Outdoor_Station_Service_Switchgear_Oahe_Dwgs.PDF
PDF 43 MB Posted
- Attached to
- Oahe Station Service Switchgears Federal contract opportunity
- Solicitation number
- W9128F18Q0001
About this file
Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_0002,_OA_Service_Station_Switchgears.pdf | ||
| Am0001_Dwgs.pdf | ||
| Amendment_0001,_OA_Service_Station_Switchgear.pdf | ||
| 01_22_00.00_26.pdf | ||
| Site_Visit_Notes.pdf | ||
| Site_Visit_Attendance_List.pdf | ||
| Specs_Station_Service_Switchgear_Replacement_Oahe.pdf | ||
| W9128F18Q0001,_OA_Switchgears.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg10:52:20 AM 6/5/2018
...\30500 - Construction E&D\OA79\30DA0 - Plans & Specs\CAD_BIM\_Sheets\30DA0 - Plans & Spec
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
of Engineers
US Army Corps
®of Engineers
US Army Corps
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R
F
IL
E N
A M
E
E N
A M
Omaha District
IL
E N
U M
B E
R
F
IL
E N
U M
B E
R
O A
G -0
.d g n
O A
G -0
.d g n
A N
S I
D
G-001
A N
S I
D
L .B .C
G-001
L .B .C
L .B .C
L .B .C
L .B .C
L .B .C
L .B .C
L .B .C
O M
A H
A D
IS
T R
IC
T O
M A
H A D
IS
T R
IC
T
OAHE DAM, SOUTH DAKOTA
O A
H E D
A M S
O U
T H D
A K
O T
A O
A H
E D
A M S
O U
T H D
A K
O T
A
O A
D -0
O M
A H
A
N E
B R
A S
K A
O M
A H
A
N E
B R
A S
K A
O A
D -0
C
A P
IT
O L A
V E
C
A P
IT
O L A
V E
C O
V E
R C
O V
E R
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
STATION SERVICE SWITCHGEAR REPLACEMENT
W F -1
-Q
-0
W9128F-18-Q-0001
W F -1
-Q
-0
J U
N E
J U
N E
JUNE 2018
ADVERTISEMENTADVERTISEMENT
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg9:34:37 AM 6/4/2018
®of Engineers
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
E N
A M
E
A N
S I
D A
N S I
D
F
IL
E N
A M
SHEET SEQUENCE NUMBER
w/ Level 2 Designator
DISCIPLINE DESIGNATOR
M - 2 0 1
2. DISCIPLINE DESIGNATORS:1. SHEET IDENTIFICATION NUMBERS:
R
T
E
M
D
P
F
Q
I
A
S
L
C
B
V
H
G
RESOURCE
TELECOMMUNICATIONS
ELECTRICAL
MECHANICAL
PROCESS
PLUMBING
FIRE PROTECTION
EQUIPMENT
INTERIORS
ARCHITECTURAL
STRUCTURAL
LANDSCAPE
CIVIL
GEOTECHNICAL
SURVEY / MAPPING
HAZARDOUS MATERIALS
GENERAL
INDEX LEGEND:
SHEET TYPE DESIGNATOR
3. SHEET TYPE DESIGNATORS:
3D REPRESENTATIONS
USER DEFINED
USER DEFINED
SCHEDULES & DIAGRAMS
DETAILS
LARGE-SCALE VIEWS
SECTIONS
ELEVATIONS
PLANS
GENERAL
INDEX
L .B .C
IN
D
E X
G-002
L .B .C
L .B .C
L .B .C
F
IL
E N
U M
B E
R
F
IL
E N
U M
B E
R
L .B .C
IN
D
E X
G-002
L .B .C
L .B .C
L .B .C
O A
G -0
.d g n
O A
G -0
.d g n0
/0
/2
O M
A H
A D
IS
T R
IC
T /0
/2
O M
A H
A D
IS
T R
IC
T
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O A
H E D
A M S
O U
T H D
A K
O T
A O
A H
E D
A M S
O U
T H D
A K
O T
A
O A
D -0
O A
D -0
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
Designator)
RELEASE 6.0 for Level 2
(see A/E/C CADD STANDARD
W F -1
-Q
-0
W F -1
-Q
-0
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg9:37:09 AM 6/4/2018
ABBREVIATIONS
COURSE(S)CRS
CROSS GRAINCRG
CORROSIVE RESISTANT STEELCRES
CIRCUMFERENCECRCMF
CARPETCPT
COMPRESSIBLECPRS
COVERCOV
CORRIDORCORR
CONTRACTORCONTR
CONTINUE CONT
CONSTRUCTIONCONSTR
CONNECTCONN
CONCRETECONC
COMPARTMENTCOMPT
COMBUSTIONCOMB
COMMONCOM
COLUMNCOL
CARBON DIOXIDECO2
CLEANOUTCO
COUNTERCNTR
CORNERCNR
CONDUCTIVE NEOPRENE LATEXCNL
CONDUITCND
CONCRETE MASONRY UNITCMU
COMPOSITECMPST
CORRUGATED METAL PIPECMP
CENTIMETER(S)cm
CLEAR WIRED GLASSCLWG
CLEAR(ANCE)CLR
CLOSURECLOS
CLOSETCLO
CONTRACT LIMIT LINECLL
CLEAR GLASSCLGL
CEILING HEIGHTCLG HT
CEILINGCLG
CENTER LINECL
CIRCUIT BREAKERCKT BRKR
CIRCUITCKT
CONSTRUCTION JOINTCJ
CONTROL JOINTCJ
CIRCULARCIRC
CAST-IN-PLACECIP
CURB INLETCI
CAST IRONCI
CHROME PLATEDCHR PL
CHECKCHK
CHIMNEYCHIM
CHAMFERCHFR
CHALKBOARDCH BD
CORNER GUARDCG
CUBIC FEET PER MINUTECFM
COUNTERFLASHINGCFLG
CONDUCTIVE FLOORINGCFI
CERAMICCER
CEMENT PLASTERCEM PLAS
CEMENTCEM
COVER ELEVATIONCE
CLOSED CIRCUIT TELEVISIONCCTV
CUBICLE CURTAIN TRACKCCT
CATCH BASINCB
CAPACITYCAP
CABINETCAB
BOTH WAYSBW
BUILT-UP ROOFINGBUR
BETWEENBTWN
BTU PER HOURBtuH
BRITISH THERMAL UNITBtu
BASEMENTBSMT
BOTH SIDESBS
BRONZEBRZ
BRACKETBRKT
BRICKBRK
BEARING PLATEBRG PL
BEARINGBRG
BRIDGINGBRDG
BRACINGBRCG
BACK PLASTER(ED)BP
BOTTOMBOT
BOTTOM OFBO
BENCHMARKBM
BELOWBLW
BUILDINGBLDG
BUILDING LINEBL
BED JOINTBJT
BITUMINOUSBITUM
BEVELBEV
BRICK EXPANSION JOINTBEJ
BOUNDARYBDRY
BOARDBD
BOOKCASEBC
BULLETIN BOARDBB
ACOUSTICAL WALL TREATMENTAWT
AMERICAN WIRE GAUGEAWG
AVERAGEAVG
AUTOMATICAUTO
ACOUSTICAL TILE CEILINGATC
ASPHALTASPH
ABOVE SUSPENDED CEILINGASC
ASBESTOSASB
AMERICAN REFRIGERATION INSTITUTEARI
ARCHITECTARCH
APPROXIMATEAPPROX
APPROVEDAPPD
AMERICAN NATIONAL STANDARDS INSTITUTEANSI
ANODIZEANOD
AMPEREAMP
AMBIENTAMB
ALUMINUMALUM
ALTERNATEALT
ACTIVE LEAFA.L.
AMERICAN INSTITUTE OF STEEL CONSTRUCTIONAISC
AMPERE INTERRUPTING CAPACITYAIC
AREA INLETAI
AIR HANDLING UNITAHU
ANCHOR AHR
AGGREGATEAGGR
ABOVE FINISHED FLOORAFF
AUTOMATIC DOOR OPERATORADO
ADJACENT, ADJOINING, ADJUSTABLEADJ
ADHESIVEADH
ADDENDUMADDM
ACOUSTICAL CEILING TILEACT
ACOUSTICACST
ALUMINUM CABLE STEEL REINFORCEDACSR
ACCESS PANELACS PNL
ACCESS DOORACS DR
ACRYLIC PLASTICACR
AMERICAN CONCRETE INSTITUTEACI
ACCESSIBLEACC
ALTERNATING CURRENTAC
ABOVEABV
ANCHOR BOLTAB
AIR CONDITIONING UNITA/C UNIT
AIR CONDITIONINGA/C
ANGLEL
FRAMINGFRMG
FORGEDFRG
FRAMEFR
FIRE RESISTANT FR
FEET PER MINUTEFPM
FIREPROOFFP
FIRE PARTITIONFP
FACE OF STUDFOS
FACE OF MASONRYFOM
FACE OF FINISHFOF
FACE OF CONCRETEFOC
FENCEFN
FLUORESCENTFLUOR
FLOOR PLATEFLR PL
FLOORINGFLG
FLEXIBLEFLEX
FLOORFLR
FLASHINGFLASH
FLUSH JOINTFJT
FIXTUREFIXT
FINISH FLOORFIN FLR
FINISHFIN
FIGUREFIG
FLAT HEAD WOOD SCREWFHWS
FIRE HOSE STATIONFHS
FIRE HOSE RACKFHR
FLAT HEAD MACHINE SCREWFHMS
FIRE HOSE CABINETFHC
FLAT HEADFH
FIRE HYDRANTFH
FIBERGLASSFGL
FACTORY FINISHFF
FIRE EXTINGUISHER CABINETFEC
FIRE EXTINGUISHER BRACKETFEB
FIRE EXTINGUISHERFE
FOUNDATIONFDTN
FIRE DAMPERFDMPR
FLOOR DRAINFD
FAN COIL UNITFCU
FLOOR CLEANOUTFCO
FLOOR CONSTRUCTION JOINTFCJ
FACINGFCG
FACE BRICKFC BRK
FOOT CANDLEFC
FIRE BRICKF BRK
FRESH AIR INTAKEFAI
FIRE APPARATUS CLOSETFAC
FRESH AIRFA
FIRE ALARMFA
FAHRENHEITF
EXTERIOREXT
EXPANSION BOLTEXP BT
EXPOSEDEXP
EXPANSIONEXP
EXISTINGEXST
EXHAUST AIREXH A
EXHAUSTEXH
EXCAVATEEXC
ENTERING WATER TEMPERATUREEWT
ELECTRIC WATER COOLEREWC
ESTIMATE(D)EST
ESCALATORESCAL
EQUIPMENTEQUIP
EQUALEQ
EPOXY COATINGEPY
EXPLOSION PROOFEPRF
ELECTRICAL PANELBOARDEP
ENTRANCE, ENTERINGENTR
ENCLOSE(URE)ENCL
EMERGENCYEMER
ESTIMATED MAXIMUM DEMANDEMD
EXPANDED METAL EM
ELECTRICELEC
ELEVATION - GRADE OR BUILDINGEL
EXPANSION JOINTEJ
EACH FACEEF
ENTERING AIR TEMPERATUREEAT
EACHEA
EASTE
DIRECT EXPANSIONDX
DUMBWAITERDWTR
DRAWERDWR
DOWELSDWLS
DRAWINGDWG
DOVETAIL DVTL
DRAIN TILEDT
DOWNSPOUTDS
DOUBLE STRENGTH (GLASS)DS
DOOR CLOSERDR CL
DRAINBOARDDRB
DRAINDR
DOORDR
DOWNDN
DEMOUNTABLEDMT
DAMPERDMPR
DAMPPROOFINGDMPF
DEAD LOADDL
DIVISIONDIV
DISTRIBUTION PANELDISTR PNL
DISPENSERDISP
DISCONNECTDISC
DIMENSIONDIM
DIAGONALDIAG
DIAMETERDIA
DUCT HEATERDH
DOUBLE HUNGDH
DRINKING FOUNTAINDF
DETAILDET
DEPARTMENTDEPT
DEPRESSIONDEPR
DEMOLITIONDEMO
DEGREEDEG
DUMMY CONTROL JOINTDCJT
DOWELED CONTROL JOINTDCJ
DOUBLE ACTING DOORDBL ACT DR
DOUBLEDBL
DRY BULBDB
DATUMDAT
PENNY (AS IN NAIL - 10D)d
CYLINDERCYL
COLD WATERCW
CONDUCTIVE VINYL HOMOGENEOUS (SHEET TYPE)CVH
CEILING VENTCV
CUBIC YARDSCU YD
CABINET UNIT HEATERCUH
CUBIC FEETCU FT
COPPERCu
CONDENSING UNITCU
CENTERCTR
CENTER TO CENTERC TO C
CURRENT TRANSFORMERCT
CERAMIC TILECT
CASEMENTCSMT
COUNTERSUNKCSK
CAST STONECS
LIGHTINGLTG
LIGHTWEIGHTLT WT
LIGHTLT
LAWN SPRINKLERLS
LIVING ROOMLR
LOW POINTLPT
LIGHTPROOF LOUVERLPL
LIGHTPROOF DOORLPD
LIGHTPROOFLP
LONGITUDINALLONG
LINTELLNTL
LIMESTONELMST
LUMENLM
LEAD-LINED DOORLLD
LIVE LOADLL
LOCKERLKR
LINEARLIN
LEFT HAND(ED)LH
LENGTHLG
LOADINGLDG
LOADLD
LIGHT CONTROLLC
LUMBERLBR
LABELLBL
POUNDLB
LAG BOLTLB
LAVATORYLAV
LAUNDRYLAU
LEAVING AIR TEMPERATURELAT
LAMINATELAM
LADDERLAD
LABORATORYLAB
KEYWAYKWY
KILOWATTkW
KILOVOLT AMPERES REACTIVEkVAR
KILOVOLT AMPERESkVA
KILOVOLTSkV
KICKPLATEKPL
KNOCKOUT PANELKOP
KITCHENKIT
KILOPOUND (1000 POUNDS)KIP
JOINTJT
JOISTJST
JUNCTIONJCT
JUNCTION BOXJ-BOX
JANITOR’S CLOSETJAN CLO
INSIDE PIPE SIZEI.P.S.
IRON PIPE SIZEIPS
IRON PIPEIP
INVERTINV
INTERMEDIATEINTM
INTERIORINT
INSULATIONINSUL
INSULATING FILLINSF
INCLUDEDINCL
INCINERATORINCIN
INCHIN
INTERLOCKILK
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICAIESNA
INSIDE DIAMETERID
INTERCOMIC
HERTZHz
HYDRAULICHYDR
HEATING, VENTILATING AND AIR CONDITIONINGHVAC
HEATERHTR
HEATINGHTG
HEIGHTHT
HOUSEKEEPINGHSKPG
HIGH-STRENGTH GYPSUM PLASTERHSGYP
HIGH STRENGTHHS
HOURHR
HIGH POINTHPT
HORSEPOWERHP
HIGH PRESSUREHP
HORIZONTALHORIZ
HANDRAILHNDRL
HOLLOW METALHM
HOOK(S)HK
HANDHOLEHH
HEXAGONHEX
HIGH EARLY-STRENGTH CEMENTHES
HARDWOODHDWD
HARDWAREHDW
HEADERHDR
HEAD JOINTHD JT
HARDBOARDHDBD
HEAVY DUTYHD
HEADHD
HANDICAPPEDHCP
HALON CONTAINMENT DAMPERHCD
HOLLOW COREHC
HOSE BIBBHB
GYPSUM PLASTERGYP PLAS
GYPSUM BOARDGYP BD
GYPSUMGYP
GLAZED WALL TILEGWT
GROUTGT
GLAZED STRUCTURAL UNITSGSU
GLAZED STRUCTURAL TILEGST
GRATINGGRTG
GRADE LINEGR LN
GRANITEGRAN
GYPSUM TILEGPT
GALLONS PER MINUTEGPM
GOVERNMENTGOVT
GROUNDG
GLAZED CONCRETE MASONRY UNITSGLZ CMU
GLAZINGGLZ
GLASS FIBERGLF
GLASS BLOCKGL BLK
GLASSGL
GASKET(ED)GKT
GALVANIZED IRON PIPEGIP
GALVANIZED IRONGI
GOVERNMENT-FURNISHED EQUIPMENT CONTRACTOR INSTALLEDGFE/CI
GOVERNMENT-FURNISHED EQUIPMENTGFE
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GROUND FACEGF
GENERALGEN
GENERAL CONTRACTORGC
GRAB BARGB
GALVANIZED STEELGALV STL
GALVANIZEDGALV
GALLON(S)GAL
GAGEGA
NATURAL GASG
FABRIC WALL COVERINGFWC
FIRE WATERFW
FUTUREFUT
FURRINGFURG
FOOTINGFTG
FEETFT
FASTEN(ER)FSTNR
FULL SIZEFS
FIRE-RETARDANTFRT
PRESTRESSED CONCRETEPS CONC
PRESSED STEELP.S.
PIPE SPACEPS
PRESSURE-REGULATING VALVEPRV
PROJECTPROJ
PARKINGPRKG
PREFORMEDPREFMD
PREFINISHEDPREFIN
PREFABRICATE(D)PREFAB
PAIRPR
PARTS PER MILLIONPPM
POLISHED PLATE GLASSPPGL
PORTABLEPORT
PORCELAINPORC
POLISHEDPOL
PAINT(ED)PT
PANELPNL
PLYWOODPLYWD
PLATE GLASSPL GL
PILINGPLG
POUNDS PER LINEAR FOOTPLF
PLUMBINGPLBG
PLATFORMPLAT
PLASTERPLAS
PLASTIC LAMINATEPLAM
PROPERTY LINEPL
PLATEPL
POST INDICATING VALVEPIV
PREFAB ISOLATION POWER UNITPIPU
POINT OF INTERSECTIONPI
PHARMACYPHAR
PHASEPH
PERIMETERPERIM
PERFORATE(D)PERF
PEDESTALPED
PAVEMENT DRAINPD
CEMENT PLASTER (PORTLAND)PCP
POUNDS PER CUBIC FOOTPCF
PRECAST CONCRETEPCC
PIECEPC
PUSH BUTTON STATIONPBS
PARTICLE BOARDPBD
PANIC BARPB
PARALLELPAR
PUBLIC ADDRESSPA
POLEP
OBSCURE WIRED GLASSOWGL
OUTSIDE SCREW AND YOKEOS & Y
OPERATIONSOPS
OPAQUEOPQ
OPPOSITEOPP
OPENINGOPNG
OPPOSITE HANDOPH
OVALHEAD WOOD SCREWOHWS
OVALHEAD MACHINE SCREWOHMS
OVERHEADOH
OBSCURE GLASSOGL
OFFICEOFC
OUTSIDE DIAMETEROD
ON CENTER EACH WAYOCEW
ON CENTEROC
OBSERVATION WINDOWOBW
OBSCUREOBSC
OUTSIDE AIROA
NOT TO SCALENTS
NOT REQUIREDN’’REQD
NOISE REDUCTION COEFFICIENTNRC
NOISE REDUCTIONNR
NOMINALNOM
NUMBERNO
NORMALLY OPENNO
NONMETALLICNM
NEOPRENE LATEXN.L.
NAILABLENL
NOT IN CONTRACTNIC
NICKELNi
NATIONAL FIRE PROTECTION ASSOCIATIONNFPA
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNEMA
NATIONAL ELECTRICAL CODENEC
NORMALLY CLOSEDNC
NATURALNAT
NORTHN
MULLIONMULL
MOVABLEMVBL
METALMTL
METAL FURRINGMTFR
MOUNTEDMTD
MOUNTMT
METAL THRESHOLDMT
MACHINE SCREWSMS
METAL ROOF DECKINGMRD
MARBLE BASEMRB
MOP RECEPTORMR
MOVABLE PARTITIONMP
MOTORMOT
MODIFIEDMOD.
MODULARMOD
MASONRY OPENINGMO
MATERIAL NOT IN CONTRACT (INSTALLATION BY CONTRACTOR)MNIC
MILLIMETER(S)mm
MILLWORKMLWK
MOULDINGMLDG
MONOLITHICML
METAL LATHML
MISCELLANEOUSMISC
MIRRORMIRR
MINIMUMMIN
MALLEABLE IRONMI
MANHOLEMH
MATTE-GLAZED TILEMGT
MOTOR GENERATORMG
MANUFACTURERMFR
MANUFACTURINGMFG
METAL FLOOR DECKINGMFD
METAL EDGE STRIPMES
MEMBRANEMEMB
MEDIUMMED
MECHANICAL ROOMMECH RM
MECHANICALMECH
METAL DIVIDER STRIPMDS
METAL-CASED OPENINGMCO
MASONRY CONTROL JOINTMCJ
MEDICINE CABINETMC
MEMBERMBR
MACHINE BOLTSMB
MAXIMUMMAX
MATERIAL(S)MATL
MASONRYMAS
MACHINEMACH
MATCHED AND BEADEDM&B
METER(S)m
LEAVING WATER TEMPERATURELWT
LIGHTWEIGHT CONCRETELWC
LOUVERLVR
LIGHTNINGLTNG
THICK(NESS)THK
TRUSS HEADTH
TOGGLETGL
TONGUE AND GROOVET&G
TERMINALTERM
TERRAZZOTER
TEMPORARYTEMP
TEMPERATURETEMP
TELEPHONETEL
TERRA COTTATC
TOWEL BARTB
TANGENTTAN
TREADT
SYSTEMSYS
SYNTHETICSYNTH
SYMMETRICALSYMM
SWITCHBOARDSWBD
SWITCHSW
SHEET VINYL SV
SUSPENDEDSUSP
SUBFLOORSUB FL
STAIRWAYSTWY
STRUCTURALSTRUCT
STRINGERSTR
STATIC PRESSUREST PR
STORAGESTOR
STEELSTL
SEATINGSTG
STANDARDSTD
STATIONSTA
STAINLESS STEELSST
STANDING SEAM (ROOF)SS
SERVICE SINKSS
SHELF AND RODS&R
SQUARE HEADSQHD
SQUARESQ
SPEAKERSPKR
SPACE HEATERSPH
SPECIAL FINISHSP FIN
SOUNDPROOFSPF
SPECIFICATIONSPEC
SOUNDPROOF DOORSPD
SPECIALSPCL
SPACERSPC
SHUT OFF VALVESOV
SHEET METAL SCREWSSMS
SHEET METALSM
SLEEVESLV
SEALANTSLNT
SKYLIGHTSKLT
STEEL JOIST INSTITUTESJI
SIMILARSIM
SHELVINGSHV
SHEATHINGSHTHG
SHEETSHT
SHOULDERSHLDR
SHEET GLASSSG
STRUCTURAL FACING UNITSFU
STRUCTURAL FACING TILE UNITSFTU
SAFETY GLASSSFGL
SEQUENCESEQ
SECTIONSECT
STEEL DOOR INSTITUTESDI
STORM DRAINSD
STRUCTURAL CLAY TILESCT
SCREENSCRN
SCHEDULESCHED
SOLID CORESC
SECURITY BARSS.B.
SPLASH BLOCKSB
SUPPLY AIRSA
SOUTHS
RAINWATER CONDUCTORRWC
RIVETRVT
REVERSERVS
RUBBER TILE FLOORRTF
RAISED PATTERN RUBBER TILERPRT
REVOLUTIONS PER MINUTERPM
RETRACTABLE PARTITIONRP
RIGHT OF WAYROW
ROUGH OPENINGRO
ROUNDRND
ROOMRM
RAILINGRLG
RACKRK
ROOF HATCHRH
RIGHT HANDRH
RELATIVE HUMIDITYRH
ROOFINGRFG
REVISIONREV
RETURNRET
RESILIENTRESIL
REQUIREDREQD
REMOVE(ABLE)REM
REINFORCEREINF
REGLETREG
REGISTERREG
REFRIGERATIONREFR
REFLECTREFL
REFERENCEREF
RECTIFIERRECT
RECREATION ROOMREC ROOM
RECEPTACLERECPT
RIGID INSULATIONRDG INS
ROOF DRAINRD
RECEIVERRCVR
REINFORCED CONCRETE PIPERCP
REMOTE CONTROLRC
RUBBERRBR
RUBBLE STONERBL
RUBBER BASE, RESILIENT BASERB
RETURN AIR REGISTERRAR
RETURN AIR GRILLERA GR
RABBETEDRAB
RETURN AIRRA
RISERR
RANGER
RADIUSR
QUANTITYQTY
QUARTER ROUND1/4 RND
QUARTERQTR
QUARTQT.
QUARRY TILEQT
PASS WINDOWPW
PAVINGPVG
POLYVINYL CHLORIDEPVC
PAVEDPV
PAPER TOWEL RECEPTACLEPTR
PARTITIONPTN
PAPER TOWEL DISPENSERPTD
POST-TENSIONED CONCRETEPT CONC
POINTPT.
PNEUMATIC TUBEPT
POUNDS PER SQUARE INCHPSI
POUNDS PER SQUARE FOOTPSF
YARD DRAINYD
YARDYD
TRANSFORMERXFMR
WELDED WIRE REINFORCEMENTWWR
WELDED WIRE MESHWWM
WELDED WIRE FABRICWWF
WALL TO WALLW/W
WIDTHWTH
WEIGHTWT
WAINSCOTWSCT
WASTE STACKW.S.
WATERSTOPWS
WARDROBEWRB
WASTE RECEPTACLEWR
WORKING POINTWP
WEATHERPROOFWP
WATERPROOF(ING)WP
WITHOUTW/O
WIRE MESHWM
WORK SHOPWKSH
WROUGHT IRONWI
WATT-HOUR METERWHM
WHEEL BUMPERWHB
WATER HEATERWH
WALL HUNGWH
WIRED GLASSWGL
WIDE FLANGEWF
WINDOWWDW
WASTE DISPOSERWDSP
WOOD DOORWD
WOODWD
WOOD-CASED OPENINGWCO
WHEELCHAIRW/C
WATER CLOSETWC
WOOD BLOCKINGWBL
WET BULBWB
WITHW/
WESTW
VINYL WALL COVERINGVWC
VENT THRU ROOFVTR
VOLTAGE TRANSFORMERV.T.
VENT STACKVS
VERMICULITEVRM
VAPOR RETARDERVR
VOLUMEVOL
VENEERVNR
V-JOINT(ED)VJ
VINYL HOMOGENEOUSVH
VERTICAL GRAINVG
VINYL FABRICVF
VESTIBULEVEST
VERTICALVERT
VENTILATOR(TION)VENT
VAULT DOORVD
VITRIFIED CLAY TILEVCT
VINYL COMPOSITION TILEVCT
VINYL BASEVB
VARNISHVAR
VOLTV
UNIT VENTILATORUV
UTILITYUTIL
URINALUR
UNINTERRUPTABLE POWER SUPPLYUPS
UNFINISHEDUNFIN
UNEXCAVATEDUNEX
UNDERWRITERS LABORATORIESUL
UNIT HEATERUH
UNDERGROUNDUGND
UNIT COOLERUC
TYPICALTYP
TELEVISIONTV
THERMOSTATTSTAT
TRANSVERSETRANS
TRANSOMTRANS
TOILET PARTITIONTPTN
TOILET PAPER DISPENSERTPD
TOP OF WALLTOW
TOP OF STEELTOS
TOP OF SLABTOS
TOPOGRAPHYTOPO
TOLERANCETOL
TOP OFTO
TACKSTRIPTKS
TACKBOARDTK BD
THRESHOLDTHRES
A B
B R
E V
IA
T
IO
N S
F
IL
E N
A M
E
A N
S I
D
L .B .C
G-003
L .B .C
L .B .C
L .B .C
®of Engineers
US Army Corps
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
F
IL
E N
U M
B E
R
O A
G -0
.d g n0
/0
/2
O M
A H
A D
IS
T R
IC
T
O A
D -0
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O A
H E D
A M S
O U
T H D
A K
O T
A
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
VACUUM CIRCUIT BREAKERVCB
CURRENT LIMITING REACTORCLR
AIR CIRCUIT BREAKERACB
PROJECT SPECIFIC ABBREVIATIONS
W F -1
-Q
-0
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg9:39:34 AM 6/4/2018
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
E N
A M
E
A N
S I
D A
N S I
D
F
IL
E N
A M
DHW
DCW
VENT
ACID WASTE
SANITARY
ACID VENT
ACID
SAN
WF
WH
ACID
RDHW
WALL FAUCET
WALL HYDRANT
RECIRCULATING DOMESTIC HOT WATER
DOMESTIC HOT WATER
DOMESTIC COLD WATER
A-7A-5 A-6 A-7 A-8
A
C D
A
A-
B
A
A-
CLEAN OUT
FLOOR DRAIN
CO
D
CO
ST
ST
RL
RD
RS
CWS
CWR
CR
CHWS
CHWR
GCWS
THERMOSTATT
GCWR
C
FOR ADDITIONAL LEGEND
WALL CLEAN OUT
STORM DRAIN BELOW FLOOR
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
REFRIGERANT STRAINER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE (HOT GAS)
REFRIGERANT LIQUID
CHILLED-HOT WATER RETURN
GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
CHILLED-HOT WATER SUPPLY
THERMOSTATIC EXPANSION VALVE
STORM DRAIN ABOVE FLOOR
SEE TEMPERATURE CONTROL DRAWINGS
SECTION NUMBER
SHEET NUMBER OF DWG.
OF ELEV. ON PLAN
DIRECTION OF SIGHT
ELEV. IS SHOWN
OF ELEV. ON PLAN
DIRECTION OF SIGHT
WHERE ELEV. IS SHOWN *
NOTE: LOCATION OF DWG. WHERE
WHERE SECTION IS SHOWN *
SHEET NUMBER OF DRAWING
WHERE SECTION IS CUT *
SHEET NUMBER OF DRAWING
DRAWING WHERE SECTION IS SHOWN
SECTION IS CUT WILL BE LISTED ONLY ON
ANY ADDITIONAL DRAWINGS WHERE
CUT AND DETAILED ON SAME DRAWING.
* SHEET NUMBERS OMITTED IF SECTION IS
S
N
OA
E
H
P
PB
HUMIDITY SENSOR
PRESSURE SENSOR
EMCS SENSOR
MANUAL OVER-RIDE SWITCH
NIGHT THERMOSTAT
TEMPERATURE SENSOR
AND HATCHED THUSLY.
3. EXISTING FACILITIES TO BE REMOVED ARE INDICATED BY USE OF THESE SYMBOLS
ON THIS SHEET.
SET OF DRAWINGS TO INDICATE SPECIFIC CONDITIONS IN LIEU OF SYMBOLS SHOWN
2. ADDITIONAL LEGENDS AND/OR ANOTHER LEGEND SHEET MAY APPEAR IN THIS
THE CONDITIONS ON THIS SET OF DRAWINGS TO THE EXTENT APPLICABLE.
1. THESE LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE PERTINENT TO
20 x 12 RG
20 x 12 SG
700 CFM
20 x 12 GR
20 x 12 SR
700 CFM
700 CFM
20 O/
700 CFM
700 CFM
HPS
LPC
FW
PC
FEED WATER
PUMPED CONDENSATE
LPS
MPS
MPC
HTWS
HPC
LOW PRESSURE CONDENSATE
MEDIUM PRESSURE CONDENSATE
HIGH PRESSURE CONDENSATE
LOW PRESSURE STEAM
MEDIUM PRESSURE STEAM
HIGH PRESSURE STEAM
HIGH TEMPERATURE WATER SUPPLY
DOOR GRILLE
12 x 12
700 CFM
DG
12 x 6
20 x 12
R
BBD
FOG
BOILER BLOW-DOWN
FUEL OIL GAGE LINE
FOS
FOF
FOR
GASG
FOV
FUEL OIL FILL
F & T TRAP
FUEL OIL RETURN
FUEL OIL SUPPLY
THERMODYNAMIC TRAP
FUEL OIL TANK VENT
HTWR
HWS
HWR
GHWS
GHWR
F FLOAT TRAP
THERMOSTATIC TRAP
BUCKET TRAP
A
VAC
F
FC
F
VACUUM
FIRE LINE
COMPRESSED AIR
FOAM CONCENTRATE
HIGH TEMPERATURE WATER RETURN
HOT WATER HEATING RETURN
HOT WATER HEATING SUPPLY
UNDERSLAB FIRE LINE
FOR AFFF SYSTEMS
GLYCOL HOT WATER HEATING RETURN
GLYCOL HOT WATER HEATING SUPPLY
ROADS
WALKS
CULVERT
77.2
77.2
SD
W
FW
S
FW
WD
OR OR
FM
SD
W
S
FW
FM
FW
WD
PIV
MW-2
MT
MW-1
MT
DH-2 DH-2
PIV
BUILDINGS
CURB & GUTTER
RAILROAD
CONTOURS
STORM DRAIN
DIRECTION OF DRAINAGE
SPOT GRADE ELEVATIONS
SUBDRAIN
FIRE WATER LINE
FORCE MAIN
SANITARY SEWER
WATER LINE
SUBDRAIN OUTLET LINE
OBSERVATION RISER
UTILITY LINE
WASTE DRAIN
SUBDRAIN FLUSHING &
AREA INLET
FIRE HYDRANT
POST INDICATOR VALVE
MONITORING WELL
CONTROL POINT
DRILL HOLE
CURB INLET
DEPENDING ON TYPE OF
OR SERVICE STOP & BOX
PROPERTY LINE MONUMENT
FIRE PROTECTION WATER LINE
MANHOLE SELF EXPLANATORY
GATE VALVE & VALVE BOX
MODSEC.
VD
OR
FD
AD
SD
AD
AD
AS INDICATED
WOOD
XX
X
EARTH
CONCRETE
XX
X
AS INDICATED
GRAVEL
BRICK
METAL
PLYWOOD
WOOD (FINISH)
WOOD (ROUGH)
AS INDICATED
CRUSHED ROCK
PLASTER
GLASS (ELEVATION)
BLANKET INSULATION
RIGID INSULATION
GYPSUM WALLBOARD
WOOD STUD PARTITION
CONCRETE MASONRY UNITS (PLAN)
CONCRETE MASONRY UNITS (SECTION)
GLASS (LARGE SCALE SECTION)
METAL STUD PARTITION
WOVEN WIRE
BARBED WIRE
CHAIN LINK SECURITY
SUPPLY GRILLE (SG)
FLOW DIRECTION
FLOW DIRECTION
DIRECTION OF FLOW
SPLITTER DAMPER
ACCESS PANEL (AP)
ACCESS DOOR (AD)
FLEXIBLE DUCT
TURNING VANES
SMOKE DAMPER
(TYPE AS SPECIFIED) INDICATE
SUPPLY OUTLET, CEILING, RECTANGULAR
(TYPE AS SPECIFIED) INDICATE
SUPPLY OUTLET, CEILING ROUND
CEILING (INDICATE TYPE)
EXHAUST OR RETURN AIR INLET
+ INTEGRAL VOL. CONTROL)
SUPPLY REGISTER (SR) (A GRILLE
GRILLE (NOTE AT FLR. OR CLG.)
RETURN (RG) OR EXHAUST (EG)
VENTILATOR-SUPPLY (SRV)
POWER OR GRAVITY ROOF
UNIT HEATER (VERTICAL)
POINT OF CHANGE IN DUCT CONSTRUCTION
VENTILATOR-EXHAUST (ERV)
POWER OR GRAVITY ROOF
UNIT HEATER (HORIZONTAL)
PARALLEL BLADE DAMPERS
FOR NET FREE AREA
2ND FIGURE, SIDE NOT SHOWN)
DUCT (1ST FIGURE, SIDE SHOWN
FLAT ON TOP OR F.O.B. FLAT
TRANSITIONS: GIVE SIZES. NOTE F.O.T.
IN DIRECTION OF AIR FLOW
INCLINED RISE (R) OR DROP (D) ARROW
DUCT SECTION (EXHAUST OR RETURN)
DUCT SECTION (SUPPLY)
ACOUSTICAL LINING DUCT DIMENSIONS
(BY STATIC PRESSURE CLASS)
OPPOSED BLADE DAMPERS
AUTOMATIC DAMPERS MOTOR OPERATED
VOLUME DAMPER MANUAL OPERATION
& RETURN (NO SPLITTER)
STANDARD BRANCH FOR SUPPLY
FLEXIBLE CONNECTION
ON BOTTOM IF APPLICABLE
PLUMBING
REFRIGERATION
TEMPERATURE CONTROLS
STANDARD NORTH ARROWS
SECTION IDENTIFICATION
ELEVATION IDENTIFICATION
ARCHITECTURAL SYMBOLS
GENERAL NOTES:
DUCTWORK
MECHANICAL LEGEND
HEATING
MISCELLANEOUS PIPING
NEWEXISTING
CIVIL LEGEND
NEWEXISTING
ARCHITECTURAL LEGEND
FENCES
T
GLOBE VALVE
W/TAMPER SWITCH
NEEDLE VALVE
STRAINER
HOSE GATE VALVE
GATE VALVE
M
S
SOLENOID VALVE
RELIEF VALVE
PA
FLOAT VALVE
BALL VALVE
BUTTERFLY VALVE
ANCHOR
WAFER CHECK VALVE
O, S, & Y GATE VALVE
PRESSURE REDUCING VALVE
MOTOR OPERATED VALVE
AUTOMATIC BALANCING VALVE AS INDICATED
CALIBRATED BRONZE BALANCING VALVE OR
PLUG VALVE OR BALANCING COCK
TEMPERATURE REGULATING VALVE
CAP
ELBOW UP
TEE UP
TEE DOWN
ELBOW DOWN
UNION
BLIND FLANGE
FLANGE
EXPANSION JOINT, BELLOWS
EXPANSION JOINT, SLIDING
PIPE INCREASER OR DECREASER
VALVES & FITTINGS
COND CONDENSATE DRAIN LINE
OR SENSOR (AS INDICATED)
OUTDOOR AIR THERMOSTAT
V
FCO FLOOR CLEAN OUT
FIRE DAMPER:
SHOW VERTICAL POS.
SHOW HORIZ. POS.
101 ROOM NUMBER
DOOR NUMBERS
COLUMN LINES NUMBER-LETTER (OPPOSITE DIR.)
MATCH LINE
WINDOW TYPES
CENTER LINE
X DIRECTION OF SIGHT OF PHOTOGRAPH
WALL AND PARTITION TYPES
A
A
A 1
101101
L .B .C
L E
G E
N D
G-004
L .B .C
L .B .C
L .B .C
F
IL
E N
U M
B E
R
F
IL
E N
U M
B E
R
L .B .C
L E
G E
N D
G-004
L .B .C
L .B .C
L .B .C
O A
G -0
.d g n
O A
G -0
.d g n0
/0
/2
O M
A H
A D
IS
T R
IC
T
O A
D -0
/0
/2
O M
A H
A D
IS
T R
IC
T
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O A
D -0
O A
H E D
A M S
O U
T H D
A K
O T
A
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
O A
H E D
A M S
O U
T H D
A K
O T
A
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
W F -1
-Q
-0
W F -1
-Q
-0
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg9:42:04 AM 6/4/2018
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
M
A H
A
N E
F
IL
E N
A M
E
O M
A H
A
N E
F
IL
E N
A M
POLE, NO., LENGTH, AND CLASS AS INDICATED
CLASS 7 SOIL) "MT" INDICATES TWIN EYE ANCHOR ROD
(ANCHOR STRENGTH IS BASED ON HOLDING POWER IN
DOWN GUY AND ANCHOR. STRENGTH IN LBS. INDICATED
OVERHEAD COMMUNICATIONS LINE
EXTERIOR ELECTRICAL LEGEND
EXIST NEW
LUMINAIRES AND APPROX. HORIZ. AIMING
INSTALLATION. ARROWS INDICATE NO. OF
POLE MOUNTED FLOODLIGHTING
CONDUCTOR AND LINE VOLTAGE AS INDICATED.
SERVICE DROP NO., SIZE AND TYPE OF
OVERHEAD POWERLINE-SECONDARY OR
VOLTAGE AS INDICATED
NO., SIZE, AND TYPE OF CONDUCTORS AND LINE
OVERHEAD POWERLINE-PRIMARY DISTRIBUTION.
SIZE AND TYPE OF WIRE AS INDICATED.
LIGHTING CIRCUIT RESPECTIVELY. NO.,
SERIES STREET LIGHT AND AIRFIELD
OR PER CROSS SECTION DETAIL
LINE). NO., SIZE AND VOLTAGE OF CABLE AS INDICATED
ELECTRICAL POWER LINE, "C" A COMMUNICATIONS TYPE
MIN. IF NOT IDENTIFIED). LETTER "P" INDICATES
SPECS). NUMERAL INDICATES QUANTITY OF DUCTS (4"
UNDERGROUND DUCT LINE, CONCRETE ENCASED (SEE
ANSI (C84.1) VOLTAGE CONFIGURATION AS INDICATED.
CONCRETE PAD MOUNTED TRANSFORMER INSTALLATION
NUMBER, SIZE, AND TYPE OF CABLE AS INDICATED
VOLTAGE), "C" A COMMUNICATIONS TYPE LINE.
CABLES ARE USED), "S" SECONDARY POWER (LOW
PRIMARY POWER (#8 MIN. IF SINGLE-CONDUCTOR
DIRECT BURIED LINE. THE LETTER "P" DESIGNATES
AND RACEWAY AS DESCRIBED ( * ) OR DETAILED
CONFIGURATIONS. NO. AND SIZE OF CONDUCTORS
UNDERGROUND DISTRIBUTION-MISC.
NO., AND TYPE AS INDICATED
PULLBOX, HANDHOLE OR MANHOLE.
VAULT (POWER OR CONTROLS)
UNDERGROUND ELECTRICAL EQUIPMENT
CABINET OR EQUIPMENT ASSEMBLY
ELECTRICAL EQUIPMENT IN PAD MOUNTED
NUMERAL IF PRESENT DESIGNATES KVA RATING
CONFIGURATION AS INDICATED, SINGLE
FENCED APPLICATONS. ANSI VOLTAGE
INDIVIDUAL TRANSFORMER FOR OVERHEAD OR
PHOTOELECTRIC CONTROL RELAY
AERIAL AUTOMATIC RECLOSER.
AERIAL AUTO SECTIONALIZER
(COUNTERPOISE) (BARE COPPER) SIZE AS INDICATED
GROUNDING SYSTEM. ELECTRODE AND CONDUCTOR
LIMITS OF CONDUIT CASING OR SLEEVE
CAPPED CONDUIT
DRAWOUT FUSE ASSEMBLY
RESPECTIVELY, SIZE AS INDICATED
FUSE-POWER AND CONTROL APPLICATIONS
BUS NUMBER FOR ANALYSIS AND REFERENCE ONLY
VOLTAGE RATING AND SIZE AS INDICATED
FUSED CUTOUT OR FUSED SWITCH ASSEMBLY.
FRAME SIZE WITH ADJUSTABLE TRIP SETTINGS.
MOLDED CASE CIRCUIT BREAKER OF A GIVEN
THREE POLE UNLESS DESIGNATED '1P' OR '2P'.
MOLDED CASE CIRCUIT BREAKER, FIXED TRIP.
MOLDED CASE CB TYPE). SIZE AS INDICATED.
INDICATES INSULATED CASE, "MC" INDICATES
("LVP" INDICATES LOW VOLTAGE POWER CB, "IC"
DRAWOUT TYPE CIRCUIT BREAKER ASSEMBLY
RATING AND CLASS AS INDICATED
SURGE ARRESTOR - VOLTAGE
- NUMBER DENOTES KVAR RATING
POWER FACTOR CORRECTION CAPACITOR
STEEL (#6 MIN. CONDUCTOR IF NOT SHOWN)
TYPE ELECTRODE, TO NEAREST STRUCTURAL
GROUND CONNECTION - TO STANDARD ROD
BETWEEN BREAKERS, RELAY/CONTACTOR, ETC.)
BETWEEN 2 OR MORE DEVICES (KEY INTERLOCK
CONTROL INTERFACE OR OPERATING RELATIONSHIP
IDENTIFIED). AMPACITY AS INDICATED
ASSEMBLIES (HIGH OR MEDIUM VOLTAGE). (CU BUS IF NOT
FEEDER TYPE BUS DUCT (FB) OR METAL-ENCLOSED BUS
LOADBREAK AND NON-LOADBREAK STYLES RESPECTIVELY
(ELBOW TERMINATOR AND BUSHING COMBINATION)-
SEPARABLE CONNECTOR IN PRIMARY DISTRIBUTION LINE
KILOWATT-HOUR METER (WH IS WATT-HOUR METER)
PARENTHESIS INDICATES QUANTITY OF CT'S
OF METERING/ACCESSORY CIRCUIT. NUMERAL IN
TRANSFORMATION RATIO IDENTIFIES NOMINAL CURRENT
CURRENT TRANSFORMER (CT). SECOND NUMERAL OF
INDICATED
AND NON-DRAWOUT. QUANTITY AND VOLTAGE RATING AS
VOLTAGE (POTENTIAL) TRANSFORMER (VT/PT), DRAWOUT
INDICATED.
VOLTAGE, CONNECTIONS, COOLING CLASS AND TYPE AS
POWER & DISTRIBUTION TRANSFORMER, RATED kVA, USED BY A TRANSFORMER SYMBOL.
TRANSFORMER DELTA CONNECTION DESIGNATION WHEN
IT IS AN UNGROUNDED OR FLOATING WYE CONNECTION.
RESPECTIVELY. IF THE GROUND SYMBOL IS MISSING, THEN
DIRECT GROUNDED AND RESISTOR GROUNDED
DESIGNATION WHEN USED BY A TRANSFORMER SYMBOL,
TRANSFORMER GROUNDED-WYE CONNECTION
AMMETER AND VOLTMETER WITH PHASE SELECTOR SWITCH
INTERLOCKING CONTROL AS INDICATED
WITH TRIP SETTING AT DESIGNATED TIME DELAY
GROUND FAULT INTERRUPTING EQUIPMENT (SEE SPECS)
FUNCTION PER ANSI/IEEE C37.2
ELECTROMECHANICAL); NUMERAL IDENTIFIES TYPE OR
SENSOR, DEVICE OR APPARATUS (ELECTRICAL OR
EXISTING AND NEW, RESPECTIVELY
CORRESPONDING SWITCH
THEN 2' X 2' IN SIZE - LETTER IDENTIFIES
INCANDESCENT OR H.I.D. LUMINAIRE LESS
OMITTED IN CONTINUOUS ROW CONFIGURATIONS)
SIZE (THE OUTLET SYMBOL WILL NORMALLY BE
FLUORESCENT OR HID LUMINAIRE 2' x 2' OR LARGER IN
OF EGRESS
CEILING EXIT LIGHT. ARROWS IDENTIFY DIRECTION
VOLTAGE RATINGS AS INDICATED
LIGHTING CONTACTOR - NO. OF POLES, CURRENT AND
RATINGS AND PHYSICAL SIZE AS INDICATED
BATTERY INVERTER SET (OR FORWARD TRANSFER UPS),
EMERGENCY POWER SYSTEM FOR EGRESS LIGHTING -
LUMINAIRE HEADS AS INDICATED
BATTERY OPERATED EMERGENCY LIGHT SET, NO. OF
WITH THE 'E' ANNOTATION
2-LAMP FIXTURE WILL BE SHOWN SHADED OR UNSHADED
SUPPLIED FROM EMERGENCY POWER. A 1-LAMP OR
INDICATES 2 LAMPS OF A 3 OR 4 LAMP FIXTURE ARE
THE SHADED PORTION OF THE FLUORESCENT SYMBOL
FIXTURE, RESP. SUPPLIED FROM AN EMERGENCY CIRCUIT.
FEEDER, DEVICE OR FIXTURE, AND FLUORESCENT TYPE
CEILING AND WALL MOUNT TYPES INDICATED.
JUNCTION BOX, 4" SQUARE UNLESS NOTED OTHERWISE.
DIMMING CONTROL FOR LIGHTING
OVERLOADS (MOTOR RATED SWITCH)
MANUAL STARTER WITH THERMAL
DOUBLE POLE SINGLE THROW SWITCH
SINGLE POLE SWITCH
THREE WAY SWITCH
FOUR WAY SWITCH
SINGLE POLE SWITCH WITH PILOT LIGHT
TIMER OPERATED SWITCH
KEY OPERATED SWITCH
MOMENTARY CONTACT SWITCH
8.
OUTLETS, NEMA 5-XX SERIES. DEFAULT SIZE IS 15A. SEE NOTE
CLOCKOUTLET, FO= FAN OUTLET, IG= ISOLATED GROUND TYPE
DUPLEX & SIMPLEX "SW" INDICATES SPLIT WIRED, CO=
2P,3W GROUNDING TYPE RECEPTACLE - 125V, CONVENTIONAL
FIXTURES
SWITCHED
IDENTIFY
WHERE USED,
C, ETC.
LETTERS A, B,
4'-0" UP
APPLICATIONS) UNLESS NOTED OTHERWISE
PLANS) IN SURFACE MOUNTED RACEWAY. WALL MOUNTED AT
RECEPTACLES SPACED AT INTERVAL INDICATED (SEE FLOOR
RECEPTACLE STRIP ASSEMBLY - DUPLEX NEMA 5-15
OTHERWISE.
BOTTOM OF THE OUTLET BOX, UNLESS INDICATED
BE MOUNTED 15 - INCHES A.F.F. AS MEASURED TO THE
8. ALL RECEPTACLE AND COMMUNICATION OUTLETS SHALL
ABBREVIATIONS SHEET FOR DEFINITIONS.
INDICATE SPECIAL CONSTRUCTION IS REQUIRED. SEE
7. LETTERS SUCH AS "WP", "EP" ADJACENT TO ANY SYMBOL
CONDUCTORS UNLESS INDICATED OTHERWISE.
6. SIZES OF WIRE AND CABLE ARE BASED ON COPPER
FIXTURE PER FIXTURE SCHEDULE.
ADJACENT TO SYMBOL INDICATES FIXTURE TYPE FOR EACH
(B) CAPITAL LETTER OR FIXTURE DESIGNATION INSIDE OR
WHEN ADJACENT TO THE FIXTURE SYMBOL.
NAME OR NUMBER DESIGNATION OR FOR SINGLE FIXTURE
FOR ENTIRE ROOM OR AREA WHEN ADJACENT TO THE ROOM
(A) INDICATES FIXTURE TYPE, PER FIXTURE SCHEDULE,
BOTH OF THE FOLLOWING METHODS:
5. ELECTRIC LIGHT FIXTURES ARE IDENTIFIED BY EITHER OR
(FILLED-IN) SYMBOL.
OPEN SYMBOL; NEW ITEMS WITH A THICK LINE OR CLOSED
4. EXISTING ITEMS ARE DESIGNATED BY A THIN LINE OR AN
3. NOT USED.
SHEET.
SPECIFIC CONDITIONS IN LIEU OF SYMBOLS SHOWN ON THIS
ITEMS NOT COVERED BY THIS SHEET OR TO INDICATE
THIS SET OF DRAWINGS TO ESTABLISH SYMBOLS FOR
2. SUPPLEMENTAL ELECTRICAL LEGENDS MAY APPEAR IN
PREFERRED FORM IS SHOWN FIRST.
1. WHERE MORE THAN ONE SYMBOL FORMAT IS SHOWN, THE
K
234B1
NOTED
ELECTRIC WATER COOLER (DRINKING WATER DISPENSER) SIZE AS
RECESSED (FLUSH MOUNTED) TYPE, SEE SPECS
MOUNTED TYPE (ABOVE FLOOR SERVICE FITTING), 'R' DENOTES
INDIVIDUAL FLOOR OUTLET ASSEMBLY.'SM' DENOTES SURFACE
TO EXTEND ABOVE SUSPENDED CEILING. SEE NOTE 8.
RELOCATIBLE SERVICE POST ASSEMBLY - LENGTH AS REQUIRED
TELEPHONE, P= PUBLIC TELEPHONE, SEE NOTE 8.
THE DEVICE INDICATE IT IS FLOOR MOUNTED. HL=HOTLINE
WITHOUT LEG(S) REQUIRES DUPLEX JACKS. A SQUARE AROUND
CONFIGURATIONS (8 PIN JACKS). SEE SPECS. SYMBOL SYMBOL
TELEPHONE OUTLET, SINGLE AND DUPLEX JACK
DIMENSIONS AS INDICATED (W X D)
CABLE TRAY FOR COMMUNICATIONS AND DATA PROCESSING,
TELEPHONE TERMINAL CABINET, SIZE AS INDICATED
TELEPHONE TERMINAL BOARD (PLYWOOD BACKBOARD);
- PART WINDING TYPE.
REDUCED VOLTAGE TYPE, 'AT' - AUTO TRANSFORMER TYPE, 'PW"
FULL VOLTAGE TYPE (DEFAULT IF NOT INDICATED), 'RV' -
INDICATES: 'R' - REVERSING TYPE, '2S' - TWO SPEED TYPE, 'FV'-
NUMERAL DESIGNATES NEMA SIZE; LOWER LETTER, IF USED,
MOTOR CONTROLLER - MAGNETIC OR AS INDICATED, UPPER
MOTOR - USE AND SIZE AS INDICATED
COMBINATION STARTER W/EXTERNALLY OPERATED DISCONNECT
240V, 30A MIN)
DISCONNECT SWITCH, SIZE AND TYPE AS INDICATED (OR 3P,
EMERGENCY POWER OFF.
PUSHBUTTON CONTROL STATION - 1, 2, OR 3 BUTTONS "EPO" =
'MAN-OFF-AUTO' (OR 'H.O.A.)
LEGEND PLATE DESIGNATIONS WILL BE 'ON-OFF' AND
3 POSITION AS INDICATED. IF NOT SPECIFIED ELSEWHERE,
SELECTOR SWITCH (SEPARATE FROM STARTER)- 2 POSITION OR
THERMOSTAT - SEE MECH. SPECS, 5'-0" UP
SCHEDULE FOR SIZES, RATINGS, AND LOADS
(MIN) VERTICAL SECTIONS INDICATED. SEE DIAGRAM AND/OR
MOTOR CONTROL CENTER, FREE STANDING W/NO. OF 20" WIDE
SCHEDULE. OPEN SYMBOL INDICATES EXISTING
AND SURFACE MOUNTED TYPES, SEE CORRESPONDING PANEL
LIGHTING AND APPLIANCE TYPE PANELBOARD - FLUSH MOUNTED
DISTRIBUTION TYPE PANEL
DIMENSIONS, CLEARANCES, AND ELECTRICAL RATINGS
SPELLED OUT), SEE FLOOR PLANS AND DIAGRAMS FOR
MAIN SWITCH BOARD OR MAIN SWITCH GEAR (ABBREVIATED OR
EQUIPMENT GROUND RESPECTIVELY (AS APPLICABLE).
CONDUCTOR, NEUTRAL, EQUIPMENT GROUND, AND ISOLATED
DOT AND DOUBLE DOT HASH MARKS REPRESENT PHASE
BRANCH CIRCUIT AND FEEDER WIRING. LONG, SHORT, SINGLE
THE CIRCUIT IS TWO-WIRE (MIN #12 IN 1/2"C).
SEGMENTS. A CIRCUIT WITHOUT ANY DESIGNATION INDICATES
UNDERSTOOD TO APPLY TO ALL UNMARKED INTERVENING
SEGMENTS, AND END-OF-LINE DEVICES, REQUIRED QUANITY IS
IF HASH MARKS ARE OMITTED BETWEEN HOME-RUNS, TRANSITION
ARROWS AND LETTER/NUMERALS IDENTIFY HOME-RUN CIRCUITS.
CONDUIT ONLY - NO CONDUCTORS, PULL WIRE IF OVER 50'
LIGHT LINE - EXISTING, OR BY OTHER TRADES
COATED R.S. CONDUIT UNLESS INDICATED OTHERWISE
COMM OR POWER FEEDER INSTALLED UNDER FLOOR SLAB IN
HEAVY LINE - NEW ELECTRICAL WORK
MATCH LINES, ETC.)
(TO LIGHTING SHEET FROM POWER OR COMM DWG., ACROSS
FUTURE WORK OR ELECTRICAL ITEM REPEATED FOR CLARITY
(NEW LOCATION)
EXISTING EQUIPMENT; EXISTING EQUIPMENT AS RELOCATED
GENERATOR OR GENERATOR CONNECTION.
XRX
LP-2,4,6
MSGMSB
LP2
MCC-2
B
NOTE 5
G
CO
UF
MC
K
T
P
TO
20A
X"
INTERIOR ELECTRICAL LEGEND
FIRE ALARM CONTROL PANEL, (SEE SPECS)
SPECS
W/OR W/O GRAPHIC REPRESENTATION, SEE
FIRE ALARM ANNUNCIATION PROVISIONS,
ANTENNA FOR FM RADIO TYPE), SEE SPECS
FIRE ALARM SIGNAL TRANSMITTING (WITH
MANUAL FIRE ALARM STATION - 4'-0" A.F.F.
"CO"=CARBON DIOXIDE
ABORT STATION. "F"= FIRE; "H"=HALON;
TUBULAR SENSING ELEMENT REQUIRED
RATE ("RATE ANTICIPATION") TYPE WITH
SEE SPECS; 'CR' INDICATES COMPENSATED
COMBINATION F.T. AND RATE OF RISE TYPE,
SYMBOL INDICATES FIXED TEMPERATURE OR
HEAT DETECTOR - UNDIFFERENTIATED
LOCATION IS NOT OTHERWISE INDICATED.
INSTALLED IN THE SUPPLY DUCT IF THE
DUCTS, A SINGLE DETECTOR WOULD BE
LOCATIONS ARE IN SUPPLY AND RETURN
DUCT DETECTORS ARE SHOWN IN PAIRS,
DUCT TYPE SMOKE DETECTOR. WHERE
PHOTOELECTRIC TYPE. 'D' STIPULATES A
PRESENT, STIPULATES IONIZATION OR
SMOKE DETECTOR. THE LETTER 'I' OR 'P', IF
SWITCH, SEE MECH. SPECS
VALVES, WATER FLOW INDICATOR AND FLOW
Y) VALVE, TAMPER SWITCH, ALARM CHECK
FIRE ALARM CONTACTS AT SOLENOID (OS &
24-INCH LIGHTNING AIR TERMINAL.
60-INCH LIGHTNING AIR TERMINAL.
LIGHTNING PROTECTION MAIN CONDUCTOR
NOTES:
ELECTRICAL POWER DIAGRAM LEGEND
#2
40'-4 40'-4
6M
12 MT
6M
II
WP2#6
OHSOHS
4-#6 ACSR
3#1
OHPOHP
13.8KV
3#1
OHC OHC
1-#6 CWC
AFL
1#6
SL
USE
4#8, TYPE
DBP DBP
DBS
DBCDBC
DBS
4P
4P/2C
2C 2C
+3 SPARE
1-#3 600V
3-#3,15 KV
4P
UG
UG
PB#4 HH#2 MH#4
A
EV EV
EPEP
PE PE
R
SSSS
R
#4
2" C
G
LVP
400A
3P
20 A
1600AF
1200AT
9KV
50A
SS
1600A
FBFB
KWH
1200:5
(3)
(3)
AS A VS V
400 AT
0.3 s#2
GFI
50N 51N
27B3
A
+7'
EPS
E E
OR
E
J J
D
S S S S
S
S
S
S
S
3/4HP
SM
SM
R
CT
12" X 4"
TTB-2
36X24X6
TTC#4
EF-3 2HP
M
#3
2S
SS2PHOAS
T
FCP FCP
FAA FAA
FSTFST
H CO F
FFFF
M
F
C
M
F F F F C
CR
I D P
WFITSSVOSY
STATIC GROUND ROD
L
L
FIXTURE C )
WALL FIXTURE - MOUNTING HEIGHT INDICATED (TO
(TO C ), ARROWS IDENTIFY DIRECTION OF EGRESS
WALL EXIT LIGHT - MOUNTING HEIGHT INDICATED
NUMERAL INDICATES IES TYPE DISTRIBUTION
INSTALLATION, WATTS AS INDICATED, ROMAN
POLE MOUNTED ROADWAY OR AREA LIGHTING
WALL MOUNTED (6'-8" A.F.F.) RESPECTIVELY
- FLASHING LIGHT, CEILING MOUNTED AND
FIRE ALARM WARNING DEVICE, VISIBLE ONLY
HORN AND MASS NOTIFICATION, 6'-8" A.F.F.
FIRE ALARM WARNING DEVICE - BELL, CHIME,
A.F.F.
NOTIFICATION, HORN, BELL, OR CHIME - 6'-8"
AND VISIBLE - FLASHING LIGHT WITH A MASS
F.A. WARNING DEVICE, COMBINED AUDIBLE
F
C
A P
IT
O L A
V E
F
IL
E N
U M
B E
R
C
A P
IT
O L A
V E
F
IL
E N
U M
B E
R
O A
G -0
.d g n
O A
G -0
.d g n
O M
A H
A D
IS
T R
IC
T O
M A
H A D
IS
T R
IC
T
O A
H E D
A M S
O U
T H D
A K
O T
A
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
O A
H E D
A M S
O U
T H D
A K
O T
A
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
W F -1
-Q
-0
/0
/2
O A
D -0
W F -1
-Q
-0
/0
/2
O A
D -0
A R
C H D
A R
C H D
S .L .O
E L E
C T
R
IC
A L L
E G
E N
D
G-005
L .B .C
S .L .O
S .L .O
S .L .O
E L E
C T
R
IC
A L L
E G
E N
D
G-005
L .B .C
S .L .O
S .L .O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
AUTOTRANSFORMER YARD
ACCESS ROAD
ACCESS ROAD
ACCESS ROAD
ACCES
S
ROAD
13.8 kV TERTIARY BUSS RACK
NEW COLUMN
AUTOTRANSFORMER PAD
NEW VCB PAD
115 kV SWITCHYARD
BAR
#4
230 kV SWITCHYARD
WITH 12" OR MORE OF FRESH CONCRETE CAST
TOP BARS ARE DEFINED AS HORIZONTAL REINF.
BELOW.
#11
#6
#7
#8
SIZE
#10
9'-5"
CONCRETE
#3
#5
#9
2'-0"
TOP OTHER
2'-8"
3'-4"
4'-0"
5'-10"
6'-8"
7'-7"
8'-6"
1'-7"
2'-1"
2'-7"
3'-1"
4'-6"
5'-2"
5'-10"
6'-7"
7'-3"
13.8kV SWITCH GEAR
ACB822
REGULATOR PAD
DEMO EXISTING VOLTAGE
REINFORCEMENT LAP LENGTH TABLE
LAP LENGTHGROUND TRANS. PAD
DEMO EXISTING 3.2 MVA
DESIGN LOADS:
SOILS & FOUNDATION DATA:
A. ALLOWABLE SOIL BEARING PRESSURE: 2500 PSF
B. SOIL DENSITY: 120 PCF
GENERAL NOTES:
A. REFERENCE ELEVATION 100'-0" = TOP OF FINISHED SLAB FOR ALL
STRUCTURES.
B. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND COORDINATE
LOCATIONS OF ALL EMBEDDED ITEMS, CONDUITS, PIPES, AND OPENINGS.
REFER TO ELECTRICAL DRAWINGS FOR ITEMS NOT INDICATED ON
STRUCTURAL DRAWINGS. THE CONTRACTING OFFICER SHALL BE
NOTIFIED IMMEDIATELY OF ANY DISCREPANCY.
CONCRETE AND REINFORCEMENT:
A. CONCRETE AND REINFORCEMENT SHALL CONFORM TO SPECIFICATION
SECTION 03 30 53 MISCELLANEOUS CAST-IN-PLACE CONCRETE.
B. ALL CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH AT 28 DAYS
(f'c) NOT LESS THAN 5,000 PSI.
C. ALL REINFORCING STEEL SHALL BE ASTM A-615, GRADE 60.
D. CLEAR COVER SHALL BE 3" FOR CONCRETE PLACED DIRECTLY
AGAINST SOIL AND 2" FOR FORMED SURFACES; UNLESS NOTED OTHERWISE.
E. PROVIDE 3/4" CHAMFER ON ALL EXPOSED EDGES.
F. NON-SHRINK GROUT SHALL CONFORM TO ASTM C1107.
STEEL:
A. MATERIAL STRENGTHS:
STRUCTURAL STEEL ROLLED W-SHAPES ASTM A992, (Fy = 50 KSI)
STRUCTURAL STEEL CHANNELS ASTM A36
BASEPLATES AND ALL OTHER MISC. PLATES ASTM A36
CONNECTION BOLTS ASTM A325
ANCHOR RODS ASTM F1554, GR. 36
WELDING ELECTRODES E70
B. ALL STRUCTURAL STEEL AND THEIR CONNECTIONS SHALL BE DETAILED,
FABRICATED AND ERECTED ACCORDING TO THE LATEST VERSION OF THE
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) MANUAL OF STEEL
CONSTRUCTION.
C. THREADED PARTS SHALL BE HOT DIPPED GALVANIZED IN ACCORDANCE WITH
ASTM F2329, STRUCTURAL STEEL SHALL BE GALVANIZED IN ACCORDANCE
WITH ASTM A123/A123M.
D. COLUMN ANCHOR RODS SHALL BE POSITIVELY LOCATED USING TEMPLATES
FOR ALL COLUMN BASEPLATES. PROVISION SHALL BE MADE FOR ALL ANCHOR
RODS TO BE RIGIDLY HELD IN POSITION TO PREVENT MOVEMENT DURING
CONCRETE PLACEMENT. ANCHOR RODS SHALL NOT BE TIGHTENED PRIOR
TO 14 DAYS FOLLOWING CONCRETE PLACEMENT.
A
B
C
D
E
F
G
H
L
K
J
M
N
15 16 19
20 21
17 18
P
Q
R
S
T
U
V
N
1 2 3 4 5 6 7 8 9 10 1311 12 14 15
L
M
N
17 18
EQUIPMENT INSTALLATION
SWITCHYARD FOUNDATION PLAN
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg10:49:02 AM 6/4/2018
E N
U M
B E
R
A N
S I
D
E N
A
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
A N
S
E N
U M
B
E N
A
T e m p
O A
H E D
A M S
O U
T H D
A K
O T
A /0
/2
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A D
IS
T R
IC
T
O A
H E D
A M S
O U
T H D
A K
O T
A /0
/2
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A D
IS
T R
IC
T
S-001S-001
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
O A S -0
.d g n
O A S -0
.d g n
D -0
O A
D -0
W
B O
E C
K
D F
R E
N C
H
W
B O
E C
K
D F
R E
N C
H
G E
N E
R A
L N
O T
E S
G E
N E
R A
L N
O T
E S
40' 80'0
SCALE: 1"=40'
W F -1
-Q
-0
W F -1
-Q
-0
W
B O
E C
K
D .J .F
S-100
S-100
86'-10"
13'-7"+/- 10'-0"
8'-0"
4'-8"5'-4"
7'-0"
16'-0"
7"
1/2" DIA. A325 BOLTS
EXISTING BEAM
DRILL 5/8" DIA. HOLE THROUGH
PL. 7"x7"x1/2"
3" 2"2"
PL. 8"x8"x1/2"
2" 4" 2" /2
/2
8"
AND LEVELING NUTS
w/ 15" EMBEDMENT
3/4" DIA. ANCHOR BOLTS
(6) #5 EVENLY SPACED
#3 TIES @ 10" O.C.
8"
#5 @ 12" OC, EW
LAP LENGTH
#5 DOWEL BARS @ 12" OC
COMPACTED FILL
3/4" CHAMFER, TYP
FINISH GRADE
8"
#5 @ 12" OC, EW
LAP LENGTH
#5 DOWEL BARS @ 12" OC
COMPACTED FILL
3/4" CHAMFER, TYP
FINISH GRADE
EXISTING COLUMNS
WITH BALL VALVE
2" DIA. DUCTILE IRON PIPE
1'-3" DIA. PIER
SLAB, MATCH SLOPE FOR DRAINAGE
INSTALL FLUSH WITH CONCRETE
2" DUCTILE IRON PIPE w/ 2" BRASS BALL VALVE
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
SEE 3/S-100
NEW W6x15 COLUMN
LOCATION W/ ELECTRICAL
PAD, SEE 7/S-100. CORDINATE
NEW GROUND TRANSFORMERSEE 8/S-100
WITH CONTAINMENT BASIN
NEW VOLTAGE REGULATOR PAD
*SLOPE
13.8 kV SWITCHGEAR
*S L
O P
NOTES:
* SLOPE = 1/4" PER FT.
S-100
SEE 7/S-100
NEW VCB PAD
*S E
E N
O T
E
S H
E E
T E -2
EXISTING BEAM
NEW W6x15 COLUMN
(3) #3 TIES IN THE TOP 5"
#3 TIES 12" O.C.
1" NON-SHRINK GROUT PAD
S-100
S-100
S-100
3/16
3/16
EQUIPMENT, SEE ELE. / ME.
EQUIPMENT, SEE ELE. / ME.
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg1:42:50 PM 6/4/2018
E N
U M
B E
R
A N
S
E N
A
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
A N
S
E N
U M
B
E N
A
T e m p
O A
H E D
A M S
O U
T H D
A K
O T
A /0
/2
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A D
IS
T R
IC
T
O A
H E D
A M S
O U
T H D
A K
O T
A /0
/2
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A D
IS
T R
IC
T
S-100S-100
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
O A S -1
.d g n
O A S -1
.d g n
13.8 kV TERTIARY BUS RACK COLUMN ADDITION
SCALE: 1/8" = 1'-0" 2
VCB CONCRETE PAD
SCALE: 1/8" = 1'-0"
O A
D -0
O A
D -0
4 5CAP PLATE
SCALE: 3" = 1'-0"
BASE PLATE
SCALE: 3" = 1'-0" 6
CONC. PIER
SCALE: 3" = 1'-0"
COLUMN ADDITION
SCALE: 1" = 1'-0"
W
B O
E C
K
D F
R E
N C
H
D F
R E
N C
H
W
B O
E C
K
D F
R E
N C
H
D F
R E
N C
H
P L
A N V
IE
W A
N D D
E T
A
IL
S P
L A
N V
IE
W A
N D D
E T
A
IL
S0 8'4' 16'
0 1' 2'6"
6"0 3" 1'
SCALE: 1/8"=1'-0"
SCALE: 3"=1'-0"
SCALE: 1"=1'-0"
EQUIPMENT PAD W/ CONTAINMENT BASIN
SCALE: 1" = 1'-0"
EQUIPMENT PAD
SCALE: 1" = 1'-0"
W F -1
-Q
-0
W F -1
-Q
-0
1/4" PER FT.
SLOPE
W
B O
E C
K
OF FRESH CONCRETE.
CONSTRUCTION JOINTS SHALL BE ROUGHENED PRIOR TO PLACEMENT
ALL JOINT LOCATIONS PER MANUFACTURERS RECOMMENDATIONS.
FROM WALLS. ELASTOMERIC WATERSTOPS SHALL BE INSTALLED AT
CONTRACTOR MAY PLACE FOUNDATION AND SLAB SEPARATELY
NOTE:
REGULATOR
VOLTAGE
(TYP. OF 3)
ARRESTER
NEW SURGE
SEE NEW NOTES 1-5
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
DS: AEC_Screen.dscriptPD: AEC_pdf.pltcfg9:26:34 AM 6/4/2018
E N
U M
B E
R
A N
S
E N
A
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
A N
S
E N
U M
B
O T
T
J L
IN
D E
M A
N
J
C H
A M
B E
R L
A
IN
J
C H
A M
B E
R L
IN
E N
A M
E
S
O T
J
L
IN
D E
M A
N
J
C H
A M
B E
R L
A
IN
J
C H
A M
B E
R L
A
IN
O P
E R
A T
IN
G D
IA
G R
A M
O P
E R
A T
IN
G D
IA
G R
A M
T e m p
GENERATORS
FORT
THOMPSON
LINE 4
FORT
THOMPSON
LINE 3
FORT
THOMPSON
LINE 2
3080 2980
MB-5
9283 9281
92822883
28822982
29833083
3081 2981 2881
3087 2987 2887
2787 2687 2587 2487
91819183
MB-3
P.T.
2780 2680 2580
PHILIP
NEW
UNDERWOOD
LINE
SULLY
BUTTES
LINE
FORT
THOMPSON
LINE 1
MB-1
230KV MAIN BUS
20822182
2181 2081
2387 2187 2087
230KV AUX. BUS
PIERRE
LINE
EAGLE BUTTE
LINE
IRV
SIMMONS
LINE
106012601460
115KV AUX. BUS
10671167126713671467
1361 1161
10621162126213621462
1463 1363 1263 1163 1063
115KV MAIN BUS
13.8KV
723 623
TRANSF.
NO. 4
206MVA
FUTURE IRRIGATION
PUMPHOUSE
G7 G6
721 621
523 423
G5 G4
521 421
323 223
221321
1000KVA
STATION
SERVICE
G3 G2
533425
424524
13.8KV
TRANSF.
NO. 3
206MVA
TRANSF.
NO. 2
206MVA
13.8KV
333225325
324 224
P.T.
TRANSF.
NO. 1
103MVA822
REACTOR 0.5
13.8KV
KVA
834 832
KVA
KVA
INTAKE
STA.
836842838
3.2MVA
(ZIG-ZAG)
13.8KV
G1
KVA
STATION
SERVICE
89.5MVA-85MW
13.8KV
1-3 -103MVA FOW
13.8-66.4/115KV
3-1 -68.7MVA FOW
13.8-132.8/230KV
3-1
OA/FA 132.8/230KV
6.2MVA
13.8KV
35.6MVA
69.4/115KV
TRANSFORMER NO. 1
TRANSFORMER BANKS NO. 2, 3 & 4
AUTO-TRANSFORMERS
35.6MVA
S1B S1C
S1A
S1A-------TO CKT. BKR. 842
S1B-------TO EXISTING UG FEEDER
S1C-------TO NEW UG FEEDER
S2B
S2D
S2T
S2C
S2A (N.O.)
S2A-------TO OVERHEAD
S2B-------TO S1
S2C-------TO MARINA BACKFEED
& MITIGATION BLDG.
S2D-------TO MAINT. FACILITIES
(S2)
(S1)
S2A
S3DS3C
S3B
(S3)
S3A-------TO #12
S3B-------TO S2
S3C-------TO #11
S3D-------TO #14A
NOTE 1
NOTE 2
NOTE 3
S1
SERV.
KVA45
& LIGHTS
SECURITY GATE
POWER HOUSE
SZ1 SZ3 SZ4S2 S3 S4 SZ5
KVA
SZ2
KVA
KVA
KVA
LIGHTS
CRESTROAD
S1
S2
KVA
KVA
LIGHTING
TRIANGLE
S1A
S1B
2A 2
BASIN
STILLING
LIGHTS
AREA
25KVA
M1 ADMIN. BLDG.
M3 MAINT. BLDG.
M2 STORAGE BLDG.
M4 MIDIGATION BLDG.
S3
THE S2 LOCATION
S2A OPEN AT
MARINA AND
BACKFEED FOR
SPILLWAY
BOAT RAMP
WEST SHORE
WORKS
OUTLET
O A
H E D
A M S
O U
T H D
A K
O T
A /0
/2
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A D
IS
T R
IC
T
O A
H E D
A M S
O U
T H D
A K
O T
A /0
/2
O M
A H
A
N E
B R
A S
K A
C
A P
IT
O L A
V E
O M
A H
A D
IS
T R
IC
T
E-101E-101
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
15/20/25MVA
90/120/150MVA 80/107MVA
14/18.6MVA
INTERLOCKED
ELECTRICALLY
DETAILS
MORE
FOR
E-103
SHEET
SEE
NEW NOTES:
O A E -1
.d g n
O A E -1
.d g n
O A
D -0
O A
D -0
FEEDER (GFCI)
UNDERGROUND
W F -1
-Q
-0
W F -1
-Q
-0
3-1
OA/FA 132.8/230KV
8.3MVA
13.8KV
50.0MVA
69.4/115KV
50.0MVA
AT1:
AT2:
AUTO-TRANSF. AT1
AUTO-TRANSF. AT2
E-103, e-201, e-205, e-206, and e-501.
6. PROVIDE AND INSTALL NEW VCB 812 AND NEW AIR BREAK SWITCH 813. REFERENCE ALSO SHEETS
ON EACH SIDE OF AIR BREAK SWITCHES 825, 829, AND 827.
NEW AIR BREAK SWITCHES. ALSO REMOVE AND REPLACE EXISTING #4/0 STRD. CU CONDUCTORS
5. EXISTING AIR BREAK SWITCHES 825, 829, AND 827 SHALL BE REMOVED AND REPLACED WITH
>1#4/0 AWG BARE COPPER GROUNDING CABLE FROM THE GROUNDING RESISTOR TO GROUND.
AND THE NEW GROUNDING RESISTOR.
>1#4/0 AWG, 15KV IN EXISTING CONDUIT 5R6-2" BETWEEN THE NEW GROUNDING TRANSFORMER
TRANSFORMER.
>3#1 AWG,15KV IN EXISTING CONDUIT 5R5-4" BETWEEN NEW VCB838 AND THE NEW GROUNDING fOLLOWS:
WITH THE GROUNDING RESISTOR AND GROUNDING TRANSFORMER SHALL ALSO BE REPLACED AS
new grounding transformer ON A NEW CONCRETE PAD. ALL CONDUCTORS ASSOCIATED
REPLACED with A new grounding resistor ON THE EXISTING CONCRETE PAD and A
4. EXISTING grounding resistor and grounding transformer SHALL BE REMOVED AND
500KVA VOLTAGE REGULATOR ON A NEW OIL CONTAINMENT CONCRETE PAD.
3. EXISTING 450KVA VOLTAGE REGULATOR SHALL BE REMOVED AND REPLACED WITH A NEW
ALL CONNECTIONS PROPERLY CLEANED OF OXIDE BEFORE REINSTALLATION.
REMAIN CONTINUOUS. EXISTING COPPER TUBING THAT IS REMOVED MAY BE REUSED WITH
WHERE CLR'S WERE REMOVED TOWARD NEW VCB 822 SO THAT BUS CONNECTIONS
SHALL BE REMOVED. MOVE VERTICAL BUS MEMBERS INCLUDING BUS TAPS AND ELBOWS
2. EXISTING 3 X 0.5 OHM, 400A, 13.8KV, OUTDOOR, CURRENT LIMITING REACTORS (CLR'S)
WITH VCB'S HAVING THE SAME DESIGNATIONS AS THE EXISTING ACB'S.
BE REMOVED AND REPLACED WITH NEW OUTDOOR SWITCHGEAR ON THE EXISTING CONCRETE PADS
1. EXISTING OUTDOOR SWITCHGEAR WITH ACB'S 822, 832, 834, 836, 838, AND 842 SHALL
COPPER BUS
2" SCHEDULE 40
RIGID OVERHEAD
NEW 1200A, 15 KV
IN DUCT BANK
1000 KCMIL CABLE
NEW 15 KV,
NEW WORK
NEW VCB 812
DISCONNECT SWITCH 813
NEW GROUP OPERATED
REFERENCE ALSO SHEETS E-101, E-201, E-205, E-206, and E-501.
1. PROVIDE AND INSTALL NEW VCB 812 AND NEW AIR BREAK SWITCH 813.
NOTE:
(3) 1200:5
(3) 1200:5
91819183
METERING
(3) 800:5
(3) 1200:5
(3) 1200:5
(3) 1200:5
13.8kV BUS
STA. SVC.
N
U
E D
N
E D
N
E D
V
B
D
K V
S Y
N C
M E
T E
R I
N G
TRANSF. 2
230kV MAIN BUS
230kV AUX BUS
NOT USED (3) 1200:5
(3) 600:5NOT USED
LINE 1
THOMPSON
FORT
(3) 1200:5(3) 800:5 (3) 1200:5
N
E D
N
E D
NOT USED (3) 2000:5 NOT USED (3) 1200:5 NOT USED (3) 1200:5
LINE RELAYS
NOT USED NOT USED
87T287AT1
MB-1
M B
M B
M 2087M 2187M 2387
208021802380
C-PHASE
(1) 132.8KV-115V
(3) 97KV L.A.
L
A
(3) 15KV L.A.
NOTES
(3) 97KV L.A.
A
(3) 15KV L.A.
230kV
115kV
230kV
115kV
B F
M R
M R
21BF
(3) 600:5MR
(3) 600:5MR
(1) 800:5
(1) 400:5
(1) 1000:5
(3) 1200:5MR
51AT1
USED
NOT
USED
NOT
(3) 600:5
(3) 600:5
(3) 1200:5
(1) 400:5
64AT1
AUTOTRANSFORMER AT2
AUTOTRANSFORMER AT1
(3) 2000:5
87AT2
USED
NOT
USED
NOT
USED
NOT
A T
N
E D
50/51N
(3) 2000:5MR
(3) 2000:5MR
(3) 2000:5MR
(3) 1200:5MR
87BDMB1 87BDMB1 87BDMB1
66.4/115V
66.4/115V
(3) 132.8KV-
(3) 2000:5
(3) 2000:5MR
(3) 2000:5MR
(3) 2000:5MR
(3) 2000:5MR
69/115V
69/115V
(3) 132.8KV-
CORRECTIONS.
PROVIDE THOSE RATIOS TO THIS DRAWING FOR AS-BUILT
FOR DIRECTION ON DETERMINING THE DESIRED RATIOS AND
MULTI-RATIO. SEE THE CORRESPONDING THREE LINE DIAGRAMS
2. CURRENT TRANSFORMERS IN NEW CIRCUIT BREAKERS ARE
1. HEAVIER WEIGHT LINES AND TEXT INDICATE INSTALLATION.
13.8kV
230kV SWITCHYARD
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
SHEET E-101
CONTINUED ON
N
S
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
A N
S
O T
T
E-103
J L
IN
D E
M A
N
J
C H
A M
B E
R L
A
IN
J
C H
A M
B E
R L
H E D
A M S
O U
T H D
A K
O T
A
O M
A H
A D
IS
T R
IC
T
O A
H E D
A M S
O U
T H D
A K
O T
A
O M
A H
A D
IS
T R
IC
T S
T A
T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
9:28:45 AM 6/4/2018 PD: AEC_pdf.pltcfg DS: AEC_Screen.dscript
E -1
.d g n
E Q
U
IP
M E
N T I
N S
T A
L L
A T
IO
N
O N
E L
IN
E D
IA
G R
A M
K V S
W
IT
C H
Y A
R D
/0
/2
/0
/2
O A
D -0
W F -1
-Q
-0
W F -1
-Q
-0
IN CONCRETE ENCASED DUCTBANK
(1000 KCMIL) AND 6" SCH. 40 PVC
NEW 15KV UNDERGROUND CABLE
115' (+/- 10%)
NEW COLUMN
EXISTING COLUMN
(SEE DETAILS ON SHEET E-503)
NEW 4' X 4' X 6'D MANHOLE
(SEE DETAILS ON SHEET E-503)
NEW 4' X 4' X 6'D MANHOLE
SWITCH 813
DISCONNECT
OPERATED
NEW GROUP
IN CONCRETE ENCASED DUCTBANK
(1000 KCMIL) AND 6" SCH. 40 PVC
NEW 15KV UNDERGROUND CABLE
COPPER BUS
2" SCHEDULE 40 RIGID
NEW 15 KV OVERHEAD
(DEPTH 3'-0" TO TOP OF DUCTBANK)
IN CONCRETE ENCASED DUCTBANK
(1000 KCMIL) AND 6" SCH. 40 PVC
NEW 15KV UNDERGROUND CABLE
CONNECTION DETAILS
AND E-502 FOR TERTIARY
SEE SHEETS E-212, E-213,
SEE SHEET E-211
5'-3" TO TOP)
(APPROX. DEPTH
EXISTING DUCTBANK
PANELBOARD REPLACEMENT AREA (SEE SHEETS E-208, E-209, AND E-210)
" 812
VCB
NEW
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
O T
T
E-201
J L
IN
D E
M A
N
J
C H
A M
B E
R L
A
IN
J
C H
A M
B E
R L
H E D
A M S
O U
T H D
A K
O T
A
O M
A H
A D
IS
T R
IC
T
O A
H E D
A M S
O U
T H D
A K
O T
A
O M
A H
A D
IS
T R
IC
T S
T A
T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
S T
A T
IO
N S
E R
V
IC
E S
W
IT
C H
G E
A R R
E P
L A
C E
M E
N T
9:30:36 AM 6/4/2018 PD: AEC_pdf.pltcfg DS: AEC_Screen.dscript
W
IT
C H
Y A
R D S
IT
E P
L
E -2
.d g n
EXISTING AUTOTRANSFORMER BANK
SWITCHGEAR OVERHEAD BUS
EXISTING 13.8KV STATION SERVICE
(SEE SHEET E-203 FOR DETAILS)
TRANSFORMER
GROUNDING
NEW AUTOTRANSFORMER (BY OTHERS)
/0
/2
/0
/2
O A
D -0
RESISTOR
GROUNDING
E-201
E-502
N
E Q
U
IP
M E
N T I
N S
T A
L L
A T
IO
N P
L A
N
SEE NOTE 6
NEW NOTES:
NOT TO SCALE
W F -1
-Q
-0
W F -1
-Q
-0
REGULATOR
VOLTAGE
SURROUNDING GRADE AND PROVIDE A 6" MINIMUM DEPTH.
2. REPLACE CRUSHED ROCK AFTER INSTALLING NEW DUCTBANK TO MATCH THE
1. REPAIR GROUND MAT CONNECTIONS WITH EXOTHERMIC WELDS WHERE DISTURBED.
GENERAL NOTES:
(SEE NOTE 8)
ARE NO LONGER THAN 10'-0".
8. DISTANCE IS APPROXIMATE. LOCATE NEW PAD AND VCB 812 SO THAT NEW COPPER BUSSES
DRAINAGE OF THE DUCT BANK.
TOWARD THE BOTH MANHOLES AT A MINIMUM OF 3 INCHES PER 100 FEET TO ALLOW PROPER
AND SLOPED DOWNWARD FROM THE HIGHEST POINT IN THE CENTER AT THE CROSSING POINT
7. NEW DUCT BANK SHALL BE BURIED AT 3'-0" AT THE CROSSING POINT WITH EXISTING DUCT BANK
THE DUCT BANK TRENCH.
ALONG A CLEAN LINE. PROTECT THE SURROUNDING SIDEWALK DURING EXCAVATION OF
SPECIFICATION 03 60 00.00 26 CONCRETE DEMOLITION AND REPAIR. CUT THE CONCRETE
6. REPLACE SECTION OF SIDEWALK AT NEW DUCTBANK CROSSING POINT. REFERENCE
CONDUCTORS ON EACH SIDE OF AIR BREAK SWITCHES 825, 829, AND 827.
WITH NEW AIR BREAK SWITCHES. ALSO REMOVE AND REPLACE EXISTING #4/0 STRD. CU
5. EXISTING AIR BREAK SWITCHES 825, 829, AND 827 SHALL BE REMOVED AND REPLACED
>1#4/0 AWG BARE COPPER GROUNDING CABLE FROM THE GROUNDING RESISTOR TO GROUND.
TRANSFORMER AND THE NEW GROUNDING RESISTOR.
>1#4/0 AWG, 15KV IN EXISTING CONDUIT 5R6-2" BETWEEN THE NEW GROUNDING
GROUNDING TRANSFORMER.
>3#1 AWG,15KV IN EXISTING CONDUIT 5R5-4" BETWEEN NEW VCB838 AND THE NEW
FOLLOWS:
WITH THE GROUNDING RESISTOR AND GROUNDING TRANSFORMER SHALL ALSO BE REPLACED AS
NEW GROUNDING TRANSFORMER ON A NEW CONCRETE PAD. ALL CONDUCTORS ASSOCIATED
REPLACED WITH A NEW GROUNDING RESISTOR ON THE EXISTING CONCRETE PAD AND A
4. EXISTING GROUNDING RESISTOR AND GROUNDING TRANSFORMER SHALL BE REMOVED AND
500KVA VOLTAGE REGULATOR ON A NEW OIL CONTAINMENT CONCRETE PAD.
3. EXISTING 450KVA VOLTAGE REGULATOR SHALL BE REMOVED AND REPLACED WITH A NEW
ALL CONNECTIONS PROPERLY CLEANED OF OXIDE BEFORE REINSTALLATION.
REMAIN CONTINUOUS. EXISTING COPPER TUBING THAT IS REMOVED MAY BE REUSED WITH
WHERE CLR'S WERE REMOVED TOWARD NEW VCB 822 SO THAT BUS CONNECTIONS
SHALL BE REMOVED. MOVE VERTICAL BUS MEMBERS INCLUDING BUS TAPS AND ELBOWS
2. EXISTING 3 X 0.5 OHM, 400A, 13.8KV, OUTDOOR, CURRENT LIMITING REACTORS (CLR'S)
PADS WITH VCB'S HAVING THE SAME DESIGNATIONS AS THE EXISTING ACB'S.
BE REMOVED AND REPLACED WITH NEW OUTDOOR SWITCHGEAR ON THE EXISTING CONCRETE
1. EXISTING OUTDOOR SWITCHGEAR WITH ACB'S 822, 832, 834, 836, 838, AND 842 SHALL
ENTRANCE
TUNNEL
13.8 KV MAIN VCB
13.8 KV SWITCHGEAR
DS 2191
DS 1371
17P
MA *
MA *
S O
L
IC
IT
A T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T E
D B
Y
D A
T E
C O
N T
R A
C T N
O
C H
E C
K E
D B
Y
D R
A W
N B
Y
IS
S
U E D
A T
E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
(TYP. OF 3)
230kV SURGE ARRESTER
(TYP. OF 3)
230kV BUSHING
(TYP. OF 3)
115kV BUSHING
(TYP. OF 3)
ARRESTER
115kV SURGE
OUTLINE
CONCRETE PAD
NO SCALE
NO SCALE
LINER BOUNDARY
GEOSYNTHETIC
QUENCHING STONE
Q U
E N
C H I
G
O N
E
S W I
T C
H Y
A
A V
O P
QUENCHING STONE
Q U
E N
C H I
O N
E
S W I
T C
H Y
A
A V
O P
SWITCHYARD GRAVEL SLOPED AT 4 TO 1
OUTLINE
CONCRETE PAD
SWITCHYARD GRAVEL SLOPED AT 4 TO 1
NO SCALE
TOP OF GRADE
TOP OF CONCRETE
T
A D
E
M I
N I
M U
M
"WUNPEECE" UNDERGROUND DEVICES
SIMILAR TO "CARLON" SNAP-LOC OR
INTERVALS ALONG LENGTH OF DUCTBANK,
REBAR HOLDERS, PLACED AT 48" MAX.
MODULAR PLASTIC DUCT SPACER WITH
CONCRETE ENCASEMENT
M I
N
T Y
P
M I
N
T Y
P
MIN
TYP
2"
SCHEDULE 80 PVC DUCT
MIN
TYP
3"
M I
N
T Y
P
#4 REBAR, LONGITUDINAL ALONG DUCTBANK (TYP. OF 8)
#4 REBAR LATERAL TIE, TYP.