AIR TERMINAL, 60" MINIMUM HEIGHT
3/4" X 10' GROUND ROD
3/4" X 10' GROUND ROD WITH TEST WELL
AIR TERMINAL, 24" MINIMUM HEIGHT, SEE EG501 DETAIL 3 TYPICAL AIR TERMINAL
MOUNTING DETAIL
SUPPLEMENTAL LIGHTNING PROTECTION
AND GROUNDING LEGEND
AIR TERMINAL, 12" MINIMUM HEIGHT
MAIN GROUND BAR, SEE EG505 FOR SIZE. MH = 24" TO CENTER, UON.MGB
TELECOMMUNICATIONS MAIN GROUND BAR, SEE EG504 FOR SIZE. MH = 24" TO
CENTER, UON.
TELECOMMUNICATIONS GROUND BAR, SEE EG504 FOR SIZE. MH = 24" TO CENTER,
UON.
GROUND BAR, 2" H x 6" W. MH = 24" TO CENTER, UON.GB
TMGB
TGB
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
EG100
G R
O U
N D
I N G
N O
TE
S
A N D
SU
P P
LE
M
EN
TA
L
LE
G
EN
D
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
N . S
C O
TT
N . S
C O
TT
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
GENERAL LIGHTNING PROTECTION AND GROUNDING NOTES:
(APPLICABLE TO ALL EG### SHEETS; SEE SHEET EG501 FOR ADDITIONAL NOTES
1. THE LIGHTNING PROTECTION SYSTEM DESIGN IS BASED ON THE ROLLING SPHERE DESIGN. IT IS APPROXIMATE AND IS SUBJECT TO DESIGN VERIFICATION AND APPROVAL BY CONTRACTOR. ENSURE THAT DURING INSTALLATION ALL POINTS ARE WITHIN 2'-0" OF OUTSIDE BUILDING EDGE, OUTSIDE CORNERS, AND RIDGE ENDS. THE MAXIMUM SPACING OF PERIMETER TERMINALS SHALL NOT EXCEED 20'-0" FOR 12" COPPER AIR TERMINALS AND 25;-0" FOR 24" COPPER AIR TERMINALS ALONG THE PERIMETER OF THE STRUCTURES BEING PROTECTED. SUBMIT INSTALLATION DRAWINGS AND PROVIDE A UL MASTER LABEL CERTIFIED SYSTEM COORDINATING WITH ACTUAL SUBMITTED
MECHANICAL EQUIPMENT, ROOF INFORMATION, AND ROOFING MANUFACTURER REQUIREMENTS.
2. SYSTEM SHALL BE INSTALLED AS SHOWN TO ENSURE PROPER CODE COMPLIANCE AND SYSTEM CERTIFICATION
BY UL. ANY MAJOR VARIANCE SHALL ENTAIL RESUBMITTAL AND NEW APPROVAL.
3. CONTRACTOR SHALL BOND TO BUILDING STEEL, ELECTRICAL SERVICE, WATER SERVICE, AND OTHER PIPING
SYSTEMS AS REQUIRED BY NFPA 70 AND NFPA 780.
4. CONTRACTOR SHALL VERIFY STRUCTURAL MEMBER LOCATIONS.
5. CONTRACTOR SHALL VERIFY MECHANICAL EQUIPMENT LOCATIONS.
6. COORDINATE INSTALLATION OF LOOP CONDUCTOR WITH INCOMING UTILITIES. BARE COPPER COUNTERPOISE SHALL BE INSTALLED AT A MINIMUM DEPTH OF 30 INCHES, BURIED BETWEEN 3' AND 8' AWAY FROM THE BUILDING
AND HAVE NO BENDS LESS THAN 90 DEGREES.
7. CONTRACTOR SHALL PROVIDE CONDUCTOR FROM ROOF CONDUCTOR TO GROUND ROD, ROUTE CONDUCTOR
AROUND GUTTER, PARAPET WALL, AND/OR ROOF EVE AND ALL INCOMING UTILITIES.
8. ALL CONNECTIONS AND EQUIPMENT BONDING SHALL BE IN ACCORDANCE WITH SPECIFICATIONS AND NFPA 780.
9. ENSURE THAT ALL AIR TERMINAL POINTS ALONG ROOF EDGE ARE WITH 24 INCHES OF OUTSIDE BUILDING EDGE
AND OUTSIDE CORNERS.
10. BOND EXHAUST HOODS, ROOF ACCESS HATCHES/LADDERS, AND PIPES TO LIGHTNING PROTECTION
CONDUCTOR.
11. CONTRACTOR SHALL PROVIDE 3/4" X 10'-0" CU CLAD STEEL GROUND RODS AT MINIMUM LOCATIONS SHOWN.
12. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN CONDUCTOR AND INSURE THAT ALL BENDS HAVE AT
LEAST A 8" RADIUS AND DO NOT EXCEED 90 DEGREES.
13. GROUND BARS TO BE ANCHORED AT INTERVALS NOT TO EXCEED 2'-0".
14. GROUND BARS SHALL BE PRE-DRILLED.
15. AIR TERMINALS SHALL BE BLUNT TIP TYPE.
16. ALL PERIMETER COLUMNS SHALL BE BONDED TO COUNTERPOISE SYSTEM. PERIMETER COLUMN BONDS AT THE LOCATION OF A DOWN CONDUCTOR ARE OMITTED FOR CLARITY. SIZE SHALL BE AS SHOWN ON EG601. LOOP CONDUCTOR SHALL HAVE A GROUND ROD AT EACH STRUCTURE CORNER AND INTERMEDIATE COLUMN CONNECTION.
17. GROUNDING AND BONDING CONDUCTORS SHOULD NOT BE PLACED IN FERROUS METALLIC CONDUIT. IF IT IS NECESSARY TO PLACE GROUNDING AND BONDING CONDUCTORS IN FERROUS METALLIC CONDUIT THAT EXCEEDS 3 FEET IN LENGTH, THE CONDUCTORS SHALL BE BONDED TO EACH END OF THE CONDUIT USING A GROUNDING
BUSHING OR A #6 AWG CONDUCTOR, MINIMUM.
18. EACH TELECOMMUNICATIONS GROUNDING AND BONDING CONDUCTOR SHALL BE LABELED. LABELS SHALL BE LOCATED ON CONDUCTORS AS CLOSE AS PRACTICABLE TO THEIR POINT OF TERMINATION IN A READABLE POSITION. LABELS SHALL BE NONMETALLIC AND SHALL BE IN ACCORDANCE WITH TIA 606. SEE DETAIL 4 EG505.
19. PENETRATION OPENINGS THROUGH AIR BARRIERS SHALL COMPLY WITH THE BUILDING AIR BARRIER REQUIREMENTS. CORRECT ALL PENETRATIONS THAT ARE DETERMINED DEFICIENT DURING TESTING.
21. SUPPORT EXPOSED ROOF CABLES AS SHOWN IN APPLICABLE DETAILS AT 36" ON CENTER MAXIMUM.
22. LIGHTNING STRIKE TERMINALS LOCATED ALONG THE ROOF PERIMETER SHALL BE MOUNTED WITHIN 2' OF THE
EDGE OF THE ROOF.
23. LIGHTNING STRIKE TERMINALS LOCATED ALONG THE ROOF RIDGE SHALL BE MOUNTED WITHIN 2' OF THE TOP OF
THE RIDGE.
24. WHERE SPACING BETWEEN LIGHTNING STRIKE TERMINALS IS NOT INDICATED, TERMINALS SHALL BE SPACED
EVENLY ALONG ROOF PERIMETER OR RIDGE.
25. LIGHTNING PROTECTION CONDUCTOR SIZES SHALL BE IN ACCORDANCE WITH TABLE 4.1.1.1.1 OF NFPA 780.
26. REFER TO SHEETS EG601AS, EP602AS, EP603AS, EG601RE, EP602RE, EP603RE, AND T-100 FOR ADDITIONAL
INFORMATION REGARDING SURGE PROTECTIVE DEVICES (SPD).
KEYED LIGHTNING PROTECTION AND GROUNDING NOTES:
(APPLICABLE TO ALL EG### SHEETS)
1. MOUNT LIGHTNING STRIKE TERMINAL ON VENT. REFER TO DETAIL 3 ON SHEET EG502.
2. MOUNT LIGHTNING STRIKE TERMINAL ON VENT. REFER TO DETAIL 4 ON SHEET EG502.
1 1/2" = 1'-0"EG100
1 EG100 - SUPPLEMENTAL GROUNDING AND LIGHTNING PROTECTION LEGEND
M
AR
K D
ES
C
R
IP
TI
O
N D
AT
E
EG501
TYPICAL BONDING STRAPS DETAILS
NTS
EG501
TYPICAL AIR TERMINAL MOUNTING DETAIL
NTS
EG501
TYPICAL GROUND ROD DETAIL
NTS
EG501
TYPICAL CABLE SUPPORT
NTS
EG501
TYPICAL BONDING LUGS/PLATES DETAILS
NTS
EG501
TYPICAL BONDING/FASTENING CLAMPS DETAIL
NTS
EG501
TYPICAL CONDUCTOR SPLICING DETAIL
NTS
EG501
ROOF DOWN CONDUCTOR DETAIL
NTS
EG501
COLUMN BONDING DETAIL
NTS
COL.
ROOF CONDUCTOR
FASTENER CLAMP
CONDUCTOR
BOND LUG
CONDUCTOR
BOND LUG
CONDUCTOR
BOND PLATE
CONDUCTOR
CONDUCTOR
BOND STRAP
CONDUCTOR
BOND STRAP
CONDUCTOR
BOND CLAMP
BOND CLAMP
CONDUCTOR
CONDUCTOR
SPLICER
CONDUCTOR
SPLICER
CONDUCTORS
TO AIR TERMINALS
TO GROUND ROD,
REFER TO DETAIL 1
3/8" x 24" BLUNT-TIP
SOLID COPPER AIR
TERMINAL
CLAMP AND
EXOTHERMICALLY
WELD CABLE TO ROD.
3/4" DIA x 10' COPPER
CLAD
GROUND ROD
ADHESIVE CABLE HOLDER.
ADHERE TO CLEAN FLAT
SURFACE.
LIGHTNING PROTECTION NOTES:
1. LOCATE AIR TERMINALS AS INDICATED. INSURE THAT ALL POINTS
ARE WITHIN 24" OF OUTSIDE BUILDING EDGE, OUTSIDE CORNERS, AND
THAT MAXIMUM SPACING BETWEEN TERMINALS ALONG THE ROOF
PERIMETER DOES NOT EXCEED 20', AND THAT MINIMUM AIR TERMINAL
PROJECTION ABOVE OBJECT IS 24".
2. MAINTAIN HORIZONTAL OR DOWNWARD COURSING OF MAIN
CONDUCTOR AND INSURE THAT ALL BENDS HAVE AT LEAST A 8" RADIUS
AND DOES NOT EXCEED 90 DEGREES.
3. SUPPORT EXPOSED ROOF CABLES AS SHOWN IN APPLICABLE
DETAILS AT 36" ON CENTER MAXIMUM.
4. BOND TO WATER SERVICE, BUILDING STEEL, ELECTRICAL SERVICE,
AND OTHER PIPING SYSTEMS AND AS REQUIRED BY CODES.
5. SYSTEM SHALL BE INSTALLED AS SHOWN TO INSURE PROPER CODE
COMPLIANCE AND SYSTEM CERTIFICATION BY UL. ANY MAJOR
VARIANCE SHALL ENTAIL RESUBMITTAL AND NEW APPROVAL.
6. VERIFY MECHANICAL EQUIPMENT LOCATIONS.
7. VERIFY STRUCTURAL MEMBER LOCATIONS.
8. COORDINATE DOWN CONDUCTORS WITH ALL INCOMING UTILITIES.
9. PROVIDE CONDUCTOR FROM ROOF CONDUCTOR TO STEEL COLUMN.
ROUTE CONDUCTOR AROUND GUTTER OR ROOF EVE AND PENTRATE
WALL OR SOFFITT AND ATTACH TO COLUMN. PENTRATE WALL AT
GRADE AND ATTACH TO COLUMN PER DETAIL 1, THIS SHEET.
10. ALL CONNECTIONS AND EQUIPMENT BONDING IN ACCORDANCE
WITH SPECIFICATIONS AND NFPA 780.
11. CONNECT BOTTOM OF STEEL COLUMN TO LOOP CONDUCTOR. LOOP
CONDUCTOR SHALL HAVE A GROUND ROD AT EACH STRUCTURE
CORNER AND INTERMEDIATE COLUMN CONNECTION.
12. COORDINATE INSTALLATION OF LOOP CONDUCTOR WITH INCOMING
UTILITIES.
13. CONNECT LOOP CONDUCTOR TO NOT LESS THAN 1/2 OF THE
EXTERIOR COLUMNS. THE INTERVALS AT WHICH THE GROUND LOOP
CONDUCTOR SHALL BE CONNECTED TO THE PERIMETER STEEL
COLUMNS SHALL NOT AVERAGE MORE THAN 60 FEET.
WALL
STEEL COLUMN
CONCRETE SLAB
FOOTING STEEL
WALL FOOTING BEYOND
8' (MAX)
3' (MIN)
1/0 CU CABLE
1" PVC CONDUIT
BACK FACE OF WALL PIER
COLUMN PIER
(M
IN
2' -0
GRADE LEVEL
1/0 CU CABLE
EXOTHERMIC WELD
3/4" X 10'-0" CU CLAD
STEEL GROUND ROD
1/0 CU CABLE
EXOTHERMIC WELD (TYP.)
BRASS SWIVEL ADAPTER
STAINLESS STEEL NUT
STAINLESS STEEL WASHER
AND LEAD WASHER
CONCEALED POINT BASE
ASSEMBLY THROUGH
BOLTED TO ROOF
LOOP CLIP
MAIN
CONDUCTOR
LINE OF RIDGE
OR DORMER
SEAL AROUND WASHERS
WITH URETHANE SEALANT
STANDING SEAM
METAL ROOFING
CONCRETE SLAB
1" PVC CONDUIT
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
EG501
G R
O U
N D
IN
G
A N
D L
IG
H
TN
IN
G P
R O
TE
C
TI
O
N D
ET
AI
L S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
B.
A
D
KI
N S
B.
A
D
KI
N S
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
M
AR
K D
ES
C
R
IP
TI
O
N D
EG502
LIGHTNING PROTECTION DETAIL 1
NTS
EG502
LIGHTNING PROTECTION DETAIL 2
NTS
EG502
LIGHTNING PROTECTION DETAIL 3
NTS
EG502
LIGHTNING PROTECTION DETAIL 4
NTS
EG502
LIGHTNING PROTECTION DETAIL 5
NTS
EG502
EQUIPMENT GROUNDING
NTS
INTERIOR EXTERIOR
MAIN CONDUCTOR
THROUGH WALL ASSEMBLY
WITH ALUMINUM EXTERIOR AND
COPPER INTERIOR
THREADED ROD
GASKET
CONNECTOR
COPPER MAIN CONDUCTOR
WALL
BUILDING STEEL
8" MINIMUM
RADIUS BEND
90 MAXIMUM
BEND ANGLE
MAIN CONDUCTOR
AHESIVE SUPPORT,
TYPICAL
ALUMINUM AIR
TERMINAL
VENTILATION FAN
MAIN CONDUCTOR
BONDING LUG
BONDING CONDUCTOR
FLASHING
ROOF
AIR TERMINALPLUMBING VENT
THROUGH ROOF
U-BOLT CLAMP
MAIN CONDUCTOR
FLASHING ROOF
TEE CONNECTION TO
MAIN CONDUCTOR
BONDING NOTES:
1. ITEMS 1-10 SHOWN IN DIAGRAM ARE TYPICAL BODIES OF CONDUCTANCE AS NOTED BELOW.
USE FULL SIZE MAIN CONDUCTOR AND APPROPRIATE FITTING FOR CONNECTION.
2. ITEM 11 (PLUMBING VENTS) REQUIRES BONDING WITH MAIN SIZE CABLE ONLY IF WITHIN 6'-0"
OF SYSTEM.
3. ITEMS 12-15 ARE TYPICAL BODIES OF CONDUCTANCE AS NOTED BELOW. USE SECONDARY
SIZE SMALLER CONDUCTOR AND APPROPRIATE FITTING FOR CONNECTION (ITEM 12
TYPICALLY OCCURS AT EACH DOWN-LEAD AND ROOF LEVEL CHANGE AS SHOWN).
4. BONDING CONNECTIONS SHOWN ARE TYPICAL EXAMPLES. MAKE ALL CONNECTIONS
REQUIRED TO MEET CODES AS NOTED BELOW. ADJUST FITTING TYPE AS REQUIRED tO SUIT
FIELD CONDITIONS.
5. BONDING DIAGRAM REPRESENTS BONDING FOR TYPICAL BONDING CONDITIONS FOUND
FOR GENERAL BUILDING CONSTRUCTION. BONDING FOR CMF ROOF SHALL SUIT INSTALLED
WORK. SEE MECHANICAL AND ARCHITECTURAL DRAWINGS FOR FANS, VENTS, ETC.
1 2
9 10
PROVIDE SECOND
MAIN CONDUCTOR
TO ROOF
CONDUCTOR IF A
SINGLE CONDUCTOR
IS LONGER THAN 8'-0"
TEE CONNECTION TO
MAIN CONDUCTOR
TERMINAL BASE,
ADHESIVE
CONNECTION
BRONZE BONDING PLATE,
8 SQUARE INCHES
CONTACT SURFACE
EQUIPMENT SUPPORT STRUCTURE
3/8" MIN STEEL STUD,
LENGTH AS REQUIRED.
ARC WELD TO TANK WALL
CU GROUNDING LUG
THERMITE WELD
CABLE TO LUG
#2 AWG BARE CU CABLE
TO GROUNDING LOOP
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
EG502
G R
O U
N D
IN
G
A N
D L
IG
H
TN
IN
G P
R O
TE
C
TI
O
N D
ET
AI
L S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
N . S
C O
TT
N . S
C O
TT
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
M
AR
K D
ES
C
R
IP
TI
O
N D
EG504
TYPICAL GROUND ROD AND TEST WELL DETAIL
NTS
NON-METALLIC COVER.
SHALL READ "GROUND ROD".
FINISHED SLAB OR GRADE
8" DUCTILE OR CAST
IRON PIPE 24" LONG
#3/0 BARE CU GROUNDING RING
CONDUCTOR 18" BELOW GRADE
EXOTHERMIC WELD
3/4" X 10'-0" COPPER CLAD
STEEL GROUND ROD
AUGERED HOLE
GRAVEL OR CRUSHED ROCK
FINISHED GRADE
SLURRY OF POWDERED
BENTONITE CLAY
NATIVE SOIL TO GRADE
EXOTHERMIC WELD
AUGERED
HOLE
SLURRY OF POWDERED
BENTONITE CLAY
#3/0 AWG BARE COPPER
EXOTHERMICALLY
BONDED TO GROUND ROD 3/4" X 10'-0" COPPER
CLAD STEEL
GROUND ROD
9" 12
6"
4"
6"
'-6
6"
4"
TY
P
TY
P
TY
P
M
IN
EG504
TYPICAL GROUND ROD DETAIL
NTS
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
EG503
G R
O U
N D
IN
G
A N
D L
IG
H
TN
IN
G P
R O
TE
C
TI
O
N D
ET
AI
L S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
B.
A
D
KI
N S
B.
A
D
KI
N S
D . M
AL
EN
E
S.
L.
O
/1
0/
W
F-
-R
-0
F2
-7 0-
M
AR
K D
ES
C
R
IP
TI
O
N D
PROVIDE TWO HOLE BOLTED
CONNECTORS WITH GROUND
RATED BELLEVILLE WASHERS
BETWEEN BUS AND
CONNECTOR. PROVIDE
CONDUCTIVE GREESE BETWEEN
BUS AND COONNECTIONS.
PROVIDE FULL WRAP STRAP
CONNECTORS. CLAMPING OF
THE STRAPS SHALL BE WITH
FULL SURFACE CLAMPING TOOL
TO INSURE EVEN COMPRESSION
AROUND THE CABLE.
#6 AWG MINIMUM GROUND
WIRE TO METAL CONDUITS
IN ROOM.
GROUND WIRE TO
EXPOSED BUILDING
COLUMN IN ROOM IF
PRESENT.
#4 AWG MINIMUM GROUND
WIRE TO CATV ENCLOSURE
IN ROOM IF PRESENT.
#4 AWG MINIMUM GROUND
WIRE TO PANELBOARD
ENCLOSURE IN ROOM.
#4 AWG MINIMUM GROUND
WIRE TO CABLE TRAY(S) IN
ROOM.
STAND-OFF INSULATOR
MOUNTED TO WALL.
TYPICAL FOR TWO
LOCATIONS.
#4 AWG MINIMUM GROUND
WIRE TO PROTECTIVE
ENTRANCE TERMINALS IN
ROOM IF PRESENT.
COPPER TMGB SIZE: 4"
HIGH BY 1/4" THICK BY 24"
LONG MINIMUM.
FOR TMGB: #3/0 AWG GROUND WIRE TO
BUILDING MAIN ELECTRICAL SERVICE.
SEE SHEET EP601.
#3/0 AWG GROUND WIRE
TO BUILDING GROUND
LOOP IF PRESENT.
FOR TMGB: #6 AWG
MINIMUM GROUND WIRE
TO UNDERGROUND
CONDUIT STUB-UPS.
#6 AWG MINIMUM GROUND
WIRE TO BUILDING OUTSIDE
PLANT CONDUITS.
PROVIDE TWO HOLE BOLTED
CONNECTORS WITH GROUND
RATED BELLEVILLE WASHERS
BETWEEN BUS AND CONNECTOR.
PROVIDE CONDUCTIVE GREESE
BETWEEN BUS AND
CONNECTIONS. PROVIDE FULL
WRAP STRAP CONNECTORS.
CLAMPING OF THE STRAPS SHALL
BE WITH FULL SURFACE
CLAMPING TOOL TO INSURE EVEN
COMPRESSION AROUND THE
CABLE.
#6 AWG MINIMUM GROUND
WIRE TO THROUGH-FLOOR
CONDUITS IF PRESENT.
#6 AWG MINIMUM GROUND
WIRE TO UNDERGROUND
CONDUIT STUB-UPS IF
PRESENT.
#1/0 AWG MINIMUM GROUND WIRE TO
TMGB (OR TR TGB AS IDENTIFIED).
COPPER TGB SIZE: 2" HIGH
BY 1/4" THICK BY 24" LONG
MINIMUM.
#4 AWG MINIMUM GROUND
WIRE TO PROTECTIVE
ENTRANCE TERMINALS IN
ROOM IF PRESENT.
STAND-OFF INSULATOR
MOUNTED TO WALL.
TYPICAL FOR TWO
LOCATIONS.
#4 AWG MINIMUM GROUND
WIRE TO CABLE TRAY(S) IN
ROOM.
#4 AWG MINIMUM GROUND
WIRE TO PANELBOARD
ENCLOSURE IN ROOM.
#4 AWG MINIMUM GROUND
WIRE TO CATV
ENCLOSURE IN ROOM IF
PRESENT.
GROUND WIRE TO EXPOSED
BUILDING COLUMN IN ROOM
IF PRESENT.
#6 AWG MINIMUM GROUND
WIRE TO METAL CONDUITS
IN ROOM.
1. GROUND CONDUCTOR SIZES ARE IDENTIFIED AS MINIMUMS. PROVIDE
ACTUAL CABLE SIZE BASED ON ACTUAL CABLE ROUTING AND ANSI
J-STD-607A STANDARDS IF LARGER.
2. ALL GROUND CABLES SHALL BE LABELED AT BOTH ENDS.
3. ALL GROUNDING CONDUCTORS ARE NOT SHOWN. SEE PLANS AND
SPECIFICATIONS FOR ADDITIONAL GROUNDING CONDUCTORS OR
REQUIREMENTS.
4. PROVIDE EXOTHERMIC WELD CONNECTIONS AND BOLTED LUG
CONNECTIONS AT GROUND BARS AS PER SPECIFICATIONS.
GENERAL SHEET NOTES
GROUND WIRE TO
EQUIPMENT
STAND-OFF INSULATOR
MOUNTED TO WALL
GROUND WIRE TO
EQUIPMENT
1/4" THICK BY 24"
LONG COPPER
GROUND BUS
WALLSUPPORT BRACKET
EG505
GROUND BAR CONNECTION DETAIL
NTS
EG505
CRIMPING AND TAGGING DETAIL
NTS
EG505
MAIN/TELECOMMUNICATION MAIN GROUND BAR (MGB/TMGB) DETAIL
NTS
EG505
TYPICAL TELECOMMUNICATION GROUND BAR (TGB)
NTS
EG505
TYPICAL GROUND BAR SIDE VIEW
NTS
CORRECT
CONNECTION
GROUND WIRE FROM OTHER
GROUND BARS, EQUIPMENT
GROUNDS, ETC.
TO GROUNDING ELECTRODE
SURFACE RACEWAY,
SCHEDULE 40 PVC
INCORRECT CONNECTION
NOT ACCEPTABLE
TO GROUNDING ELECTRODE
GROUND WIRE FROM OTHER
GROUND BARS, EQUIPMENT
GROUNDS, ETC.
FINISHED FLOOR
FINISHED FLOOR
9"
9"
SILICONE BRONZE
BOLTING HARDWARE
TAGGING CABLE IS REQUIRED AT
AT BOTH ENDS OF CABLE.
BOLTING HARDWARE MUST BE
SILICONE BRONZE.
TAGGING NOTE:
INSPECTION HOLE
TYPICAL
COMPRESSION
CONNECTOR
CABLE TAGS
NO MORE THAN 1/16"
PROTRUDING FROM
END OF LUG.
CLEAR HEAT SHRINK
OMITTED FOR
CLARITY.
OPEN SLOT;
ENSURE CABLE IS
INSERTED
COMPLETELY INTO
LUG.
D O
N O
T D
ISC
O
N N
E C
T
LE
AD
CABLE TAGS
(TYPICAL BOTH ENDS)
ALL COMPRESSION
CONNECTORS
No-Ox-ID
COMPOUND
UNDER LUG
GROUND BUS BAR
ASSEMBLY
CRIMPING LOCATION
(TYPICAL BOTH ENDS)
FIRST CRIMP
SECOND CRIMP
THIRD CRIMP
FOURTH CRIMP
TO GROUND BUS BAR
(TYPICAL BOTH ENDS)
R O
U
TIN
G
TA
G
DETAIL 4 NOTES:
1. EPOXY OR SPOT WELD THREAD
COUPLING AFTER COMPLETING
ALIGNMENT WITH HANGAR FLOOR
INCLUDING COVER ALIGNMENT.
2. MAXMUM RESISTANCE TO GROUND
SHALL BE 25 OHMS FROM ANY GROUND
ROD.
3. INSTALL PIGTAIL TO CONNECT TO
FACILITY GROUND GRID. DO NOT CUT
GROUND GRID CONDUCTORS.
4. EXOTHERMIC BOND. INSTALL BELOW
CONCRETE SLAB.
5. PAINT THE GROUND POINT
IDENTIFIER NUMBER IN 1" BLACK
LETTERS. SEE EG111, EG112, EG113
AND EG210 FOR IDENTIFIERS.
6. PAINT THE WORD "GROUND" IN 1"
BLACK LETTERS.
7. PAINT THE DATE THE GROUND POINT
WAS TESTED IN 1/2" BLACK LETTERS.
8. PAINT IS APPLIED DIRECTLY TO THE
FLOOR AND IS NOT APPLIED TO THE
RECEPTACLE.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
EG504
G R
O U
N D
IN
G
A N
D L
IG
H
TN
IN
G P
R O
TE
C
TI
O
N D
ET
AI
L S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
N . S
C O
TT
N . S
C O
TT
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
M
AR
K D
ES
C
R
IP
TI
O
N D
DUAL TECHNOLOGY (ULTRASONIC AND PASSIVE INFRARED) LOW
VOLTAGE OCCUPANCY SENSOR, WALL MOUNTED AT 7'-6" UNLESS
OTHERWISE NOTED.
SYMBOL DENOTES GENERAL TYPE OF LUMINAIRE
LUMINAIRE TYPE DESIGNATION (SEE SCHEDULE AND DETAILS)
SWITCH DESIGNATION
CIRCUIT IDENTIFICATION (IF PRESENT)
PC
LCP
OS
OS
SUPPLEMENTAL LIGHTING LEGEND
DIGITAL TIME SWITCH WITH MANUAL-ON/TIMED-OFF OPERATION AND
MANUAL-OFF OVERRIDE. TIME-OUT SETTING SHALL BE SET FOR 15
MINUTES UNLESS OTHERWISE NOTED.
A2 LP1-1,a
LIGHTING CONTROL PANEL
WALL-MOUNTED PHOTOCELL
'3'
'p'
'4' 'a'
'mc'
'wp'
DUAL TECHNOLOGY (ULTRASONIC AND PASSIVE INFRARED) LOW
VOLTAGE OCCUPANCY SENSOR, CEILING MOUNTED UNLESS OTHERWISE
INDICATED.
DUAL TECHNOLOGY WALL SWITCH OCCUPANCY SENSOR.
SINGLE POLE 20A SWITCH. SUBSCRIPT (WHERE PRESENT)
DENOTES THE FOLLOWING:
LOW VOLTAGE SWITCH. SUBSCRIPT (WHERE PRESENT)
DENOTES THE FOLLOWING:
T a
LV
'bi' BI-LEVEL SWITCH. PROVIDE TWO TOGGLE SWITCHES SIDE BY
SIDE IN A SHARED JUNCTION BOX. SEE LIGHTING PLANS
INDICATING SWITCH DESIGNATIONS PER FIXTURE ("a" or "b").
ELECTRONIC MULTI-SCENE DIMMING SWITCH CONTROL FOR LIGHTING.
"M" INDICATED MASTER OR PRIMARY CONTROL, "S" INDICATED SLAVE
OR SECONDARY CONTROL.
OS
D M D S
S
S
S
S
DS DAYLIGHT SENSOR, CEILING- OR PENDANT-MOUNTED. "a" DENOTES
CONTROL ZONE DESIGNATION.
DS DAYLIGHT SENSOR, WALL- OR SKYLIGHT WELL-MOUNTED. "a" DENOTES
CONTROL ZONE DESIGNATION.
a a
WEATHERPROOF (GASKETED) SWITCH.
PILOT LIGHT SWITCH.
SWITCH CONTROLLING MATCHING LETTERED FIXTURES
(TYPICAL, SINGLE LOWER CASE LETTERS).
FOUR-WAY SWITCH.
THREE-WAY SWITCH.
'D' DIMMER SWITCH.
ELECTRONIC MULTI-SCENE DIMMING SWITCH.
MOMENTARY CONTACT SWITCH. LETTER (WHERE PRESENT)
DENOTES SWITCH CONTROLLING MATCHING LETTERED
FIXTURES.
'050' RELAY SWITCH. LOWER CASE LETTER
(WHERE PRESENT) IDENTIFIES SWITCH WITH RELAYS.
'a' RELAY SWITCH. LOWER CASE LETTER
(WHERE PRESENT) IDENTIFIES SWITCH WITH RELAYS.
'K' KEYED SWITCH. COORDINATE KEYING WITH BASE CIVIL ENGINEERING.
EMERGENCY LIGHTING FIXTURES
'K(##)' KEYED SWITCH. COORDINATE KEYING WITH FORT CARSON DPW.
"(##)" INDICATES ZONE CONTROLLED.
'D'
WALL-MOUNTED AND CEILING-MOUNTED EXIT SIGNS.
HATCHING INDICATES ILLUMINATED SIDE(S). ARROW(S) INDICATE(S)
CHEVRON DIRECTION(S) FOR EGRESS. FIXTURE MAY BE SHOWN IN
FULLTONE OR HALFTONE.
ELTS EMERGENCY LIGHTING TRANSFER SWITCH
DUAL TECHNOLOGY WALL SWITCH VACANCY SENSOR.VSS
MULTI-ZONE COMBINATION DAYLIGHT HARVESTING AND MANUAL
DIMMING CONTROL.
DD
'X' HAZARDOUS AREA-RATED SWITCH. UL LISTED FOR CLASS I,
DIVISION 1 HAZARDOUS LOCATIONS.
##E
EPS EMERGENCY POWER SYSTEM FOR EGRESS LIGHTING - BATTERY
INVERTER SET
NT "NIGHT TIME" UNSWITCHED LIGHT
ERP EGRESS RELAY PANEL. SUPPLY CIRCUIT CONNECTS TO
DEDICATED FIRE ALARM BRANCH CIRCUIT PANEL.
COORDINATE WITH EL500 AND FIRE ALARM MATRIX.
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL100
LI
G
H
TI
N G
S U
PP
LE
M E N
TA
L
LE
G
E N D
A N
D N
O
TE
S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
GENERAL LIGHTING NOTES:
(APPLICABLE TO ALL EL SERIES SHEETS)
1. RACEWAYS SHALL HAVE A SEPARATE EQUIPMENT GROUNDING/BONDING CONDUCTOR. RACEWAY
SHALL NOT BE USE AS THE SOLE GROUNDING/BONDING PATH.
2. COORDINATE THE LOCATIONS AND MOUNTING HEIGHTS OF LIGHTING FIXTURES IN MECHANICAL AND ELECTRICAL ROOMS WITH THE FINAL LOCATIONS OF PIPES, DUCTS AND OTHER EQUIPMENT FOR BEST
ARRANGEMENT. FIXTURES SHALL BE EASILY ACCESSIBLE FOR RELAMPING.
3. CIRCUIT EXIT SIGNS TO NEAREST LIGHTING CIRCUIT (UNLESS OTHERWISE INDICATED) USING UNSWITCHED
PHASE LEG.
4. OCCUPANCY SENSOR AND DAYLIGHT PHOTOSENSOR LAYOUT IS CONCEPTUAL ONLY AND IS SHOWN FOR COVERAGE INTENT ONLY. CONTRACTOR TO DETERMINE ACTUAL QUANTITY AND LOCATIONS WITHIN EACH
ROOM PER MANUFACTURER'S INSTRUCTION.
5. LIGHTING FIXTURES ARE CONTROLLED BY SWITCHING DEVICE WITHIN SAME ROOM OR AREA, UON.
6. ALL EGRESS ZONE LIGHT FIXTURES CONTROLLED BY AN OCCUPANCY SENSOR MUST COMPLY WITH
NFPA 101 PARAGRAPH 7.8.1.2.2.
7. FIXTURES SERVED BY BOTH DIMMING AND EMERGENCY DRIVERS SHALL PROVIDE 100% LIGHT OUTPUT
UPON EMERGENCY ACTIVATION.
8. EMERGENCY BALLASTS, DRIVERS, AND INVERTERS SHALL BE WIRED TO UNSWITCHED CONDUCTORS
(WIRED AHEAD OF ANY LOCAL SWITCHING).
9. DO NOT PENETRATE STRUCTURAL COLUMNS, BEAMS, AND TRUSSES. AFFIX DEVICES AND RACEWAY WITH BEAM C-CLAMPS, BRACKETS, CLIPS, UNISTRUT, AND OTHER NON-PENETRATING AND NON-ADHESIVE
HARDWARE.
10. CONDUIT AND CONDUCTOR SIZES LISTED ARE MINIMUM SIZES. CIRCUITS MAY BE COMBINED INTO COMMON CONDUIT. CONTRACTOR IS RESPONSIBLE FOR RESIZING CONDUITS PER NFPA 70 FILL RATIO AND
DERATING REQUIREMENTS.
11. INTERIOR EMERGENCY FIXTURES SHALL BE SWITCHED BY THE LOCAL SWITCHING DEVICE IN THE ROOM AND SHALL HAVE AUTOMATIC TESTING CAPABILITY. UPON LOSS OF POWER, EMERGENCY FIXTURES SHALL
BYPASS THE LOCAL SWITCHING DEVICE AND COME ON AUTOMATICALLY.
12. EACH LIGHTING BRANCH CIRCUIT HOME RUN SHALL CONSIST OF MINIMUM 2-#12,#12G CONDUCTORS IN MINIMUM 3/4" CONDUIT UNLESS OTHERWISE NOTED. ENTIRE CIRCUIT SHALL BE SAME SIZE AS HOME RUN
SIZE INDICATED.
13. INTERIOR LIGHT FIXTURES IN ROOMS WITH DAYLIGHT PHOTOSENSORS AND/OR DIMMER SWITCHES SHALL HAVE DIMMING DRIVERS AND SHALL WORK IN CONJUNCTION WITH THE OCCUPANCY SENSOR
AND/OR WALL SWITCHES IN THE ROOM.
14. COORDINATE DIMMER TYPE AND WIRING WITH ASSOCIATED LIGHT FIXTURE DIMMING REQUIREMENTS (I.E. 3-WIRE 0-10V, ELECTRONIC LOW VOLTAGE, ETC.) OR WITH THE LIGHTING CONTROL SYSTEM PROPRIETARY REQUIREMENTS (I.E. LUTRON, nLIGHT, DALI, ETC.) AS NECESSARY. 3-WIRE DIMMERS SHALL BE PROVIDED WITH A DEDICATED NEUTRAL FOR EACH CONTROL ZONE. COORDINATE PHASE CONTROL OF LED DRIVERS (I.E. REVERSE PHASE, FORWARD PHASE, ETC.) WITH LIGHT FIXTURE MANUFACTURER'S RECOMMENDATIONS. LOW-VOLTAGE CONTROL WIRING IS NOT SHOWN ON PLANS FOR CLARITY, BUT SHALL
BE PROVIDED AS REQUIRED.
15. LINE VOLTAGE AND LOW VOLTAGE WIRING SHALL BE PROVIDED IN SEPARATE CONDUITS/RACEWAYS.
16. WIRELESS CONTROLS SHALL NOT BE USED.
17. JUNCTION BOXES, DEVICES, BACKBOXES, ASSOCIATED CONDUIT, ETC., LOCATED ON STEEL MEMBERS, PRECAST CONCRETE, CONCRETE, AND CONCRETE BLOCK WALLS SHALL BE SURFACE MOUNTED.
JUNCTION BOXES, DEVICES, BACKBOXES, ASSOCIATED CONDUIT, ETC., SHALL BE RECESS MOUNTED ON
GYPSUM WALLS. COORDINATE WITH ARCHITECTURAL SHEETS.
18. THE FOLLOWING CLEARANCES SHALL BE PROVIDED BETWEEN RADIANT HEATERS AND ELECTRICAL EQUIPMENT AND INFRASTRUCTURE, EXCEPT FOR ELECTRICAL SUPPLY CIRCUITS TO THE RADIANT
HEATERS:
- MAINTAIN MINIMUM 1'-8" HORIZONTAL SEPARATION FROM THE WIDEST POINT OF THE RADIANT HEATER.
- MAINTAIN MINIMUM 4'-0" BELOW THE LOWEST POINT OF THE RADIANT HEATER.
- MAINTAIN MINIMUM 0'-4" ABOVE THE HIGHEST POINT OF THE RADIANT HEATER.
CLEARANCES SHALL FORM A RECTANGULAR PRISM AROUND THE RADIANT HEATER. THE HORIZONTAL SEPARATION SHALL APPLY AS THE END CLEARANCE AS WELL. THESE CLEARANCES ARE BASED ON THE RADIANT HEATER BASIS OF DESIGN MODELS INDICATED IN THE ELECTRICAL-MECHANICAL EQUIPMENT SCHEDULES ON SHEETS EP601AS AND EP601RE FOR 0° MOUNTING ANGLE. SHOULD A DIFFERENT MANUFACTURER OR MODEL BE USED OR INSTALLATION ANGLE EMPLOYED, THE CLEARANCES SHALL BE
COORDINATED WITH THE COR BASED ON MANUFACTURER REQUIREMENTS.
19. WHERE CEILING OCCUPANCY SENSORS ARE SHOWN IN UNFINISHED AREAS, OCCUPANCY SENSORS
SHALL BE MOUNTED AT HEIGHT OF LIGHTS U.O.N.
KEYED LIGHTING NOTES:
(APPLICABLE TO ALL EL SHEETS)
A1. SEE DETAIL 1 ON SHEET EL502.
A2. SEE DETAIL 2 ON SHEET EL502.
A3. SEE DETAIL 3 ON SHEET EL502.
A4. SEE DETAIL 4 ON SHEET EL502.
A5. SEE DETAIL 5 ON SHEET EL502.
A6. SEE DETAIL 6 ON SHEET EL502.
A7. SEE DETAIL 7 ON SHEET EL502.
B1. SEE DETAIL 1 ON SHEET EL503.
B2. SEE DETAIL 2 ON SHEET EL503.
B3. SEE DETAIL 3 ON SHEET EL503.
B4. SEE DETAIL 4 ON SHEET EL503.
B5. SEE DETAIL 5 ON SHEET EL503.
B6. SEE DETAIL 6 ON SHEET EL503.
C1. SEE DETAIL 1 ON SHEET EL504.
D1. SEE DETAIL 1 ON SHEET EL505.
D2. SEE DETAIL 2 ON SHEET EL505.
1. LCP-2 STACKED ON LCP-1.
2. MOUNT AT 9'-0" AFF.
3. MOUNT AT 10'-0" AFG.
4. MOUNT AT 8'-0" AFF.
M
AR
K D
ES
C
R
IP
TI
O
N D
NOTE: BODINE GTD20A RELAY DEVICE OR EQUAL FOR CONTROL OF POWER TO FIXTURES WITH EXTERNAL EMERGENCY BATTERY SUPPLY IN LIEU OF INTEGRAL EMERGENCY DRIVER/BALLAST/BATTERY. UNDER NORMAL CIRCUMSTANCES, RELAY SHALL BE CONTROLLED BY SWITCH ON WALL AND NORMAL POWER. IN THE EVENT OF A POWER OUTAGE, RELAY SHALL BYPASS TOGGLE SWITCH CONTROL AND SUPPLY POWER FROM THE EMERGENCY
BATTERY INVERTER.
INSTALL PER MANUFACTURER RECOMMENDATION. LOCATE RELAY ABOVE CEILING NEAR SWITCH, UNLESS NOTED
OTHERWISE. PROVIDE IN ENCLOSURE FOR THE ENVIRONMENT IN WHICH RELAY IS INSTALLED.
1 2 3 4 5 6 7 1 2 3 4 5 6 7
GTD20A
ELECTRONICS
COVER
GTD20A TERMINAL
BLOCKS
LOCAL
SWITCHING
MEANS
FIXTURE(S)
HOT
NEUTRAL
HOT
NEUTRAL
CKT BKR
PANEL
T1 T2
EXTERNAL
BATTERY/
INVERTER
CEILING HANGER WIRE SUPPORT
FIXTURE HANGER SUPPORT WIRE,
12 GAUGE MIN.
(TYP OF 4)
TROFFER
TEE-BAR SUPPORT
ELEVATION AS
INDICATED ON PLANS
NOTES:
1. SUSPEND CHAIN FROM BEAM CLAMP OR FROM METAL FRAMING CHANNEL, WHEN BEAM SPACING DOES NOT COINCIDE WITH
FIXTURE SPACING AND PLACEMENT.
2. METAL FRAMING CHANNEL CAN ALSO BE USED AS RACEWAY (WHEN U.L. APPROVED FOR USE)
3. PROVIDE SUPPORT FOR JUNCTION BOXES.
CONDUIT SUPPORT
JUNCTION BOX (SEE NOTE 3)
BRANCH CIRCUIT CONDUIT
FLEXIBLE METAL
CONDUIT CONNECTOR
BEAM CLAMP (SEE NOTE 1)
METAL FRAMING CHANNEL
(SEE NOTE 1 & 2)
STRUCTURAL FLOOR
BEAM CLAMP
METAL FRAMING CHANNEL BOLT, SPRING NUT,
AND EYE BOLT AS REQUIRED (TYP)
NYLON TIE WRAPS EVERY 6'-0" (TYP)
CUT LENGTH OF CHAIN AS REQUIRED (TYP)
FLEXIBLE METAL CONDUIT
CHAIN HANGER LIGHT FIXTURE
HVAC CONNECTION NOTES
1. ALL LIGHTING ZONES SHALL HAVE THE CAPABILITY OF PROVIDING RELAYS (COMMON,
NO, NC) TO LOCAL HVAC EQUIPMENT. RELAY SHALL BE PROVIDED VIA POWER PACK
OR OCCUPANCY SENSOR.
2. WHERE POWER PACKS OR OTHER CONTROLLER DOES NOT HAVE THIS CAPABILITY
FOR A GIVEN ZONE, THE ALTERNATIVE HVAC CONNECTION FROM THE OCCUPANCY
SENSOR SHALL BE USED.
3. WHERE HVAC EQUIPMENT RELAYS ARE PROVIDED FROM THE POWER PACK, THE
POWER PACK SHALL BE CAPABLE OF TRANSMITTING THE OCCUPANCY SIGNAL TO THE
HVAC CONTROLLER REGARDLESS OF LIGHTING MANUAL ON/OFF STATE. IF THE
POWER PACK IS INCAPABLE OF SUCH OPERATION, THE ALTERNATIVE HVAC
CONNECTION FROM THE OCCUPANCY SENSOR SHALL BE USED.
POWER PACK
HOT
WHT
RED (LINE)
RED (LOAD)
LOAD
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
NEUTRAL
BLK
WHT
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
WHITE (NEUTRAL)
(TYP)
COMMON
NO INPUT
NC INPUT
HVAC
EQUIPMENT
CONTROLLER
BLACK
RED
CLASS 2 WIRING DESIGNATIONS
BLUE
BLUE/WHITE
YELLOW
ORANGE
YELLOW/ORANGE
DC RETURN
POWER (24VDC)
OCCUPANCY: AUTO-ON/AUTO-OFF
OCCUPANCY: MANUAL ON/AUTO-OFF
HOLD-ON
HOLD-OFF
LOCAL SWITCH INPUT
BROWN
GREEN
BROWN/WHITE
DRY CONTACT NC (NORMALLY CLOSED)
DRY CONTACT COMMON
DRY CONTACT NO (NORMALLY OPEN)
HVAC WIRING DESIGNATIONS
NO RELAY
NC RELAY
COMMON
CONTROL
COMMON
+24VDC
TO HVAC
EQUIPMENT
CONTROLLER
TO LIGHTING
POWER PACK
OCCUPANCY
SENSOR
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL500
LI
G
H
TI
N G
C O
N
TR
O L
D
IA
G R
AM
S
G
EN
ER
AL
IN
FO
R M
AT
IO
N
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
N.T.S.EL500
5 EMERGENCY LIGHTING CONTROL RELAY DETAIL
N.T.S.EL500
4 TYPICAL - RECESSED TROFFER
N.T.S.EL500
3 TYPICAL - SUSPENDED FIXTURE
KEYED NOTES - EL500 SHEETS
1 PROVIDE QUANTITY OF SWITCHES AS INDICATED ON PLANS AT A MINIMUM. CIRCUIT IN PARALLEL.
2 PROVIDE SWITCHES IN COMMON ENCLOSURE AT LOCATIONS INDICATED ON PLANS.
3 FIRE ALARM/MASS NOTIFICATION SYSTEM PANEL DRY CONTACT ACTUATES "HOLD ON" DURING FIRE ALARM, AS
INDICATED IN THE FIRE ALARM EGRESS HOLD-ON NOTES ON SHEET EL500
5 PROVIDE SWITCHES IN ADJACENT TO EACH OTHER AT LOCATIONS INDICATED ON PLANS.
6 SEE HVAC CONNECTION DIAGRAM ON EL500. COORDINATE WITH MECHANICAL PLANS FOR APPLICATION. WHERE
CONNECTIONS ARE NOT USED, WIRES SHALL BE CAPPED.
7 SEE LIGHTING CONTROL DIAGRAM REFERENCED ON THE LIGHTING PLANS FOR EACH SPACE IDENTIFYING USE
OF NON-HVAC POWER PACK CONNECTIONS. WHERE CONNECTIONS ARE NOT USED, WIRES SHALL BE CAPPED.
8 SEE THREE WAY AND FOUR WAY SWITCHES SHOWN IN EL101AS
N.T.S.EL500
1 HVAC CONNECTION
FIRE ALARM EGRESS HOLD-ON NOTES:
1. FIRE ALARM EGRESS RELAY PANEL (ERP) SHALL BE COORDINATED WITH THE FIRE ALARM SYSTEM.
RELAYS SHALL INDICATE THE FIRE ALARM SYSTEM IS IN AN ALARM STATE. UPON TERMINATION OF ALARM
STATE, RELAYS SHALL OPEN AND LIGHTING SYSTEM SHALL RETURN TO NORMAL OPERATION.
2. THE ERP SHALL BE FAIL ON (NORMALLY CLOSED) OPERATION.
3. THE ERP SHALL PROVIDE INPUT TO THE POWER PACKS IN THE FOLLOWING LOCATIONS AS INDICATED FOR THE ZONES OR BALLASTS INDICATED IN THE RESPECTIVE CONTROL DIAGRAMS (THE FOLLOWING LIST
INCLUDES COVERAGE SPACES, NOT NECESSARILY THE QUANTITY OF RELAY OUTPUTS):
AMMUNITION STOREHOUSE
100 VESTIBULE
101 LOBBY
102 PROCESSING
103 CORRIDOR
104 CORRIDOR
105 MEN'S RR
106 WOMEN'S RR
109 OPEN OFFICE - WS
110 CORRIDOR
117 BREAK ROOM
121B BRASS STORAGE AND DRY STORAGE BAYS
121D BRASS STORAGE AND DRY STORAGE BAYS
121E BRASS STORAGE AND DRY STORAGE BAYS
123 SCREENING AND WEIGHING BAY #1
125 SCREENING AND WEIGHING BAY #3
REPACKING BUILDING
100 VESTIBULE
101 CORRIDOR
108 BREAK ROOM
109 CORRIDOR
110 MEN'S RR
112 WOMEN'S RR
114 WORK BAY #1
115 WORK BAY #2
116 WORK BAY #3
117 WORK BAY #4
118 STORAGE BAY
N.T.S.EL500
2 ALTERNATIVE HVAC CONNECTION
GENERAL NOTES - EL500 SHEETS
1 MAXIMUM NUMBER OF SENSORS PER POWER PACK MAY VARY BETWEEN MANUFACTURERS.
2 DO NOT CONNECT THE RED (+24VDC) WIRES TOGETHER ACROSS POWER PACKS.
3 UNLESS OTHERWISE NOTED, THE OCCUPANCY SENSOR SHUT OFF TIME DELAY SHALL BE 15 MINUTES.
4 POWER PACKS SHALL CONTAIN A GRACE PERIOD (MIN. 15 SECONDS, MAX. 60 SECONDS) FOR "MANUAL ON" OPERATION
WHEREBY THE LOAD TURNS OFF WHEN THE SENSOR TIME DELAY EXPIRES, THEN THE LOAD TURNS BACK ON IF OCCUPANCY SENSOR INPUT IS TRIGGERED DURING THE GRACE PERIOD. IF THE GRACE PERIOD EXPIRES WITH NO SENSOR INPUT, THE
MOMENTARY CONTACT SWITCH MUST BE USED TO TURN THE LOAD ON.
5 POWER PACKS UNDER AUTO ON/OFF WITH OVERRIDE SWITCH FUNCTION: WHEN THE LOAD IS TURNED OFF USING THE MOMENTARY SWITCH, THE POWER PACK SHALL NOT TURN THE LOAD ON AUTOMATICALLY UNTIL AFTER THE SENSOR TIME DELAY EXPIRES. PRESSING THE MOMENTARY SWITCH BEFORE THE SENSOR TIME DELAY EXPIRES SHALL TURN THE LOAD ON, AND WHEN THE OCCUPANCY SENSOR'S TIME DELAY EXPIRES, THE POWER PACK REVERTS TO AUTO ON OPERATION.
6 INPUTS ON THE "HOLD ON" LINE SHALL OVERRIDE THE AUTOMATIC OFF FUNCTIONS. "HOLD ON" INPUTS SHALL ALSO
OVERRIDE THE MANUAL OFF STATE AT THE TIME OF "HOLD ON" INITIATION.
7 POWER PACKS SHALL BE PROVIDED WITH FAIL-SAFE CIRCUITRY WHEREBY THE CONTACT FAILS IN THE CLOSED POSITION IN
THE EVENT OF POWER FAILURE OR MALFUNCTION.
8 LIGHTING CONTROLS INCLUDING DIMMING BALLASTS/DRIVERS, DIMMING SWITCHES, AND OCCUPANCY SENSORS SHALL BE
FULLY COMPATIBLE.
9 POWER PACKS SHALL BE MOUNTED ABOVE THE CEILING IMMEDIATELY IN FRONT OF THE DOOR WHERE CEILING SPACE IS ACCESSIBLE. POWER PACK BOXES SHALL BE SINGLE OR DOUBLE GANG IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE SENSOR MANUFACTURER. POWER PACKS SHALL BE MOUNTED IN A RECESSED SWITCH BOX WHERE CEILING IS INACCESSIBLE. POWER PACK WALL BOXES SHALL BE LOCATED 6 INCHES FROM INSIDE CORNER OF THE ROOM AND 46 INCHES A.F.F. THE BOX FACEPLATE SHALL BE PERMANENTLY ENGRAVED "OCCUPANCY SENSOR POWER PACK".
10 CONTROL WIRE COUNTS ARE NOT SHOWN ON LIGHTING PLANS. CONSULT LIGHTING CONTROL FUNCTIONAL DIAGRAMS AND
MANUFACTURER REQUIREMENTS FOR GUIDANCE.
11 QUANTITY OF FIXTURES, SENSORS, POWER PACKS, AND OTHER DEVICES NOT REPRESENTED IN THESE DIAGRAMS. PROVIDE QUANTITY OF DEVICES SHOWN (MINIMUM) OR AS REQUIRED. MAXIMUM NUMBER OF SENSORS PER POWER PACK MAY VARY
BETWEEN MANUFACTURERS.
12 BRANCH CIRCUIT(S) TO EMERGENCY BALLAST/DRIVER IN FIXTURES ARE NOT SHOWN TO COMPLETION IN THESE DIAGRAMS.
PROVIDE CONDUCTORS FROM THE BRANCH CIRCUIT TO THE FIXTURES HAVING EMERGENCY BALLASTS/DRIVERS WITHOUT
ROUTING THROUGH THE FIXTURE SWITCHING, TIMER, OR OCCUPANCY CONTROLS.
13 PROVIDE CONDUIT RACEWAY FOR ALL WIRING. PROVIDE LOW VOLTAGE CONTROL RACEWAY SYSTEM SEPARATE FROM 120V
AND/OR 277V RACEWAY SYSTEM.
14 SUBMIT SHOP DRAWINGS WITH LIGHTING CONTROL DIAGRAMS FOR THE ACTUAL MANUFACTURER'S DEVICES PROVIDED AND
REVISE THE LIGHTING CONTROL DIAGRAMS "AS-BUILT".
15 THE LIGHTING CONTROL FUNCTIONAL DIAGRAMS SHOW ONE METHOD OF ACCOMPLISHING THE LIGHTING CONTROL STRATEGIES INTENDED FOR EACH SPACE OR ZONE. ALTERNATE METHODS ARE ACCEPTABLE ONLY IF THERE IS NO LOSS OF FUNCTIONALITY AS DESCRIBED BY THE LIGHTING CONTROL FUNCTIONAL DIAGRAMS AND THE CONTRACT SPECIFICATIONS. A DETAILED DESCRIPTION INDICATING HOW THE PROPOSED ALTERNATE METHODS SATISFY THE CONTRACT DOCUMENTS SHALL BE SUBMITTED TO THE GOVERNMENT FOR EVALUATION AND APPROVAL. INSTALLATION SHALL NOT PROCEED WITHOUT GOVERNMENT APPROVAL. PROCUREMENT PENDING GOVERNMENT APPROVAL SHALL BE AT THE CONTRACTOR'S
RISK.
16 ADDITIONAL POWER PACKS MAY BE REQUIRED FOR LONG MOMENTARY CONTACT SWITCH LOW VOLTAGE CIRCUITS, PARTICULARLY IN THE SERVICE BAY AREAS. VERIFY MAXIMUM LOW VOLTAGE CIRCUIT LENGTH WITH MANUFACTURER.
17 DAYLIGHTING CONTROL SYSTEMS SHALL BE OPEN LOOP.
18 ALL DAYLIGHT HARVESTING SYSTEM COMPONENTS SHALL BE FULLY COMPATIBLE
WITH ALL OTHER INTERCONNECTED COMPONENTS.
19 INITIAL DAYLIGHT SETTINGS SHALL BE AS FOLLOWS:
RAMP UP RATE: 20% PER SECOND
RAMP DOWN RATE: 2% PER SECOND
M
AR
K D
ES
C
R
IP
TI
O
N D
BLK
WHT
YL
W
O R
N O
R N
/Y
LW
BL
U
BL
U
/W H
T G
R N
BR
N
/W H
T
BR
N R
ED
BL
K
RED (LINE)
RED (LOAD)
WHITE (NEUTRAL)
POWER PACK "b"
OCCUPANCY
SENSOR
RED (LOAD)
LOAD
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
BLK
WHT
WHITE (NEUTRAL)
POWER PACK "a"
WHT
HOT
NEUTRAL
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
RED (LINE)
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
TO CONTROLLED LOADS
(WHERE APPLICABLE)
YL
W
O R
N O
R N
/Y
LW
BL
U
BL
U
/W H
T G
R N
BR
N
/W H
T
BR
N R
ED
BL
K
RED (LINE)
RED (LOAD)BLK
WHT
WHITE (NEUTRAL)
POWER PACK
ZONE "b"
HOT
WHTNEUTRAL
CIRCUIT
"b"
LOAD
RED (LINE)
RED (LOAD)
WHITE (NEUTRAL)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
CIRCUIT
"a"
LOAD
NEUTRAL
HOT
WHT
OCCUPANCY
SENSOR
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
POWER PACK
ZONE "a"
BLK
WHT
YL
W
O R
N O
R N
/Y
LW
BL
U
BL
U
/W H
T G
R N
BR
N
/W H
T
BR
N R
ED
BL
K
RED (LINE)
RED (LOAD)
WHITE (NEUTRAL)
POWER PACK
ZONE "a"
POWER PACK
ZONE "b" LOAD
"b"
BALLASTS
LOAD
"a"
BALLASTS
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
BLK
WHT
WHITE (NEUTRAL)
WHT
HOT
NEUTRAL
RED (LINE)
OCCUPANCY
SENSOR
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL501
LI
G
H
TI
N G
C O
N
TR
O L
D
IA
G R
AM
S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
N.T.S.EL501
MULTIPLE CONTROL DEVICES
EXCEEDING POWER SUPPLY RATINGS
N.T.S.EL501
MULTIPLE CIRCUITS UTILIZING
COMMON CONTROL DEVICES N.T.S.EL501
MULTIPLE LOADS EXCEEDING
SINGLE POWER SUPPLY RATINGS
KEYED LIGHTING NOTES:
SEE KEYED NOTES ON SHEET EL500.
GENERAL LIGHTING NOTES:
SEE GENERAL NOTES ON SHEET EL500.
M
AR
K D
ES
C
R
IP
TI
O
N D
WHITE (NEUTRAL)
SENSOR SWITCH
RED (LOAD)
DESCRIPTION OF OPERATION:
MANUAL ON VIA SENSOR SWITCH.
MANUAL/AUTO OFF VIA SENSOR SWITCH.
NEUTRAL
LOAD
HOT
WHT
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE) HOT
WHT
WHITE (NEUTRAL)
RED (LOAD)
DESCRIPTION OF OPERATION:
MANUAL ON VIA SWITCH.
MANUAL OFF VIA SWITCH.
NEUTRAL
LOAD
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
3-WAY SWITCHES
WHERE SHOWN
HOT
NEUTRAL WHT
RED
WHITE (NEUTRAL)
LOADTRAVELERS
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
4-WAY SWITCH WHERE SHOWN
3-WAY SWITCHES WHERE SHOWN
TRAVELERS TRAVELERS
WHITE (NEUTRAL)
LOAD
HOT
NEUTRAL WHT
RED
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
WHITE (NEUTRAL)
SENSOR SWITCH
RED (LOAD)
DESCRIPTION OF OPERATION:
AUTO ON VIA SENSOR SWITCH.
MANUAL/AUTO OFF VIA SENSOR SWITCH.
NEUTRAL
LOAD
HOT
WHT
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
RED (LOAD)
DESCRIPTION OF OPERATION:
MANUAL ON VIA TIMER SWITCH.
MANUAL/AUTO OFF VIA TIMER SWITCH.
TIMER SHALL TURN OFF LIGHTS AUTOMATICALLY AFTER
15 MINUTES.
NEUTRAL
LOAD
HOT
WHT
WHITE (NEUTRAL)
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
TIMER SWITCH
OPERATIONAL BASIS OF DESIGN:
1. LOAD "a" / "c" IS AUTO ON/OFF FUNCTION WITH MANUAL OVERRIDE.
2. LOAD "a" / "c" SHALL HAVE FIRE ALARM EGRESS "HOLD-ON" OVERRIDE CONTROL CONNECTED TO POWER PACK(S).
3. LOAD "b" / "d" IS MANUAL ON FUNCTION WITH AUTO/MANUAL OFF.
4. LOADS "a" / "c" AND "b" / "d" HAVE SEPARATE ON/OFF SWITCHES.
24VDC VIA FACP
LOAD
"b" OR "d"
LOAD
"a" OR "c"
WHITE (NEUTRAL)
POWER PACK
ZONE "a" OR "c"
POWER PACK
ZONE "b" OR "d"
RED (LINE)
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
HOT
WHTNEUTRAL
BLK
WHT
WHITE (NEUTRAL)
BLK
WHT
YL
W
O R
N O
R N
/Y
LW
BL
U
BL
U
/W H
T G
R N
BR
N
/W H
T
BR
N R
ED
BL
K
RED (LINE)
RED (LOAD)
MANUAL ON SWITCHES
AUTO ON SWITCHES
FIRE ALARM
EGRESS RELAY
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
MOMENTARY
SWITCH MOMENTARY
SWITCH
(TYP)1
MOMENTARY
SWITCH MOMENTARY
SWITCH
(TYP)1
(TYP)2
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL502
LI
G
H
TI
N G
C O
N
TR
O L
D
IA
G R
AM
S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
N.T.S.EL502
WALL SWITCH
VACANCY SENSOR
N.T.S.EL502
2 WALL TOGGLE SWITCH
N.T.S.EL502
3 THREE-WAY TOGGLE SWITCH
N.T.S.EL502
4 FOUR-WAY TOGGLE SWITCH
N.T.S.EL502
WALL SWITCH
OCCUPANCY SENSOR
N.T.S.EL502
6 WALL TIMER SWITCH
N.T.S.EL502
BI-LEVEL SWITCHING WITH FIRE ALARM HOLD ON
HALF MANUAL ON, HALF AUTO ON
KEYED LIGHTING NOTES:
SEE KEYED NOTES ON SHEET EL500.
GENERAL LIGHTING NOTES:
SEE GENERAL NOTES ON SHEET EL500.
M
AR
K D
ES
C
R
IP
TI
O
N D
WHITE (NEUTRAL)
24VDC VIA FACP
WHTNEUTRAL
HOT
OPERATIONAL BASIS OF DESIGN:
1. AUTOMATIC ON/OFF VIA OCCUPANCY SENSOR.
2. FIRE ALARM EGRESS "HOLD-ON" OVERRIDE CONTROL SHALL BE CONNECTED TO ALL POWER PACKS.
RED (LOAD) LOAD
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
BLK
WHT
POWER PACK
RED (LINE)
FIRE ALARM
EGRESS RELAY
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
BLK
WHT
WHITE (NEUTRAL)
NEUTRAL
HOT
WHT
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
OPERATIONAL BASIS OF DESIGN:
1. LOAD IS MANUAL ON FUNCTION
WITH AUTO/MANUAL OFF.
2. FIRE ALARM EGRESS "HOLD-ON"
OVERRIDE CONTROL SHALL BE
CONNECTED TO ALL POWER PACKS.
24VDC VIA FACP
RED (LOAD) LOAD
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
POWER PACK
RED (LINE)
FIRE ALARM
EGRESS RELAY
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
(TYP)
MOMENTARY
SWITCH
LOAD
0-10V
DIMMING
BALLASTS
PURPLE
GREY
NEUTRAL
HOT
WHT
OPERATIONAL BASIS OF DESIGN:
1. LOAD IS MANUAL ON FUNCTION WITH
AUTO/MANUAL OFF WITH MANUAL DIMMING
CONTROL CO-LOCATED WITH AN ON/OFF
SWITCH.
2. FIRE ALARM EGRESS "HOLD-ON"
OVERRIDE CONTROL SHALL BE CONNECTED
TO ALL POWER PACKS.
24VDC VIA FACP
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
BLK
WHT
WHITE (NEUTRAL)
POWER PACK
RED (LINE)
FIRE ALARM
EGRESS RELAY
(TYP)
MOMENTARY
SWITCH
MOMENTARY
SWITCH
LOW VOLTAGE
DIMMING ONLY
CONTROL
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
BLK
WHT
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
WHITE (NEUTRAL)
NEUTRAL
HOT
WHT
OPERATIONAL BASIS OF DESIGN:
1. LOAD IS MANUAL ON FUNCTION
WITH AUTO/MANUAL OFF.
RED (LOAD) LOAD
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
POWER PACK
RED (LINE)
(TYP)1
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
LOAD
0-10V
DIMMING
BALLASTS
PURPLE
GREY
NEUTRAL
HOT
WHT
OPERATIONAL BASIS OF DESIGN:
1. LOAD IS MANUAL ON FUNCTION WITH
AUTO/MANUAL OFF WITH MANUAL
DIMMING CONTROL CO-LOCATED WITH
AN ON/OFF SWITCH.
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
BLK
WHT
WHITE (NEUTRAL)
POWER PACK
RED (LINE)
(TYP)
MOMENTARY
SWITCH
MOMENTARY
SWITCH
LOW VOLTAGE
DIMMING ONLY
CONTROL
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
WHITE (NEUTRAL)
WHT
AUTO-ON
LOAD
WHT
BLK
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
BLK
WHT
POWER PACK
RED (LINE)
SHOWER
AREA
LOAD
24VDC VIA FACP
FIRE ALARM
EGRESS RELAY
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
HOT
NEUTRAL
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
OPERATIONAL BASIS OF DESIGN:
1. "AUTO-ON LOAD" IS AUTO ON/OFF FUNCTION.
2. "AUTO-ON LOAD" SHALL HAVE FIRE ALARM EGRESS "HOLD-ON" OVERRIDE CONTROL CONNECTED TO POWER PACK(S).
3. "SHOWER AREA LOAD" IS MANUAL ON/OFF FUNCTION NOT CONNECTED TO A POWER PACK.
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL503
LI
G
H
TI
N G
C O
N
TR
O L
D
IA
G R
AM
S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
N.T.S.EL503
1 AUTO ON-AUTO OFF WITH FIRE ALARM HOLD ON
N.T.S.EL503
2 MANUAL ON, AUTO OFF WITH FIRE ALARM HOLD-ON
N.T.S.EL503
MANUAL ON, AUTO OFF WITH
MANUAL 0-10V DIMMING AND FIRE ALARM HOLD-ON
N.T.S.EL503
6 MANUAL ON, AUTO OFF
KEYED LIGHTING NOTES:
SEE KEYED NOTES ON SHEET EL500.
GENERAL LIGHTING NOTES:
SEE GENERAL NOTES ON SHEET EL500.
N.T.S.EL503
5 MANUAL ON, AUTO OFF WITH MANUAL 0-10V DIMMING
N.T.S.EL503
3 PPE/RESTROOMS LIGHTING CONTROL DIAGRAM
M
AR
K D
ES
C
R
IP
TI
O
N D
24VDC VIA
EGRESS RELAY
PANEL
POWER PACK
ZONE "a"
RED (LINE)
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
HOT
WHTNEUTRAL
BLK
WHT
FIRE ALARM
EGRESS RELAY
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
PHOTOCELL HEAD
(LS-290C)
A7 A8 A9 A1
A1
A1
D
D
D
D
D
D
B1 B2 B3 B4 B5 B6 B7 B8 B9 B1
B1
B1
LOAD
"c" 0-10V
DIMMING
BALLASTS
LOAD
"a" 0-10V
DIMMING
BALLASTS
LOAD
"b" 0-10V
DIMMING
BALLASTS
LCD-203
DAYLIGHT
DIMMING
CONTROLLER
L3 L2 L1 BT-203
POWER PACK WHT
BLK
BLK
RED (LINE)
RED
BLU
S1 S2 S3 S4 S5
COM
P1 P2 P3 P4
LOC
LS-5C SWITCH
SECONDARY MOMENTARY SWITCH
(APPLICABLE TO FLIGHT PLANNING ONLY; LOCATED AT SECURE PLANNING DOOR)
C O
M (G
R
EE
N
S1 (B
LA
C
K) S2
(W H
IT
E)
S3 (B
LU
E)
S4 (O
R
AN
G E)
P1 (B
R O
W N
P2
(R
ED
D O
O R
S W
IT
C
H
RJ12 CABLE
PU
R
PL
E
I/O
G R
EY
PU
R
PL
E
G R
EY
PU
R
PL
E
G R
EY
R
ED
(L O
AD
R
ED
(L O
AD
R
ED
(L O
AD
COMBINATION DAYLIGHT AND MANUAL DIMMING SYSTEM FUNCTIONALITY NOTES:
1. THE OVERALL SYSTEM FOR EACH SPACE SHALL ACCEPT A HOLD-ON FIRE ALARM
EGRESS RELAY.
2. BASIS OF DESIGN FOR DIAGRAM SHOWN IS WATTSTOPPER BT-203/LCD-203 SYSTEM
WITH LS-290C PHOTOCELL, AND LS-5C MANUAL SWITCH, WITH AN ADDITIONAL
MOMENTARY CONTACT SWITCH AND OCCUPANCY SENSORS. A POWER PACK FOR FIRE
ALARM EGRESS RELAY AND ADDITIONAL OCCUPANCY SENSORS IS SHOWN. THE
LCD-203 CAN HANDLE UP TO TWO OCCUPANCY SENORS.
3. THE LCD-203 SYSTEM SHALL BE SET TO THE "MANUAL ON" MODE.
4. DAYLIGHT HARVESTING SETTINGS SHALL MAINTAIN 40 FC AVERAGE THROUGHOUT
SPACE.
5. LCD-203 WIRE COLORS ARE BASED ON WATTSTOPPER INSTRUCTION MANUAL.
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL504
LI
G
H
TI
N G
C O
N
TR
O L
D
IA
G R
AM
S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
N.T.S.EL504
1 COMBINATION DAYLIGHT HARVESTING AND MANUAL DIMMING SYSTEM WITH FIRE ALARM HOLD ON
KEYED LIGHTING NOTES:
SEE KEYED NOTES ON SHEET EL500.
GENERAL LIGHTING NOTES:
SEE GENERAL NOTES ON SHEET EL500.
M
AR
K D
ES
C
R
IP
TI
O
N D
NEUTRAL
BLK
WHT
WHITE (NEUTRAL)
BLK
WHT
YL
W
O R
N O
R N
/Y
LW
BL
U
BL
U
/W H
T G
R N
BR
N
/W H
T
BR
N R
ED
BL
K
RED (LINE)
RED (LOAD)
OPERATIONAL BASIS OF DESIGN:
1. LOAD "a" IS AUTO ON/OFF FUNCTION WITH MANUAL OVERRIDE.
2. LOAD "a" SHALL HAVE FIRE ALARM EGRESS "HOLD-ON" OVERRIDE CONTROL CONNECTED TO POWER PACK(S).
3. LOAD "b" IS MANUAL ON FUNCTION WITH AUTO/MANUAL OFF.
4. LOADS "a" AND "b" HAVE SEPARATE ON/OFF SWITCHES.
LOAD
"b"
LOAD
"a"
WHITE (NEUTRAL)
(TYP)
AUTO ON SWITCHES
MANUAL ON SWITCHES
POWER PACK
ZONE "a"
POWER PACK
ZONE "b"
(TYP)
24VDC VIA FACP
RED (LINE)
RED (LOAD)
YL
W
O R
N O
R N
/Y
LWBL
U
BL
U /W
H T
G R
N
BR
N /W
H T
BR
N
R
EDBL
K
HOT
WHT
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
OCCUPANCY
SENSOR
MOMENTARY
SWITCH MOMENTARY
SWITCH
6 MOMENTARY
SWITCH MOMENTARY
SWITCH
FIRE ALARM
EGRESS RELAY
TO EMERGENCY AND OTHER LOADS
(WHERE APPLICABLE)
(TYP)1
$ mc a, b $D, mc a, b
LOW VOLTAGE
DIMMING ONLY
CONTROL
PURPLE
GREY
H-O-A
PC
TC
ASTRONOMIC
TIME CLOCK
(TC), NEMA 1
ENCLOSURE
TC
HAND-OFF-AUTO
SELECTOR SWITCH
ON ENCLOSURE
C1
C1
HOT
CIRCUIT
AS: PPL-13
RE: PPL-11
WHTNEUTRAL
C2
SPARE
SPARE
SPARE
C2
C2
C2
C2
C1
C1
C1
PC
NORTH-FACING
EXTERIOR
PHOTOCELL
C1 OPERATION:
PHOTOCELL ON AT DUSK.
PHOTOCELL OFF AT DAWN.
MANUAL OVERRIDE.
C2 OPERATION:
BUILDING-MOUNTED
EGRESS LIGHTS
2#8,#8G,1"C
PHOTOCELL ON AT DUSK.
TIMECLOCK OFF AT 2000.
TIMECLOCK ON AT 0530.
PHOTOCELL OFF AT DAWN.
MANUAL OVERRIDE.
AS: PARKING LIGHTS
RE: PERIMETER LIGHTS
2#6,#6G,1"C
LCP-1
LIGHTING CONTACTOR WITH 120V COIL
AND 30A CONTACTS.
MOUNT IN NEMA 1 ENCLOSURE.
2#10,#10G
BUILDING-MOUNTED
NON-EGRESS LIGHTS
LCP-2
LIGHTING CONTACTOR WITH 120V COIL
AND 30A CONTACTS.
MOUNT IN NEMA 1 ENCLOSURE.
AS: PPL-15
RE: PPL-13
NOTE:
CONDUIT SIZE NOT LISTED FOR SITE
LIGHTING. THOSE CIRCUITS SHALL UTILIZE
CONDUIT SIZES INDICATED ON SITE PLANS.
WIRE SIZES ON THE SUPPLY SIDE ARE
EQUIVALENT TO WIRE SIZES ON THE LOAD
SIDE, UNLESS OTHERWISE NOTED.
TO EMERGENCY BATTERIES (HOT AND NEUTRAL)
AS: PPL-13
RE: PPL-11
AS: PPL-16
RE: PPL-12
SPARE
SPARE
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
A W N
B Y:
D
ES
IG
N
ED
B
Y:
SU
B M
IT
TE
D B
Y:
SI
ZE
C H
E C
KE
D B
Y:
AN
S I
'D
FI
LE
N
AM
E:
IS
SU
E D
AT
E :
C O
N
TR
AC
T
N O
SO
L I
C
IT
AT
IO
N N
O
FI
LE
N U
M
BE
R
1 2 3 4 5
D
C
B
A
US Army Corps of Engineers ® Omaha District
EL505
LI
G
H
TI
N G
C O
N
TR
O L
D
IA
G R
AM
S
FO
R
T C
AR
SO
N , C
O
LO
R
AD
O
AM
M U
N
IT
I O N
S U
P P
LY
P O
IN
T
PN
(F Y1
8) O
M A H
A D
IS
T R
IC
T
C
AP
IT
O
L
AV
E O
M A H
A, N
E 6 8
J.
L
IN
D
EM
AN
J.
L
IN
D
EM
AN
D . M
AL
EN
E
S.
O
TT
/1
0/
W
F-
-R
-0
F2
-7 0-
N.T.S.EL505
BI-LEVEL SWITCHING WITH FIRE ALARM HOLD ON,
HALF MANUAL ON, HALF AUTO ON WITH 0-10V DIMMING KEYED LIGHTING NOTES:
SEE KEYED NOTES ON SHEET EL500.
GENERAL LIGHTING NOTES:
SEE GENERAL NOTES ON SHEET EL500.
N.T.S.EL505
1 SITE LIGHTING CONTROL DIAGRAM
M
AR
K D
ES
C
R
IP
TI
O
N D
REVISED: AUGUST 2004 LIGHTING PLATE:
HIGH EFFICIENCY RECESSED 2' X 2' LED FIXTURE
3.5"
NOMINAL
NL-81
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITY.
ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. FIXTURE SHALL NOT PERMANENTLY
DEFORM OUT OF "SQUARE" WHEN PICKED UP FROM ANY CORNER.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH
REFLECTANCE (MINIMUM 85%), BAKED WHITE ENAMEL FINISH.
3. REFLECTORS - TWO-PIECE CURVED ALUMINUM WITH MATTE WHITE FINISH.
4. SHIELDING - HIGH-TRANSMISSION ACRYLIC.
5. LAMPS - SEE LIGHTING FIXTURE SCHEDULE.
6. DRIVER - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR (≥0.95), ELECTRONIC
TYPE WITH SOUND RATING A. SEE SPECIFICATION OR LIGHTING FIXTURE SCHEDULE FOR
DRIVER OPTIONS AND SPECIFICS. DRIVER SHALL BE DIMMABLE TO 10% WHERE CONNECTION
TO DIMMING SWITCHES IS INDICATED ON THE DRAWINGS.
7. CERTIFICATION - UL LISTED AND LABELED.
8. PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU) AND EFFICIENCY, GIVEN INTERIOR CAVITY REFLECTANCES OF 80-50-20:
RCR
CU
TYPE C2
REVISED: AUGUST 2004 LIGHTING PLATE:
HIGH EFFICIENCY RECESSED 2' X 4' LED FIXTURE
NOMINAL
3.5"
NL-80
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR RIGIDITY.
ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. FIXTURE SHALL NOT PERMANENTLY DEFORM
OUT OF "SQUARE" WHEN PICKED UP FROM ANY CORNER.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH REFLECTANCE
(MINIMUM 85%), BAKED WHITE ENAMEL FINISH.
3. REFLECTORS - TWO-PIECE CURVED ALUMINUM WITH MATTE WHITE FINISH.
4. SHIELDING - HIGH-TRANSMISSION ACRYLIC.
5. LAMPS - SEE LIGHTING FIXTURE SCHEDULE.
6. DRIVER - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR (≥0.95), ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION OR LIGHTING FIXTURE SCHEDULE FOR DRIVER OPTIONS AND SPECIFICS. DRIVER SHALL BE DIMMABLE TO 10% WHERE CONNECTION TO DIMMING SWITCHES
IS INDICATED ON THE DRAWINGS.
7. CERTIFICATION - UL LISTED AND LABELED.
8. PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU) AND EFFICIENCY, GIVEN
INTERIOR CAVITY REFLECTANCES OF 80-50-20:
EFFICIENCY - 80% MINIMUM
RCR
CU
TYPE C17
LUMINAIRE REQUIREMENTS:
1. HOUSING - ONE-PIECE, IMPACT-RESISTANT, FIBERGLASS REINFORCED
POLYESTER WITH ENCLOSED COLD-ROLLED STEEL WIREWAY.
CONTINUOUS GASKETING BETWEEN DIFFUSER AND HOUSING.
2. FINISH - STEEL REFLECTOR WITH MULTI-STAGE PHOSPHATE BONDING
TREATMENT FINISHED WITH HIGH REFLECTANCE (MINIMUM 85%), BAKED
WHITE ENAMEL FINISH.
3. LENS - 100% CLEAR ACRYLIC/DR OPTICAL DIFFUSER. STIPPLED INTERIOR
SURFACES AND SMOOTH EXTERIOR. CLOSED CELL NEOPRENE GASKET
WITH CAPTIVE NONMETALLIC, SIX CORROSION-RESISTANT, SNAP-ACTION,
CAM-LOADED LATCHES TO SECURE LENS TO HOUSING.
4. LAMPS - 4' LED, TYPICALLY WITH WATTAGES AS INDICATED. SEE
LIGHTING FIXTURE SCHEDULE.
5. DRIVER - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR
(≥.95), ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION OR
LIGHTING FIXTURE SCHEDULE FOR DRIVER OPTIONS AND SPECIFICS.
6. CERTIFICATION - UL LISTED AND LABELED. SUITABLE FOR DAMP OR WET
LOCATION AS DESIGNATED IN LIGHTING FIXTURE SCHEDULE.
7. PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU)
AND EFFICIENCY, GIVEN INTERIOR CAVITY REFLECTANCES OF 80-50-20:
REVISED: AUGUST 2004 NL-19LIGHTING PLATE:
EFFICIENCY - 76%
2 LAMP (F32/T8)
FIBERGLASS HOUSING DRY/DAMP LOCATION LED FIXTURE
5" NOMINAL
7" NOMINAL
4'
NOMINAL
RCR
CU
TYPE F14
4-1/2" NOMINAL
4-1/2" NOMINAL
SEE SCHEDULE
REVISED: AUGUST 2004 LIGHTING PLATE:
WALL-MOUNTED TASK LED FIXTURE
TYPE G22, G41
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL OR EXTRUDED ALUMINUM, WITH
REINFORCEMENT RIBS FOR RIGIDITY. ENDCAPS SECURED WITH TABS, SCREWS, OR…