A.07.24_Solicitation_A0004_Email_From_Schneider_Provider.pdf
PDF 4 MB Posted
- Attached to
- Replace Generator Cables and Cooling System Federal contract opportunity
- Solicitation number
- W9127S-18-R-0008
About this file
Solicitation Amendment 0004 - Email from Schneider Provider
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A.07.24_Solicitation_A0004_Projnet_Q&A.pdf | ||
| A.07.24_Solicitation_A0004.pdf | ||
| A.07.24_Solicitation_A0004_Average_Branson_Temperatures.pdf | ||
| A.07.24_Solicitation_A0004_Drawing.pdf | ||
| A.07.24_Solicitation_A0003.pdf | ||
| A.07.24_Solicitation_A0002.pdf | ||
| A.07.24_Solicitation_A0001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Jim Lyles
From: Amy Pavell <amy.pavell@veris.com>
Sent: Wednesday, June 14, 2017 1:48 PM
To: Kaveh Ghods
Subject: RE: Control Valve
Attachments: Schneider Electric PIBCV.PDF
Hi Kaveh, Attached you will find our Schneider Electric PIBCV recommendation based on the specs you gave me. I tried finding
Belimo’s appropriate match, but there was no option for 2 ½ “ 70gpm valve so I would suggest you call Belimo directly if you would like to use their spec. You can use either but Veris is owned by Schneider, hence my push for Schneider v&a.
Schneider:
VP220A-65S-070-U231: VB: 2-1/2 in, 2W, PI, FLG, 70 gpm, 90 PSI; Act (MP500C-SRU): Elec, Prop/Float, SR, NO, 24 VAC/VDC, No leads, 500 N, Linear, I
Let me know if you have any other questions.
Thanks, Amy
From: Kaveh Ghods [mailto:KGhods@ejesinc.com]
Sent: Wednesday, June 14, 2017 9:11 AM
To: Amy Pavell Subject: Control Valve
Amy, It was great talking to you. As discussed, I would like to check and see if the model number indicated in the attached
(boxed in blue) is suitable for the following application:
“A control valve with electric actuator is required to control water flow through a 2-1/2” chilled water pipe serving a coil.
The max water flow rate is 70 gpm. The actuator is to be controlled by a temperature sensor in from of the coil.”
Thanks for your help
Kaveh Ghods, ME, PE
EJES Incorporated 12655 N Central Expy., Suite 500 | Dallas, TX 75243 TEL 214.343.1210-ex: 149 | FAX 214.343.3885
CELL 469.939.4353
kghods@ejesinc.com | www.ejesinc.com
VP228E-15BQNT+MP300
161212 - PIBCV Phase III Renderings Review
– The correct and maximum design flow ensures a high differential in supply and return temperatures to provide high operational efficiency of the chiller or boiler.
• Improved Comfort
– The SmartX PIBCV valves are not affected by other valves in the system that may be opening and closing throughout the day or other piping system disturbances providing more constant, comfortable, room temperatures.
• Reduced Pumping Costs
– A reduction in overflows through the network reduces pumping costs. A smaller pump head and equipment is required compared to traditional configurations.
• Reduced Installation Costs
– Only one valve needs to be installed rather than two or three since the SmartX PIBCV covers the pressure balancing, flow limitation and control modulation.
• Easy and quick Commissioning
– SmartX PIBCV setup time is significantly reduced with a simple and accurate flow setting procedure without the need for flow charts, calculations or measuring equipment.
• Improved Reliability
– Improved mechanical equipment reliability from reduced actuator movements.
Product Description The SmartX PIBCV range is a comprehensive selection of automatic balancing and control valves that provide flow limitation, with full control authority over hydronic regulation.
Automatic balancing within PIBCV valves provide stable flow regulation regardless of pressure fluctuations in the system and all valves have an adjustable flow limitation set point. The control valve portion of the PIBCV further regulates the water/ glycol flow from close-off up to the maximum flow limit setting.
Typical applications are temperature control of chillers, air-handling units, heat exchanges and terminal units such as fan coils, induction units and radiant panels.
Features
• Reduced Energy Consumption
– Pressure independence ensures no overflow of water/ glycol through the valve. Limiting water/glycol flow to the design load of the coil has a significant effect on energy efficiency since systems operate for the majority of the time on a partial load.
– The overflow of water/glycol causes a degradation in heat transfer at the heat exchanger. Uncontrolled overflow of water/glycol beyond the design flow of the heat exchanger is an extremely wasteful and inefficient use of heat.
actuators are
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc Document Number: F-27947-1 www.schneider-electric.com schneider-electric.com | 1Selection Guide
SmartX PIBCV ½"…10" Pressure Independent Balancing and Control Valve Assemblies
Contents 2 Theory 2 Applications 3 Control Performance
3 Easy Implementation 3 Valve Assembly Part Number System 3 Flow Direction 4 SmartX PIBCV Selection Overview 4 1: Complete Method: Valve Assembly Selection 4 2. Custom Method: Valve Body and Actuator Field Assembly
4 3. Valve Body Only: Automatic Flow Limited Balance Example 5 PIBCV Flow Setting
5 ½…1¼" Size Valves 5 PIBCV Flow Setting 5"…10" 5 PIBCV Flow Setting 1½"…4"
6 Valve Assembly and Suitable Actuators 6 Table 1. Valve Assemblies ½…1¼” With Female NPT End
Connectors, Without PT Ports 7 Table 2. Valve Assemblies ½…1¼” With Female NPT End
Connectors, With PT Ports 7 Table 3. Specification ½…1¼” Valve Body Actuators 8 Table 4. Valve Assemblies 1½”…2” With Female NPT End
Connectors, With PT Ports 8 Table 5. Valve Assemblies 2½"…4” with ANSI Standard B16.1
Flanges, With PT Ports 9 Table 6. Specification 1½”…4” Valve Body Actuators 9 Table 7. Valve Assemblies 5”…6” With PT Ports with ANSI
Standard B16.1 Flanges 9 Table 8. Specification 5”…6” Valve Body Actuators 10 Table 9. Valve Assembly 8”…10” With PT Ports with ANSI
Standard B16.1 Flanges 10 Table 10. Specification 8”…10” Valve Body Actuators 10 Table 11. Application: Operation of PIBCV Valve Body Without
Actuator 11 Technical Data
11 Table 12. Specification Threaded Version, ½…2" 12 Table 13. Specification Flange Version, 2½"…4" 12 Table 14. Specification Flange Version, 5"…10" 13 Table 15. Assembly Valve Body Configurations
14 Table 16. Selection: Valve Actuator Codes 14 Table 17. Selection: ½"…2" Valve Body Tail Pieces 15 Dimensions
15 Threaded Valves 1½"…2" (inches) 16 Flanged Valves 2½"…4" 17 Flanged Valves 5"…6" 17 Flanged Valves 8"…10" 20 Specification Submittal Text
SmartX PIBCV Summary SmartX PIBCV valves and Actuators can be used with actuators for pressure independent balancing and control applications or without actuators for automatic flow limiting balance applications.
PIBCVs immediately react to all changes in system pressures, providing stable valve control independent from the fluctuating pressures in the piping system. No valve authority, pressure calculations or complicated valve flow setting calculations are required. At partial system load there is no resulting overflow because the valve always limits the flow corresponding to the design flow of the coil.
SmartX PIBCV valves with actuators include an integrated control valve with flow regulation for HVAC applications, plus an automatic flow limiting function for energy efficiency. A full range of Schneider Electric actuators are available for every control application including two position, proportional, floating, spring return open, spring return close, and non-spring return.
Applications Variable flow systems: A SmartX PIBCV with a Schneider Electric actuator is used as a control valve for terminal units, like an AHU (Air Handling Unit), FCU (Fan Coil Unit) or radiation panel, and controls the required flow on every terminal unit maintaining hydronic balance in the system.
Constant flow systems: There are numerous applications in which SmartX PIBCV can be used. In a constant flow system with FCUs or in a one pipe heating system, SmartX PIBCVs can be installed as an automatic balancing valve in every riser.
SmartX PIBCVs limit the flow to the set value, thus automatically achieving hydronic balance. Whenever an automatic flow limiter or a control valve is needed, the advantages of cost-saving properties are inherent with SmartX PIBCVs. This includes systems with (floor) heating/cooling, concrete core activation or radiation panels.
Air handling unit (AHU) Radiation panel
2 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Document Number: F-27947-1
Control Performance SmartX PIBCV actuators can be used to change the flow response from linear to logarithmic (equal percentage).
This makes the SmartX PIBCV suitable for all applications, including AHUs, where the equal percentage characteristic is needed to get a stable control loop. The actuators can be switched from linear to equal percentage by changing a dipswitch setting.
Easy Implementation
• No Cv or authority calculations needed. Flow is the only parameter to be considered when designing.
• Compact design, essential when only limited space is available such as in fan-coil units.
• Easy commissioning and troubleshooting. No specialized staff or measuring equipment needed.
• Trouble-free segmentation of the building project. SmartX
PIBCVs will automatically control the flow, even when sections of the installation are unfinished. There is no requirement to re-adjust the SmartX PIBCV flow setting after finalization of the building project.
V P 2 2 8 E - 1 5 L N - L 1 0 - F 1 0 1
Valve
Pressure Independent
2 Way
2 = Linear Flow Curve
8 = M30 Short Stroke 9 = M30 Long Stroke
0 = U Bolt Medium Stroke 1 = Long Stroke 2 = Long Stroke
E = External Threads A = ANSI Flanges
Actuator Code
Actuator Input Signal A = On/Off (Two Position) B = BACnet F = Floating S = Proportional U = Universal (Proprtional & Floating)
Flow Rate in GPM L = Flow Rate Less Than 10 GPM (Divide Number by 10) No L = Actual Flow Rate in GPM
N = Does not have PT Ports No N = Does have PT Ports
Body Flow Rate L = Low Flow S = Standard Flow H = High Flow
Orifice Size (mm)
Valve Assembly Part Number System
LI
N se ttin g st ay s c on sta nt at a ny av ail ab le pre ss ur e
LOG setting stays consta nt at a ny a va ila bl e pr es su re
0 10 V
100%
Fo r an y g iv en s et tin g
Flow Direction A SmartX PIBCV valve is mono-directional, meaning the valve operates when the arrow on the valve body is aligned with the flow direction. When this rule is ignored, the valve acts as a variable orifice that causes water/glycol hammer at sudden closing when available pressure has increased, or the valve has been set to a lower value.
In the case when a system condition allows backflows, it is strongly recommended to use a backflow preventer in order to avoid possible water/glycol hammer that can damage the valve as well as other elements in the system.
It is recommended to fit a strainer upstream of the valve to in-crease reliability and to follow water/glycol treatment guidelines as detailed in VDI 2035.
The pipework system should be flushed prior to the operation.
Theory The SmartX PIBCV valve consists of two parts:
1. Differential Pressure Controller
2. Control Valve
1. Differential Pressure Controller (PC)
The differential pressure controller maintains a constant differential pressure across the control valve. The pressure difference is balanced so that when the differential pressure across the control valve changes (due to a change in avail-able pressure, or movement of the control valve) the pressure regulator automatically aligns to a new position. This brings a new equilibrium and therefore keeps the differential pressure at a constant level.
2. Control Valve (CV)
The control valve has a linear characteristic. It features a stroke limitation that allows adjustment of the value. The maximum flow allowed by the control valve can be adjustable to a per-centage of the valve's maximum flow rate.
schneider-electric.com | 3Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
SmartX PIBCV Selection Options There are three methods for selecting SmartX PIBCV valves and Actuators:
1: Complete Method: Valve Assembly Selection
2. Custom Method: Valve Body and Actuator Field Assembly
3. Valve Only Method: Automatic Flow Limited Balance
1: Complete Method: Valve Assembly Selection To select a PIBCV valve assembly select the required flow rate and actuator type. For example, to select a PIBCV valve assembly with a flow rate of 1.5 GPM and a non-spring return proportional actuator refer to Table 1. Valve Assemblies ½…1¼” With Female NPT End Connectors, Without PT Ports on page 6.
Select the 1.5 GPM flow rate with the left column of the table.
Select the actuator from the top row of the table.
The intersecting valve assembly part number from the left column and top row selections shows VP228E-15SN-L15-S101 which includes the set 1.5 GPM flow rate, installed actuator, female NPT end connectors, and metal tag with flow rate.
Specifications for the selected valve body actuators are in Table 3. Specification ½…1¼” Valve Body Actuators on page 7 and for the valve body in Table 12. Specification Threaded Version, ½…2" on page 11.
2. Custom Method: Valve Body and Actuator Field Assembly Select the individual parts then set the flow rate and field assemble a valve assembly.
Table 12. Specification Threaded Version, ½…2" on page 11 shows the valve body specifications and Table 23. ½…2” Valve Flow Ranges (Qmin to Qnom) on page 18, and Table 24.
2½”…10” Flanged Valve Flow Ranges (Qmin to Qnom) on page 19, show the valve body flow rate ranges.
For example, to select a valve body that can be used in the flow rate range of 1 to 2 GPM, from Table 23. ½…2” Valve Flow Ranges (Qmin to Qnom) on page 18, select the VP-228E- 15BQSNT valve body that does not include PT ports, or select the VP-228E-15BSQ valve body if PT Ports are required.
Other larger valves could also provide the 1 to 2 GPM flow rates, but the VP-228E-15BQSNT was selected because it will be using a higher percentage of its flow range (in general, best accuracy is achieved when a higher percentage of flow rate is used).
The ½” to 2” PIBCV valves use convenient valve body tail pieces for connection to the piping system.
From Table 17. Selection: ½"…2" Valve Body Tail Pieces on page 14, select the desired ½” tail piece – part number 9112108015 for Female NPT, 9112110015 for Male NPT, or 9112109015 for Sweat. Each tail piece part number includes two tail pieces.
Table 3. Specification ½…1¼” Valve Body Actuators on page 7 shows the compatible actuators.
Select the MP131-24T for two position control, the MP131-24F for floating control, the MP-131-24MP for proportional control, the MP300-SRU for spring return open universal control, or the MP300-SRD for spring return close universal control. Universal control actuators provide both proportional and floating input functionality. The valve body flow can easily be set before the actuator is installed as shown in the PIBCV Flow Setting on page 5.
3. Valve Body Only: Automatic Flow Limited Balance Example PIBCV valves can be used without actuators to limit the circuit flow to an adjustable flow rate.
Table 12. Specification Threaded Version, ½…2" on page 11 shows the valve body specifications and Table 23. ½…2” Valve Flow Ranges (Qmin to Qnom) on page 18 and Table 24.
2½”…10” Flanged Valve Flow Ranges (Qmin to Qnom) on page 19 show the valve body flow rate ranges.
For example, to select a valve body that can be used in the flow rate range of 2 to 5 GPM from Table 23 select the VP229E- 15BQHNT valve body part number. The ½” to 2” PIBCV valves use convenient valve body tail pieces for connection to the piping system.
From Table 17. Selection: ½"…2" Valve Body Tail Pieces on page 14, select the desired ½” tail piece: part number 9112108015 for Female NPT, 9112110015 for Male NPT, or 9112109015 for Sweat. Each tail piece part number includes two tail pieces.
The 1-½" and larger sized valves require a stem lock when used without an actuator as shown in Table 11. Application:
Operation of PIBCV Valve Body Without Actuator on page 10 (which also shows application information for the valve bodies without actuators). The valve body flow can easily be set as shown in the PIBCV Flow Setting Section.
4 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
2 43
PIBCV Flow Setting
½…1¼" Size Valves The calculated flow can be adjusted easily without using spe-cial tools. To change the presetting (factory setting is 100% for separately purchased PIBCV valve bodies) follow the four steps below:
1 Remove the black protective cover or the mounted actuator.
2 Raise the green pointer.
3 Turn (clock wise to decrease) to the new presetting.
4 Press the pointer back into the lock position. After the pointer is clicked back into place the presetting is locked.
The presetting scale indicates values from 100% flow to 20%.
Clock wise turning would decrease the flow value while counter clock wise would increase it.
Example: VP229E-15HN With this ½" valve the nom flow = 5 gal/min = 100% presetting.
To set a flow of 4 gal/min you have to set: 4/5 = 80%.
Schneider Electric recommends a presetting/flow from 20% to 100%.
To set a PIBCV valve to a Qhigh setting above 100%, turn the green pointer counter clock wise from 100%. The Qhigh setting is the scale setting plus 90%. For example, to set the VP229E- 15HN to a flow rate of 5.5 gal/min, set 5.5/5.0 = 110% setting.
Obtain the 110% setting by turning the green pointer counter clock wise from 100% to 20% (20% and 90% = 110%). As shown on page 11, Qhigh settings above 100% slightly in-crease the valve’s required minimum differential pressure.
PIBCV Flow Setting 1½"…4"
Note: 1 turn = 10%
Max 25Nm
PIBCV Flow Setting 5"…10"
Note:
1 turn = 5%
Setting 60% schneider-electric.com | 5Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Valve Assembly and Suitable Actuators
Table 1. Valve Assemblies ½…1¼” With Female NPT End Connectors, Without PT Ports Flow Rate (GPM)a
Valve Size (inch)
24 Vac Two Position with Auxiliary Switch (MP131-24T)
24 Vac Three Wire Floating with Auxiliary Switch
(MP131-24F)
24 Vac Proportional with Position Output Signal
(MP131-24MP)
24 Vac Proportional/Floating with Position Output Signal Spring Return Open (MP300-SRU)
24 Vac Proportional/Floating with Position Output Spring Return Closed
(MP300-SRD)
MP131 +
VP228E / VP229E0.5 1/2 VP228E-10LN-L05-A101 VP228E-10LN-L05-F101 VP228E-10LN-L05-S101 VP228E-10LN-L05-U201 VP228E-10LN-L05-U301
1.0 1/2 VP228E-15LN-L10-A101 VP228E-15LN-L10-F101 VP228E-15LN-L10-S101 VP228E-15LN-L10-U201 VP228E-15LN-L10-U301
1.5 1/2 b VP228E-15SN-L15-F101 VP228E-15SN-L15-S101 VP228E-15SN-L15-U201 VP228E-15SN-L15-U301
2.0 1/2 VP228E-15SN-L20-A101 VP228E-15SN-L20-F101 VP228E-15SN-L20-S101 VP228E-15SN-L20-U201 VP228E-15SN-L20-U301
2.5 1/2 b VP229E-15HN-L25-F101 VP229E-15HN-L25-S101 VP229E-15HN-L25-U201 VP229E-15HN-L25-U301
3.0 1/2 b VP229E-15HN-L30-F101 VP229E-15HN-L30-S101 VP229E-15HN-L30-U201 VP229E-15HN-L30-U301
3.5 1/2 b VP229E-15HN-L35-F101 VP229E-15HN-L35-S101 VP229E-15HN-L35-U201 VP229E-15HN-L35-U301
4.0 1/2 b VP229E-15HN-L40-F101 VP229E-15HN-L40-S101 VP229E-15HN-L40-U201 VP229E-15HN-L40-U301
4.0 3/4 VP228E-20SN-L40-A101 VP228E-20SN-L40-F101 VP228E-20SN-L40-S101 VP228E-20SN-L40-U201 VP228E-20SN-L40-U301
4.5 1/2 b VP229E-15HN-L45-F101 VP229E-15HN-L45-S101 VP229E-15HN-L45-U201 VP229E-15HN-L45-U301
5.0 1/2 VP229E-15HN-L50-A101 VP229E-15HN-L50-F101 VP229E-15HN-L50-S101 VP229E-15HN-L50-U201 VP229E-15HN-L50-U301
5.5 3/4 b VP229E-20HN-L55-F101 VP229E-20HN-L55-S101 VP229E-20HN-L55-U201 VP229E-20HN-L55-U301
6.0 3/4 b VP229E-20HN-L60-F101 VP229E-20HN-L60-S101 VP229E-20HN-L60-U201 VP229E-20HN-L60-U301
6.5 3/4 b VP229E-20HN-L65-F101 VP229E-20HN-L65-S101 VP229E-20HN-L65-U201 VP229E-20HN-L65-U301
7.0 3/4 b VP229E-20HN-L70-F101 VP229E-20HN-L70-S101 VP229E-20HN-L70-U201 VP229E-20HN-L70-U301
7.5 3/4 VP229E-20HN-L75-A101 VP229E-20HN-L75-F101 VP229E-20HN-L75-S101 VP229E-20HN-L75-U201 VP229E-20HN-L75-U301
7.5 1 VP229E-25SN-L75-A101 VP229E-25SN-L75-F101 VP229E-25SN-L75-S101 VP229E-25SN-L75-U201 VP229E-25SN-L75-U301
8 1 b VP229E-25HN-L80-F101 VP229E-25HN-L80-S101 VP229E-25HN-L80-U201 VP229E-25HN-L80-U301
8.5 1 b VP229E-25HN-L85-F101 VP229E-25HN-L85-S101 VP229E-25HN-L85-U201 VP229E-25HN-L85-U301
9.0 1 b VP229E-25HN-L90-F101 VP229E-25HN-L90-S101 VP229E-25HN-L90-U201 VP229E-25HN-L90-U301
9.5 1 b VP229E-25HN-L95-F101 VP229E-25HN-L95-S101 VP229E-25HN-L95-U201 VP229E-25HN-L95-U301
10 1 b VP229E-25HN-010-F101 VP229E-25HN-010-S101 VP229E-25HN-010-U201 VP229E-25HN-010-U301
11 1 b VP229E-25HN-011-F101 VP229E-25HN-011-S101 VP229E-25HN-011-U201 VP229E-25HN-011-U301
12 1 VP229E-25HN-012-A101 VP229E-25HN-012-F101 VP229E-25HN-012-S101 VP229E-25HN-012-U201 VP229E-25HN-012-U301
13 1¼ b VP229E-32SN-013-F101 VP229E-32SN-013-S101 VP229E-32SN-013-U201 VP229E-32SN-013-U301
14 1¼ VP229E-32SN-014-A101 VP229E-32SN-014-F101 VP229E-32SN-014-S101 VP229E-32SN-014-U201 VP229E-32SN-014-U301
15 1¼ b VP229E-32HN-015-F101 VP229E-32HN-015-S101 VP229E-32HN-015-U201 VP229E-32HN-015-U301
16 1¼ b VP229E-32HN-016-F101 VP229E-32HN-016-S101 VP229E-32HN-016-U201 VP229E-32HN-016-U301
17 1¼ VP229E-32HN-017-A101 VP229E-32HN-017-F101 VP229E-32HN-017-S101 VP229E-32HN-017-U201 VP229E-32HN-017-U301
a. Factory set. Complete flow ranges shown in tables for 1/2…2" on page 11 and page 18.
b. Field adjust the next available higher flow rate part number.
MP300-SRU
6 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Flow Rate (GPM)a
Valve Size (inch)
24 Vac Two Position with Auxiliary Switch (MP131-24T)
24 Vac Three Wire Floating with Auxiliary Switch
(MP131-24F)
24 Vac Proportional with Position Output Signal
(MP131-24MP)
24 Vac Proportional/Floating Spring Return Open (MP300-SRU)
24 Vac Proportional/Floating Spring Return Closed (MP300-SRD)
0.5 1/2 VP228E-10L-L05-A101 VP228E-10L-L05-F101 VP228E-10L-L05-S101 VP228E-10L-L05-U201 VP228E-10L-L05-U301
1.0 1/2 VP228E-15L-L10-A101 VP228E-15L-L10-F101 VP228E-15L-L10-S101 VP228E-15L-L10-U201 VP228E-15L-L10-U301
1.5 1/2 b VP228E-15S-L15-F101 VP228E-15S-L15-S101 VP228E-15S-L15-U201 VP228E-15S-L15-U301
2.0 1/2 VP228E-15S-L20-A101 VP228E-15S-L20-F101 VP228E-15S-L20-S101 VP228E-15S-L20-U201 VP228E-15S-L20-U301
4.0 3/4 VP228E-20S-L40-A101 VP228E-20S-L40-F101 VP228E-20S-L40-S101 VP228E-20S-L40-U201 VP228E-20S-L40-U301
7.5 1 VP229E-25S-L75-A101 VP229E-25S-L75-F101 VP229E-25S-L75-S101 VP229E-25S-L75-U201 VP229E-25S-L75-U301
14 1¼ VP229E-32S-014-A101 VP229E-32S-014-F101 VP229E-32S-014-S101 VP229E-32S-014-U201 VP229E-32S-014-U301
Table 3. Specification ½…1¼” Valve Body Actuators 1/2” to 1¼” Valve Body Actuator Part Number
(actuator code)
MP131-24T
(A101)
MP131-24F
(F101)
MP131-24MP
(S101)
MP300-SRU
(U201)
MP300-SRD
(U301)
Input Signal Two Position, 3 Wire with selectable input jumper signal action selection
Three Wire Floating
Proportional, 0…10 Vdc, 2…10 Vdc, 4…20 mA, sequencing with selectable input signal ac-tion, DIP switch selectable
Proportional, 0…10 Vdc, 2…10 Vdc, 4…20 mA, sequencing with selectable input signal action and Floating, DIP switch selectable
Electrical Connection Screw terminal with conduit connector
Position Feedback Output Signal
– – 0…10 Vdc 0…10 Vdc, 2…10 Vdc
Spring Return – – – Open Valve Close Valve
Auxilary Switch Yes Yes – – –
Other Features – – Weekly anti blocking selection, auto calibration, LED indication
Valve stroke length selection, LED indication
Linear/Equal% Valve Flow Curve Selection
– – Yes Yes
Actuator Speed s/mm 60 Hz (50 Hz)
10 (12) 20 (24) 11.7 (14)
Power Consumption 1 VA 1.5 VA 9 VA
Actuator Weight (lb.) .9 2.0 1.3
Operating Temperature Limits °F (°C)
32…131 (0…55)
Regulatory Compliance cULus according to UL 60730-1A/-2-14 and CAN/CSA E60730-1/-2-14 and CE according to EN 60730-1/-2-14 per EMC [2014/30/EU] and LVD [2014/35/EU]
Specification Data Sheet F-27961 F-27961 F-27961 F-27962
Installation Data sheet F-27938 F-27949 F-27948 F-27954
All actuators are 24 Vac. 50/60 HZ with removable conduit connector plate and wiring terminal block, manual override
Table 2. Valve Assemblies ½…1¼” With Female NPT End Connectors, With PT Ports
a. Factory set. Complete flow ranges shown in tables for 1/2…2" on page 11 and page 18.
b. Field adjust the next available higher flow rate part number.
MP300-SRU
schneider-electric.com | 7Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Table 4. Valve Assemblies 1½”…2” With Female NPT End Connectors, With PT Ports
Flow Rate (GPM)a
Valve Size (inch)
24 Vac Proportional with Position Output Signal
(MP500C)
24 Vac Proportional/Floating with Position Output Signal Spring Return Open
(MP500C-SRU)
24 Vac Proportional/Floating with Position Output Spring Return Closed
(MP500C-SRD)
18 1½ VP220E-40S-018-U131 VP220E-40S-018-U231 VP220E-40S-018-U331
19 1½ VP220E-40S-019-U131 VP220E-40S-019-U231 VP220E-40S-019-U331
20 1½ VP220E-40S-020-U131 VP220E-40S-020-U231 VP220E-40S-020-U331
22 1½ VP220E-40S-022-U131 VP220E-40S-022-U231 VP220E-40S-022-U331
24 1½ VP220E-40S-024-U131 VP220E-40S-024-U231 VP220E-40S-024-U331
26 1½ VP220E-40S-026-U131 VP220E-40S-026-U231 VP220E-40S-026-U331
28 1½ VP220E-40S-028-U131 VP220E-40S-028-U231 VP220E-40S-028-U331
30 1½ VP220E-40S-030-U131 VP220E-40S-030-U231 VP220E-40S-030-U331
32 1½ VP220E-40S-032-U131 VP220E-40S-032-U231 VP220E-40S-032-U331
34 2 VP220E-50S-034-U131 VP220E-50S-034-U231 VP220E-50S-034-U331
36 2 VP220E-50S-036-U131 VP220E-50S-036-U231 VP220E-50S-036-U331
38 2 VP220E-50S-038-U131 VP220E-50S-038-U231 VP220E-50S-038-U331
40 2 VP220E-50S-040-U131 VP220E-50S-040-U231 VP220E-50S-040-U331
44 2 VP220E-50S-044-U131 VP220E-50S-044-U231 VP220E-50S-044-U331
48 2 VP220E-50S-048-U131 VP220E-50S-048-U231 VP220E-50S-048-U331
52 2 VP220E-50S-052-U131 VP220E-50S-052-U231 VP220E-50S-052-U331
a. Factory set. Complete flow ranges shown in tables for 1/2…2" on page 11 and page 18.
Flow Rate (GPM)a
Valve Size (inch)
24 Vac Proportional with Position Output Signal (MP500C) 24 Vac Proportional/Floating with Position Output
Signal Spring Return Open
(MP500C-SRU)
24 Vac Proportional/Floating with Position Output Signal Spring Return Closed (MP500C-SRD)
56 2½ VP220A-65S-056-U131 VP220A-65S-056-U231 VP220A-65S-056-U331
60 2½ VP220A-65S-060-U131 VP220A-65S-060-U231 VP220A-65S-060-U331
65 2½ VP220A-65S-065-U131 VP220A-65S-065-U231 VP220A-65S-065-U331
70 2½ VP220A-65S-070-U131 VP220A-65S-070-U231 VP220A-65S-070-U331
75 2½ VP220A-65S-075-U131 VP220A-65S-075-U231 VP220A-65S-075-U331
80 2½ VP220A-65S-080-U131 VP220A-65S-080-U231 VP220A-65S-080-U331
90 3 VP220A-80S-090-U131 VP220A-80S-090-U231 VP220A-80S-090-U331
100 3 VP220A-80S-100-U131 VP220A-80S-100-U231 VP220A-80S-100-U331
165 (min. 66) 4 VP220A-100S-165-U131 VP220A-100S-165-U231 VP220A-100S-165-U331
Table 5. Valve Assemblies 2½"…4” with ANSI Standard B16.1 Flanges, With PT Ports
a. Factory set. Complete flow ranges shown in tables for 2-½"…4" on page 12 and page 19.
8 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
1½”…4” Valve Body Actuator Part Number (actuator code)
MP500C
(U131)
MP500C-SRU
(U231)
MP500C-SRD
(U331)
Input Signal Proportional, 0…10 Vdc, 2…10 Vdc, 4…20 mA, sequencing with selectable input signal action and Floating, DIP switch selectable
Electrical Connection Screw terminal with conduit connector
Position Feedback Output Signal 2…10 Vdc 2…10 Vdc, 0…5 Vdc
Spring Return – Open Valve Close Valve
Auxilary Switch Optional Module
Other Features Auto calibration, field selectable floating input signal travel time, powered manual override
Auto calibration, field selectable floating input signal travel time
Linear/Equal% Valve Flow Curve Selection Yes Yes
Actuator Speed Full Stroke 60 Hz (50 Hz)
Proportional 15 (15) Floating 60 or 300 (60 or 300)
Proportional 15 (15) Floating 60 or 300 (60 or 300) Spring Return 13 (13)
Power Consumption Running 15 VA, Transformer Sizing 50 VA Running 30 VA, Transformer Sizing 50 VA
Operating Temperature Limits °F (°C) 14…122 (-10…50)
Actuator Weight (lb.) 4.0 6.0
Regulatory Compliance Underwriters Laboratory (E9429) compliance as Temperature Indicating & Regulatory Equipment cULus LISTED per UL873 and Canadian Standard C22.2 No. 24. European Community compliance per EMC directive (2014/30/EU) and LVD directive (2014/35/EU). Australian/New Zealand community RCM mark.
Specification Data Sheet F-27944 F-27945
Installation Data sheet F-27942 F-27943
All actuators are 24 Vac. 50/60 HZ with conduit connector holes and wiring terminal block, manual override
Table 6. Specification 1½”…4” Valve Body Actuators
Flow Rate (GPM) a
Valve Size (inch)
24 Vac Proportional with Position Output Signal
(MP2000-NSR)
24 Vac Proportional/Floating with Position Output Signal Spring Return Open (MP2000-SRU)
24 Vac Proportional/Floating with Position Output Spring Return Closed (MP2000-SRD)
395 (min. 158) 5 VP220A-125S-395-U161 VP220A-125S-395-U261 VP220A-125S-395-U361
485 (min. 194) 5 VP220A-125H-485-U161 VP220A-125H-485-U261 VP220A-125H-485-U361
640 (min. 256) 6 VP220A-150S-640-U161 VP220A-150S-640-U261 VP220A-150S-640-U361
830 (min. 332) 6 VP220A-150H-830-U161 VP220A-150H-830-U261 VP220A-150H-830-U361
Table 7. Valve Assemblies 5”…6” With PT Ports with ANSI Standard B16.1 Flanges
5”…6” Valve Body Actuator Part Number (actuator code)
MP2000-NSR (U161) MP2000-SRU (U261) MP2000-SRD (U361)
Input Signal Proportional, 0…10 Vdc, 2…10 Vdc, 0…20 mA, 4…20 mA, with selectable input signal action and Floating, DIP swtich selectable
Electrical Connection Screw terminal with conduit connector
Position Feedback Output Signal 0…10 Vdc, 2…10 Vdc, 0…20 mA, 4…20 mA a
Spring Return – Open Valve Close Valve
Auxilary Switch Yes
Other Features Auto calibration, 3-color LED indication, powered manual override, configurable position outpout signals, selectable speed, adjustable equal percentage flow curve
Linear/Equal% Valve Flow Curve Selection
Yes
Actuator Speed s/mm 60 Hz (50 Hz) 4 or 6 (4 or 6)
Power Consumption 14.4 VA 19.2 VA
Operating Temperature Limits °F (°C) 14…122 (-10…50)
Actuator Weight (lb.) 13.0 21.0
Regulatory Compliance cULus according to UL 60730-1A/-2-14 and CAN/CSA E60730-1/-2-14 and CE according to EN 60730-1/-2-14 per EMC [2014/30/EU] and LVD [2014/35/EU]
Specification Data Sheet F-27969
Installation Data sheet F-27956
a. When used with a proportional input signal. All actuators are 24 Vac. 50/60 HZ with conduit connector holes and wiring terminal block, manual override
Table 8. Specification 5”…6” Valve Body Actuators
a. Factory set. Complete flow ranges shown in tables for 5"…6" on page 12 and page 19.
schneider-electric.com | 9Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Table 9. Valve Assembly 8”…10” With PT Ports with ANSI Standard B16.1 Flanges
Table 10. Specification 8”…10” Valve Body Actuators
Table 11. Application: Operation of PIBCV Valve Body Without Actuator
Operation of the PIBCV valve body without an actuator for an automatic flow limiting balancing application.
Flow Rate (GPM)
* Valve Size
(inch) 24 Vac Proportional with Position
Output Signal (MP4000)
880 (min. 352) 8 VP222A-200S-880-U181
1188 (min. 475) 8 VP222A-200H-1188-U181
1320 (min. 528) 10 VP222A-250S-1320-U181
1630 (min. 652) 10 VP222A-250H-1630-U181
* Factory set. Complete flow ranges shown in tables for 8"…10" on page 12 and page 19.
8"…10" Valve Body Actuator Part Number (actuator code) MP4000 (U181)
Input Signal Proportional, 0…10 Vdc, 2…10 Vdc, 0…20 mA, 4…20 mA, with selectable input signal action and Floating, DIP swtich selectable
Electrical Connection Screw terminal with conduit connector
Position Feedback Output Signal 0…10 Vdc, 2…10 Vdc, 0…20 mA, 4…20 mA a
Spring Return –
Auxilary Switch Yes
Other Features Auto calibration, LED indication, powered manual override, adjustable speed
Linear/Equal% Valve Flow Curve Selection Yes
Actuator Speed s/mm 60Hz (50 Hz) 3 or 6 (3 or 6)
Power Consumption 35 VA
Operating Temperature Limits °F (°C) 32…131 (0…55)
Actuator Weight (lb.) 19
Regulatory Compliance cULus according to UL 60730-1A/-2-14 and CAN/CSA E60730-1/-2-14 and CE according to EN 60730-1/-2-14 per EMC [2014/30/EU] and LVD [2014/35/EU]
Specification Data Sheet F-27971
Installation Data sheet F-27958
a. When used with a proportional input signal.
All actuators are 24 Vac. 50/60 HZ with conduit connector holes and wiring terminal block, manual override.
PIBCV Valve Size Valve Body Series Valve Stem Lock Part Number Recommended Installation and Valve Shut Off Capability
1/2”…1-1/4” VP228E-xxxxxxx, VP229E-xxxxxxx Use black cap provided with VP228E-xxxxxxx or
VP229E-xxxxxxx valve body
Install valve in the supply water pipe for best shutoff valve performance. To shutoff valve tighten black cap (max. close off pressure is 14.5 psi). To shut off against a higher differential pressure set the valve flow to 0%.
1-1/2”…2” VP220E-xxxxx
9114070000 (not included with valve body)
Install valve in either the supply or return water pipe. To shutoff valve tighten bottom knob (max. close off pressure is 232 psi)
2-1/2”…4” VP220A-xxxxx Install valve in either the supply or return water pipe. To shutoff valve tighten bottom insert with a 8 mm allen wrench (max. close off pressure is 232 psi)
5”…6” VP221A-xxxxxx 9114071000 (not included with valve body) No shut off knob, set the valve to a 0% flow setting to shutoff flow
8”…10” VP222A-xxxxx 9114072000 (not included with valve body)
The 9114070000, 9114071000, and 9114072000 Valve Stem Locks are secured to the valve body with a 10 mm allen wrench.
See Table 15. Assembly Valve Body Configurations on page 13 for a listing of all PIBCV valve body part numbers.
10 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Technical Data
Table 12. Specification Threaded Version, ½…2"
Valve Size 1/2" 3/4" 1" 1¼" 1½" 2"
Valve Assembly Part Number without PT Ports 1)
VP228E
-10LN-
VP228E
-15LN-
VP228E
-15SN-
VP229E
-15HN-
VP228E
-20SN-
VP229E-
20HN-
VP229E
-25SN-
VP229E-
25HN-
VP229E-
32SN-
VP229E-
32HN-
Valve Assembly Part Number with PT Ports 1)
VP228E
-10L-
VP228E
-15L-
VP228E
-15S-
VP228E
-20S-
VP229E
-25S-
VP229E-
32S-
VP220E-
40S-
VP220E-
50S-
Flow range
Qmin gal/min
.13 .24 .4 1 .8 1.5 1.5 2.4 2.82 3.5 13.2 22
Qnom (100%)2)
.66 1.2 2 5 4 7.5 7.5 12 14.1 17.5 33 55
Qhigh .79 1.45 2.4 5.5 4.75 8.25 8.2 13.2 15.5 19.25 33 55
Setting range 3) % 20-120% 20-110% 20-120% 20-110% 40-100%
Diff.
pres-sure 4), 5)
∆pQnom
(∆pQhigh) psi [kPa]
2.32-58 (2.61-58) [16-400
(18-400)]
5-58 (5.8- 58)
[35-400 (40-400)]
2.32-58 (2.61-58) [16-400
(18-400)]
5-58 (5.8- 58)
[35-400 (40-400)]
2.9-58 (3.63-58) [20-400
(25-400)]
5-58 (5.8-58) [35-400
(40-400)]
2.9-58 (3.63-58) [20-400
(25-400)]
5-58 (5.8-58) [35-400
(40-400)]
4.35-58 [30-400]
Stroke Qnom in. (mm) 0.09 (2.25) .157 (4) 0.09 (2.25) .157 (4) .177 (4.5) .39 (10)
Connection ext. thread
(ISO
228/1) G ½ A G ¾ A G 1 A G 1¼ A G 1½ A G 2 A G 2½ A actuators MP131-24T, MP131-24F, MP131-24MP, MP300-SRU, MP300-SRD
MP500C,
MP500C-SRU/SRD
Body Pressure Rating psi EN 12516-2:2004, 250 psi, PN 16
Leakage acc. to standard IEC 60534
Class 4, max. 0.01% of Qnom 0.05% of Qnom
Max. close off differential pressure across the valve
90 psi
Control range Acc. to standard IEC 60534 control range is high as flow characteristic is linear (1:1000)
Control valve’s characteristic Stem up open, Linear (can be converted by actuator to equal percentage)
For shut off function Acc. to ISO 5208 class A - no visible leakage
Flow medium Water and water mixture for closed heating and cooling systems according to plant type I for DIN EN 14868.
When used in plant Type II for DIN EN 14868 appropriate protective measures are taken.
The requirements of VDI 2035, part 1 + 2 are observed.
Medium tempera-ture
°F (°C) (water/glycol) 15…250 (−10 ... +120)
Materials in the water/glycol
Valve bodies Dezincification Resistant Brass (CuZn36Pb2As - CW 602N) per EN 12420 Grey iron
EN-GJL-250 (GG
25) per EN 1561
Cone (Pc) Stainless Steel, W.Nr. 1.4305
Wrought copper CuZn40Pb3-CW
614N, Stainless Steel, W.Nr.
1.4305
Seat (Pc) EPDM Stainless Steel, W.Nr. 1.4305
Seat (Cv) Dezincification Resistant Brass (CuZn36Pb2As - CW 602N) Stainless Steel, W.Nr. 1.4305
Membranes and O-rings EPDM
Springs Stainless Steel, W.Nr. 1.4568, W.Nr. 1.4310
Cone (Cv) Wrought copper, CuZn40Pb3 - CW 614N
Screw Stainless Steel (A2)
Flat gasket NBR
Sealing agent (only for valves with PT Ports)
Dimethacrylate Ester
Materials out of the water/glycol
Plastic parts PA POM
Insert parts and outer screws CuZn39Pd3 - CW614N -
Note: Water/glycol Compatibility: It is the responsibility of the installer or product specifier to verify water/glycol compatibility of the valves construction materials with the supplier of water/glycol treatment/heat transfer solution.
1) See Table 15. Assembly Valve Body Configurations on page 13 for a listing of all PIBCV valve body part numbers.
2) Factory setting of the valve is done at Qnom (100%) or lower depending on flow rate ordered.
3) Regardless of the setting, the valve can modulate below 1% of set flow.
4) ∆p = (P1–P3) min~max
5) 87 psi ∆p is possible if consideration has been made to the flow velocity, cavitation and noise. For application usage please speak with Product Support
Pc - Pressure controller Cv - Control valve schneider-electric.com | 11Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Table 13. Specification Flange Version, 2½"…4"
1) Factory setting of the valve is done at Qnom (100%) or lower depending on flow rate ordered.
2) Regardless of the setting, the valve can modulate below 1% of set flow.
3) ∆p = (P1–P3) min~max
4) 87 psi ∆p is possible if consideration has been made to the flow velocity, cavitation and noise. for application usage please speak with Product Support
Pc - Pressure controller Cv - Control valve
Table 14. Specification Flange Version, 5"…10" Valve Size 5" 6" 8" 10"
Part Number VP220A-125S VP220A-125H VP220A-150S VP220A-150H VP220A-200S VP222A-200H VP222A-250S VP222A-250H
Flow range
Qmin gal / min
158 194 256 332 352 475 528 652
Qnom (100%) 1)
395 485 640 830 880 1188 1320 1630
Setting range 2) % 40-110%
Diff.
pressure 3)
∆pQnom psi [kPa]
5.8-58 [40-400]
8.7-58 [60-400]
5.8-58 [40-400]
8.7-58 [60-400]
5.8-58 [40-400]
8.7-58 [60-400]
5.8-58 [40-400]
8.7-58 [60-400]
Leakage acc. to standard IEC 60534
Class 4, max. 0.01% of Qnom
Max. close off differential pres-sure across the valve
90 psi
Connection flange ANSI Class 125 actuators MP2000-NSR, MP2000-SRU, MP2000-SRD MP4000
Flow medium Water and water mixture for closed heating and cooling systems according to plant type I for DIN EN 14868. When used in plant Type II for DIN EN
14868 appropriate protective measures are taken. The requirements of VDI 2035, part 1 + 2 are observed.
Body Pressure Rating psi Class 125 per ASME B16.1-2010 Material Class B per ASTM A 126-04 (2014), 200 psi to 150°F, 190 psi to 200°F, 180 psi to 225°F, 175 psi to 250°F
Control range Acc. to standard IEC 60534 control range is high as flow characteristic is linear.
Control valve’s characteristic Stem up open, Linear (could be converted by actuator to equal percentage)
Medium temperature °F (°C)
(water/glycol) 15…250 (−10 ... +120)
Stroke (Qnom) in.
(mm)
1.18 (30)
Materials in the water/glycol
Valve bodies Grey iron EN-GJL-250 (GG 25)
Membranes/ Bellow / O-Rings W.Nr.1.4571 EPDM
Springs Stainless Steel, W.Nr.1.4401 Stainless Steel, W.Nr.1.4310
Cone (Pc) / Cone (Cv) Stainless Steel, W.Nr.1.4404NC Stainless Steel, W.Nr.1.4021
Flat gasket Graphite gasket Non asbestos
Seat (Pc) / Seat (Cv) Stainless Steel, W.Nr.1.4027
Screw Stainless Steel, W.Nr.1.1181
Valve Size 2½" 3" 4"
Part Number VP220A-65S VP220A-80S VP220A-100S
Flow range Qmin gal/min
34 48 66
Qnom (100%)
1) 85 120 165
Setting range 2) % 40-100%
Diff. pressure3), 4) ∆pQnom psi [kPa] 4.35-58 [30-400]
Body Pressure Rating psi Class 125 per ASME B16.1-2010 Material Class B per ASTM A 126-04 (2014), 200 psi to 150°F, 190 psi to 200°F, 180 psi to 225°F, 175 psi to 250°F
Control valve’s characteristic Stem up open, Linear (can be converted by actuator to equal percentage)
Leakage acc. to standard IEC 60534 Max. 0.05% of Qnom
For shut off function Acc. to ISO 5208 class A - no visible leakage
Flow medium Water and water mixture for closed heating and cooling systems according to plant type I for DIN EN 14868. When used in plant Type II for
DIN EN 14868 appropriate protective measures are taken. The requirements of VDI 2035, part 1 + 2 are observed.
Medium temperature °F (°C) (water/glycol) 15…250 (−10 ... +120)
Stroke Qnom in. (mm) .59 (15)
Connection flange ANSI Class 125 actuators MP500C, MP500C-SRU, MP500C-SRD
Materials in the water/glycol
Valve bodies Grey iron EN-GJL-250(GG25)
Membranes / Bellow / O-rings EPDM
Springs Stainless Steel, W.Nr. 1.4568, W.Nr. 1.4310
Cone (Pc) Wrought copper, CuZn40Pb3 - CW 614N, Stainless Steel, W.Nr. 1.4305
Seat (Pc) / Seat (Cv) W.Nr. 1.4305
Cone (Cv) CuZn40Pb3 - CW 614N
Screw Stainless Steel (A2)
Flat gasket NBR
12 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Pipe Size (in.)
Valve Assembly Part
Number Series Complete Valve Body Part
Number Valve Type
Female NPT End Connectors (included with all 1/2” through 2” Valve Actuator Assemblies)
PT Ports Installation Data
Sheet
1/2 VP228E-10LN- VP228E-10BQLNT Threaded 911 2108 010
F-27961
1/2 VP228E-10L- VP228E-10BQL Threaded 911 2108 010 Yes
1/2 VP228E-15LN- VP228E-15BQLNT Threaded 911 2108 015
1/2 VP228E-15L- VP228E-15BQL Threaded 911 2108 015 Yes
1/2 VP228E-15SN- VP228E-15BQSNT Threaded 911 2108 015
1/2 VP228E-15S- VP228E-15BQS Threaded 911 2108 015 Yes
1/2 VP229E-15HN- VP229E-15BQHNT Threaded 911 2108 015
3/4 VP228E-20SN- VP228E-20BQSNT Threaded 911 2108 020
3/4 VP228E-20S- VP228E-20BQS Threaded 911 2108 020 Yes
3/4 VP229E-20HN- VP229E-20BQHNT Threaded 911 2108 020
1 VP229E-25SN- VP229E-25BQSNT Threaded 911 2108 025
1 VP229E-25S- VP229E-25BQS Threaded 911 2108 025 Yes
1 VP229E-25HN- VP229E-25BQHNT Threaded 911 2108 025
1-1/4 VP229E-32SN- VP229E-32BQHNT Threaded 911 2108 032
1-1/4 VP229E-32S- VP229E-32BQS Threaded 911 2108 032 Yes
1-1/4 VP229E-32HN- VP229E-32BQHNT Threaded 911 2108 032
1-1/2 VP220E-40S- VP220E-40CQS Threaded 911 2108 040 Yes
F-27962
2 VP220E-50S- VP220E-50CQS Threaded 911 2108 050 Yes
2-1/2 VP220A-65S- VP220A-65CQS Flanged Yes
3 VP220A-80S- VP220A-80CQS Flanged Yes
4 VP220A-100S- VP220A-100CQS Flanged Yes
5 VP220A-125S- VP221A-125CQS Flanged Yes
F-27963
5 VP220A-125H- VP221A-125CQH Flanged Yes
6 VP220A-150S- VP221A-150CQS Flanged Yes
6 VP220A-150H- VP221A-150CQH Flanged Yes
8 VP222A-200S- VP222A-200CQS Flanged Yes
8 VP222A-200H- VP222A-200CQH Flanged Yes
10 VP222A-250S- VP222A-250CQS Flanged Yes
10 VP222A-250H- VP222A-250CQH Flanged Yes
Table 15. Assembly Valve Body Configurations schneider-electric.com | 13Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Table 17. Selection: ½"…2" Valve Body Tail Pieces
Table 16. Selection: Valve Actuator Codes Actuator Part
Number Actuator
Code Valve Sizes Non Spring Return Spring Return Open Sprint Return Close
MP131-24T A101
½"…1¼"
√MP131-24F F101
MP131-24MP S101
MP300-SRU U201 √
MP300-SRD U301 √
MP500C U131
1-½"…4"
MP500C-SRU U231 √
MP500C-SRD U331 √
MP2000-NSR U161
5"…6"
MP2000-SRU U261 √
MP2000-SRD U361 √
MP4000 U181 8"…10" √
Part Number Pipe Size Approximate Length inches
(mm)
Approximate Nut Size inches (mm)
Approximate Valve Body Thread
Engagement inches (mm)
Comments Image
911 2108 010 1/2” 1.1 (28) 0.99 (25) 0.29 (7.2) For VP228E-10BQLNT and VP228E-10BQL 1/2” valve bodies only
911 2108 015 1/2” 1.1 (28) 1.19 (30.2) 0.29 (7.2) For all 1/2” valve bodies except VP228E- 10BQLNT and VP228E-10BQL
911 2108 020 3/4” 1.26 (32) 1.46 (37) 0.33 (8.4) For all 3/4” valve bodies
911 2108 025 1” 1.5 (38) 1.81 (45.8) 0.41 (10.4) For all 1” valve bodies
911 2108 032 1-1/4” 1.65 (42) 2.05 (52.1) 0.42 (10.7) For all 1-1/4” valve bodies
911 2108 040 1-1/2” 1.85 (47) 2.52 (63.9) 0.55 (14) For 1-1/2” valve body
911 2108 050 2” 1.93 (49) 3.24 (82.2) 0.69 (17.5) For 2” valve body
911 2110 010 3/8” 1.24 (31.5) 0.99 (25) 0.29 (7.2) For VP228E-10BQLNT and VP228E-10BQL 1/2” valve bodies only
911 2110 015 1/2” 1.32 (33.5) 1.19 (30.2) 0.29 (7.2) For all 1/2” valve bodies except VP228E- 10BQLNT and VP228E-10BQL
911 2110 020 3/4” 1.5 (38) 1.46 (37) 0.33 (8.4) For all 3/4” valve bodies
911 2110 025 1” 1.73 (44) 1.81 (45.8) 0.41 (10.4) For all 1” valve bodies
911 2110 032 1-1/4” 1.85 (47) 2.05 (52.1) 0.42 (10.7) For all 1-1/4” valve bodies
911 2110 040 1-1/2” 2.28 (58) 2.52 (63.9) 0.55 (14) For 1-1/2” valve body
911 2110 050 2” 2.81 (71.5) 3.24 (82.2) 0.69 (17.5) For 2” valve body
911 2109 010 3/8” Tubing (with 1/2” OD)
1.06 (27) 0.99 (25) 0.29 (7.2) For VP228E-10BQLNT and VP228E-10BQL 1/2” valve bodies only
911 2109 015 1/2” Tubing (with 5/8” OD)
1.32 (33.5) 1.19 (30.2) 0.29 (7.2) For all 1/2” valve bodies except VP228E- 10BQLNT and VP228E-10BQL
911 2109 020 3/4” Tubing (with 7/8” OD)
1.5 (38) 1.46 (37) 0.33 (8.4) For all 3/4” valve bodies
911 2109 025 1” Tubing (with 1-1/8” OD)
1.73 (44) 1.81 (45.8) 0.41 (10.4) For all 1” valve bodies
911 2109 032 1-1/4” Tubing (with 1-3/8” OD)
1.85 (47) 2.05 (52.1) 0.42 (10.7) For all 1-1/4” valve bodies
911 2109 040 1-1/2” Tubing (with 1-5/8” OD)
2.36 (60) 2.52 (63.9) 0.55 (14) For 1-1/2” valve body
911 2109 050 2” Tubing (with 2-1/8” OD)
2.81 (71.5) 3.24 (82.2) 0.69 (17.5) For 2” valve body
M al e N
P T
Tw o
M al e N
P T
C on ne ct or s, T w o N ut s, Tw o G as ke ts
Fe m al e
S w ea t
Tw o
Fe m al e
S w ea t E nd s, T w o N ut s, T w o G as ke ts
Fe m al e
N P
T Tw o Fe m al e N
P T
C on ne ct or s, T w o G as ke ts
14 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Dimensions
Threaded Valves ½ to 1¼" (inches)
Threaded Valves 1½"…2" (inches)
Table 19. Threaded Valves 1½"…2" (inches)
Type L1 H1 H2 H3 b
ISO 228/1
Valve Body Weight lb
1½" 4.33
6.7 6.85 11
G 2 15.8
2" 5.11 G 2½ 18.0
½ to 1¼" with close off cap
Table 18. Threaded Valves ½ to 1¼" (inches) Type
L1 L2 L3
(PLUGS)
L4 L5 H1 H2
H3 b
ISO
228/1
Valve Body Weight
(lb.)MP131 MP300
-SRU
MP300
-SRD MP131 MP300
-SRU/SRD MP131 MP300
-SRU/SRD
1/2"
VP228E-
10Lx 2 1.41
3.11
4.37 5.11 5.90
5.35 5.7
2.9 .78 5.6 7.2 G ½ .83
1/2" 2.5 1.7 4.64 5.39 6.14 3 1 5.7 7.4 G ¾ 1
3/4" 3.2 2.2 4.96 5.7 6.53 3 1.2 5.8 7.5 G 1 1.43
1" 4 2.7 5.55 6.3 7.08 3.5 1.5 6.14 7.83 G 1 ¼ 3.2
1¼" 5.1 3.5 6.26 7 7.8 3.9 2.3 6.58 8.27 G 1 ½ 4.8
1½" with MP500C-SRU/SRD1½"
L2
H b
H
1½" with MP500C
H
With MP300-SRDWith MP300-SRUWith MP131 Actuator
L5
L4
H
L5
L6
H
L5
L4
L4
H
H
L5
L4
MP300-SRU
L5
L4
H 3H
L5
H
L2
L3 L1 b
H
H
L3 L2
H
H b
L1 L1
See page page 14 for the valve body tail piece dimensions.
See page page 14 for the valve body tail piece dimensions.
schneider-electric.com | 15Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Flanged Valves 2½"…4"
Table 20. Flanged Valves 2½"…4"
Type L1 H1 H2 H3 a (EN 1092-2) Valve Body Weight (lb)
2½" 11.4 8.6 6.77 13 7.2 84
3" 12.2 8.9 6.96 13.1 7.87 99
4" 13.7 9.44 7.36 13.7 8.66 126
H
L1 a
H
2½"…4"
H
2½"…4" with MP500C 2½"…4" with
MP500C-SRU/SRD
H 3 H
16 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Table 21. Flanged Valves 5"…6"
Type L1 H1 H2
H3
MP2000-SRU/SRD/
NSR
a
(EN 1092-2)
Valve Body Weight (lb.)
5" 15.7 10.7 21.1 20.94 9.84 188
6" 18.9 12.1 19.6 22.36 11.22 304
Table 22. Flanged Valves 8"…10"
Type L1 H1 H2 H3
MP4000
a
(EN 1092-2)
Valve Body Weight (lb.)
8" 23.6 17.0 19.0 24.3 13.38 482
10" 28.7 16.9 20.9 27.8 15.9 753
8", 10" with MP4000
H a
L1
H
H
8", 10"
Flanged Valves 8"…10"
Flanged Valves 5"…6"
5" 5" with MP2000-SRU/SRD/NSR 6" MP2000-SRU/SRD/NSR 6"
H
H a
L1 a
L1
H
H
H
H schneider-electric.com | 17Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. March, 2017 tc
Table 23. ½…2” Valve Flow Ranges (Qmin to Qnom)
Flow Rate (GPM) 1/2” 3/4” 1” 1¼” 1½” 2"
Without PT Ports
VP228E-
10BQLNT
VP228E-
15BQLNT
VP228E-
15BQSNT
VP229E-
15BQHNT
VP228E-
20BQSNT
VP229E-
20BQHNT
VP229E-
25BQSNT
VP229E-
25BQHNT
VP229E-
32BQSNT
VP229E-
32BQHNT
With PT Ports
VP228E-
10BQL
VP228E-
15BQL
VP228E-
15BQS
VP228E-
20BQS
VP229E-
25BQS
VP229E-
32BQS
VP220E-
40CQS
VP220E-
50CQS
0.5 1 1 1
1.0 1 1 1 1
1.5 1 1 1 1 1
2.0 1 1 1 1 1
2.5 1 1 1 1 1
3.0 1 1 1 1 1 1
3.5 1 1 1 1 1 1 1
4.0 1 1 1 1 1 1 1
4.5 1 (1) 1 1 1 1 1
5.0 1 1 1 1 1 1
5.5 (1) 1 1 1 1 1
6.0 1 1 1 1 1
6.5 1 1 1 1 1
7.0 1 1 1 1 1
7.5 1 1 1 1 1
8.0 (1) (1) 1 1 1
8.5 1 1 1
9.0 1 1 1
9.5 1 1 1
10 1 1 1
11 1 1 1
12 1 1 1
13 (1) 1 1 1
14 1 1 1
15 (1) 1 1
16 1 1
17 1 1
18 (1) 1
19 (1) 1
20 1
21 1
22 1 1
23 1 1
24 1 1
25 1 1
26 1 1
27 1 1
28 1 1
29 1 1
30 1 1
31 1 1
32 1 1
33 1 1
34 1
35 1
36 1
37 1
38 1
39 1
40 1
44 1
48 1
52 1
55 1
(Qhigh setting)
18 | schneider-electric.com Selection Guide
March, 2017 tc © 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies.
Table 24. 2½”…10” Flanged Valve Flow Ranges (Qmin to Qnom) Size 2½” 3” 4” 5” 6” 8” 10”
Flow Rate
(GPM)
VP220A-
65CQS
VP220A-
80CQS
VP220A-
100CQS
VP221A-
125CQS
VP221A-
125CQH
VP221A-
150CQS
VP221A-
150CQH
VP222A-
200CQS
VP222A-
200CQH
VP222A-
250CQS
VP222A-
250CQH
35 34
40 1
45 1
50 1 48
55 1 1
60 1 1
65 1 1
70 1 1 66
75 1 1 1
80 1 1 1
85 85 1 1
90 1 1
95 1 1
100 1 1
120 120 1
140 1
160 165 158
180 1
200 1 194
250 1 1 256
300 1 1 1
350 1 1 1 332 352
400 395 1 1 1 1
450 485 1 1 1 475
500 1 1 1 1 528
550 1 1 1 1 1
600 640 1 1 1 1
650 1 1 1 1 652
700 1 1 1 1 1
750 1 1 1 1 1
800 830 1 1 1 1
850 880 1 1 1
900 1 1 1
950 1 1 1
1000 1 1 1
1100 1188 1 1
1200 1 1
1300 1320 1
1400 1
1500 1
1600 1630
All flanged valves come standard with the PT ports schneider-electric.com | 19Selection Guide
© 2017 Schneider Electric. All rights reserved. All trademarks are owned by Schneider Electric Industries SAS or its…
This is the start of the file's text. The full file is on GovTribe.