EXHIBIT A
DRAWINGS
HUNTINGTON DISTRICT
OF ENGINEERS
US ARMY CORPS
HAYSI, VIRGINIA
JOHN W. FLANNAGAN LAKE
REHABILITATION
SPILLWAY TAINTER GATE
PLANS FOR
JUNE 2017
D. RENEWAL OF QUALIFICATION - RE-QUALIFICATION OF A WELDER OR WELDING
OPERATOR IS REQUIRED UNDER ANY OF THE FOLLOWING CONDITIONS:
1. IT HAS BEEN MORE THAN 6 MONTHS SINCE THE WELDER OR WELDING OPERATOR
HAS USED THE SPECIFIC WELDING PROCESS FOR WHICH HE IS QUALIFIED.
OPERATOR’S ABILITY TO MAKE WELDS THAT MEET THE REQUIREMENTS OF
THESE SPECIFICATIONS.
3. THE WELDER OR WELDING OPERATOR WAS QUALIFIED BY AN EMPLOYER OTHER
THAN THOSE FIRMS PERFORMING WORK UNDER THIS CONTRACT, AND A
QUALIFICATION TEST HAS NOT BEEN TAKEN WITHIN THE PAST 12 MONTHS.
SUBMIT AS EVIDENCE OF CONFORMANCE ALL RECORDS SHOWING PERIODS OF
EMPLOYMENT, NAME OF EMPLOYER WHERE WELDER, OR WELDING OPERATOR,
WAS LAST EMPLOYED, AND THE PROCESS FOR WHICH QUALIFIED.
4. A TACKER WHO PASSES THE QUALIFICATION TEST IS CONSIDERED ELIGIBLE
TO PERFORM TACK WELDING INDEFINITELY IN THE POSITIONS AND WITH
THE PROCESSES FOR WHICH HE IS QUALIFIED, UNLESS THERE IS SOME
THE TACKER IS REQUIRED TO PASS THE PRESCRIBED TACK WELDING TEST.
ALL PERSONNEL PERFORMING NON-DESTRUCTIVE INSPECTION SHALL BE CERTIFIED
UNDER ASNT-RP SNT-TC-1A WITHIN A PERIOD OF 1 YEAR BEFORE THE DATE OF
METHOD. THE INSPECTOR MAY BE SUPPORTED BY ASSISTANT WELDING INSPECTORS WHO
ARE NOT QUALIFIED TO ASNT RP SNT-TC-1A, AND ASSISTANT INSPECTORS MAY
PERFORM SPECIFIC INSPECTION FUNCTIONS UNDER THE SUPERVISION OF THE QUALIFIED
INSPECTOR. OTHER QUALIFICATIONS OR CERTIFICATION MAY BE ACCEPTED AT THE
CONTRACTING OFFICER’S DISCRETION. QUALIFIED INSPECTORS SHALL BE ABLE TO
JUDGE THE ACCEPTABILITY OR NON-ACCEPTABILITY OF WELDS IN CONFORMANCE WITH
SAFE WELDING PRACTICES AND SAFETY PRECAUTIONS DURING WELDING MUST CONFORM
TO AWS Z49.1.
WELDING WIRE, AND FLUXES MUST BE CAPABLE OF PRODUCING SATISFACTORY WELDS
WHEN USED BY A QUALIFIED WELDER OR WELDING OPERATOR PERFORMING QUALIFIED
WELDING PROCEDURES. ALL WELDING EQUIPMENT AND MATERIALS SHALL COMPLY WITH
THE CONTRACTOR SHALL SUBMIT A COMPLETE SCHEDULE OF WELDING
PROCEDURES FOR EACH STEEL STRUCTURE TO BE WELDED. THE SCHEDULE
PRESCRIBED IN AWS D1.1 SECTION 4. THE SCHEDULE SHALL PROVIDE
DETAILED PROCEDURE SPECIFICATIONS AND TABLES OR DIAGRAMS SHOWING
THE PROCEDURES TO BE USED FOR EACH REQUIRED JOINT. WELDING
PROCEDURES MUST INCLUDE FILLER METAL, PREHEAT, AND INTERPASS
TEMPERATURE REQUIREMENTS. EACH WELDING PROCEDURE SHALL BE CLEARLY
IDENTIFIED AS BEING PREQUALIFIED OR REQUIRED TO BE QUALIFIED BY
TESTS. WELDING PROCEDURES MUST SHOW TYPES AND LOCATIONS OF WELDS
DESIGNATED OR IN THE SPECIFICATIONS TO RECEIVE NONDESTRUCTIVE
EXAMINATION.
2. WELDING PROCESS - WELDING OF STRUCTURAL STEEL SHALL BE BY AN
ELECTRIC ARC WELDING PROCESS USING A METHOD WHICH EXCLUDES THE
ATMOSPHERE FROM THE MOLTEN METAL AND SHALL CONFORM TO THE
MINIMIZE RESIDUAL STRESSES, DISTORTION AND SHRINKAGE.
A. FILLER METAL - THE ELECTRODE, ELECTRODE-FLUX COMBINATION AND
GRADE OF WELD METAL SHALL CONFORM TO THE APPROPRIATE AWS
SPECIFICATION FOR THE BASE METAL AND WELDING PROCESS BEING
USED OR SHALL BE AS SHOWN WHERE A SPECIFIC CHOICE OF AWS
SPECIFICATION ALLOWABLES IS REQUIRED. THE AWS DESIGNATION
OF THE ELECTRODES TO BE USED SHALL BE INCLUDED IN THE
SHALL BE USED FOR MANUAL SHIELDED METAL-ARC WELDING
TEMPERATURE STORAGE OVEN SHALL BE USED AT THE JOB SITE AS
MOISTURE OF LOW HYDROGEN ELECTRODES.
B. PREHEAT AND INTERPASS TEMPERATURE - PREHEATING SHALL BE
5.6 OR AS OTHERWISE SPECIFIED EXCEPT THAT THE TEMPERATURE
OF THE BASE METAL SHALL BE AT LEAST 70 DEGREES F. THE
WELDMENTS TO BE PREHEATED SHALL BE SLOWLY AND UNIFORMLY
HEATED BY APPROVED MEANS TO THE PRESCRIBED TEMPERATURE,
HELD AT THAT TEMPERATURE UNTIL THE WELDING IS COMPLETED AND
THEN PERMITTED TO COOL SLOWLY IN STILL AIR.
4. WORKMANSHIP - WORKMANSHIP FOR WELDING SHALL BE IN ACCORDANCE
OF THESE REQUIREMENTS.
A. PREPARATION OF BASE METAL - PRIOR TO WELDING THE CONTRACTOR
SHALL INSPECT SURFACES TO BE WELDED TO ASSURE COMPLIANCE
AND ERECTION SHALL BE MADE UNDER THE CONTROLLED CONDITIONS
MADE USING LOW-HYDROGEN WELDING ELECTRODES AND BY WELDERS
QUALIFIED FOR PERMANENT WORK AS SPECIFIED IN THESE
SPECIFICATIONS. PREHEATING FOR TEMPORARY WELDS SHALL BE AS
REQUIRED BY AWS D1.1 FOR PERMANENT WELDS EXCEPT THAT THE
MINIMUM TEMPERATURE SHALL BE 120 DEGREES F IN ANY CASE.
IN MAKING TEMPORARY WELDS ARCS SHALL NOT BE STRUCK IN
OTHER THAN WELD LOCATIONS. EACH TEMPORARY WELD SHALL BE
REMOVED AND GROUND FLUSH WITH ADJACENT SURFACES AFTER
SERVING ITS PURPOSE.
THE PERMANENT WORK SHALL BE SUBJECT TO THE SAME QUALITY
REQUIREMENTS AS THE PERMANENT WELDS AND SHALL BE CLEANED
AND THOROUGHLY FUSED WITH PERMANENT WELDS. PREHEATING
SHALL BE PERFORMED AS SPECIFIED ABOVE FOR TEMPORARY WELDS.
MULTIPLE-PASS TACK WELDS SHALL HAVE CASCADED ENDS.
DEFECTIVE TACK WELDS SHALL BE REMOVED BEFORE
PERMANENT WELDING.
A. SUBMIT WRITTEN RECORDS TO INDICATE THE LOCATION OF WELDS
MADE BY EACH WELDER, WELDING OPERATOR, OR TACKER.
OPERATOR, OR TACKER WITH AN ASSIGNED NUMBER, LETTER, OR
SYMBOL TO IDENTIFY WELDS MADE BY THAT INDIVIDUAL. THE
CONTRACTING OFFICER MAY REQUIRE WELDERS, WELDING OPERATORS,
AND TACKERS TO APPLY THEIR SYMBOL NEXT TO THE WELD BY MEANS
OF RUBBER STAMP, FELT-TIPPED MARKER WITH WATERPROOF INK, OR
OTHER METHODS THAT DO NOT CAUSE AN INDENTATION IN THE METAL.
PLACE THE IDENTIFICATION MARK FOR SEAM WELDS ADJACENT TO THE
WELD AT 3 FOOT INTERVALS. IDENTIFICATION WITH DIE STAMPS OR
ELECTRIC ETCHERS IS NOT ALLOWED.
TESTS. WHEN MATERIALS OR WORKMANSHIP DO NOT CONFORM TO THE SPECIFICATION
TECHNICAL CONSULTANT; OR IF APPROVED, THE CONTRACTOR’S INSPECTION AND
TESTING PERSONNEL MAY BE USED INSTEAD OF THE COMMERCIAL INSPECTION OR
TESTING LABORATORY OR TECHNICAL CONSULTANT.
WELDS SHALL BE CLEANED AND CAREFULLY EXAMINED FOR INSUFFICIENT THROAT
OR LEG SIZES, CRACKS, UNDERCUTTING, OVERLAP, EXCESSIVE CONVEXITY OR
REINFORCEMENT AND OTHER SURFACE DEFECTS TO ENSURE COMPLIANCE WITH THE
THE CONTRACT DRAWINGS TO DETERMINE CONFORMANCE WITH PARAGRAPH STANDARDS
DETAILS OF WELDS, AND QUALITY OF WELDS WITH THE APPLICABLE REQUIREMENTS
TESTS PERFORMED BY THE CONTRACTOR FOR QUALITY CONTROL, THE GOVERNMENT MAY
PERFORM INSPECTION AND TESTING FOR ACCEPTANCE TO THE EXTENT DETERMINED BY
THE CONTRACTING OFFICER. THE COSTS OF SUCH INSPECTION AND TESTING WILL BE
GOVERNMENT IF THE WELDS ARE SATISFACTORY. THE WORK MAY BE PERFORMED BY THE
TESTING. THE GOVERNMENT RESERVES THE RIGHT TO PERFORM SUPPLEMENTAL
STANDARDS OF ACCEPTANCE.
IN THE WELD JOINTS, REPAIR DEFECTIVE WELDS USING A QUALIFIED WELDER OR
WELDING OPERATOR AS APPLICABLE. CONDUCT CORRECTIONS IN ACCORDANCE WITH
AWS D1.1 AND THE PROVISIONS OF THESE REQUIREMENTS. REPAIR ALL DEFECTS
AND REPAIR BY WELDING IS NOT REQUIRED, BLEND THE AFFECTED AREA INTO THE
SURROUNDING SURFACE TO ELIMINATE SHARP NOTCHES, CREVICES, OR CORNERS. AFTER
REPAIRED WELDS SHALL MEET THE INSPECTION REQUIREMENTS FOR THE ORIGINAL
RE-EVALUATION BY NONDESTRUCTIVE METHODS OR BY SURFACE CONDITIONING SHOWS
WORKMANSHIP OR BOTH AT ANY TIME BEFORE FINAL ACCEPTANCE OF THE STRUCTURE
CONTAINING THE WELDMENT.
2. THERE IS SPECIFIC REASON TO QUESTION THE WELDER OR WELDING
1. WELDING PROCEDURES FOR STRUCTURAL STEEL - WELDING PROCEDURES FOR
3. WELDING TECHNIQUE
B. TEMPORARY WELDS - TEMPORARY WELDS REQUIRED FOR FABRICATION
C. TACK WELDS - TACKS WELDS THAT ARE TO BE INCORPORATED INTO
5. IDENTIFICATION - IDENTIFY ALL WELDS IN ONE OF THE FOLLOWING WAYS:
B. IDENTIFY ALL WORK PERFORMED BY EACH WELDER, WELDING
A. NONDESTRUCTIVE EXAMINATION - THE WELDING IS SUBJECT TO INSPECTION AND
B. PERFORM TESTING USING AN APPROVED INSPECTION OR TESTING LABORATORY OR
D. MAGNETIC PARTICLE INSPECTION OF THE WELDS AND EXTENT IDENTIFIED ON
C. PERFORM 100% VISUAL INSPECTION OF ALL COMPLETED WELDS. ALL COMPLETED
GENERAL REQUIREMENTS
A. WELDING OF STRUCTURAL STEEL
SHALL CONFORM TO THE REQUIREMENTS SPECIFIED IN THE PROVISIONS
AWS D1.1, SUBSECTION 4.1 OR SHALL BE QUALIFIED BY TESTS AS
BE REMOVED, REWELDED AND RETESTED TO ENSURE CONFORMANCE.
E. ULTRASONIC TESTING - MAKING, EVALUATING AND REPORTING ULTRASONIC TESTING
OF WELDS SHALL CONFORM TO THE REQUIREMENTS OF AWS D1.1, SECTION 6, PART C.
THE ULTRASONIC EQUIPMENT SHALL BE CAPABLE OF MAKING A PERMANENT RECORD
OF THE TEST INDICATIONS. A RECORD SHALL BE MADE OF EACH WELD TESTED.
SHALL NOT BE REPRODUCTIONS OF CONTRACT DRAWINGS. INCLUDE COMPLETE
INFORMATION FOR THE FABRICATION AND ERECTION OF THE STRUCTURE’S COMPONENTS,
INCLUDING THE LOCATION, TYPE, AND SIZE OF BOLTS, WELDS, MEMBER SIZES AND
LENGTHS, CONNECTION DETAILS, BLOCKS, COPES, AND CUTS. USE AWS A2.4 STANDARD
WELDING SYMBOLS. MEMBER SUBSTITUTIONS OF DETAILS SHOWN ON THE CONTRACT
DRAWINGS SHALL BE CLEARLY HIGHLIGHTED ON THE FABRICATION DRAWINGS. EXPLAIN
THE REASONS FOR ANY DEVIATIONS FROM THE CONTRACT DRAWINGS.
ORDERS, MILL ORDERS, SHOP ORDERS AND WORK ORDERS FOR ALL MATERIALS ORDERS
AND ITEMS USED IN THE WORK. WHERE MILL TESTS ARE REQUIRED PURCHASE ORDERS
SHALL CONTAIN THE TEST SITE ADDRESS AND THE NAME OF THE TESTING AGENCY.
SHAPE, ETC.) TO BE SUPPLIED TO THE FABRICATOR, THE HEAT NUMBER AND THE
BE MADE.
A. STRUCTURAL FABRICATION - MATERIAL MUST BE STRAIGHT BEFORE BEING LAID
OFF OR WORKED. IF STRAIGHTENING IS NECESSARY IT SHALL BE DONE BY
METHODS THAT WILL NOT IMPAIR THE METAL. SHARP KINKS OR BENDS SHALL
BE ACCEPTED EXCEPT WHERE WELDING IS DEFINITELY SPECIFIED, INDICATED
OR OTHERWISE APPROVED. WHERE HEATING IS REQUIRED, PRECAUTIONS SHALL
BE TAKEN TO AVOID OVERHEATING THE METAL AND IT SHALL BE ALLOWED TO
COOL IN A MANNER THAT WILL NOT IMPAIR THE ORIGINAL PROPERTIES OF THE
METAL. SHEARING SHALL BE ACCURATE AND ALL PORTIONS OF THE WORK SHALL
BE NEATLY FINISHED. CORNERS SHALL BE SQUARE AND TRUE UNLESS
OTHERWISE SHOWN. RE-ENTRANT CUTS SHALL BE FILLETED TO A MINIMUM
RADIUS OF 3/4 INCH UNLESS OTHERWISE APPROVED. FINISHED MEMBERS SHALL
BE FREE OF TWISTS, BENDS AND OPEN JOINTS.
MEASURED BY AN APPROVED CALIBRATED STEEL TAPE OF APPROXIMATELY THE
SAME TEMPERATURE AS THE MATERIAL BEING MEASURED. THE OVERALL
DIMENSIONS OF AN ASSEMBLED STRUCTURAL UNIT SHALL BE WITHIN AN
MECHANICALLY GUIDED OR HAND-GUIDED TORCHES, PROVIDED AN ACCURATE
PROFILE WITH A SURFACE THAT IS SMOOTH AND FREE FROM CRACKS AND
NOTCHES IS OBTAINED. SURFACES AND EDGES TO BE WELDED SHALL BE
PREPARED IN ACCORDANCE WITH AWS D1.1, SUBSECTION 5.15. WHERE
STRUCTURAL STEEL IS NOT TO BE WELDED, CHIPPING OR GRINDING WILL
NOT BE REQUIRED EXCEPT AS NECESSARY TO REMOVE SLAG AND SHARP EDGES
OF MECHANICALLY GUIDED OR HAND-GUIDED CUTS NOT EXPOSED TO VIEW.
HAND-GUIDED CUTS WHICH ARE TO BE EXPOSED OR VISIBLE SHALL BE
CHIPPED, GROUND OR MACHINED TO SOUND METAL.
NONDESTRUCTIVE TESTING PERSONNEL, WELDERS, WELDING OPERATORS, AND
TACKERS HAVE BEEN QUALIFIED AND THE SUBMITTALS APPROVED BY THE
CONTRACT MUST BE QUALIFIED IN ACCORDANCE WITH THE APPLICABLE
REQUIREMENTS OF AWS D1.1. WELDERS, WELDING OPERATORS, AND TACKERS
CONSIDERED QUALIFIED FOR THE WELDING PROCEDURE USED.
CONTRACTING OFFICER, WELDERS, WELDING OPERATORS, AND TACKERS
QUALIFIED BY TEST WITHIN THE PREVIOUS 6 MONTHS MAY BE ACCEPTED FOR
THIS CONTRACT WITHOUT RE-QUALIFICATION IF ALL THE FOLLOWING
CONDITIONS ARE MET:
1. COPIES OF THE WELDING PROCEDURE SPECIFICATIONS, THE PROCEDURE
QUALIFICATION TEST RECORDS, AND THE WELDER, WELDING OPERATOR,
AND TACKER QUALIFICATION TEST RECORDS ARE SUBMITTED AND APPROVED
IN ACCORDANCE WITH THE SPECIFIED REQUIREMENTS FOR DETAIL DRAWINGS.
2. TESTING WAS PERFORMED BY AN APPROVED TESTING LABORATORY,
TECHNICAL CONSULTANT, OR THE CONTRACTOR’S APPROVED QUALITY
CONTROL ORGANIZATION.
REQUIREMENTS OF THIS SPECIFICATION AND IS APPLICABLE TO WELDING
CONDITIONS ENCOUNTERED UNDER THIS CONTRACT.
CONFORM TO THE REQUIREMENTS OF THIS SPECIFICATION AND ARE
APPLICABLE TO WELDING CONDITIONS ENCOUNTERED UNDER THIS CONTRACT.
TACKER TO WORK UNDER THIS CONTRACT, SUBMIT THE NAMES OF THE WELDERS,
WELDING OPERATORS, AND TACKERS TO BE EMPLOYED, AND CERTIFICATION THAT
EACH INDIVIDUAL IS QUALIFIED AS SPECIFIED. THE CERTIFICATION MUST
STATE THE TYPE OF WELDING AND POSITIONS FOR WHICH THE WELDER, WELDING
OPERATOR, OR TACKER IS QUALIFIED, THE CODE AND PROCEDURE UNDER WHICH
THE INDIVIDUAL IS QUALIFIED, THE DATE QUALIFIED, AND THE NAME OF THE
FIRM AND PERSON CERTIFYING THE QUALIFICATION TESTS. KEEP THE
CERTIFICATION CURRENT, ON FILE, AND FURNISH 3 COPIES.
C. CERTIFICATES - BEFORE ASSIGNING ANY WELDER, WELDING OPERATOR, OR
3. THE PREVIOUSLY QUALIFIED WELDING PROCEDURE CONFORMS TO THE
4. THE WELDER, WELDING OPERATOR, AND TACKER QUALIFICATION TESTS
B. PREVIOUS PERSONNEL QUALIFICATIONS - AT THE DISCRETION OF THE
C. STRUCTURAL STEEL FABRICATION - STRUCTURAL STEEL MAY BE CUT BY
B. DIMENSIONAL TOLERANCES FOR STRUCTURAL WORK - DIMENSIONS SHALL BE
PROCEDURES" IN SPECIFICATION SECTION 09 97 02, "PAINTING: HYDRAULIC STRUCTURES".
SPECIFICATION SECTION 09 97 02, "PAINTING: HYDRAULIC STRUCTURE".
PREPARED IN ACCORDANCE WITH AISC 326, AISC 316 AND AISC 317. FABRICATION DRAWINGS
SUBMIT FABRICATION DRAWINGS, ANSI "D" SIZE, FOR APPROVAL PRIOR TO FABRICATION.
1. ALL SUBMITTALS SHALL BE SUBMITTED IN ACCORDANCE WITH PARAGRAPH "SUBMITTAL
2. THE COMPLETED STRUCTURES SHALL BE CLEANED AND PAINTIED IN ACCORDANCE WITH
ALLOWABLE VARIATION OF 3/32 INCH.
BE CAUSE FOR REJECTION OF THE MATERIAL. MATERIAL WITH WELDS WILL NOT
CONTRACT FOR LEVELS I OR II IN THE APPLICABLE NON-DESTRUCTIVE TESTING
CONTRACTING OFFICER AND THE DESIGN ENGINEER OF RECORD.
WHO MAKE ACCEPTABLE PROCEDURE QUALIFICATION TEST WELDS WILL BE
THE APPLICABLE REQUIREMENTS OF AWS D1.5.
A CERTIFICATE FROM THE MILL STATING, FOR EACH ARTICLE (SHEET, PLATE, BAR,
SPECIFIC REASON TO QUESTION THE TACKER’S ABILITY. IN SUCH A CASE,
REQUIREMENTS, THE GOVERNMENT RESERVES THE RIGHT TO REJECT MATERIAL OR
NONDESTRUCTIVE AND DESTRUCTIVE TESTS TO DETERMINE COMPLIANCE WITH PARAGRAPH
CHEMICAL AND PHYSICAL PROPERTIES OF THE METAL FROM WHICH THE ARTICLE IS TO
A. EACH WELDER, WELDING OPERATOR, AND TACKER ASSIGNED TO WORK ON THIS
THE REQUIREMENTS OF AWS D1.5.
APPLICABLE REQUIREMENTS OF AWS D1.1 AND ASTM E 709.
THE AREA BY SUITABLE METHODS TO ENSURE THAT THE DEFECT HAS BEEN ELIMINATED.
3.
4. DRAWING REQUIREMENTS
5. MATERIAL ORDERS - THE CONTRACTOR SHALL FURNISH FOUR COPIES OF PURCHASE
6. REPORTS OF MATERIAL - THE CONTRACTOR SHALL FURNISH THE CONTRACTING OFFICER
7. FABRICATION
8. DO NOT COMMENCE WELDING UNTIL WELDING PROCEDURES, INSPECTORS,
9. WELDER, WELDING OPERATOR, AND TACKER QUALIFICATION
10. INSPECTOR QUALIFICATION
11. SAFETY
12. WELDING EQUIPMENT AND MATERIALS - ALL WELDING EQUIPMENT, ELECTRODES,
13. WELDING OPERATIONS
14. QUALITY CONTROL
15. STANDARDS OF ACCEPTANCE - DIMENSIONAL TOLERANCES FOR WELDED CONSTRUCTION,
16. GOVERNMENT INSPECTION AND TESTING - IN ADDITION TO THE INSPECTION AND
17. CORRECTIONS AND REPAIRS - IF INSPECTION OR TESTING INDICATES DEFECTS
BORNE BY THE CONTRACTOR IF UNSATISFACTORY WELDS ARE DISCOVERED, OR BY THE
STRUCTURAL STEEL SHALL BE PREQUALIFIED AS DESCRIBED IN AWS D1.1.
GOVERNMENT’S OWN FORCES OR UNDER A SEPARATE CONTRACT FOR INSPECTION AND
APPLICABLE PROVISIONS OF AWS D1.1. WELDING SHALL BE SUCH AS TO
PRESCRIBED BY AWS D1.1, SUBSECTION 5.3 TO MAINTAIN LOW
SCHEDULE OF WELDING PROCEDURES. ONLY LOW HYDROGEN ELECTRODES
REGARDLESS OF THE THICKNESS OF THE STEEL. A CONTROLLED
PERFORMED AS REQUIRED BY AWS D1.1/D1.1M, SUBSECTION 3.5 AND
WITH AWS D1.1, SECTION 5 AND OTHER APPLICABLE PROVISIONS
WITH AWS D1.1, SUBSECTION 5.15.
PRESCRIBED FOR PERMANENT WORK. TEMPORARY WELDS SHALL BE
REQUIREMENTS OF AWS D1.1, SECTION 6.
OF ACCEPTANCE. CONFORM PROCEDURES AND TECHNIQUES FOR INSPECTION WITH
OF AWS D1.1 AND THE CONTRACT DRAWINGS. WELDS NOT PASSING SHALL
ALL OTHER SHAPES - ASTM A36
W SHAPES - ASTM A992, GR 50.
ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING, UNLESS NOTED OTHERWISE:
THAT NO UNACCEPTABLE DEFECT IS PRESENT.
A DEFECT IS THOUGHT TO HAVE BEEN REMOVED, AND BEFORE RE-WELDING, EXAMINE
IN ACCORDANCE WITH THE APPROVED PROCEDURES. WHEREVER A DEFECT IS REMOVED
TO THE CONTRACTING OFFICER FOR APPROVAL.
18. ANY MODIFICATIONS OR ADDITIONS TO THE CONTRACT PLANS SHALL BE SUBMITTED
S-201
T A
IN
T E
R G
A T
E R
E H
A B
J O
H N W F
L A
N N
IG
A N
H A
Y S I, V
A
P O
U N
D R
IV
E R
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
H U
N T
IN
G T
O N D
IS
T R
IC
T
H U
N T
IN
G T
O N
W E
S T V
IR
G
IN
IA
1 4
C L
C
J J
K
N O
T E
S
WELDS. ANY INDICATION OF A DEFECT IS REGARDED AS A DEFECT, UNLESS
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, JUNE 30, 2004" (RCSC).
IN SECTION 8.1 OF THE "RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS, SPECIFICATION FOR AND SHALL BE HOT-DIPPED GALVANIZED. ALL BOLTS SHALL BE INSTALLED ’SNUG TIGHT’ AS SPECIFIED
19. BOLTS - ALL BOLTS SHALL MEET THE REQUIREMENTS OF ASTM A325, UNLESS OTHERWISE NOTED, M A
R C
H
P J L
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
SHEET OF
fiof Engineers
US Army Corps
Huntington District
46’-0" 50’-0" 50’-0" 50’-0" 50’-0" 46’-0"
6 GATES @ 42’-0" AND 5 PIERS @ 8’-0" = 292’-0"
FACE OF LEFT ABUTMENT FACE OF RIGHT ABUTMENT
CREST EL. 1410.00
EL. 1400.00
MATCH C OF
EXIST’G VERTICAL
MATCH C OF
EXIST’G VERTICAL
21’-0" (FIELD VERIFY)
0"
FI
ELD
V
ERI
FY
BRACE FRAME
INSTALL NEW
EXISTING STRUT
ARM TYP.
INSTALL NEW
BRACE FRAME
TYP. ALL ARMS
INSTALL COVER P
TOP GIRDER ONLY
INSTALL COVER P
(BOTH SIDES)
INSTALL COVER P’S
SCALE: �"=1’-0"
GATE NO. 1 GATE NO. 2 GATE NO. 3 GATE NO. 4 GATE NO. 5 GATE NO. 6
L
L
L
SCALE: �"=1’-0"
C
SECTION
SCALE: �"=1’-0"
L
NOTES:
P L
A N
.d g n
2 4
IP
P
W P :d m s \P
L A
N .d g n
H E
D X J J
K
:1
/1
/2
L
R H -A
P -E
C -C
A E \A
P P
S \L
R H
W o rk s p a c e \W o rk s p a c e \P ro je c tW is e I n te rP lo t
O rg a n iz e r\ m is c \d e s ig n s c ri p t\ s td v .p e n d e fa u lt a tt a c h e d f ro m d ia lo g
-A
U G -2
:0
P O
U N
D R
IV
E R
J O
H N W F
L A
N N
A G
A N L
A K
E
H A
Y S I, V
A
T A
IN
T E
R G
A T
E R
E H
A B
H
N T
IN
G T
O N D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
S
N T
IN
G T
O N
W E
S T V
IR
G
IN
IA
S-701
J J
K
C L
C
S-701
S-702
B
S-702
A
S-701
C
S-702
L
SPILLWAY TAINTER GATE
TYPICAL PLAN VIEW
UPSTREAM ELEVATION
SPILLWAY
SHALL MATCH THE COLOR OF EXISTING STRUCTURE AFTER MODIFICATIONS ARE COMPLETE.
7. ALL UNCOATED SURFACES SHALL BE PAINTED WITH A TWO-PART EPOXY PAINT AND
6. ALL SURFACES TO BE WELDED SHALL BE FREE OF PAINT AND OTHER FOREIGN DEBRIS.
5. ALL BOLT HOLES SHALL BE �" DIAMETER UNLESS NOTED OTHERWISE.
SPECIFIED IN DRAWINGS.
HOT DIP GALVANIZED, UNLESS NOTED OTHERWISE. BOLT LENGTH TO BE AS
4. ALL BOLTS SHALL BE ASTM A325, �" DIA. HEAVY HEX HEAD WITH WASHER AND NUT,
3. ALL WELDS SHALL BE MADE USING E70XX ELECTRODES.
TO BE REHABILITATED.
2. DRAWING AND QUANTITIES SHOWN ARE FOR ONE (1) GATE. ALL SIX (6) GATES ARE
OF THE NEW CROSS-BRACE FRAME SHOWN IN THESE PLANS.
1. ALL DIMENTIONS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION
G E
N E
R A
L V
IE
W S
P J L
/1
/2
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
SHEET OF
fiof Engineers
13’-10"
27’-8"
13’-10"FIELD VERIFY
ARM TYPICAL
EXISTING STRUT
TYP.
�"X9" P
ARM TYP.
EXISTING STRUT
SPLICE AS NECESSARY
�"X9" COVER P
ARM TYPICAL
EXISTING STRUT
W10X33
4"
�" ATTACHMENT LUGS
WORKING LINE
BRACE FRAME
INSTALLATION OF NEW
TO FACILITATE
L3X3X�" BEAM SEAT
OPTIONAL
THIS SHEET
SEE SPLICE DETAIL
EACH SIDE OF ARM
�"X9" COVER P TYP.
ALL COVER P CORNERS
�" RADIUS TYP. ON
1" MAX. TYP.
1" MAX. TYP.
BRACE
C OF EXIST.
BRACE
C OF EXIST.
BRACE
C OF EXIST.
�"X9"X16’-6" P FIELD CUT TO LENGTH TYP. EACH SIDE EACH ARM
�" P
EXISTING GUSSETT P
BRACE FRAME
SCALE: �"=1’-0"
SECTION
L
SCALE: 1�"=1’-0"
SECTION
p la n .d g n
3 4
IP
P
W P :d m s \p la n .d g n
H E
D X J J
K
.6
:1
/1
/2
L
R H -A
P -E
C -C
A E \A
P P
S \L
R H
W o rk s p a c e \W o rk s p a c e \P ro je c tW is e I n te rP lo t
O rg a n iz e r\ m is c \d e s ig n s c ri p t\ s td v .p e n d e fa u lt a tt a c h e d f ro m d ia lo g
-A
U G -2
U N
D R
IV
E R
J O
H N W F
L A
N N
A G
A N L
A K
E
H A
Y S I, V
A
T A
IN
T E
R G
A T
E R
E H
N T
IN
G T
O N D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
N T
IN
G T
O N
W E
S T V
IR
G
S-702
J
K
C L
C
S-702
E
S-703
S-703
S-701
A
L
SCALE: 1�"=1’-0"
COVER PLATE
SPLICE DETAIL
L
SCALE: �"=1’-0"
DETAIL
E
S-7
S-701
L
TYP.
SHEET S-703
SEE SEC. D
CUT TO LENGTH
25% P.T.
TYP.
SCALE: 1�"=1’-0"
DETAIL
S-702
S-702
L
100% M.T.
100% U.T.
B.G.
CONTRACTOR SHALL VERIFY
ORIGINAL SHOP DWGS.
SLOPES AS GIVEN ON *
D E
T A
IL
S
L
L
L
P J L
/1
/2
12’-0"
2" TYP.
R
HORIZONTAL GIRDER
C EXISTING WF33X118
L
L
L
SCALE: 1�"=1’-0"S-701
B VIEW
100% P.T.
TYP.
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
SHEET OF
fiof Engineers
�" P TYP.
13’-10" 13’-10"
27’-8"
W10X33
W10X33
CUT TO FIT TYP.
FIELD MEASURE
W10X33
FIELD VERIFY
CUT TO LENGTH
9"X�" P
FIELD CUT
TYP
1�"
2�"
8"
EXISTING
STRUT ARM
W10X33
FIELD VERIFY
CUT TO LENGTH
EXISTING
STRUT ARM
�" P
TYP
W10X33 TYP.
INSTALL �"
STIFF. P TYP.
INSTALL �"
STIFF. P TYP.�" P
TYP
3�" LONG BOLT
FIELD DRILL FOR
2’-9" TYP.
8" TYP.
5�"
1"1" 1�" 1�"
TYP.
MIN. 1" EDGE DIST.
2" C. TO C.
LONG BOLTS
INSTALL 2-2�"
ALLOW �" TYP.
SHIM AS NEEDED
W10X33
(TYP. ALL 3 GIRDERS)
2" DIA. DRAIN HOLES
3’-6"6’-10"7’-0"6’-10"3’-6"
TYPICAL
L 4X3X�"
W10X33
GUSSET P
1’-1�"X8�"X�"
GUSSET P
2’-0"X8�"X�"
GUSSET P
9"X6"X�"
GUSSET P
2’-0"X6�"X�"
GUSSET P
1’-1�"X8�"X�"
GUSSET P
2’-0"X8�"X�"
GUSSET P
2’-0"X8�"X�"
GUSSET P
9"X6"X�"
GUSSET P
9"X6"X�" GUSSET P
2’-0"X6�"X�"
GUSSET P
2’-0"X6�"X�"
TYP.
W10X33
GUSSET P
@ C/L ALL
�" STIFF. TYP.
T
Y P
TYPICAL
L4X3X�"
GUSSET P
1’-1�"X6�"X�"
GUSSET P
1’-1�"X6�"X�"
33’-2"
1�" TYP.
5’-11"
7’-11"
13’-2�"
13’-11�"
W10X33
6’-11"
WEB STIFF. TYP.
1’-0"
13’-11�" 13’-10"
W10X33
1’ 4"
1’-6�"
1’-4"
" 1’-7"
1�
1�
9�"
11"
SECTION
SCALE: 3"=1’-0"
L
SCALE: �"=1’-0"
C
L
L
L
T Y
P
TYP
SECTION
SCALE: 3"=1’-0"
D
SCALE: 3"=1’-0"
DETAIL
L
T Y
P
LL
P L
A N
.d g n
4 4
IP
P
W P :d m s \P
L A
N .d g n
H E
D X J J
K
:1
/1
/2
L
R H -A
P -E
C -C
A E \A
P P
S \L
R H
W o rk s p a c e \W o rk s p a c e \P ro je c tW is e I n te rP lo t
O rg a n iz e r\ m is c \d e s ig n s c ri p t\ s td v .p e n d e fa u lt a tt a c h e d f ro m d ia lo g
-A
U G -2
U N
D R
IV
E R
J O
H N W F
L A
N N
A G
A N L
A K
E
H A
Y S I, V
A
T A
IN
T E
R G
A T
E R
E H
N T
IN
G T
O N D
IS
T R
IC
T
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
N T
IN
G T
O N
W E
S T V
IR
G
S-703
J
K
C L
C
S-703
S-702
2 S-703
C
S-703
D
S-702
S-703
MAKE SIX (6)
L
NOT SHOWN FOR CLARITY
NOTE: �"X9" COVER P
S-702 FOR SLOPE
-SEE SECTION A,*
SCALE: 6"=1’-0"
SHIM PACK DETAIL
DETAIL - BRACE FRAME
L
D E
T A
IL
S
PROVIDE �", �", �" THICK
AS SHOWN TWELVE (12) EACH PER GATE
A
S-703
SCALE: �"=1’-0"S-703
A TOP VIEW
L
L L
LL L
L
L L
LL
T Y
P
T Y
P
T Y
P
T Y
P
L
TYP
B.G.
TYP. ALL
GUSSETS
25% UT
P J L
/1
/2
G-1
G-2
G-3
WT. APPROX. 4,000 LB
ADJUST DIMENSIONS TO FIT GATE
FABRICATION OF THIS BRACE FRAME
FIELD VERIFY ALL DIMENSIONS PRIOR TO
E
S-703
E
S-703
L
C WORKING POINT
LC WEB STIFFENER
DIMENSIONS SHOWN SYMETRICAL ABOUT THE CL
SCALE: 3"=1’-0"S-703
E SECTION G-2
SCALE: 3"=1’-0"S-703
F SECTION G-1 & G-3
LC WEB STIFFENER
TYP.
TYP.
TO GUSSET PL
ANGLE MEMBERS
SPACING FOR
BOLT HOLE
TYPICAL
MATERIAL: NAVAL BRASS, COPPER ALLOY C464 OR EQUAL
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
SHEET OF
fiof Engineers
EXHIBIT B
LAB RESULTS
Analysis Report
Client:
Project/Test Address:
Pinnacle Env. Consultants (WV)
7469 Whitepine Rd
Telephone: 800.347.4010
Richmond, VA 23237
Environmental Hazards Services, L.L.C.
Flannigan PRC 72084030;
Client Number:
50-3547
Fax Number:
304-757-5205Laboratory Results
Analyzed Date:
Client Sample Number
Lab Sample Number
Pb (ug/g) ppm
Lead Paint Chip
07/31/2017
07/31/2017
17-07-04258
Reported Date:
Received Date:
Report Number:
400 D Prestige Park Hurricane, WV 25526
Narrative
ID
07/31/2017
Collection Location % Pb by Wt.
07/27/2017Collection Date:
117-07-04258-001 51000 5.1
Missy Kanode
QA/QC Clerk
Analysis Method: EPA SW846 7000B
The HUD lead guidelines for lead paint chips are 0.50% by Weight, 5000 ppm, or 1.0 mg/cm². The Reporting Limit (RL) for samples prepared by ASTM E-1979-12 is 10.0 ug Total Pb. The RL for samples prepared by EPA SW846 3050B is 25.0 ug Total Pb. Paint chip area and results are calculated based on area measurements determined by the client. All internal quality control requirements associated with this batch were met, unless otherwise noted.
LEGEND Pb= lead ug = microgram ppm = parts per million ug/g = micrograms per gram Wt. = weight
Reviewed By Authorized Signatory:
Preparation Method: ASTM E-1979-12
The condition of the samples analyzed was acceptable upon receipt per laboratory protocol unless otherwise noted on this report. Results represent the analysis of samples submitted by the client. Sample location, description, area, etc., was provided by the client. Results reported above in mg/cm3 are calculated based on area supplied by client. This report shall not be reproduced except in full, without the written consent of the Environmental Hazards Service, L.L.C. California Certification #2319 NY ELAP #11714.
Page 1of1
EXHIBIT C
PHOTOS
Fig. 1 Upstream view of spillway gates from parking area
Fig. 2 Downstream view of spillway gates from concrete apron
Fig. 3 Downstream view of work area
Fig. 4 Downstream view of work area
Fig. 5 Close up view of gate
Fig. 6 Close up view of gate strut arm
| Blank Page |