W912HV-17-B-0002,_Amendment_0002.pdf
PDF 166 KB Posted
- Attached to
- Tactical Equipment Maintenance Facility Federal contract opportunity
- Solicitation number
- W912HV-17-B-0002
About this file
Amendment 0002 - TEMF
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract_-_TEMF_W912HV-17-B-0002.pdf | ||
| W912HV-17-B-0002,_Am-0002_(Combined_Drawings).pdf | ||
| W912HV-17-B-0002,_Am_0002_-_Revised_Specs.pdf | ||
| Amendment_0001_-_TEMF_(extend_response_date).pdf | ||
| TEMF_Drawing_(Volume_4_of_4).pdf | ||
| TEMF_Drawing_(Volume_2_of_4).pdf | ||
| OneTime_Multiple_Access_Roster_USAG-J_Form_1529-1.pdf | ||
| TEMF_Drawing_(Volume_3_of_4).pdf | ||
| OneTime_Multiple_Access_Roster_USAG-J_Form_1529.pdf | ||
| Solicitation_W912HV-17-B-0002.pdf | ||
| TEMF_Specifications.pdf | ||
| TEMF_Drawing_(Volume_1_of_4).pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04 EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
TACTICAL EQUPMENT MAINTENANCE FACILITY, SAGAMI DEPOT, JAPAN
The purpose of this amendment is to:
1) Revise Technical Specifications and Drawings
2) Provide responses to Bidder Inquiries
The response date of 20 January 2017 at 2:00pm, Japan Local Time, remains unchanged.
1. CONTRACT ID CODE PAGE OF PAGES
1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA 15C. DATE SIGNED 15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer) (Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912HV-17-B-0002
X 9B. DATED (SEE ITEM 11)
07-Oct-2016
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
27-Dec-2016
CODE
CONTRACTING DIVISION
USACE-JAPAN DISTRICT
RM 147, BLDG. 250
CAMP ZAMA
ZAMA-CITY, KANAGAWA 252-8511
JAPAN
W912HV 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODE CODE
EMAIL: TEL:
W912HV-17-B-0002
14. DESCRIPTION OF AMENDMENT (continued)
A. CHANGES TO SPECIFICATIONS – The amendment mark “(Am-0002)” is shown on each page of the amended specification section(s).
(1) Revised Section(s) to Project Specifications. Attached hereto are the following revised section(s) to the specifications. Revised section(s) will replace like-numbered section(s) in the subject solicitation specifications. Changes are indicated by a red line in the left margin of revised areas. All portions of the revised section(s) shall apply whether or not changes have been indicated.
Revised Section(s)
01 11 00.20 33 03 20 00.00 10 13 34 19 26 12 19.10 (new section) 31 00 00 32 13 13.06 33 11 00 33 40 00
(2) DELETED SECTION(S). The following section(s) are deleted from the specifications:
32 13 73
B. CHANGES TO DRAWINGS (ISSUED) – The amendment mark “(Am-0002)” is shown on each sheet of the amended drawing sheet(s).
(1) Revised Sheet(s) to Drawings. Attached hereto are the following revised sheets to the drawings. Revised sheets will replace like-numbered sheets in the subject solicitation drawings. Changes are indicated in revision clouds. All portions of the revised sheet(s) shall apply whether or not changes have been indicated.
DRAWING NO. DESCRIPTION
Vol 1 CU-108 Utility Plan – Sewer and Water Vol 1 C-501 Concrete Pavement Joint Details Vol 1 CU-502 Storm Drainage Details
Vol 1 CU-503 Storm Infiltration System Details Vol 1 CU-504 Sanitary Sewer Details -1 Vol 1 CU-506 Water Supply Details Vol 1 C-507 Chain Link Fence and Gates Details
Vol 1 CS-509 Details of Trash Enclosure and Dumpster Vol 1 C-510 Miscellaneous Details – 1 Vol 1 C-511 Miscellaneous Details – 2 Vol 2 G-000 Cover Sheet Vol 2 A-001 General Notes, Abbreviations, and Symbols
Legend
Vol 2 A-002 Wall Types Vol 2 A-101 Architectural Floor Plan Vol 2 A-102 Floor Plan View @Clerestory Elevation Vol 2 A-401 Enlarged Plans Vol 2 A-403 Interior Elevations
Vol 2 A-501 Details Vol 2 A-505 Section Details Vol 2 A-511 Ceiling Details Vol 2 A-601 Door and Window Schedules Vol 2 P-601 Plumbing Schedules Vol 2 MP102 Mechanical Refrigeration, Fuel Oil and Condensate
Drainage Piping Plan Vol 2 E-001 Legend and Abbreviations Vol 2 ES101 Electrical Site Plan North Vol 2 ES102 Electrical Site Plan South Vol 2 ES103 Electrical Site Plan West Vol 2 ES503 Site Details Vol 2 EG102 Lighting Protection Plan Vol 2 EP101 Power Plan Vol 2 EP401 Enlarged Power Plans Vol 2 E-601 One-line Diagram Vol 3 G-000 Cover Sheet Vol 3 S-003 Miscellaneous Typical Details Vol 3 A-601 Door and Window Schedules
C. The following page contains questions that were submitted by potential offerors. Answers provided to the respective questions do not amend the solicitation (specifications, drawings, etc.) unless revision to the specifications or drawings is specifically noted and incorporated into the solicitation. Please see attached list of questions.
D. The response date of 20 January 2017 at 2:00pm, Japan Local Time remains unchanged.
FY13 TACTICAL EQUIPMENT MAINTENANCE FACILITY, SAGAMI DEPOT, JAPAN
SECTION 00 10 00, Solicitation, Contract Line Item Number (CLIN) Schedule SECTION 00 21 00, Instructions SECTION 00 45 00, Representations and Certifications SECTION 00 70 00, Conditions of the Contract SECTION 00 73 00, Supplementary Conditions DIVISION 01, General Requirements DIVISION 02 THRU 41, Technical Provisions (to include Specification Appendix A)
DRAWINGS
FUNDS ARE NOT PRESENTLY AVAILABLE FOR THIS ACQUISITION. NO CONTRACT AWARD WILL BE MADE UNTIL APPROPRIATED FUNDS
ARE MADE AVAILABLE.
X
TEDRA N THOMPSON 046-252-0994
NOTE: In sealed bid solicitations "offer" and "offeror" mean "bid" and "bidder".
10. THE GOVERNMENT REQUIRES PERFORMANCE OF THE WORK DESCRIBED IN THESE DOCUMENTS
NEGOTIATED
07-Oct-2016
(RFP)
(IFB)
CALL:
B. TELEPHONE NO. (Include area code) (NO COLLECT CALLS)
See Item 7
2. TYPE OF SOLICITATION
SEALED BID
3. DATE ISSUED
9. FOR INFORMATION A. NAME
SOLICITATION
NSN 7540-01-155-3212 1442-101 STANDARD FORM 1442 (REV. 4-85)
Prescribed by GSA FAR (48 CFR) 53.236-1(e)
11. The Contractor shall begin performance within _______ 15 calendar days and complete it within ________ 560 calendar days after receiving award, X notice to proceed. This performance period is X mandatory, negotiable. (See _________________________ 52.211-10
12 A. THE CONTRACTOR MUST FURNISH ANY REQUIRED PERFORMANCE AND PAYMENT BONDS?
(If "YES," indicate within how many calendar days after award in Item 12B.)
X YES NO
13. ADDITIONAL SOLICITATION REQUIREMENTS:
A. Sealed offers in original and __________ 1 copies to perform the work required are due at the place specified in Item 8 by ___________ local time ______________ 20 Jan 2017 (date).
If this is a sealed bid solicitation, offers must be publicly opened at that time.
shall be marked to show the offeror's name and address, the solicitation number, and the date and time offers are due.
B. An offer guarantee X is, is not required.
C. All offers are subject to the (1) work requirements, and (2) other provisions and clauses incorporated in the solicitation in full text or by reference.
D. Offers providing less than _______ 120 calendar days for Government acceptance after the date offers are due will not be considered and will be rejected.
SOLICITATION, OFFER,
AND AWARD
(Construction, Alteration, or Repair)
1. SOLICITATION NO.
IMPORTANT - The "offer" section on the reverse must be fully completed by offeror.
4. CONTRACT NO.
7. ISSUED BY CODE
CONTRACTING DIVISION
USACE-JAPAN DISTRICT
RM 147, BLDG. 250
CAMP ZAMA
ZAMA-CITY, KANAGAWA 252-8511
JAPAN
W912HV
PAGE OF PAGES
1 OF
CODE
(Title, identifying no., date):
12B. CALENDAR DAYS
02:00 PM (hour) Sealed envelopes containing offers
5. REQUISITION/PURCHASE REQUEST NO. 6. PROJECT NO.
8. ADDRESS OFFER TO (If Other Than Item 7)
FAX: TEL: 046-252-0994 TEL: FAX:
Ref # Reference Question Government Response
R001 Drawing C-510 Referring to drawing # C-510, please provide specifications for the underlay paper layer located under the concrete pavement.
See amended drawing C-510. Revised details 9, 10, and 13 include JIS P 3401, TYPE 1 for underlay paper.
R002 Drawing C-501
Referring to drawing # C-501, Please provide full description for the kind of wire mesh shown in detail D9. See amended drawing C-501. Revised detail D9 states that the wire mesh size is D6 @150x150.
R003 Drawing C-501 Referring to drawing # C-501, Please provide specifications for the bituminous material spreading coating the slip bars
See amended drawing C-501. Revised detail D5 include JIS K2208, Petroleum asphalt emulsion to the bituminous material spreading coating the slip bars.
R004 Drawing C-501 Referring to drawing # C-501, detail D6, please confirm that the length of the slip bar or tie bar is 900 mm and its interval is 100 mm.
See amended drawing C-501. Revised detail D6 by changes D16X100 ctc 900 to D16x1000 ctc 900 (1000 mm length, 900 mm interval).
R005 Drawing C-501 Referring to drawing # C-501, detail D4, please confirm that the length of the slip bar or tie bar is 400 mm and its interval is 500 mm.
Refer to drawing C-501, detail D4. The slip bar interval is 400 mm and the length is 500 mm, as shown. The slip bar interval is NOT 500 mm and the length is NOT 400 mm as mentioned in the RFI.
R006 Please provide geotechnical report for this bid Refer to specification package, Appendix A - Site Investigation Report
R007 Please clarify if dewatering is required for this bid. Refer to specification package, Appendix A - Site Investigation Report.
Each contractor needs to evaluate dewatering based on their method of construction.
R008
Please clarify whether it is required to have soil replacement under foundations of buildings or not Refer to specification package, Appendix A - Site Investigation Report.
Replacement with well graded soil is required if the foundation soil excavated are not in good condition, such as top soil and loam.
R009 Drawing S-003 Regarding VWF building, there is a conflict regarding the width of the pile cap PC2, it was shown to be 1800 mm on plan on drawing # S-003, while 2000 mm in the elevation on drawing # S-003, please provide the correct dimension.
See amended drawing S-003. Revised width of pile cap to 1800 mm on Elevation/Section Detail.
R010 Drawing S-204 For building TEMF, please provide the heights of walls labelled W1 as they are shown in elevations to be variable on drawing # S-204.
Refer to drawing S-201 for wall elevations for wall height "W1" in drawing S-204.
R011 Drawing CU-502 Referring to drawing # CU-502, detail #4, free gradient ditch (normal type), please provide type and structural detail for walls.
See amended drawing CU-502 detail 4. Revised walls for free gradient ditch (normal type) to be typical pre-cast concrete.
R012 Drawing CU-502 Referring to drawing # CU-502, detail #5, free gradient ditch (for road crossing), please provide type and structural detail for walls.
See amended drawing CU-502 detail 5. Revised walls for free gradient ditch (for road crossing) to be typical pre-cast concrete.
R013 Drawing CU-502 Referring to drawing # CU-502, detail #6, storm drainage inlet (for free gradient ditch), please provide type and structural detail for walls.
See amended drawing CU-502 detail 6. Revised walls for storm drainage inlet (for free gradient ditch) to be typical pre-cast concrete.
R014 Drawing CU-502 Referring to drawing # CU-502, detail #2, storm drainage manhole, please provide structural detail for bottom slab.
See amended drawing CU-502 detail 2. Revised walls for storm drainage manhole (No. D4-2) to be typical pre-cast concrete.
R015 Drawing CU-506 Referring to drawing # CU-506, detail #4, fire hydrant guard post detail, please provide structural detail for concrete slab and concrete base.
See amended drawing CU-506. Revised detail 4 shows concrete slab is not required and the concrete base for guard post shall be plain concrete with a dimension of 16" diameter and 24" height.
R016 Drawing CU-509 Referring to drawing # CU-509, detail #B3, gate for dumpster area, please provide structural detail for gate footings.
See amended drawing CS-509. Revised detail B3 shows gate footing to be plain concrete.
R017 Drawing C-104 Please provide full structural details (concrete dimensions and steel reinforcement details) for the walls containing the diesel fuel storage tank and its concrete pad shown on drawing # C-104.
See amended drawing C-511. New details 8, B1, and B2 have been added to show structural details of concrete pad for diesel fuel oil storage tank.
R018 Drawing C-104 Please provide full structural details (concrete dimensions and steel reinforcement details) for the VSAT pad shown on drawing # C-104.
See amended drawing C-511. New details 7 and A1 have been added to show structural details of concrete pad for VSAT.
R019 Drawing CU-502 Referring to drawing # CU-502, detail #2, please clarify type of manhole walls. See amended drawing CU-502, detail 2. Added pre-cast concrete for manhole wall type.
R020 Drawing CU-503 Referring to drawing # CU-503, detail #3, please clarify type of manhole walls. See amended drawing CU-503, detail 3. Added pre-cast concrete for manhole wall type.
R021 Drawing CU-504 Referring to drawing # CU-504, detail #3, please clarify type of manhole walls. See amended drawing CU-504, detail 1. Added pre-cast concrete for manhole wall type. Refer to detail 3 for reinforced concrete sections.
R022 Specs Section 12 21 00 Reference to specification section 12 21 00 WINDOW BLINDS, please clarify the location of window blinds as it is not mentioned neither on drawings nor in the specifications.
See amended drawing A-601 of Volume 2, general note 3. Added 'ALL
(W1) & (W4) WINDOWS SHALL RECEIVE WINDOW BLINDS.'
R023 Sheet A-601 Reference to building Vehicle Wash Facility sheet A-601, the frame type in door schedule is type A, while in frame types details it is called type 1, please advise.
See amended drawing A-601 of Volume 3, frame types. Changed type '1' to type 'A'.
R024 Specs Section 32 13 13.06; Drawings C- 110 and C-510
Reference to specification section 32 13 13.06, the joints of concrete pavement for roads and site Facilities shall be under specification section “32 13 73 COMPRESSION JOINT SEALS FOR CONCRETE PAVEMENTS”; While on drawings sheet C-110, C-510 the joints of concrete pavement is under specification section “32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS IN RIGID PAVEMENTS” please confirm that we shall follow the drawings in pricing.
See amended specification section 32 13 13.06. Deleted paragraph
2.1.6. Also section 32 13 73 has been deleted in its entirety, as it is not applicable to this project.
R025 Drawing ES-103 Referring to site dwg ES 103, please confirm that power poles 157-3 &157-4 are existing poles. See amended drawing ES103. Added notes to power poles 157-3 and
157-4 to note that the poles are existing.
R026 Drawing ES-103 Referring to site dwg ES 103 note 1, Please specify if any modifications required for power pole 157-4, and if yes please provide detail drawing for the modifications.
See amended drawing ES503, detail 2. Fixed mislabeling error showing detail for pole 157-4.
R027 Drawing ES-503 Please specify if Detail#2 per ES-503 with the down conductors is for power pole 157-3 or 157-4, since power pole 157-4 is the pole before the transformer.
See amended drawing ES503, detail 2. Fixed mislabeling error showing detail for pole 157-4.
R028 Drawing ES-102 Referring to site dwg ES 102 please specify if power poles from 175-4 to 175-10 need modification or not, and will it accommodate the new overhead circuit “D” or not, as line is bold.
See amended drawing ES102. Conductor routed through poles is existing.
Revised line thickness for existing overhead line.
R029 Drawing ES-103 Referring to site dwg ES 103, please specify if the overhead circuit “E” is new or existing, if new please specify its size and specs also its connection point.
See amended drawing ES103. Revised circuit 'E' language states "EX 6600V, 3PH, 50HZ, CIRCUIT "E"" to show that the circuit is existing.
R030 Drawing ES-102 Referring to site dwg ES 102 please specify if power poles from 156-5 to 156-9 need modification or not, and will it accommodate a new overhead circuit “E” or not, as line is bold.
See amended drawing ES102. Conductor routed through poles is existing.
Revised line thickness for existing overhead line.
R031 Drawing ES-102 Referring to site dwg ES 102 please specify if power poles from main line 166-6 need modification or not, and will it accommodate new overhead circuit “E” or not, as line is bold.
See amended drawing ES102. Conductor routed through poles is existing.
Revised line thickness for existing overhead line.
R032 Drawing ES-101 and ES-102 Referring to site dwg ES 101,102, Please specify the connection point of overhead circuit “D” feeding 500KVA transformer.
Refer to drawing ES101. The connection point of the overhead circuit 'D' is the intersection of circuits 'D' and 'J' on pole 166-5, as shown.
R033 Drawing ES-101 and ES-103 Referring to site dwg ES 101,103, Please specify the connection point of overhead circuit “E” feeding 225KVA transformer.
See amended drawing ES102. Added note stating 'Connection point of overhead circuit "E" to circuit "J"' which points to pole 156-5.
R034 Drawing ES-101 and ES-102 Referring to site dwg ES 101,102, Please specify if overhead Circuit “D” between Poles 176-1 and 176-2 is 33Kv or 6.6 KV.
Refer to drawing ES102, note 3. The system voltage is 6600 volts.
R035 Please provide foundation details for the power poles. Refer to drawing ES502, detail 5. Detail 5 shows that the power poles are direct buried.
R036 Specs Section 26 12 19.10 Please provide spec sec 26 12 19.10 for the 500KVA and 225KVA pad mounted transformers. See amendment for added new specification section 26 12 19.10.
R037 Drawing E-601 and Specs Section 26 20 00, Paragraph 2.14
Referring to TEMF dwg E 601 Confirm that T3 (150KVA) transformer E601 for TEMF will follow Spec Sec 26 20 00 para 2.14.
Follow specification section 26 20 00, para 2.14, TRANSFORMERS for interior distribution.
R038 Drawing EP-101 Referring to bldg. VWF dwg EP101, please specify what EMS Refers to? See amended drawing E-001. Amended abbreviation list to include EMS -
ENERGY MANAGEMENT SYSTEM and EMCS - ENERGY
MANAGEMENT AND CONTROL SYSTEM.
R039 Specs Section 26 20 00, Para. 2.26.a
Referring to spec sec 26 20 00 para 2.26.a, please specify if Energy Monitoring and Control System (EMCS) is required, and if it is, please provide its SLD.
See amended drawing E-001. Amended abbreviation list includes EMS and EMCS. Refer to specification section 23 09 23 paragraphs 2.8.7 through 2.8.7.5 for EMCS requirements. EMCS is required per specification section 26 20 00, paragraph 2.26.
R040 Drawing ES-101
Referring to site dwg ES 101, please confirm that H1, H2 are light poles, and please provide legend for them. Yes, H1 and H2 are light poles. See amended drawing ES101. Legend updated to show naming convention (H1) on new area lighting standard symbol. See EL-501 Detail 8 for Lighting type H1/H2.
R041 TY Drawings
Please confirm that Security systems (in TY drawings) equipment and cabling out of contractor’s scope Refer to TY001, general note 1. All equipment and wiring is Government furnished and Government installed.
R042 Please confirm that no area lighting required for the POV parking area Refer to sheet ES101. Area lighting is required in POV parking area.
R043 Please confirm that no grounding system is required for the new fence, otherwise please provide detail drawings
Refer to drawing CU507, detail 1. The grounding system is dia. 14mm X1500mm, at every 1000 feet (305m) intervals.
R044 Drawing EG-102, Note G Please specify Lightning secondary cabling size as per dwg TEMF (EG102) note G See amended drawing EG102. Added general note H: 'Secondary lightning protection cables a #14AWG strand, 41, 100 CM loose-lay cable.
R045 Drawing EP-101, General Note A
Referring to DWG TEMF EP101 general note (A) which states that all conduit shall be concealed in wall, while most of walls and ceiling are metal, please clarify if exposed metal conduits are acceptable or not in metal areas
See amended drawing EP101. Revised general note A: 'All conduit shall be concealed in finished wall or above ceiling. Conduit to floor outlet shall not be routed in concrete slab. Penetrate the slab and run conduit below deck. Conduit in non-finished areas shall be run exposed.'
R046 Drawing CU-108 and CU-503 Referring to drwgs (CU-108) & detail# (2/CU-503), please clarify the material type of the storm drain infiltration pipe.
See amended drawing CU-503, detail 2. Updated storm drain infiltration pipe to be pre-cast concrete pipe.
R047 Drawing CU-205 and CU-208 Referring to drwgs (CU-205:208), VU type is requested for storm drainage pipe while specification section 33 40 00 refers to concrete type. Please advise which type should be followed.
See amended specification section 33 40 00, paragraph 2.1.2 and 2.1.3.
Added PVC PIPE and PVC PIPE FITTING paragraphs.
R048 Section 00 21 00, Instructions 20
Reference 00 21 00 Instructions 20. Required Submittals for IFB, please clarify the number of Original, Copies, and Electronic copies of the proposal to be submitted.
Refer to standard form 1442 Box 13(a). One original and one copy of the proposal are required.
R049
Will the Govt. allow for the offerors to seek further clarifications or re-directs on the submitted RFIs once answered by the Govt.?
The Contractor may submit additional questions; however, as the deadline for submission of RFIs was November 4th at 4pm, Japan Standard Time, response is at the Government's discretion.
R050 Sheet C-104
Reference to sheet C-104, please provide us with Architecture drawing for VSAT. See amended drawing C-511, detail 7. Added concrete pad size for VSAT. VSAT equipment information shall be provided to successful offeror after Contract Award.
R051 Sheet A-002 Reference to Sheet #A-002 please provide detail showing the security mesh in wall type 6C & 6D. See amended drawing A-002, detail for wall type 6C. Added security mesh detail.
R052 Architectural Floor Plans A-101 and A-102
Reference to Architectural Floor Plan #A-101 the east wall for Weapons Vault room & Cosmec Vault room is type 6 but reference to sheet #A-102 it’s type 6C, please advise.
See amended drawing A-101. Revised floor plan name to "architectural floor plan (below ceiling line)" from "architectural floor plan."
R053 Architectural Floor Plans A-101 and A-102
Reference to Architectural Floor Plan #A-101 the west wall for Weapons Vault room & Cosmec Vault room is type 6 but reference to sheet #A-102 it’s type 6B, please advise.
See amended drawings A-101 and A-102. Revised floor plan name to "architectural floor plan (below ceiling line)" from "architectural floor plan" on drawing A-101. Revised floor plan name to "architectural floor plan (above ceiling line)" from "architectural floor plan" on A-102.
R054 Architectural Floor Plans A-101 and A-102
Reference to Architectural Floor Plan #A-101 the east & west walls for Corridor 101 are type 1E but reference to sheet #A-102 it’s type 2B, please advise.
See amended drawings A-002 and A-102. Revised detail 2 on drawing A- 002 to show wall type 1E from floor line to roof line with notation. Revised drawing A-102 to show wall type 1E.
R055 Sheet A-302 and A-601 Reference to VWF sheet A-302 the wall finish is PT-4 & PT-6 but reference to finish schedule sheet #A-601 the finish is PT-4 only, please advise.
See amended drawing Vol 3 A-601. Revised finish schedule.
R056 Specs Section 26 20 00, Para. 2.4 and 2.8
Referring to specification section 26 20 00 para 2.4&2.8, please clarify where the Receptacles with metal face plates will be used, and specify where is the unfinished walls areas
Refer to drawings EP101 and EP401 for receptacle placement as well as specification 26 20 00 paragraphs 2.4, 2.8, and 2.11 for receptacle face plate material types. The Contractor shall determine the material type for special purpose outlets/receptacles in EP101 and EP401 via product data submittals. Refer to drawing A-002 for wall type schedule for unfinished wall types.
R057
Please confirm that no combination motor starters are required, only manual starters are required as per electrical drawings.
Refer to drawings M-601 and M-602 for mechanical schedules and drawing EP102 for equipment power plan. As shown on the drawings, only 120 volt, single phase devices will require manual motor starters.
Refer to notes on schedules on drawings M-601 and M-602 for motor starter requirements not shown on drawing EP102.
R058
Drawing EP-401 Referring to drawing TEMF EP401 detail 3, please specify the method of mounting for the receptacles, please specify if it will be recessed in furniture with dual channel by others, otherwise please provide details
See amended drawing EP401, enlarged floor plan 3. Added notes 5 and 6 to clarify the intention of the junction box and electrical contractor's scope of work for furniture outlets.
R059 SPEC 31 62 13.20, 1.4.3 This clause calls for a Registered Professional Geotechnical Engineer to perform the required tasks. May we understand a Japanese “Gijutsushi” as equivalent certificate for this requirement?
No, Gijyutsushi is not acceptable. Provide qualified personnel as stated in specification section 31 62 13.20
R060 SPEC 03 20 00.00 10, 3.1.3.2
Concrete Cover, Variation for minimum cover “plus 1313mm” shall read as 13mm. Minimum cover 100100mm shall read as 100mm, and Variation shall be “10mm.” Minimum cover 7575mm shall be 75mm, and variation “plus 10” shall mean “plus 10mm.” In following page, all of the Minimum Cover seems to be typo. 50mm, 38mm, 25mm, and 19mm. Please verify.
See amended specification 03 20 00.00 10 paragraph 3.1.3.2. Revised minimum cover information.
R061 SPEC 31 00 00, 2.1
Line 6: Warning and identification to LINE read “CAUTION, BERIED (intended service) BELOW” or similar wording. May we understand we can use warning tapes with Japanese language used as such caution?
See amended specification 31 00 00 paragraph 2.1. Added Japanese language warning tapes are acceptable, as long as they are provided with English warnings.
R062 SPEC 05 12 00, 2.3.1.3
Washers: ASTM F 436M washers for ASTM A325M or JIS B 1186 bolts. Please verify that this clause intends to use ASTM F 436M washers only for this project. Although JIS B 1186 is titled as “Sets of high strength hexagon bolt, hexagon nut and plain washers for friction grip joints,” Government does not intend to allow using of JIS standard washers. Or Attachment 01 11 00.20 33-A, 05 12 00 Washer JIS B 1256 govern?
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R063 Spec 05 12 00, 2.3.2.2
Anchor Nuts: ASTM A563, Grade A, hex style. Although use of JIS B 1220 Anchor Bolts are allowed for use, Government does not allow using JIS B 1220 anchor bolt and nut set, only using ASTM nuts.
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R064 SPEC 05 12 00, 2.3.2.3
Anchor Washers: ASTM F 844. Please verify that Government allows using of ASTM Anchor Washers only, and does not allow JIS Anchor Washers.
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R065 SPEC 05 05 23, 1.5.5
Welders, Welding Operator, and Tracker Qualification: AWS D1.1/D1.1M. Please verify that Government does not allow substitution by equivalent JWS qualified welders.
Conduct work in accordance with drawings and specifications. Refer to specification 05 05 23 paragraph 1.5.5.
R066 SPEC 05 05 23, 2.1
Welding Equipment and Materials: All welding equipment and materials shall comply with the applicable requirements of AWS D1.1/D1.1M. Please verify that Government will not allow substituting with equivalent JWS standards.
Conduct work in accordance with drawings and specifications. Refer to specification 05 05 23 paragraph 2.1.
R067 SPEC 05 05 23, 3.1.1
Requirements: Conform workmanship and techniques for welded construction to the requirements of AWS D1.1/D1.1M and ANSI/AISC 360. Please verify that Government will not allow substituting with equivalent JWS standards.
Conduct work in accordance with drawings and specifications. Refer to specification 05 05 23 paragraph 3.1.1.
R068 Specs Section 13 34 19 - Metal Building Systems
Section 1.4 System Description: Provide a complete integrated set of metal building system manufacture’s standard mutually dependent components and assemblies…inclusive of metal roof panels and metal wall panels. These metal panels are furthered defined throughout this division as standard factory-assembled and tested assembly to ASTM standards. While the primary and secondary structure “could” be fabricated in Japan the metal panel assemblies as defined in this specification are not available. Therefore a complete Metal Building System from a single manufacture in Japan cannot be procured. Please advise if a MBS engineered and fabricated can be obtained from outside of Japan.
Refer to specification section 13 34 19. Yes, a complete MBS may be obtained from either inside and outside of Japan.
R069 Specs Section 13 34 19 - Metal Building Systems
If the building MBS can be procured outside of Japan, then please provide a variation to 1.6.3 Manufacture’s Qualifications that would allow for a 3rd party verification of a licensed engineer in the geographical area for local codes.
Refer to specification 13 34 19 paragraph 1.6.3. MBS outside of Japan must be certified by a licensed engineer in the geographical area where construction will take place. Spec does not disallow for 3rd party verification.
R070 Specs Section 13 34 19 - Metal Building Systems
If the MBS can be procured outside of Japan, then please revise Div 01 33 29 1.3 Description to allow for a less than LEED Silver rating. The bulk of the LEED points for this solicitation are based on the MBS systems being of products extracted, harvested, or recovered, as well as manufactured within a 805 K radius. The goal of LEED silver is unobtainable if the MBS is procured outside of Japan
Refer to specification 01 33 29. The total LEED credits potentially earned is 54 points. When referring to 805 k radius, this is referencing 2 credits for MRc5. With the total points currently at 54, if the regional priority credit cannot be achieved it will reduce the credits down to 52 and still be above 50 points (min. LEED Silver).
R071 Specs Section 13 34 19 - Metal Building Systems
If the MBS is to be manufactured in Japan, then please provide specification revisions that would allow for a standard market product for the insulated panel systems with equivalent testing to be allowed. Please also define what the equivalent panel system testing requirements under JIS would be for following: 1.2.5 Thermal Performance, 1.2.6 Air Infiltration for Metal Panels, 1.2.7 Air Infiltration for Metal Wall Panels, 1.2.8 Water Penetration for Metal Roof Panels, 1.2.9 Water Penetration for Metal Wall Panels, 1.4.8 Exterior Wall System,
2.5.2 Foam-Insulated Core Wall Panel and roof panel sub sections (A, B, C, D, & F), 3.4 Metal Wall Panel Installation, and 3.5 Roof Panel Installation.
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R072 Specs Section 13 34 19 - Metal Building Systems
If the MBS is to be manufactured in Japan, then please provide an equivalent JIS specification for 2.2.9 High- Strength Bolts, Nuts, and Washers. Japan MBS fabricators design analysis software does not support ASTM
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R073 Specs Section 13 34 19 - Metal Building Systems
If the MBS is to be manufactured in Japan, then please provide an equivalent JIS specification for 2.2.11 b.
Nuts and c. Washers likewise please also provide a JIS under 2.2.12 a. Nuts and b. washers.
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R074 Specs Section 13 34 19 - Metal Building Systems
If the MBS is to be manufactured in Japan, then please allow a variation to specifications to allow for the JSCE Standard Specification for Steel and Composite Construction “latest Edition” to be substituted in lieu of (MBMA MBSM); ASCE 7-10, NRCA 0405 and ASTM E 1592. Japan MBS manufactures design analysis software does not requirements that are not based in JIS specifications.
Acceptable JIS alternatives are included in specification 01 11 00.20 33- A. The offeror may submit Japanese alternative standards not currently in the solicitation as a variance request to the Contracting Officer after Contract award. The government has the discretion to accept or reject any variance requests.
R075 Specs Section 13 34 19 - Metal Building Systems
The maximum standard insulated panel system in Japan uses 600 mm o.c. spacing. If the MBS is manufactured using Japan standard market designs, will the Govt. allow for a pricing adjustment to the increased girts and secondary structure supports that would be required?
Conduct work in accordance with drawings and specifications. Pricing adjustments are not allowed for fixed price contracts.
R076 Please allow for a 3 week extension once the above questions are answered to allow for our MBS manufactures to analyze and re-bid the structure.
Extension was issued in Amendment 001. No additional extension shall be granted at this time.
R077 13 09 00.00 44
Specifications Section 13 09 00.00 44, Anti-Terrorism/Force Protection Measures, Item 1.2.1 General Requirements states:
“…The basic force formula for lateral restraint shall be 0.5 times the weight of the supported equipment, component, or system (including the weight of fluid or material within) applied in any horizontal direction at the center of gravity of the equipment, component, or system. The basic force formula for vertical restraint shall be
1.5 times the weight of the supported equipment, component, or system (including the weight of fluid or material within) in the downward direction….”
If our design is to include Anti-Terrorism/Force Protection loads, please advise if we are to design the structure for 1.5 times the overhead crane’s 10 tons current lifting capacity, and 1.5 times the 35 tons lifting capacity for the future crane option?
Refer to specification 13 09 00.00 44 paragraph 1.2.2 for applicable equipment. The requirement does not apply to the crane.
R078 01 11 00.20 33 1.2.b
This project requires a superintendent who is a licensed architect (kenchiku-shi). Would USACE accept a first class sekko kanrigishi in lieu of this requirement as it is more appropriate. A licensed architect (kenchiku-shi) is for design work. Sekko kanrigishi is for construction work. Since this project has already been designed there should be no need for design.
See amended specification section 01 11 00.20 33, paragraph 1.2(b).
Revised site supervisor (superintendent) requirements to have a 1st Class Kenchiku Sekou Kanrigishi certification and have at least a minimum of five years of experience as a superintendent on construction projects similar in size and scope of this contract.
R079 Sprinkler System
After performing basic hydraulic calculations from the information provided on the contract drawings we believe a fire pump will be required for the sprinkler system. There is no fire pump shown or mentioned and there does not seem to be space to install one. Please confirm that a fire pump is not required.
Fire pump is not required in this project.
R080 07 27 00.45 10
The air barrier testing requires a 3rd party testing agency that has very specific US qualifications/standards and experience requirements. Would the Government accept equivalent Japanese testing qualifications and experience or must we follow the prescribed US standards (i.e. a US specialist).
Provide qualified personnel according to contract documents.
R081 S-001, General Notes Section G Please confirm that the USACE will only accept driven piles and no other piling methods will be accepted. Only driven piles are acceptable. Conduct work in accordance to contract drawings and specifications.
R082 41 22 13.15 2.1
The specifications specify an under running bridge crane but the drawings show an over running gantry crane.
Please confirm the drawings show the
This specification section covers top-running and under-running single girder electric traveling (OET) cranes with under-running trolleys and hoists. The offeror shall make their own determination based on the solicitation. The means and methods shall be determined by the contractor.
R083 01 11 00.20 33
Specification Section 01 11 00.20 22 Part 1.2 notes a requirement for a LEED Documentation Manager on the contractor’s staff. The section also indicates “the LEED documentation for this project is expected to be significant.” Is the LEED Documentation Manager required to be a US Green Building Council LEED AP?
A LEED AP will be required to prepare documentation and coordinate with the Project Engineer and SEPM during construction in accordance with the requirements of specification 01 33 29. Refer to specification 01 33 29 paragraph 1.4. Paragraph - Quality Assurance states "Engage a responsible, experienced LEED Accredited Professional to coordinate LEED requirement."
R084 MP102
Please confirm if the VRF condensing unit it to be installed on grade or upon a concrete equipment pad See amended drawing MP102. Revised drawing to add note for contractor to "provide concrete equipment pad for condensers."
R085 P-601 Backflow schedule lists RPZ-5. Please indicate where RPZ-5 is to be installed See amended drawing P-601. Revised backflow preventor schedule removes reference to RPZ-5.
R086 General For those systems/assemblies provided by US sourced vendors/suppliers will a US certified installer be required?
Provide installer based on manufacturer's instructions, unless otherwise noted in the contract documents.
R087 M-501 Please confirm explosion proof requirements for electrical water heaters at the Vehicle Wash Facility Refer to drawing M-501. Electrical unit heater schedule note 2 states, 'provide explosion proof motor.'
R088 DWG T501 Detail 5
Which drawing shows a detail for penetrations through STC rated partitions? Refer to drawing A-002. Reference applicable details for penetrations based on location and wall assembly type of STC rated partitions. Refer to General Notes 2 & 3 on drawing A-002 for supplemental information regarding typical wall-type details.
R089 DWG S001 Reinforced Concrete Note 4
There is a conflict on the slump requirement on note 4 and spec Sections 03 30 00.00 10 para 1.2.13 / 32 13
13.06 para 2.3.
The slump values in the specifications 13 30 00.00 10 paragraph 1.2.13 and 32 13 13.06 paragraph 2.3 are correct where different structural slump values are shown for each structural element. Sheet S-001 note 4 states the total ranges of slump.
R090 DWG A001, A403
Fixture Height requirements are in conflict between DWG A001 & A403 See amended drawing A-403, dimensions have been removed to resolve conflict. Refer to A-001 for height requirements.
R091 DWG A002, A101
1. Wall type details for 1A, 1B, 1C, 2A, 2B, 2E, 6A, 6B, 6C, 6D are not clear. For 6C&D, there is no specification for security mesh such as size, material etc.
2. Location of walls on A101 is not consistent with wall types and notes on A002
See amended drawing A-002. Revised partition type details for 6C and removed 6D. Refer to specification 05 50 13 paragraph 2.11 for security mesh specification. See amended drawings A-101 and A-102. Revised floor plan name to "architectural floor plan (below ceiling line)" from "architectural floor plan" on drawing A-101. Revised floor plan name to "architectural floor plan (above ceiling line)" from "architectural floor plan" on A-102.
R092 DWG A002
Are Water resistant GWB and Moisture resistant GWB the same? See amended sheet A-002. Revised language to provide clarity. Water resistant GWB and Moisture resistant GWB are equivalent.
R093 DWG C002 Civil Note 9 Please list all Sagamihara city regulation needed for approval (such as , regulation titles/ numbers, editions etc.)
Refer to specification section 01 11 00.20 33, paragraph 1.7. Contractor shall acquire all necessary permits.
R094 CU108
a. Spec section 33 11 00 provide requirements for valves greater than 80mm. What is the requirement for valves for smaller than 80mm?
b. Water meter box on detail 5 / CU506 appears to have by-pass line but there are no valves shown
a. See amended specification 33 11 00 paragraph 2.2.2.2. Revised wording to "Gate valves smaller than 80 mm 3 on buried piping MSS SP- 80,Class 150, solid wedge, nonrising stem or JIS G 5502. Valves shall have flanged or threaded end connections with union on one side of the valve."
b. See amended drawing CU-108. Added gate valve to the by-pass line for water line "B" near the sta. A1+4.04 connection point.
R095 DWG TY101, TY401, EP101
Note 7: It requires two 120V quad outlets at each PCU location(Rm 104, 105, 119 , 109 & 110) . However they are not shown on the power plan (EP101)
See amended sheet EP101. Revised room 119 to include 2 quadplex receptacles at PCU location. Refer to EP101 and EP401 for quadplex receptacles at each PCU location in rooms 104, 105, 109, and 110.
R096 DWG TY101, EP401
Appears to be a conflict as PCU location in RM105 is in the same location as panel LP6 The Contractor may adjust the equipment and device locations along the wall in Room 105 to suite the actual equipment size and clearance required by the equipment manufacturer.
R097 DWG TY501 Detail 8: Second conduit run is for SCIF locations only. Can second conduit run be deleted since this is not a
SCIF.
No, second conduit run shall not be deleted. Conduct work in accordance with drawings and specifications.
R098 DWG TY501, TY502
1. TY502 Detail 6 & 7: What are the camera conduit and box sizes to be home run to the TR closet
2. TY501 Detail 3: Is stainless steel whip and BMS switch to be install by contractor?
(1).Refer to TY502 details 6. Minimum size is 102mm x 102mm DEEP Box for both the camera and power. The conduits are minimum 27mm.
(2). Refer to TY001 general note 1. Whip and switch is part of the wiring and equipment that is government furnished and government installed.
R099 DWG TY101 note3 Which outlet box does note 3 refer to? Refer to sheet TY101 note 3. Note 3 refers to all outlet boxes "Unless Noted Otherwise" or shown otherwise in the details.
R100 Specs Section 23 07 00, Page 21 - Table
Is it possible to use a Cellular Glass or Flexible Elastomeric Cellular Pipe Insulation for hot water pipe insulation? Using Phenol Foam might be very expensive and unsure the possibility of work. We have an experience of using a Flexible Elastomeric Cellular Pipe Insulation at the Zama camp.
Refer to specification section 23 07 00 paragraph 2.3 for acceptable insulations. Both cellular glass and flexible elastomeric cellular pipe insulation are within the list of acceptable insulations.
R101 Specs Section 23 07 00, Page 22 - Table 1
Is it possible to use a Cellular Glass or Flexible Elastomeric Cellular Pipe Insulation for cold water pipe insulation? Using Phenol Foam might be very expensive and unsure the possibility of work. Moreover, Polyisocyanurate foam might be used for pipe insulation under the minus degree. We believe the weather in Sagamihara would not be less than minus degree. We have an experience of using a Flexible Elastomeric Cellular Pipe Insulation at the Zama camp.
Refer to specification section 23 07 00 paragraph 2.3. Both cellular glass and flexible elastomeric cellular pipe insulation are within the list of acceptable insulations.
R102 Specs Section 23 07 00, Page 22 - Table 1
Is it possible to use a Refrigerant pipe with insulation? Refrigerant pipe shall be required per the manufacturer's recommendations. If insulation is required per the manufacturer, then insulation shall be provided in accordance with Specs Section 23 07 00, Table 1.
| Revised SF30.pdf |
| (1) Revised Section(s) to Project Specifications. Attached hereto are the following revised section(s) to the specifications. Revised section(s) will replace like-numbered section(s) in the subject solicitation specifications. Changes are indicated... |
| Revised Section(s) |
| B. CHANGES TO DRAWINGS (ISSUED) – The amendment mark “(Am-0002)” is shown on each sheet of the amended drawing sheet(s). |
| (1) Revised Sheet(s) to Drawings. Attached hereto are the following revised sheets to the drawings. Revised sheets will replace like-numbered sheets in the subject solicitation drawings. Changes are indicated in revision clouds. All portions of th... |
| Amendment 0002 - TEMF RFI Responses.pdf |