Attachment_2_Work_Plans.pdf

PDF 180 KB Posted

Attached to
HVAC Preventive Maintenance Services Federal contract opportunity
Solicitation number
W912JB18Q5035
Issued by
Department of the Army Michigan Army National Guard

About this file

Work Plans

View the file

Other files for this federal contract opportunity

Other files attached to HVAC Preventive Maintenance Services, newest first.
File Type Posted
Filter_List_Estimate_20180712.xls XLS spreadsheet
Questions_and_Answers.docx DOCX document
Synopsis_Solicitation_HVAC_6_Aug_18_REVISED_14_AUG.pdf PDF
Attachment_3_Maintenance_Action_Sheets_(MAS).pdf PDF
Base_Access_18Q5035_HVAC.docx DOCX document
WD_15-4867_(Rev.-9)_7-3-18.pdf PDF
Attachment_1_HVAC_Service_PWS_Final.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

JOB PLAN 838 REPLACEMENT OF AIR FILTERS

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Open access panel or door and replace air filters. (MERV8 pleated) 3- Secure access panel or door.

4- Restore power and bring system back on line.

5- Dispose of dirty air filters properly 6- Cleanup work area, put system back in service.

7- Notify building manager and or occupants when complete.

JOB PLAN 841 BASE HVAC PUMP LUBRICATION / INSPECTION

1- Check condition and alignment of coupling.

2- Check condition of motor mounts 3- Check condition of wicking and lubricate.

4- Oil at all applicable oil ports.

5- Remove plug and grease motor.

6- Clean/wipe up any excess oil and grease.

7- Check motor operation, verify voltage and amp draw.

8- Cleanup work area, put back system in service.

9- Notify building manager and or occupants when complete.

10- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213

JOB PLAN 847 IR HEATER ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check condition of burner head assembly.

3- Remove burner cup and assess condition.

4- Inspect the igniter for serviceability.

5- Check to see that the burner observation window is clean and free of cracks or holes.

6- Check the inside of firing tube with a light. If scale or carbon are present document observation.

7- Clean and Inspect burner tubes for cracks and defects.

8- Clean outside surfaces of burner tubes with a damp cloth.

9- Clean and check that reflector shields are secure and properly in place.

10- Clean reflector shields with a damp cloth.

11- Visually observe flame for proper flame characteristics.

12- Check and adjust gas pressure to nameplate.

13- Cleanup work area, put back system in service.

14- Notify building manager and or occupants when complete.

15- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 851 AIR COMPRESSOR OIL CHANGE BI-ANNUAL

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Remove dip stick and document oil condition and level.

3- Remove drain plug and open drain valve and let dirty oil drain into bucket.

4- Replace dirty oil filters.

5- Close drain valve and reinstall drain plug.

6- Refill with new clean oil to proper level on dip stick.

7- Secure dip stick 8- Properly dispose of used oil.

9- Cleanup work area, put back system in service.

10- Notify building manager and or occupants when complete.

11- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 859 AIR HANDLING UNIT BI-ANNUAL INSPECTION <40TONS

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Inspect sheaves and pulleys 3- Inspect condition of cabinet 4- Clean/wipe up any excess oil and grease.

5- Inspect dampers for full travel operation 6- Inspect all electrical connections 7- Inspect unit disconnect 8- Check motor operation

9- Cleanup work area, put back system in service.

10- Notify building manager and or occupants when complete.

11- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 860 AIR HANDLING UNIT BI-ANNUAL INSPECTION >40TONS

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Inspect sheaves and pulleys 3- Inspect condition of cabinet 4- Clean/wipe up any excess oil and grease.

5- Inspect dampers for full travel operation 6- Inspect all electrical connections 7- Inspect unit disconnect 8- Check motor operation 9- Cleanup work area, put back system in service.

10- Notify building manager and or occupants when complete.

11- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 861 AIR HANDLING UNIT BI-ANNUAL PM<40TONS

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections 11- Inspect unit disconnect 12- Check motor operation, verify voltage and amp draw.

13- Check heating coils and fittings for leaks 14-Check cooling coils and fittings for leaks 15- Clean coils by brushing, and vacuuming 16- Straighten any bent coil fins.

17- Inspect/clean condensate pans 18- Check and clear condensate drains 19- Check freeze stat for proper operation.

20- Cleanup work area, put back system in service.

21- Notify building manager and or occupants when complete.

22- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213

JOB PLAN 869 EXHAUST FAN ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections 11- Inspect unit disconnect 12- Check motor operation, verify voltage and amp draw.

13- Cleanup work area, put back system in service.

14- Notify building manager and or occupants when complete.

15- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 870 MAKEUP AIR SYSTEM ANNUAL INSPECTION

2- Inspect fan assembly 3- Inspect sheaves and pulleys 4- Check condition and security of motor mounting 5- Inspect dampers for full range of motion 6- Clean/wipe up any excess oil and grease.

7- Inspect/tighten all electrical connections 8- Inspect unit disconnect 9- Check motor operation, verify voltage and amp draw.

10- Check heating coils and fittings for leaks 11- Check heating electrical elements for proper resistance 12- Inspect gas burners 13- Inspect Heat exchanger for defects 14- Inspect condensate pans for leaks 15- Check condensate drains to ensure proper drainage 16- Check freeze stat for proper operation 17- Cleanup work area, put back system in service.

18- Notify building manager and or occupants when complete.

19- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 871 MAKEUP AIR SYSTEM ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections

12- Check motor operation, verify voltage and amp draw.

13- Check heating coils and fittings for leaks 14- Check heating electrical elements for proper resistance 15- Inspect gas burners 16- Inspect Heat exchanger for defects 17- Clean coils by brushing, and vacuuming 18- Straighten any bent coil fins.

19- Inspect/clean condensate pans 20- Check and clear condensate drains 21- Check freeze stat for proper operation.

22- Cleanup work area, put back system in service.

23-Notify building manager and or occupants when complete.

24- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 874 UNIT HEATER HW ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check and adjust heater deflector fins.

3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections 11- Inspect unit disconnect 12- Check motor operation, verify voltage and amp draw.

13- Check heating coils and fittings for leaks 14- Clean coils by brushing, and vacuuming 15- Straighten any bent coil fins.

16- Check for loose electrical connections in unit and tighten as necessary.

17- Cleanup work area, put back system in service.

18- Notify building manager and or occupants when complete.

19- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 883 VARIABLE AIR VOLUME BOX ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Inspect hose connections for security.

3- Inspect connected ducts for security.

4- Clean/Inspect/lubricate dampers 5- Check for loose electrical connections in unit and tighten as necessary.

6- Inspect dampers for full range of motion 7- Check air flow with flow hood to verify matches and tracks with sensor readings. Adjust as necessary.

8- Cleanup work area, put back system in service.

9- Notify building manager and or occupants when complete.

10- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 888 UNIT HEATER GAS ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check and adjust heater deflector fins.

3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections 11- Inspect unit disconnect

13- Check operation of safety devices as applicable.

14- Inspect heat exchanger for cracks and defects.

15- Perform carbon monoxide testing 16- Cleanup work area, put back system in service.

17- Notify building manager and or occupants when complete.

18- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 890 FURNACE GAS ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check integrated controls for any trouble codes 3- Check fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Inspect dampers 7- Inspect/tighten all electrical connections 8- Inspect unit disconnect 9- Check motor operation, verify voltage and amp draw.

10- Check operation of safety devices as applicable.

11- Inspect heat exchanger for cracks and defects.

12- Perform carbon monoxide testing 13- Cleanup work area, put back system in service.

14- Notify building manager and or occupants when complete.

15- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 891 FURNACE GAS ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Vacuum/clean interior of unit.

7- Oil at all applicable oil ports.

8- Grease motor and all fittings 9- Clean/Inspect/lubricate dampers 10- Clean/wipe up any excess oil and grease.

11- Inspect/tighten all electrical connections 12- Inspect unit disconnect 13- Check motor operation, verify voltage and amp draw.

14- Inspect gas burners 15- Inspect Heat exchanger for defects 16- Check hoses to pressure switches, controls, and drains 17- Check and clear condensate drains 18- Check exhaust and intake air pipes for obstructions 19- Check and set manifold gas pressures to name plate values 20- Cleanup work area, put back system in service.

21- Notify building manager and or occupants when complete.

22- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 894 HEATPUMP GEOTHERMAL ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check/clean fan assembly 3- Inspect sheaves and pulleys 4- Check condition and security of motor mounting 5- Vacuum/clean interior of unit.

6- Inspect dampers 7- Clean/wipe up any excess oil and grease.

8- Inspect/tighten all electrical connections 9- Inspect unit disconnect 10- Check motor operation, verify voltage and amp draw.

11- Check hoses to pressure switches, controls, and drains 12- Check and clear condensate drains 13- Verify that air and water flow rates are at proper levels 14- Check amp draw on compressor to name plate.

15- Check and record refrigerant circuit pressures 16- Cleanup work area, put back system in service.

17- Notify building manager and or occupants when complete.

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

18- Cleanup work area, put back system in service.

19- Notify building manager and or occupants when complete.

20- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 896 HEATPUMP AIR & WATER ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check/clean fan assembly 3- Inspect sheaves and pulleys 4- Check condition and security of motor mounting 5- Vacuum/clean interior of unit.

6- Inspect dampers 7- Clean/wipe up any excess oil and grease.

8- Inspect/tighten all electrical connections 9- Inspect unit disconnect 10- Check motor operation, verify voltage and amp draw.

11- Check hoses to pressure switches, controls, and drains 12- Check and clear condensate drains 13- Verify that air and water flow rates are at proper levels 14- Check amp draw on compressor to name plate.

15- Clean coils by brushing and vacuuming 16-Check coils and fittings for leaks 17- Use fin comb to straighten any bent coil fins.

18- Flush and clean condensate pans and drains, 19- Vacuum interior of unit 20- Check and record refrigerant circuit pressures 21- Notify building manager and or occupants when complete.

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

22- Cleanup work area, put back system in service.

23-Notify building manager and or occupants when complete.

24- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 897 HEATPUMP AIR & WATER BI-ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Vacuum/clean interior of unit.

7- Oil at all applicable oil ports.

8- Grease motor and all fittings 9- Clean/Inspect/lubricate dampers 10- Clean/wipe up any excess oil and grease.

11- Inspect/tighten all electrical connections 12- Inspect unit disconnect 13- Check hoses to pressure switches, controls, and drains 14- Check and clear condensate drains 15- Check condensate pump operation.

16- Check for proper sequence of operation.

17- Verify that air and water flow rates are at proper levels 18- Check amp draw on motors to name plate 19- Check amp draw on compressor to name plate 20- Check and record refrigerant circuit pressures 21- Clean coils by brushing and vacuuming 22-Check coils and fittings for leaks 23- Use fin comb to straighten any bent coil fins.

24- Flush and clean condensate pans and drains, 25- Vacuum interior of unit 26- Cleanup work area, put back system in service.

27- Notify building manager and or occupants when complete.

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

28- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 898 AIR COMPRESSOR ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Clean out debris and dust from heat exchanger cooling coils.

3- Clean/ check surface of air compressor and surrounding area of excess oil and debris.

4- Check accuracy of gauges 5- Test safety relief valves 6- Check operation of unloaders 7- Check compressor suction and discharge valves for proper operation.

8- Check tightness of all electrical connections.

9- Check for proper amp draw on motor.

10- Check cut in and cut out of pressure controller, 11- Make sure belt guard is secure and properly installed 12- Clean coils by brushing and vacuuming 13-Check coils and fittings for leaks 14- Use fin comb to straighten any bent coil fins.

15- Flush and clean condensate pans and drains, 16- Vacuum interior of unit 17- Test auto drain for proper operation.

18- Cleanup work area, put back system in service.

19- Notify building manager and or occupants when complete.

20- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 899 AIR COMPRESSOR ANNUAL PM

2- Check oil level and top off 3- Replace air intake filters 4- Replace belts 5- Clean out debris and dust from heat exchanger cooling coils.

6- Clean surface of air compressor and surrounding area of excess oil and debris.

7- Test safety relief valves 8- Check operation of unloaders 9- Check compressor suction and discharge valves for proper operation.

10- Check tightness of all electrical connections.

11- Grease motor bearings if applicable.

12- Check for proper amp draw on motor.

13- Check cut in and cut out of pressure controller, 14- Make sure belt guard is secure and properly installed 15- Clean coils by brushing and vacuuming 16- Check coils and fittings for leaks 17- Use fin comb to straighten any bent coil fins.

18- Flush and clean condensate pans and drains, 19- Vacuum interior of unit 20- Cleanup work area, put back system in service.

21-Notify building manager and or occupants when complete.

22- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 900 AIR COMPRESSOR 3 YEAR VE INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Perform Internal/external Inspection of pressure vessel -Looking for corrosion or any internal or exterior defects to tank 3- Clean coils by brushing and vacuuming 4-Check coils and fittings for leaks

5- Use fin comb to straighten any bent coil fins.

6- Flush and clean condensate pans and drains 7- Vacuum interior of unit 8- Document AF Form 1222 9- Cleanup work area, put back system in service.

10-Notify building manager and or occupants when complete.

11- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 902 AIR DRYER ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check/clean fan assembly 3- Inspect sheaves and pulleys 4- Check condition and security of motor mounting 5- Vacuum/clean interior of unit.

6- Clean/wipe up any excess oil and grease.

7- Inspect/tighten all electrical connections 8- Inspect unit disconnect 9- Check motor operation, verify voltage and amp draw.

10- Check hoses to pressure switches, controls, and drains 11- Check amp draw on compressor to name plate.

12- Clean coils by brushing and vacuuming 13-Check coils and fittings for leaks 14- Use fin comb to straighten any bent coil fins.

15- Flush and clean condensate pans and drains, 16- Check and record refrigerant circuit pressures

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

18- Cleanup work area, put back system in service.

19-Notify building manager and or occupants when complete.

20- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 903 ROOFTOP UNIT BI-ANNUAL INSPECTION

2- Check/clean fan assembly 3- Inspect sheaves and pulleys 4- Check condition and security of motor mounting 5- Inspect dampers for full movement 6- Clean/wipe up any excess oil and grease.

7- Inspect/tighten all electrical connections 8- Inspect unit disconnect 9- Check motor operation, verify voltage and amp draw.

10- Inspect gas burners 11- Inspect Heat exchanger for defects 12- Check hoses to pressure switches, controls, and drains 13- Check and clear condensate drains 14- Check exhaust and intake air pipes for obstructions 15- Check amp draw on compressor to name plate 16- Check and record refrigerant circuit pressures 17- Cleanup work area, put back system in service.

18-Notify building manager and or occupants when complete.

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

19- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 904 ROOFTOP UNIT BI-ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys

7- Oil at all applicable oil ports.

8- Grease motor and all fittings 9- Clean/Inspect/lubricate dampers 10- Clean/wipe up any excess oil and grease.

11- Inspect/tighten all electrical connections 12- Inspect unit disconnect 13- Check motor operation, verify voltage and amp draw.

14- Inspect gas burners 15- Inspect Heat exchanger for defects 16- Check hoses to pressure switches, controls, and drains 17- Check and clear condensate drains 18- Check exhaust and intake air pipes for obstructions 19- Clean coils by brushing and vacuuming 20-Check coils and fittings for leaks 21- Use fin comb to straighten any bent coil fins.

22- Flush and clean condensate pans and drains, 23- Check and record refrigerant circuit pressures

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

24- Check and set manifold gas pressures to name plate values 25- Cleanup work area, put back system in service.

26- Notify building manager and or occupants when complete.

27- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 905 CONDENSING UNIT ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly

7- Oil at all applicable oil ports.

8- Grease motor and all fittings 9- Clean/Inspect/lubricate dampers 10- Clean/wipe up any excess oil and grease.

11- Inspect unit disconnect 12- Check amp draw on compressor to name plate 13- Check tightness of all electrical connections.

14- Check and record refrigerant circuit pressures 15- Check coils and fittings for leaks 16- Use fin comb to straighten any bent coil fins.

17- Check hoses to pressure switches, controls, and drains 18- Cleanup work area, put back system in service.

19- Notify building manager and or occupants when complete.

20- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 907 HUMIDIFIER EVAPORATIVE ANNUAL INSPECTION

1 -Inspect exterior of unit for leakage and operation 2- Check media and water distribution for serviceability 3- Verify set point to 40% 4- Clear drain lines 5- Verify operation and water flow 6- Cleanup work area, put back system in service.

7- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 908 HUMIDIFIER EVAPORATIVE ANNUAL PM

1- Replace pad or media 2- Replace through/distributor 3- Clean interior and exterior of unit

4- Clean inlet water screen 5- Verify water flow 6- Set Humidistat at 40% 7- Cleanup work area, put back system in service.

8- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 909 HUMIDIFIER STEAM ANNUAL PM

1- Inspect tank and gaskets for leaks.

2- Measure current draw of heaters and verify amp values 3- Verify all safety devices function properly 4- Replace belts 5- Check/clean fan assembly 6- Inspect sheaves and pulleys 7- Check condition and security of motor mounting 8- Vacuum/clean interior of unit.

9- Oil at all applicable oil ports.

10- Grease motor and all fittings 11- Clean/Inspect/lubricate dampers 12- Replace media or bags 13- Fill and verify operation 14- Cleanup work area, put back system in service.

15- Notify building manager and or occupants when complete.

16- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 910 HUMIDIFIER STEAM ANNUAL INSPECTION

1- Inspect tank and gaskets for leaks.

2- Measure current draw of heaters and verify amp values 3- Verify all safety devices function properly 4- Check/clean fan assembly 5- Inspect sheaves and pulleys

6- Check condition and security of motor mounting 7- Fill and verify operation 8- Cleanup work area, put back system in service.

9-Notify building manager and or occupants when complete.

10- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 914 AIR CURTAIN UNIT ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Replace belts 3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections 11- Inspect unit disconnect 12- Check motor operation, verify voltage and amp draw.

13- Check heating electrical elements for proper resistance.

14- Cleanup work area, put back system in service.

15-Notify building manager and or occupants when complete.

16- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 915 FURNACE ELECTRIC ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check and adjust heater deflector fins.

3- Check/clean fan assembly

6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections 11- Inspect unit disconnect 12- Check motor operation, verify voltage and amp draw.

13- Check heating electrical elements for proper resistance 14- Clean coils by brushing, and vacuuming 15- Straighten any bent coil fins.

16- Cleanup work area, put back system in service.

17-Notify building manager and or occupants when complete.

18- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 917 DEHUMIDIFIER ANNUAL INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check condensate pump operation.

3- Check for proper sequence of operation.

4- Verify that air and water flow rates are at proper levels 5- Check amp draw on motors to name plate 6- Check amp draw on compressor to name plate 7- Check tightness of all electrical connections.

8- Check and record refrigerant circuit pressures 9- Cleanup work area, put back system in service.

10- Notify building manager and or occupants when complete.

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

11- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 918 DEHUMIDIFIER ANNUAL PM

2- Check condensate pump operation.

4- Check for proper sequence of operation.

5- Check amp draw on motors to name plate 6- Check amp draw on compressor to name plate 7- Check tightness of all electrical connections.

8- Replace media or bags 9- Check and record refrigerant circuit pressures 10- Check heating electrical elements for proper resistance 11- Clean coils by brushing, and vacuuming 12- Straighten any bent coil fins.

13- Cleanup work area, put back system in service.

14- Notify building manager and or occupants when complete.

OUTDOOR TEMPERATURE: REFRIGERANT TYPE:

HI SIDE PRESSURE: LOW SIDE PRESSURE:

15- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 919 UNIT HEATER ELECTRIC INSPECTION

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Check and adjust heater deflector fins.

3- Check/clean fan assembly 4- Inspect sheaves and pulleys 5- Check condition and security of motor mounting 6- Oil at all applicable oil ports.

7- Grease motor and all fittings 8- Clean/Inspect/lubricate dampers 9- Clean/wipe up any excess oil and grease.

10- Inspect/tighten all electrical connections

13- Check heating electrical elements for proper resistance 14- Clean coils by brushing, and vacuuming 15- Straighten any bent coil fins.

16- Cleanup work area, put back system in service.

17-Notify building manager and or occupants when complete.

18- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 1384 VARIABLE AIR VOLUME BOX FAN POWERED ANNUAL PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Inspect hose connections for security.

3- Inspect connected ducts for security.

4- Clean and adjust heater deflector fins.

5- Check blower wheel and clean 6- Check heating coil and clean 7- Check motor amp draw to name plate 8- Clean coils with brush and vacuum 9- Clean/Inspect/lubricate dampers 10- Check for loose electrical connections in unit and tighten as necessary.

11- Oil motor bearing if applicable.

12- Check operation of controls and safety devices as applicable. 6- Inspect dampers for full range of motion 13- Check air flow with flow hood to verify matches and tracks with sensor readings 14- Cleanup work area, put back system in service.

15-Notify building manager and or occupants when complete.

16- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213

JOB PLAN 1385 VARIABLE AIR VOLUME BOX REHEAT ANNUAL PM

2- Inspect hose connections for security.

3- Inspect connected ducts for security.

4- Clean and adjust heater deflector fins.

5- Clean coils with brush and vacuum 6- Clean/Inspect/lubricate dampers 7- Check for loose electrical connections in unit and tighten as necessary.

8- Check operation of controls and safety devices as applicable.

9- Inspect dampers for full range of motion 10- Check air flow with flow hood to verify matches and tracks with sensor readings 11- Cleanup work area, put back system in service.

12- Notify building manager and or occupants when complete.

13- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 1386 FAN COIL UNIT PM

1- Notify building manager and or occupants that system will be down while performing maintenance.

2- Inspect hose connections for security.

3- Inspect connected ducts for security.

4- Clean and adjust heater deflector fins.

5- Clean coils with brush and vacuum 6- Clean/Inspect/lubricate dampers 7- Check for loose electrical connections in unit and tighten as necessary.

8- Oil motor bearing if applicable.

9- Check operation of controls and safety devices as applicable.

10- Inspect dampers for full range of motion 11- Check air flow with flow hood to verify matches and tracks with sensor readings 12- Cleanup work area, put back system in service.

13-Notify building manager and or occupants when complete.

14- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 1414 CHEMICAL FEEDWATER TANK PM

1- Inspect all valves operations 2- Inspect condition of tank (corrosion) 3- Flush and check for proper function 4- Check for leaks 5- Cleanup work area, put back system in service.

6- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213.

JOB PLAN 1415 IR PUMP INSPECTION

1- Check condition and alignment of coupling.

2- Check condition of motor mounts 3- Inspect exhaust pipe/ hose connections for security and condition 4- Oil at all applicable oil ports.

5- Remove plug and grease motor.

6- Clean/wipe up any excess oil and grease.

7- Check motor operation, verify voltage and amp draw.

8- Cleanup work area, put back system in service.

9- If any problems are found during pm write down unit ID#, Brand Name, Model #, Serial #, and Specific details of parts that need to be replaced. ****If system needs to be put out of service until repairs are made notify BASE HVAC Supervisor 586-239-6676 or 586-239-5213