Text version

Power Supply System; UPS 50kW 208V for External Batteries, Start-up 5x8, Equipment/Parts and Services, or equivalent

General

Bypass Voltage Tolerance +/-10%

Max Bypass Input Current 175 A

Output

Output Power Capacity 50.0 KW / 50.0 kVA

Max Configurable Power (Watts) 50.0 KW / 50.0 kVA

Nominal Output Voltage 208 3PH

Output Voltage Distortion Less than 3%

Output Frequency (sync to mains) 50 Hz , 60 Hz

Other Output Voltages 200, 220V

Crest Factor 2.5

Double Conversion Online

Waveform Type Sine wave

Output Connections (1) Hard Wire 5-wire (3PH + N + G) (Battery

Backup)

Output Voltage Tolerance +/-1% after 50ms

Output Voltage THD <1% linear load and <3% non-linear load

Overload Operation 150% for 1 minute 125% for 10 minutes

Bypass Built-in Static Bypass

Input

Nominal Input Voltage 208 3PH

Input Frequency 40 - 70 Hz

Input Connections Hard Wire 4-wire (3PH + G) , Hard Wire 5-wire

(3PH + N + G)

Input voltage range for main operations 177 - 239 (208V) V

Other Input Voltages 200 , 220

Maximum Input Current 182 A

Maximum Short Circuit Withstand (Icw) 65.0

Input Total Harmonic Distortion Less than 3% for full load

Batteries & Runtime

Battery Type No internal battery - uses external battery system

Nominal Battery Voltage 384-480VDC

End of Discharge Battery Voltage 307 VDC

End of Discharge Max Battery Current 170 A

Communications & Management

Interface Port(s) GVS_Cable2ndBatCab , GVS_MBCKIT_UL , GVS_NarrowCBC_Seismic , GVS_NarrowSeismicKit , GVS_Parallel , GVS_WideCBC_Seismic , GVS_WideUPSMBC_SeismicKit , GVS_WideUPS_AirFilter , GVS_XFMRSeismicKit

Available SmartSlot™ Interface Qty 1

Control panel Touch Screen LCD User Interface

Audible Alarm Audible and visible alarms prioritized by severity

Physical

Maximum Height 58.46 inches (1485.0 mm)

Maximum Width 20.51 inches (521.0 mm)

Maximum Depth 33.35 inches (847.0 mm)

Net Weight 551.16 lbs (250.0 kg)

Shipping Weight 606.27 lbs (275.0 kg)

Shipping Height 66.14 inches (1680.0 mm)

Shipping Width 25.2 inches (640.0 mm)

Shipping Depth 38.98 inches (990.0 mm)

Color Gloss level 85% , RAL 9003

Environmental

Operating Environment 32 - 104 °F (0 - 40 °C)

Operating Relative Humidity 0 - 95 (non-condensing) %

Operating Elevation 0-3281 feet (0-984.3 meters)

Storage Temperature @ERROR - @ °F (-25 to 55 °C)

Storage Relative Humidity 10 - 80 (non-condensing) %

Storage Elevation 0-50000 feet (0-15000 meters)

Audible noise at 1 meter from surface of unit, 65.000 dB

Online Thermal Dissipation 10758.400 BTU/hr

Protection Class IP 21

EQUIPMENT/PARTS:

(1 EA) UPS 50kW 208V for External Batteries, Start-up 5x8 APC

(1 EA) Cable Kit for 2nd Classic Battery Cabinet APC (1 EA) Maintenance Bypass Cabinet, UL, Single-Unit 50-75kW 208V, 100-150kW 480V APC

(2 EA) Classic Battery Cabinet, UL, Type 3 APC

(1 EA) 50kW 42 Breaker Position Distribution Cabinet 300MM APC

(1 EA) InfraStructure Emergency Power OFF (EPO) APC – Data Center

SERVICES:

(2 EA) Two (2) Year On-Site Warranty Extended for One (1) 30 to 50kVA 208V UPS APC

(1 EA) Product Professional UPS Replacement/Installation APC;

(2 EA) Product Symmetra PX SyPX 40kW Travel Expenses APC

INCIDENTAL SERVICES:

Remove old UPS and install proposed UPS.

See attached PWS for removal.

File details come from the government source that posted it.