FOR CONSTRUCTION 04/29/2016
ROOM NO 2 ROOM NO 3 ROOM NO 4ROOM NO 1
ROOM NO. 5
ROOM NO. 10
ROOM NO. 12
ROOM NO. 27ROOM NO. 28
NO. 6
ROOM
NO. 7
ROOM
NO. 7
ROOM
ROOM
EQUIPT
NO. 26
ROOM
NO. 25
NO. 24
NO. 23
ROOM NO. 22
NO. 21
NO. 20
NO. 18
NO. 9
NO. 8
NO. 11
NO. 13
N0. 14
N0. 16
NO.15
C O
U N
T E
R
T O
P
L E
X A
N
G L
A S
R V I
O
U N
T E
R C
U S
T O
M E
R
Return Air Space
S P
A C
E R
E T
U
N
A I
NO.30
NO.31
N O
ONE WAY MIRROR
3' X 3' -‚"
TANG NGUYEN
REVISION DATE DESCRIPTION BY
OFFICE OF THE ENGINEER
CHATHAM COUNTY GEORGIA
DESIGN BY:
SCALE: AS SHOWN
FORT STEWART, GEORGIA
HUNTER, AAF
PLATE DRAWING NUMBER
H-
LEGEND
NOTES
NEW EXISTING
CABLES
GROUNDING RODS
DELTA ELECTRIC
MOUNTING BASE
AIR TERMINAL WITH
LIGHTNING PROTECTION
AT
PANEL BOARDS
DISTRIBUTION
ELECTRICAL
MISCELLANEOUS
DRAWN BY: L.M.LEE
NOT TO SCALE
PROJECT# E1-3-4J
SHEET OF DATE
BUILDING 1240
INSTALL LIGHTNING PROTECTION SYSTEM,
EXISTING ELECTRICAL AND FIRE ALARM CONTROL PLAN
EXISTING ELECTRICAL AND FIRE ALARM PANELS
2E-1 3
LIGHTNING PROTECTION SYSTEM CONDUCTOR.
AND FIRE ALARM SYSTEM GROUNDING CABLES TO THE
CONNECT EXISTING ELECTRICAL DISTRIBUTION PANELS
04/27/2016
OR PIGGY BACK BREAKERS.
ADDITIONAL CIRCUIT BREAKER BRANCHES, THE CONTRACTOR MAY USE TANDEM
POWER AND FIRE ALARM PANELS. IF SPACES ARE NOT AVAILABLE FOR NEW
7. CONTRACTOR SHALL INSTALL LIGHTNING ARRESTOR DEVICES TO THE EXISTING
LUMINUM TO COPPER.
RODS SHALL BE COPPER. USE BIMETALLIC CONNECTOR TO CONVERT FROM
6. LIGHTNING CONDUCTOR FOR UNDERGROUND CABLES CONNECT TO GROUNDING
OR HAVE A RADIUS LESS THAN 8".
5. CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES
4. CONDUCTOR WILL BE FASTENED EVERY 3'-0" ON CENTER MAXIMUM.
ROD COUNTERPOISE.
WHICH ENTER THE STRUCTURE TO THE NEAREST DOWN-LEAD, GROUND
3. BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER...
GROUND ON METAL WATER PIPE.
CONNECTED WITH MAIN SIZE CONDUCTOR TO LIGHTNING PROTECTION
2. ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE
LIGHTNING PROTECTION STANDARDS: LP1-175, NFPA 780 AND UL 96A.
1. LIGHTNING PROTECTION SYSTEMS SHALL BE INSTALLED AS PER
TANG NGUYEN
REVISION DATE DESCRIPTION BY
OFFICE OF THE ENGINEER
CHATHAM COUNTY GEORGIA
DESIGN BY:
SCALE: AS SHOWN
FORT STEWART, GEORGIA
HUNTER, AAF
PLATE DRAWING NUMBER
H-
DRAWN BY: L.M.LEE
PROJECT# E1-3-4J
SHEET OF
BUILDING 1240
INSTALL LIGHTNING PROTECTION SYSTEM,
3E-2 3
S L
O P
E S
L O
P E
SLOPE
S L
O P
E
SLOPE
S L
O P
E
SLOPE SLOPE
NEW LIGHTNING PROTECTION SYSTEM PLAN
SCALE: 1/8" = 1'-0"
ATAT
AT AT AT
AT
AT
AT
ATAT
AT
ATATATATATAT
AT
AT AT AT AT
ATATATAT
AT
AT AT
AT AT
AT
GROUNDING CONDUCTOR
#4/0 AWG BARE COPPER
GROUNDING ROD DETAIL
DELTA CONFIGURATION
M
IN
MIN.
2'-0"
2'-0"
NOT TO SCALE
M
IN
GROUND ROD CLAMP
NOT TO SCALE
WITH CLAMP
COPPERCLAD ROD
REQUIRED RESISTANCE TO GROUND
ADDED TO OBTAIN THE 15 OHM
10'-0" SECTIONAL RODS MAY BE
FOR SHINGLE ROOF PLACEMENT
AIR TERMINAL AND CONDUCTOR MOUNTING DETAIL
65,760 CIRCULAR MILS.
WIRE SIZE 14 GAUGE, 66 LBS WEIGHT PER 1000 FEET
NUMBER OF STRANDS: 16 SMOOTH WEAVE.
B - SECONDARY LIGHTNING CONDUCTOR SHALL BE CLASS 2 ALUMINUM.
211,000 CIRCULAR MILS.
WIRE SIZE 12 1/2 GAUGE, 204 LBS WEIGHT PER 1000 FEET
NUMBER OF STRANDS: 37 CONCENTRIC.
A - MAIN LIGHTNING CONDUCTOR SHALL BE CLASS 2 ALUMINUM.
LIGHTNING CONDUCTOR:
04/27/2016
DATE
ELECTRICAL AND FIRE ALARM CONTROL PLAN