY: C
SEISMIC:
IMPORTANCE FACTOR (Ie): 1
RISK CATEGORY: II
SITE CLASSIFICATION: D
SEISMIC DESIGN CATEGORY: D
MAPPED SPECTRAL RESPONSE ACCELERATION:
Ss: 0.828
S1: 0.293
MAPPED SPECTRAL DESIGN ACCELERATION:
SDS: 0.645
SD1: 0.355
BASIC SEISMIC FORCE RESISTING SYSTEM: PER MANUFACTURER
RESPONSE MODIFICATION COEFFICIENT (R): 1
DEFLECTION AMPLIFICATION FACTOR (Cd): 1
OVERSTRENGTH (Ω): 1
SEISMIC RESPONSE COEFFICIENT (Cs): 0.645
DESIGN BASE SHEAR (V): 54.2 K
ANALYSIS PROCEDURE: EQUIV. LATERAL
FORCE PROCEDURE
MATERIAL STRENGTHS:
CONCRETE (DESIGN PER CURRENT EDITION ACI 318)
SLAB ON GRADE: F'c=4500 PSI (MIN)
ALL REINFORCING STEEL ASTM A615 GRADE 60
FOUNDATIONS:
FOUNDATION TYPE IS SHALLOW FOUNDATIONS OF STRIP AND SPREAD FOOTINGS BEARING
ON IN SITU SOILS WITH THE FOLLOWING SOIL BEARING CAPACITIES
SOIL BEARING (DESIGN MAXIMUM): 1500 PSF
(ASSUMED)
G.C. SHALL OBTAIN THE SERVICES OF A GEOTECHNICAL ENGINEER TO PROVIDE TESTING
TO VERIFY THE EXISTING SOILS ARE CAPABLE OF DEVELOPING THE ASSUMED BEARING
CAPACITIES LISTED ABOVE.
GENERAL NOTES
CONCRETE:
UNLESS NOTED OTHERWISE (UNO) ON THE DRAWINGS, MINIMUM COVER FOR REINFORCING
SHALL BE AS FOLLOWS:
EXPOSED TO EARTH LIQUID OR WEATHER: 3"
SLABS ON GRADE: 2" FROM TOP
ALL REINFORCING SHALL BE HELD SECURELY IN POSITION WITH STANDARD ACCESSORIES
IN CONFORMANCE W/ THE CRSI MANUAL OF STANDARD PRACTICE AND ACI 315 DURING THE
PLACING OF THE CONCRETE.
ALL REINFORCING SHALL BE DETAILED IN ACCORDANCE WITH THE ACI DETAILING MANUAL,
SP-66, THE CRSI MANUAL OF CONCRETE PRACTICE AND ACI 318.
PROVIDE BAR SUPPORTS AND SPACERS IN ACCORDANCE WITH ACI 315 AND CRSI “MANUAL
OF STANDARD PRACTICE.” ALL BAR SUPPORTS IN AREA WHERE CONCRETE WILL BE
EXPOSED SHALL HAVE PLASTIC TIPPED FEET. THE CONTRACTOR IS CAUTIONED THAT CARE
MUST BE EXERCISED TO PREVENT EXPOSURE OF THE TIE WIRE OR OTHER MATERIAL
WHICH MAY CAUSE STAINING OF EXPOSED CONCRETE. PROPER COVER AS INDICATED
ABOVE SHALL BE MAINTAINED ON ALL REINFORCEMENT.
UNLESS NOTED OTHERWISE, SPLICES IN REINFORCING, WHERE PERMITTED, SHALL BE
CLASS BE TENSION SPLICES AS FOLLOWS:
REINFORCING BARS:
f'c
#6 and Smaller #7 and Larger
Other Bars Other BarsTop Bars Top Bars
Class A Class B Class A Class AClass AClass B Class BClass B
3000 psi
4000 psi
5000 psi
44 d b
38 d
34 d
45 d
50 d
57 d
57 d
50 d
45 d
58 d
65 d
74 d
72 d
93 d
62 d
81 d
56 d
55 d
48 d
43 d
56 d
62 d
NOTES:
1. ALL LAPS SHALL BE CLASS B UNLESS NOTED OTHERWISE.
2. BEAMS AND COLUMNS: INCREASE LAPS SHOWN BY 50% IF CLEAR SPACING OF BARS IS LESS
THAN 2d
, OR IF CLEAR COVER OF BARS IS LESS THAN d
3. WALLS, SLABS AND FOOTINGS: INCREASE LAPS SHOWN BY 50% IF CLEAR SPACING OF BARS IS
LESS THAN 2d
, OR IF CLEAR COVER OF BARS IS LESS THAN d
4. INCREASE LAPS BY 25% FOR GRADE 75 REINFORCEMENT.
5. INCREASE LAPS BY 33% FOR LIGHTWEIGHT CONCRETE.
LAP SPLICE SCHEDULE
ALL HOOKS IN REINFORCING BARS SHALL BE ACI STANDARD HOOKS, U.N.O.
THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, TECHNIQUES, PROCEDURES OR SEQUENCES. FOR THE ACTS OR OMISSIONS OF
THE CONTRACTOR, OR ANY OTHER PERSONS PERFORMING THE WORK, OR FOR THE FAILURE OF
ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
CONTRACTOR TO VERIFY ALL DIMENSIONS WITH ELECTRICAL AND CIVIL DRAWINGS.
SEE ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND PLUMBING DRAWINGS FOR EMBEDS,
OPENINGS, SLEEVES, ETC. NOT SHOWN ON THE STRUCTURAL DRAWINGS.
EMBEDMENT FOR EXPANSION BOLTS SHALL BE 3-1/4" MINIMUM FOR 3/4" DIAMETER BOLTS IN
CONCRETE.
ANY ENGINEERING DESIGN PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW SHALL BEAR THE
SEAL OF AN ENGINEER REGISTERED IN THE STATE OF THE PROJECT.
GENERAL CONTRACTOR MUST REVIEW AND APPROVE SHOP DRAWINGS PRIOR TO SUBMITTAL TO
ARCHITECT/ENGINEER. SUBMITTALS WHICH DO NOT CONTAIN THE CONTRACTORS SHOP DRAWING
OR STAMP OR HAVE BEEN MERELY "RUBBER STAMPED" SHALL BE RETURNED WITHOUT REVIEW.
V
1. INSPECTION OF REINFORCING STEEL,
INCLUDING PRESTRESSING TENDONS,
AND PLACEMENT.
--- X
ACI 318: 3.5, 7.1-7.7
1910.4
2. INSPECTION OF REINFORCING STEEL
WELDING IN ACCORDANCE WITH TABLE
1705.2.2, ITEM 2B.
AWS D1.4
ACI 318:3.5.2
3. INSPECTION OF ANCHORS CAST IN
CONCRETE WHERE ALLOWABLE LOADS
HAVE BEEN INCREASED OR WHERE
STRENGTH DESIGN IS USED.
X
ACI 318:8.1.3, 21.2.8 1908.5, 1909.1
4. INSPECTION OF ANCHORS
POST-INSTALLED IN HARDENED
CONCRETE MEMBERS
--- X
ACI 318: 3.8.6, 8.1.3, 21.2.8
1909.1
6. AT THE TIME OF FRESH CONCRETE IS
SAMPLED TO FABRICATE SPECIMENS
FOR STRENGTH TESTS, PERFORM
SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE
CONCRETE.
X ---
ASTM C172
ASTM C31
ACI 318: 5.6, 5.8
1910.10
7. INSPECTION OF CONCRETE AND
SHOTCRETE PLACEMENT FOR PROPER
APPLICATION TECHNIQUES.
X ---
ACI 318: 5.9, 5.10
1910.6, 1910.7, 1910.8
8. INSPECTION FOR MAINTENANCE OF
SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
--- X ACI 318: 5.11-5.13 1910.9
9. INSPECTION OF PRESTRESSED
CONCRETE:
A. APPLICATION OF PRESTRESSING
FORCES.
X
ACI 318: 18.20
ACI 318: 18.18.4
B. GROUTING OF BONDED
PRESTRESSING TENDONS IN THE
SEISMIC FORCE-RESISTING SYSTEM.
X
10. ERECTION OF PRECAST CONCRETE
MEMBERS.
--- X ACI 318: CH. 16 ---
11. VERIFICATION OF IN-SITU CONCRETE
STRENGTH, PRIOR TO STRESSING OF
TENDONS IN POST-TENSIONED
CONCRETE AND PRIOR TO REMOVAL OF
SHORES AND FORMS FROM BEAMS AND
STRUCTURAL SLABS.
--- X ACI 318: 6.2 ---
12. INSPECT FORMWORK FOR SHAPE,
LOCATION, AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
--- X ACI 318: 6.1.1 ---
5. VERIFYING USE OF REQUIRED DESIGN
MIX
--- X
ACI 318: CH. 4,5.2-5.4
1904.2, 1910.2, 1910.3
STATEMENT OF SPECIAL INSPECTIONS
RESPONSIBILITIES OF THE SPECIAL INSPECTOR
FABRICATIONS
1. CONCRETE CONSTRUCTION
THIS STATEMENT OF SPECIAL INSPECTIONS IS SUBMITTED AS REQUIRED FOR BUILDING PERMIT ISSUANCE IN
ACCORDANCE WITH THE SPECIAL INSPECTION AND STRUCTURAL TESTING REQUIREMENTS OF THE
INTERNATIONAL BUILDING CODE. THIS STATEMENT OF SPECIAL INSPECTIONS IS ONLY FOR THE STRUCTURAL
PORTION OF THE WORK. REFER TO OTHER DISCIPLINES FOR OTHER SPECIAL INSPECTION REQUIREMENTS FOR
THIS PROJECT.
THE OWNER OR REGISTERED DESIGN PROFESSIONAL IN CHARGE (ARCHITECT) ACTING AS THE OWNERS AGENT
SHALL EMPLOY ONE OR MORE AGENCIES APPROVED BY THE BUILDING OFFICIAL TO PERFORM INSPECTION
DURING CONSTRUCTION. THESE INSPECTIONS ARE IN ADDITION TO SECTION 110 OF THE IBC. CONTRACTOR IS
RESPONSIBLE TO ENSURE THE INSPECTOR IS PRESENT WHERE WORK REQUIRES PERIODIC OR CONTINUOUS
INSPECTION.
THE INSPECTOR SHALL KEEP RECORDS OF ALL INSPECTIONS AND SHALL FURNISH INSPECTION REPORTS TO
THE BUILDING OFFICIAL, AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. DISCOVERED
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF SUCH
DISCREPANCIES ARE NOT CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE
BUILDING OFFICIAL AND THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE. A FINAL REPORT
DOCUMENTING ALL THE REQUIRED SPECIAL INSPECTIONS AND TESTING, AND CORRECTION OF ANY
DISCREPANCIES NOTED PREVIOUSLY SHALL BE SUBMITTED TO THE BUILDING OFFICIAL PRIOR TO ISSUANCE OF
A CERTIFICATE OF USE AND OCCUPANCY.
SPECIAL INSPECTIONS OF THE FABRICATION PROCESS SHALL NOT BE REQUIRED WHERE FABRICATION OF
STRUCTURAL LOAD BEARING MEMBERS AND ASSEMBLIES IS BEING PERFORMED ON THE PREMISES OF A
FABRICATOR IS REGISTERED AND APPROVED TO PERFORM THE WORK WITHOUT SPECIAL INSPECTIONS. AT THE
COMPLETION OF THE FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF
COMPLIANCE TO THE BUILDING OFFICIAL.
THE SPECIAL INSPECTIONS ARE IN ADDITION TO THE MATERIAL TESTING AND INSPECTIONS LISTED IN THE
CONTRACT SPECIFICATIONS. CONTRACTOR IS TO COORDINATED SPECIAL INSPECTIONS, MATERIAL SPECIFIC
TESTING AND INSPECTIONS WITH THE OWNER FURNISHED SPECIAL INSPECTOR MATERIAL TESTING LABS.
THE SPECIAL INSPECTIONS INDICATED HEREIN DO NOT RELIEVE THE CONTRACTOR FROM THEIR
RESPONSIBILITIES. CONTRACTOR SHALL PAY FOR ANY ADDITIONAL TESTING OR INSPECTION REQUIRED FROM
WORK OR MATERIALS NOT IN CONFORMANCE WITH THE CONTRACT DOCUMENTS.
THE STATEMENT OF SPECIAL INSPECTIONS INCLUDES REQUIRED
VERIFICATION AND INSPECTION OF THE FOLLOWING SECTIONS;
COMPONENTS PART OF THE MAIN WIND FORCE RESISTING SYSTEM AND SUBJECTED TO SPECIAL
INSPECTIONS FOR WIND RESISTANCE: NONE
COMPONENTS PART OF THE MAIN SEISMIC FORCE RESISTING SYSTEM AND SUBJECTED TO SPECIAL
INSPECTIONS FOR SEISMIC RESISTANCE: NONE
CONCRETE:
CONCRETE WORK SHALL CONFORM TO THE REQUIREMENTS OF ACI 301 "SPECIFICATIONS FOR STRUCTURAL
CONCRETE FOR BUILDINGS" (LATEST EDITION). EXCEPT AS MODIFIED BY THE REQUIREMENTS OF THE
CONTRACT DOCUMENTS.
ALL CONCRETE MIXES SHALL BE PROPORTIONED BY THE FIELD EXPERIENCE METHOD OR THE LABORATORY
TRIAL METHOD IN ACCORDANCE W/ ACI 318, MAX WATER TO CEMENT RATIO SHALL BE 0.45.
SLAB-ON-GRADE SHALL HAVE A MAX. SLUMP OF 4", DO NOT USE CALCIUM CHLORIDE IN CONCRETE OR
ADMIXTURES CONTAINING CHLORIDE IONS.
PROVIDE COMPRESSIVE STRENGTH TESTS CONFORMING TO ASTM C31 AND ASTM C39. ONE SET OF FOUR
CYLINDERS FOR EACH 150 CUBIC YARDS OR FRACTION THEREOF, OF EACH STRENGTH OF CONCRETE PLACED
IN ANY ONE DAY. TEST ONE SPECIMEN AT SEVEN DAYS, TEST TWO SPECIMENS AT 28 DAYS AND HOLD ONE IN
RESERVE. PERFORM ONE SLUMP TEST FOR EACH SET OF COMPRESSIVE STRENGTH TEST SPECIMENS. SUBMIT
RESULTS DIRECTLY TO ENGINEER.
CONCRETE EXPOSED TO EARTH AND WEATHER SHALL HAVE LIMESTONE AGGREGATE AND ENTRAINED AIR.
S0.1
38'-0"
S0.1
1/4"=1'-0"
PLAN
S0.1
36'-0"
MUNITIONS STORAGE BUILDING
M U
N I T
I O
N S
S
T O
R A
G E
B
U I L
D I N
G
F.F.E. = SEE CIVIL
EXISTING RELOCATED
MUNITIONS STORAGE
BUILDING (BY ARMAG)
ANCHORAGE BY
OTHERS
8" SLAB ON GRADE WITH
#5 @ 6" O.C. TOP E.W., &
#5 @12" O.C. BOTT. E.W.
EXIST. GRADE,
SEE CIVIL
VAPOR
BARRIER
1'-4"
#5@6" O.C.
(2) #5 CONT.
48"
13"
11"
6" GRANULAR FILL
CLASS B SPLICE
299.67' F.F.E.
M I N
2'-0"
10 MIL VAPOR
BARRIER
6" GRANULAR MATERIAL
299.667' F.F.E.
(4) #5 CONT.
S0.1
STRUCTURAL
GENERAL NOTES
PLAN & SECTIONS
AS NOTED
KEH
DJS
SSR
16670450-S01
07/24/2017
16670450
MEMPHIS,
TENNESSEE
Smith Seckman Reid, Inc.
2650 Thousand Oaks BLVD. - Suite 3200 Memphis, Tennessee 38118 Phone: (901) 683 3900 Fax: (901) 683-3990
SECTION
3/4"=1'-0"
SECTION
3/4"=1'-0"
REPAIR MUNITIONS
STORAGE
PYKL132003
PARTIAL ELECTRICAL SITE PLAN
07/24/2017
16670450
MEMPHIS,
TENNESSEE
Smith Seckman Reid, Inc.
2650 Thousand Oaks BLVD. - Suite 3200 Memphis, Tennessee 38118 Phone: (901) 683 3900 Fax: (901) 683-3990
PARTIAL ELECTRICAL SITE PLAN.DWG
PARTIAL
ELECTRICAL SITE
PLAN
REPAIR MUNITIONS
STORAGE
PYKL132003
20 0 20 40
SCALE 1"=20'
GENERAL NOTES
KEYNOTES
1. ALL BUILDING GROUNDING LOOP CONDUCTORS SHALL BE #4/0 BARE CU UNLESS
NOTED OTHERWISE.
2. GROUNDING RODS AND LOOP CONDUCTORS SHALL BE SPACED 5'-0” FROM
PERIMETER FORMED BY OUTER BUILDING STRUCTURAL STEEL. COORDINATE
WITH ALL UNDERGROUND UTILITIES.
3. ALL GROUNDING CONDUCTOR CONNECTIONS & SPLICES SHALL BE BY MEANS
OF EXOTHERMIC WELDING UNLESS INDICATED OTHERWISE.
4. PROVIDE RECERTIFICATION OF THE LIGHTNING PROTECTION SYSTEM (LPS) BY
ENGAGING THE SERVICES OF A THIRD-PARTY LPS INSPECTOR TO CERTIFY THE
SYSTEM AS BEING COMPLIANT WITH AIR FORCE INSTRUCTION AFI 32-1065 AND
NFPA 780.
EXTEND EXISTING UNDERGROUND FEEDER RACEWAY (1.5” SCH. 40 PVC) TO
RELOCATED PANEL 'B'. CONDUIT ELBOWS & RISER TO PANEL 'B' SHALL BE RIGID
GALVANIZED STEEL. INSTALL NEW FEEDER CONDUCTORS (3 - #1 CU/THWN & 1 - #6
CU/THWN GROUND) FROM EXISTING PANEL 'DPA' TO RELOCATED PANEL 'B'. SEE
“SECONDARY BRANCH CIRCUIT DIRECT BURIAL CONDUIT DETAIL” ON SHEET E5.01.
PROVIDE NEW UNDERGROUND GROUND RING SYSTEM AS INDICATED.
EXTEND EXISTING UNDERGROUND GROUNDING CONDUCTOR FROM RAMP TO NEW
GROUND RING.
EXTEND EXISTING UNDERGROUND GROUNDING CONDUCTOR FROM EXISTING
GROUND RING TO THE RELOCATED BUILDING'S NEW GROUND RING.
RECONNECT EXISTING GROUND BAR TO NEW GROUND RING.
RECONNECT EXISTING BUILDING GROUND CONNECTION POINT TO NEW GROUND
RING.
GROUND GRID SYSTEM SCHEDULE
ITEM DESCRIPTION REMARKS
3/4" x 10'-0" COPPER CLAD GROUND ROD DRIVER WITH TOP MIN. 1'-6" BELOW FINISHED GRADE.
4/0 CABLE TO 3/4" GROUND ROD EXOTHERMIC WELD
4/0 CU CABLE TO 4/0 CU CABLE EXOTHERMIC WELD
NOT USED.
4/0 CU CABLE TO 3/4" GROUND ROD BOLTED CONNECTION
4/0 CU CABLE TO BUILDING CONNECTION POINT
BOLTED CONNECTION (VERIFY WITH MANUFACTURER)
07/24/2017
16670450
MEMPHIS,
TENNESSEE
Smith Seckman Reid, Inc.
2650 Thousand Oaks BLVD. - Suite 3200 Memphis, Tennessee 38118 Phone: (901) 683 3900 Fax: (901) 683-3990
ELECTRICAL
DETAILS
REPAIR MUNITIONS
STORAGE
PYKL132003
TYPICAL CABLE BEND REQUIREMENTS DETAIL
(BUILDING GROUND GRID)
ELECTRICAL DETAILS.DWG
GENERAL NOTES
KEYNOTES
1. CONCRETE SHALL BE 3000PSI AT 28 DAY COMPRESSIVE STRENGTH.
#6 SOLID BARE COPPER CONDUCTOR THROUGHOUT TRENCH (EXCEPT
UNDER BUILDING AND CONCRETE PAVED AREAS).
MEGGAR EARTH TESTER
(THREE-POINT FALL OF
POTENTIAL TEST METHOD)
GRADE
GROUND
BEING TESTED
"X" "X"
AUXILIARY OR
REFERENCE
GROUNDS
1. DISTANCE "X" SHALL BE THE SAME BUT NOT LESS THAN 50'. ALL RODS SHALL BE IN A STRAIGHT LINE.
2. ALL READINGS SHALL BE DONE IN THE CONTRACTING OFFICER'S PRESENCE AND WRITTEN REPORT PREPARED AND FILED
WITH CONTRACTING OFFICER.
3. THE ABOVE TEST SHALL BE CONDUCTED ON (6) SELECTED GROUND RODS PRIOR TO CABLE EXOTHERMIC WELD
CONNECTIONS. MAXIMUM READING SHALL BE 25 OHMS. IF 25 OHMS MAXIMUM IS NOT OBTAINED WITH ONE 10' SECTIONAL
ROD, ADDITIONAL ROD SECTIONS SHALL BE ADDED TO OBTAIN 25 OHMS MAX. THIS WILL DETERMINE DEPTH OF ALL THE
FACILITIES GROUND RODS AND DEPTHS SHALL BE ADJUSTED FOR ALL RODS PRIOR TO CABLE CONN.
4. ALL RODS SHALL BE DRIVEN USING MFGR. RECOMMENDED DRIVING SLEEVES. ANY ROD DAMAGED BY NOT USING PROPER
MFGR. RECOMMENDED DRIVING METHOD SHALL BE REMOVED AND REPLACE AT NO ADDITIONAL COST TO THE CONTRACT.
1'-0" RADIUS
ACCEPTABLE
LESS THAN 1'-0" RADIUS
NOT ACCEPTABLE
8" RADIUS
NOT ACCEPTABLE
LESS THAN 90°
4/0 STRANDED COPPER
CONDUCTOR TO
GROUND BAR
RGS CONDUIT WITH GROUND
BUSHING AT TERMINATING POINT
BONDED TO CONDUCTOR WITH #6
CU AND UL LISTED CLAMP.
4/0 BARE
COPPER
EXOTHERMERMIC
CABLE TO CABLE
WELD
STANDARD COPPER
GROUND LOOP
CONDUCTOR
STANDARD COPPER
GROUND LOOP
CONDUCTOR
'TEE' TYPE EXOTHERMIC
CABLE CONNECTION
M
I N
SCREW REMOVAL 6"
SCH. 80 PVC PIPE TOP FLUSH WITH
FINISHED PAVING
1'-4" X 1'-4" X 8", 3000
PSI CONCRETE PAD
4/0 BARE COPPER
UL LISTED
BOLTED
CONNECTION
AT TEST WELLS
ONLY
6" SCH. 80 PVC
NOTICED TO ALLOW
CABLE TO PASS
THRU
3/4" X 10'-0"
COPPER CLAD
GROUND ROD
NOTE: TYPICAL ALL
GROUND ROD
LOCATIONS
ILLUSTRATIVE GRADE
BEAM/STRUCTURAL
FLOOR SLAB.
UL LISTED
MECHANICAL
BOND
CONNECTION TO
GROUND BAR
GROUND BUSHING
4/0 BARE COPPER
4/0 AWG COPPER
BARE STRANDED
COPPER
CONDUCTOR
(TYPICAL)
NOTE: GROUND ROD CONNECTION SIMILAR WITH
EXOTHERMIC WELDS.
M
I N
±6"
FINISHED
GRADE
ELECTRICAL
WARNING TAPE
CONDUIT WITH
BRANCH CIRCUIT
CONDUCTORS
TOP OF CONDUIT
SANDY LOAM BACKFILL
COMPACTED IN 6"
LAYERS
#6 SOLID BARE COPPER
CONDUCTOR CONTINUOUS
THROUGHOUT TRENCH
NOT TO SCALE
TYPICAL BELOW GRADE GROUND CONDUCTOR
TEE CONNECTION
NOT TO SCALE
GROUND CONNECTION ACCESS TO TEST WELL
NOT TO SCALE
SECONDARY BRANCH CIRCUIT
DIRECT BURIAL CONDUIT DETAIL
NOT TO SCALE
TYPICAL COLUMN GROUNDING CONDUCTOR
NOT TO SCALE
GROUNDING DETAIL
NOT TO SCALE
PARTIAL ELECTRICAL DEMOLITION SITE PLAN
GENERAL NOTES
KEYNOTES
07/24/2017
16670450
MEMPHIS,
TENNESSEE
Smith Seckman Reid, Inc.
2650 Thousand Oaks BLVD. - Suite 3200 Memphis, Tennessee 38118 Phone: (901) 683 3900 Fax: (901) 683-3990
PARTIAL
ELECTRICAL
DEMOLITION SITE
PLAN
REPAIR MUNITIONS
STORAGE
PYKL132003
20 0 20 40
SCALE 1"=20'
1. ALL BUILDING GROUNDING LOOP CONDUCTORS AND EXTENSIONS ARE 4/0 BARE
CU UNLESS NOTED OTHERWISE.
2. GROUNDING RODS AND LOOP CONDUCTORS SHALL BE SPACED 5'-0" FROM
PERIMETER FORMED BY OUTER BUILDING STRUCTURAL STEEL. COORDINATE
WITH ALL UNDERGROUND UTILITIES.
DISCONNECT EXISTING UNDERGROUND FEEDER RUNNING FROM DISTRIBUTION
PANEL 'DPA' TO PANEL 'B'. REMOVE CONDUCTORS & PRESERVE RACEWAY FOR
EXTENSION TO NEW LOCATION OF PANEL 'B'. SEE SHEET E1.10 FOR
RECONNECTION.
DISCONNECT & REMOVE ALL GROUNDING JUMPERS BETWEEN BUILDING &
UNDERGROUND GROUND RING. SEE SHEET E1.10 FOR NEW BUILDING LOCATION.
DISCONNECT EXISTING UNDERGROUND GROUNDING CONNECTION BETWEEN
RAMP & BUILDING GROUND RING. PRESERVE CONDUCTOR FOR EXTENSION TO
BUILDING'S NEW GROUND RING. SEE SHEET E1.10 FOR NEW BUILDING LOCATION.
DISCONNECT EXISTING UNDERGROUND GROUNDING CONNECTION BETWEEN
EXISTING GROUND RINGS. PRESERVE CONDUCTORS FOR EXTENSION TO
RELOCATED BUILDING'S NEW GROUND RING. SEE SHEET E1.10 FOR NEW BUILDING
LOCATION. SEE SHEET E1.10 FOR NEW BUILDING LOCATION.
REMOVE EXISTING UNDERGROUND GROUND RING & ASSOCIATED GROUND RODS
IN THEIR ENTIRETY.
ALL ELECTRICAL DEVICES, LIGHT FIXTURES EQUIPMENT, SPECIAL SYSTEMS, ETC.,
LOCATED INSIDE OR ATTACHED TO BUILDING EXTERIOR TO REMAIN FOR THE
BUILDING RELOCATION.
| COVER SHEET |
| C100_General Notes DETAILS |
| C101_Existing & Demoliton Plan |
| C102_Site Layout & Grading Plan |
| S01_General Notes Plan & Sections |
| E1.10 PARTIAL ELECTRICAL SITE PLAN |
| E5.01 ELECTRICAL DETAILS |
| ED1.10 PARTIAL ELECTRICAL DEMOLITION SITE PLAN |