Solicitation Amendment 0004 - Projnet.org Questions & Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A.07.24_Solicitation_A0004_Email_From_Schneider_Provider.pdf | ||
| A.07.24_Solicitation_A0004.pdf | ||
| A.07.24_Solicitation_A0004_Average_Branson_Temperatures.pdf | ||
| A.07.24_Solicitation_A0004_Drawing.pdf | ||
| A.07.24_Solicitation_A0003.pdf | ||
| A.07.24_Solicitation_A0002.pdf | ||
| A.07.24_Solicitation_A0001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNCLASSIFIED\\FOR OFFICIAL USE ONLY
Bid Inquiry Contracting Officers Report All Inquiries
Project: Replace Generator Cables and Cooling System Review: RFI Review (00001) (sorted by CommentID ) Displaying 23 inquiries.
Id Discipline Sheet Detail Spec 7247134 Electrical 26 05 00.00 26 Page 6 26 05 00.00 26 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
USACE is asking for 2 conductors per phase of the 2750 KCMIL wire.
According to Okonite they only make 2500 and 3000 KCMIL. 2750 would be a special manufactured item.
The sales sheet list the amperage capability for the 2500 and 3000 size and extrapolating between the 2 then a 2750 should be about 1400 amps.
If installed correctly in cable tray with 2 conductors per phase that is 2800 amps, which is real close to what we calculated.
If we used 4 conductors per phase of 750 KCMIL that would give the same amperage and be MUCH easier to install and Would save a lot of money (which those savings would be passed to the USACE) in handling and labor to install.
If we value engineered this piece we could put 2 sets of 3 each conductors in each 15 inch cable tray. It would not change anything else in the project. Is this acceptable?
By: Christopher Powers; AVCOR Construction & Consulting; (5018501615). On: Dec 09 2017. Forward request by email.
1-0 Evaluation Concurred. Companies shall bid on contract as is. After award, contractor can perform a VE study and provide an analysis including calculations, drawings, and all required data for the Government to evaluate to determine if allowed. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501- 324-5597) On: Dec 15 2017
2-0 Evaluation Concurred. The cable is special order but you can get prices.
As for the changing to a different size cable, the contractor would also be required to do a heat loss study and would be required to redesign the power tunnel cooling system to meet the new heat load if the kW output is higher than the original. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501- 324-5597) On: Dec 19 2017
2-1 Government Response. Companies shall bid on contract as is. After award, contractor can perform a VE study and provide an analysis including calculations, drawings, and all required data for the Government to evaluate to determine if allowed.
The cable is special order but you can get prices.
As for the changing to a different size cable, the contractor would also be required to do a heat loss study and would be required to redesign the power tunnel cooling system to meet the new heat load if the kW output is higher than the original By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7247135 Electrical 26 05 00.00 40 26 05 00.00 40 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
The specs call for copper, but there is not a copper inflation contingency in the solicitation. There is absolutely no way to guess what the price of copper will be months after the bid date, since the prices fluctuate daily. With the amount of copper required in this project, we believe it is fair for the USACE to allot a copper inflation clause to cover the contractor for increases (and decreases) in the price of copper between the day the project is quoted and the actual time of contract award and NTP is issued. A three month delay in award could cost the contractor in the
Page 1 of 10ProjNet: Logged In User
2/2/2018https://www.projnet.org/projnet/binKornHome/index.cfm?strKornCob=BicAdminReportAll...
tens, if not hundreds of thousands for reasons outside of anyone's control. Will the USACE consider this as an option?
By: Christopher Powers; AVCOR Construction & Consulting; (5018501615). On: Dec 09 2017. Forward request by email.
1-0 Evaluation Concurred. A review has been conducted of the bls.gov Producer Price Index, Series ID WPU10260314, for the year 2017. Recent price fluctuations do not warrant inclusion of a Economic Price Adjustment clause. The clause will not be included. By: Robert Buchanan; SWL Contracting Division;
(501-340-1257) On: Feb 02 2018
1-1 Government Response. A review has been conducted of the bls.gov Producer Price Index, Series ID WPU10260314, for the year 2017. Recent price fluctuations do not warrant inclusion of a Economic Price Adjustment clause. The clause will not be included. By: Jonathan Sawrie; SWL Contracting Division; (501- 340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250082 Electrical CE-403 028213.00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Please provide product data on the existing 15KV 1000MCM cable as well as the 600V cable to be removed, to determine if asbestos is present.
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0 Evaluation Concurred. R-036 through R-044 has the details on the oil fill cables. Checking on the 600
V cables. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Dec 19
2-0 Evaluation Concurred. No asbestos survey on cables. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 24 2018
2-1 Government Response. R-036 through R-044 has the details on the oil fill cables. Checking on the 600 V cables.
No asbestos survey on cables. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250083 Electrical 028213.00 10 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Please provide detail on locations of all asbestos to be removed.
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0 Evaluation Concurred. Asbestos will be in the flange gaskets at the connection point of the water supply pipe.
Most cables in the plant have asbestos in them. It is the Contractor's responsibility to determine the best approach to remove the asbestos to reduce abatement requirements and follow the codes, and proper disposal. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 05
1-1 Government Response. Asbestos will be in the flange gaskets at the connection point of the water supply pipe.
Most cables in the plant have asbestos in them. It is the Contractor's responsibility to determine the best approach to remove the asbestos to reduce abatement requirements and follow the codes, and proper disposal. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250085 Electrical 028313.00 20 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Please provide location of Lead Based Paint or Lead to be removed as part of this project.
Page 2 of 10ProjNet: Logged In User
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0 Evaluation Concurred. On the larger piping where you connect to for the raw water supply.
The cable piping and ductwork may have lead.
Contract calls for removal but after testing, the contractor determines how. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 04 2018
1-1 Government Response. On the larger piping where you connect to for the raw water supply.
The cable piping and ductwork may have lead.
Contract calls for removal but after testing, the contractor determines how. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250090 Electrical 260513.00 26 Para. 2.2.4.4 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
We have only found one manufacture that will provide the 2,750 15KV cable, however, they cannot meet the specification requirement for cupro nickel tape metallic shield. Please provide basis of design manufacturer.
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0 Evaluation Concurred. Basis for 2750kcmil cable design: manufacturer was Okonite, they recommended using that shield material but that was based on immediate availability. Other material are feasible and could be substituted if the cable manufacturer recommends so. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Dec 15 2017
1-1 Government Response. Basis for 2750kcmil cable design: manufacturer was Okonite, they recommended using that shield material but that was based on immediate availability. Other material are feasible and could be substituted if the cable manufacturer recommends so. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250092 Electronic 260513.00 26 Para. 3.1.7 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
We have not found a manufacturer that will provide terminations for 2,750kcmil class 3 stress cone with long barrel compression lug.
Please provide basis of design manufacturer for terminations.
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0 Evaluation Concurred. Basis for termination design: that was generic, but for the contract from which the specs were adapted, the 2750kcmil terminations were provided by Tyco (lugs) and Raychem (HVT Series termination kits, 5-35kV class). By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br;
(501-324-5597) On: Dec 15 2017
1-1 Government Response. Basis for termination design: that was generic, but for the contract from which the specs were adapted, the 2750kcmil terminations were provided by Tyco (lugs) and Raychem (HVT Series termination kits, 5-35kV class). By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250097 Electrical CE-501 Note 1 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Per this note there has obviously been a large ARC Flash event in the past. Is there reason for concern that this could take place during construction of this project? Should consideration be given to de-energizing all power when workers are present in the tunnel.
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0
Page 3 of 10ProjNet: Logged In User
Evaluation Concurred. No! The causes of the arc flash incident has been eliminated. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 05 2018
1-1 Government Response. No! The causes of the arc flash incident has been eliminated. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018
1-2 Government Response. No! The causes of the arc flash incident has been eliminated. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250101 Electrical 260513.00 26 Para. 2.2.3 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Will it be acceptable to provide 4-750kcmil cables per phase in lieu of the 2750kcmil? This would allow use of standard available terminations and would result in a considerable savings to the government.
By: Larry Larsen; Citadel Electric; (8162674768). On: Dec 12 2017. Forward request by email.
1-0 Evaluation Concurred. See evaluation for 7247134 By: Joseph Maresh; SWL Mechanical/Electrical
Section - Des Br; (501-324-5597) On: Dec 15 2017 1-1 Government Response. See evaluation for 7247134 By: Jonathan Sawrie; SWL Contracting Division;
(501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250602 Environmental None None Abatement Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
1. Is there an existing Asbestos Inspection for the facility and if so can it be provided to us.
2. Is there an existing LBP inspection for the facility, and if so can it be provided to us.
3. We understand that abatement will be included on the scope of this project, and we understand that additional asbestos and LBP inspections work involving the collection of samples from suspect asbestos and LBP materials will be included in this scope as well. How are we to did this, will there be a unit costs pricing structure?
4. Is the outdoor substation the only area where Level 4 PPE is required?
5. Can equipment/materials be staged and operated in the outdoor substation area?
6. Do we need to conduct inspections for LBP and Asbestos before work begins?
7. Is there an existing asbestos survey?
8. Is there an existing LBP survey?
9. Does a LBP program need to be part of the bid?
10. Are there limitations to pictures and areas of access?
11. Is there a limit to number of personnel allowed on site?
12. Can a crew work on weekends?
13. Will and where will there be Power and water points?
14. Is the tunnel a confined space?
15. Is there a Security clearance process for personnel?
16. What are the restriction to Working in stages?
17. If there is a Crane on-site?/Do we need to operate it?
18. Is there a specific and designated Staging Area?
19. Is there a designated Area for roll-off?
20 Will there be an issue using 55 gallon drums for ACM?
21. Does the facility have a designated Decon area?
22. Are there Any other access for the tunnel area than the one we were shown?
23. Are there any other Ventilation requirements and points in the tunnel?
By: Christopher Powers; AVCOR Construction & Consulting; (5018501615). On: Dec 13 2017. Forward request by email.
1-0
Page 4 of 10ProjNet: Logged In User
Evaluation Concurred. 1. The surveys for asbestos did not include cables. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 24 2018
1-1 Government Response. 1. The asbestos survey that was performed did not deal with the cables. Old cables has had asbestos on previous contracts. Flange gaskets have asbestos as stated in contract.
2. There is no LBP inspection report.
3. The bid schedule has the pricing breakdown for asbestos. Lead abatement is included in the other bid items.
4. By our Arc Flash labels, only in substation.
5. No
6. Yes, then contractor shall prepare lead and asbestos plans that follow the proper codes.
7. See answer 1.
8. No.
9. Yes, then contractor shall prepare lead and asbestos plans that follow the proper codes.
10. Only in areas of work or access for this contract.
11. No limit.
12. Per contract language, necessity and availability of Government personnel to supervise will be major considerations.
13. Will add drawings in the amendment for water and power locations.
14. It not a confined space now but if you take down the air system you will need to check the codes and our EM-385-1-1 to verify that it is not.
15. in contract in 01 15 10.10 46.
16. Restrictions are in 01 14 00.00 46 in paragraph 1.3 including subparagraphs.
17. Bridge crane in the plant. Powerhouse personnel will operate but contractor supplies riggers and rigging. Ask to coordinate work to minimize the number of times the crane is needed.
18/19. Not at this time, it will be determined based on your work plan submittal, space needed, and other contract requirements.
20. That is for the contractor to determine as long as it follows the proper codes.
21. No.
22. No.
23. No, but cutting or producing of any fumes must be exhausted to the outside and not allowed to flow into the plant. Most of the time the plant operates under negative pressure. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018
2-0 Evaluation Concurred. 1. The asbestos survey that was performed did not deal with the cables. Old cables has had asbestos on previous contracts. Flange gaskets have asbestos as stated in contract.
2. There is no LBP inspection report.
3. The bid schedule has the pricing breakdown for asbestos. Lead abatement is included in the other bid items.
4. By our Arc Flash labels, only in substation.
5. No
Page 5 of 10ProjNet: Logged In User
6. Yes, then contractor shall prepare lead and asbestos plans that follow the proper codes.
7. See answer 1.
8. No.
9. Yes, then contractor shall prepare lead and asbestos plans that follow the proper codes.
10. Only in areas of work or access for this contract.
11. No limit.
12. Per contract language, necessity and availability of Government personnel to supervise will be major considerations.
13. Will add drawings in the amendment for water and power locations.
14. It not a confined space now but if you take down the air system you will need to check the codes and our EM-385-1-1 to verify that it is not.
15. in contract in 01 15 10.10 46.
16. Restrictions are in 01 14 00.00 46 in paragraph 1.3 including subparagraphs.
17. Bridge crane in the plant. Powerhouse personnel will operate but contractor supplies riggers and rigging. Ask to coordinate work to minimize the number of times the crane is needed.
18/19. Not at this time, it will be determined based on your work plan submittal, space needed, and other contract requirements.
20. That is for the contractor to determine as long as it follows the proper codes.
21. No.
22. No.
23. No, but cutting or producing of any fumes must be exhausted to the outside and not allowed to flow into the plant. Most of the time the plant operates under negative pressure. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Feb 01 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250683 Electrical 02 83 13 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Section 02 83 13 "Lead in Construction" is included in the specifications. What is the extent of the lead anticipated on this project for removal. Does the coating on the HPFF piping contain lead?
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Dec 13 2017.
Forward request by email.
1-0 Evaluation Concurred. During construction of the powerhouse, painting used red lead undercoat. Has never been tested. It is the Contractor's responsibility to determine best way to remove components with lead paint to minimize abatement requirements and properly dispose. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 05 2018
1-1 Government Response. During construction of the powerhouse, painting used red lead undercoat. Has never been tested. It is the Contractor's responsibility to determine best way to remove components with lead paint to minimize abatement requirements and properly dispose. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250691 Electrical 09 90 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Page 6 of 10ProjNet: Logged In User
Section 09 90 00 "Paints and Coatings" is included in the specifications. What exactly needs to be painted on this project?
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Dec 13 2017.
Forward request by email.
1-0 Evaluation Concurred. Piping that is insulated or non-insulated. Any steel that is not galvanized. By:
Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Dec 19 2017
1-1 Government Response. Piping that is insulated or non-insulated. Any steel that is not galvanized. By:
Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250696 Electrical cooling Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Should cooling piping be painted prior to insulation?
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Dec 13 2017.
Forward request by email.
1-0 Evaluation Concurred. Yes, paint the pipe. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Dec 19 2017
1-1 Government Response. Yes, paint the pipe. By: Jonathan Sawrie; SWL Contracting Division; (501-340- 1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250698 Electrical 01 22 00 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Section 01 22 00 paragraph 1.2.3.1.i. states that the contractor should furnish portable air conditioning to maintain the Power Tunnel ambient temperature at 86 degrees Fahrenheit during installation. We need to know what the average temperatures are during the spring, summer, fall months, so we know how much cooling is required.
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Dec 13 2017.
Forward request by email.
1-0 Evaluation Concurred. Will attach a temperature chart for Branson to the amendment. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 04 2018
1-1 Government Response. Will attach a temperature chart for Branson to the amendment By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7250701 Electrical M-100 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
•Drawing M-100 Note 5. The Schneider Modulating valve and actuator model #'s do not appear to match the Schneider Type Designation Guide. Please provide current model #'s or basis for design.
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Dec 13 2017.
Forward request by email.
1-0 Evaluation Concurred. Will attach cut sheet to the amendment. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 04 2018
1-1 Government Response. Will attach cut sheet to the amendment. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7279768 Contracting Solicitation Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Under the Solicitation, page 15 of 115, Tab 6 requires the "Pre-award Survey" to be submitted, which is 2 pages. Are Schedules A, B & C part of the Pre-Award Survey? If not, then where do Schedules A, B & C go in the proposal?
Page 7 of 10ProjNet: Logged In User
By: Arl Altman; A Cubed; (913-439-7225). On: Jan 15 2018. Forward request by email.
1-0 Evaluation Concurred. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Robert Buchanan; SWL Contracting Division; (501-340-1257) On: Feb 02 2018 1-1 Government Response. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7279777 Contracting Solicitation Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
On pg 21 of 115, Paragraph f.(3) - page limitation - states: "...and .d.(6) in attachment 3 above....". We found paragraph d.(6), but did not find attachment 3. Please clarify where attachment 3 is located.
By: Arl Altman; A Cubed; (913-439-7225). On: Jan 15 2018. Forward request by email.
1-0 Evaluation Concurred. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Robert Buchanan; SWL Contracting Division; (501-340-1257) On: Feb 02 2018 1-1 Government Response. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7279780 Contracting Solicitation Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Pg 31 of 115, Para. b. Subfactor 1.2: Personnel; All key personnel, must have a degree in the field of work. Please confirm what those degrees would be for each position. Does the site superintendent and QC Manager require a degree, if the site superintendent/QC Manager have 25 years of experience?
By: Arl Altman; A Cubed; (913-439-7225). On: Jan 15 2018. Forward request by email.
1-0 Evaluation Concurred. (if applicable to the position) is stated after evaluation. This means we want to know if those persons have a degree that would help to do that position. We are not asking for any specific degree. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On:
Jan 16 2018
1-1 Government Response. (if applicable to the position) is stated after evaluation. This means we want to know if those persons have a degree that would help to do that position. We are not asking for any specific degree. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7279781 Contracting Solicitation Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Pg 24 of 115, Tab 1, Personnel, does not specifically require personnel to have degrees, where as pg 31/115 Subfactor 1.2-Personnel does require a "degree". Does this mean a site superintendent can have a trade school certificate in welding and that will be considered a "degree"? Please clarify intent.
By: Arl Altman; A Cubed; (913-439-7225). On: Jan 15 2018. Forward request by email.
1-0 Evaluation Concurred. Both pages state if applicable. We are looking for someone that years of experience with continuing education toward their job. Degrees are a plus. Some trade schools are colleges and some are continuing education. Which one is this? By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 16 2018
1-1 Government Response. Both pages state if applicable. We are looking for someone that years of experience with continuing education toward their job. Degrees are a plus. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7279951 Contracting Solicitatioin Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Page 8 of 10ProjNet: Logged In User
Pg 24 of 115, Tab 1, Personnel, states "education degree(s), year, specialization, if applicable". We do not read this as requiring a degree. However, pg 31/115 Subfactor 1.2-Personnel seems to require a "degree". Clarify which Key Personnel are required to have a "degree", if any, and if that is a college degree, HS, vocational, etc.
By: Arl Altman; A Cubed; (913-439-7225). On: Jan 15 2018. Forward request by email.
1-0 Evaluation Concurred. On both pages it has the wording if applicable. We do not ask for a degree but take years of experience in place of degree. By: Joseph Maresh; SWL Mechanical/Electrical Section - Des Br; (501-324-5597) On: Jan 16 2018
1-1 Government Response. On both pages it has the wording if applicable. We do not ask for a degree but take years of experience in place of degree. By: Jonathan Sawrie; SWL Contracting Division; (501-340- 1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7280493 Contracting Solicitation Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
The 1442 requires an original and 2 copies of the proposal. Pg 13 of 115, Para. e.(1), has the requirement for Two
(2) hard copies and 2 CD ROM copies of the price proposal. Pg 21 of 115, para. f.(1) requests four(4) hard copies and 4 CD-ROM copies of the non-price proposal. Please clarify the number of copies to be submitted for the price and non-price proposals.
By: Arl Altman; A Cubed; (913-439-7225). On: Jan 16 2018. Forward request by email.
1-0 Evaluation Concurred. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Robert Buchanan; SWL Contracting Division; (501-340-1257) On: Feb 02 2018 1-1 Government Response. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7280753 Electrical CE-403 Note 7 Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
Drawing CE-403, Note 7 requires the replacement of existing seal-off feed-thru bushings, field verify and match existing. Please provide the make/model and photographs of the existing to allow an accurate quote prior to bid.
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Jan 16 2018.
Forward request by email.
1-0 Evaluation Concurred. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Robert Buchanan; SWL Contracting Division; (501-340-1257) On: Feb 02 2018
1-1 Government Response. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed
Information for this report is procurement sensitive.
7280755 Electrical Bid Date Comment Classification: Unclassified\\For Official Use Only (U\\FOUO)
No questions have been answered on projnet and the bid date is in less than two weeks. We request that the bid date be extended to at least two weeks after questions are answered.
By: Sheila Andrews; Koontz Electric Company, Inc - Morrilton, AR; (501-354-2526). On: Jan 16 2018.
Forward request by email.
1-0 Evaluation Concurred. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Robert Buchanan; SWL Contracting Division; (501-340-1257) On: Feb 02 2018
1-1 Government Response. The question period was closed on 13 Dec 2017. No further questions will be answered. By: Jonathan Sawrie; SWL Contracting Division; (501-340-1045) On: Feb 02 2018 Current Request Status: Request Closed