Power Supply System; UPS 50kW 208V for External Batteries, Start-up 5x8, Equipment/Parts and Services, or equivalent
General
Bypass Voltage Tolerance +/-10%
Max Bypass Input Current 175 A
Output
Output Power Capacity 50.0 KW / 50.0 kVA
Max Configurable Power (Watts) 50.0 KW / 50.0 kVA
Nominal Output Voltage 208 3PH
Output Voltage Distortion Less than 3%
Output Frequency (sync to mains) 50 Hz , 60 Hz
Other Output Voltages 200, 220V
Crest Factor 2.5
Double Conversion Online
Waveform Type Sine wave
Output Connections (1) Hard Wire 5-wire (3PH + N + G) (Battery
Backup)
Output Voltage Tolerance +/-1% after 50ms
Output Voltage THD <1% linear load and <3% non-linear load
Overload Operation 150% for 1 minute 125% for 10 minutes
Bypass Built-in Static Bypass
Input
Nominal Input Voltage 208 3PH
Input Frequency 40 - 70 Hz
Input Connections Hard Wire 4-wire (3PH + G) , Hard Wire 5-wire
(3PH + N + G)
Input voltage range for main operations 177 - 239 (208V) V
Other Input Voltages 200 , 220
Maximum Input Current 182 A
Maximum Short Circuit Withstand (Icw) 65.0
Input Total Harmonic Distortion Less than 3% for full load
Batteries & Runtime
Battery Type No internal battery - uses external battery system
Nominal Battery Voltage 384-480VDC
End of Discharge Battery Voltage 307 VDC
End of Discharge Max Battery Current 170 A
Communications & Management
Interface Port(s) GVS_Cable2ndBatCab , GVS_MBCKIT_UL , GVS_NarrowCBC_Seismic , GVS_NarrowSeismicKit , GVS_Parallel , GVS_WideCBC_Seismic , GVS_WideUPSMBC_SeismicKit , GVS_WideUPS_AirFilter , GVS_XFMRSeismicKit
Available SmartSlot™ Interface Qty 1
Control panel Touch Screen LCD User Interface
Audible Alarm Audible and visible alarms prioritized by severity
Physical
Maximum Height 58.46 inches (1485.0 mm)
Maximum Width 20.51 inches (521.0 mm)
Maximum Depth 33.35 inches (847.0 mm)
Net Weight 551.16 lbs (250.0 kg)
Shipping Weight 606.27 lbs (275.0 kg)
Shipping Height 66.14 inches (1680.0 mm)
Shipping Width 25.2 inches (640.0 mm)
Shipping Depth 38.98 inches (990.0 mm)
Color Gloss level 85% , RAL 9003
Environmental
Operating Environment 32 - 104 °F (0 - 40 °C)
Operating Relative Humidity 0 - 95 (non-condensing) %
Operating Elevation 0-3281 feet (0-984.3 meters)
Storage Temperature @ERROR - @ °F (-25 to 55 °C)
Storage Relative Humidity 10 - 80 (non-condensing) %
Storage Elevation 0-50000 feet (0-15000 meters)
Audible noise at 1 meter from surface of unit, 65.000 dB
Online Thermal Dissipation 10758.400 BTU/hr
Protection Class IP 21
EQUIPMENT/PARTS:
(1 EA) UPS 50kW 208V for External Batteries, Start-up 5x8 APC
(1 EA) Cable Kit for 2nd Classic Battery Cabinet APC (1 EA) Maintenance Bypass Cabinet, UL, Single-Unit 50-75kW 208V, 100-150kW 480V APC
(2 EA) Classic Battery Cabinet, UL, Type 3 APC
(1 EA) 50kW 42 Breaker Position Distribution Cabinet 300MM APC
(1 EA) InfraStructure Emergency Power OFF (EPO) APC – Data Center
SERVICES:
(2 EA) Two (2) Year On-Site Warranty Extended for One (1) 30 to 50kVA 208V UPS APC
(1 EA) Product Professional UPS Replacement/Installation APC;
(2 EA) Product Symmetra PX SyPX 40kW Travel Expenses APC
INCIDENTAL SERVICES:
Remove old UPS and install proposed UPS.
See attached PWS for removal.