EXHIBIT A

DRAWINGS

HUNTINGTON DISTRICT

OF ENGINEERS

US ARMY CORPS

HAYSI, VIRGINIA

JOHN W. FLANNAGAN LAKE

REHABILITATION

SPILLWAY TAINTER GATE

PLANS FOR

JUNE 2017

D. RENEWAL OF QUALIFICATION - RE-QUALIFICATION OF A WELDER OR WELDING

OPERATOR IS REQUIRED UNDER ANY OF THE FOLLOWING CONDITIONS:

1. IT HAS BEEN MORE THAN 6 MONTHS SINCE THE WELDER OR WELDING OPERATOR

HAS USED THE SPECIFIC WELDING PROCESS FOR WHICH HE IS QUALIFIED.

OPERATOR’S ABILITY TO MAKE WELDS THAT MEET THE REQUIREMENTS OF

THESE SPECIFICATIONS.

3. THE WELDER OR WELDING OPERATOR WAS QUALIFIED BY AN EMPLOYER OTHER

THAN THOSE FIRMS PERFORMING WORK UNDER THIS CONTRACT, AND A

QUALIFICATION TEST HAS NOT BEEN TAKEN WITHIN THE PAST 12 MONTHS.

SUBMIT AS EVIDENCE OF CONFORMANCE ALL RECORDS SHOWING PERIODS OF

EMPLOYMENT, NAME OF EMPLOYER WHERE WELDER, OR WELDING OPERATOR,

WAS LAST EMPLOYED, AND THE PROCESS FOR WHICH QUALIFIED.

4. A TACKER WHO PASSES THE QUALIFICATION TEST IS CONSIDERED ELIGIBLE

TO PERFORM TACK WELDING INDEFINITELY IN THE POSITIONS AND WITH

THE PROCESSES FOR WHICH HE IS QUALIFIED, UNLESS THERE IS SOME

THE TACKER IS REQUIRED TO PASS THE PRESCRIBED TACK WELDING TEST.

ALL PERSONNEL PERFORMING NON-DESTRUCTIVE INSPECTION SHALL BE CERTIFIED

UNDER ASNT-RP SNT-TC-1A WITHIN A PERIOD OF 1 YEAR BEFORE THE DATE OF

METHOD. THE INSPECTOR MAY BE SUPPORTED BY ASSISTANT WELDING INSPECTORS WHO

ARE NOT QUALIFIED TO ASNT RP SNT-TC-1A, AND ASSISTANT INSPECTORS MAY

PERFORM SPECIFIC INSPECTION FUNCTIONS UNDER THE SUPERVISION OF THE QUALIFIED

INSPECTOR. OTHER QUALIFICATIONS OR CERTIFICATION MAY BE ACCEPTED AT THE

CONTRACTING OFFICER’S DISCRETION. QUALIFIED INSPECTORS SHALL BE ABLE TO

JUDGE THE ACCEPTABILITY OR NON-ACCEPTABILITY OF WELDS IN CONFORMANCE WITH

SAFE WELDING PRACTICES AND SAFETY PRECAUTIONS DURING WELDING MUST CONFORM

TO AWS Z49.1.

WELDING WIRE, AND FLUXES MUST BE CAPABLE OF PRODUCING SATISFACTORY WELDS

WHEN USED BY A QUALIFIED WELDER OR WELDING OPERATOR PERFORMING QUALIFIED

WELDING PROCEDURES. ALL WELDING EQUIPMENT AND MATERIALS SHALL COMPLY WITH

THE CONTRACTOR SHALL SUBMIT A COMPLETE SCHEDULE OF WELDING

PROCEDURES FOR EACH STEEL STRUCTURE TO BE WELDED. THE SCHEDULE

PRESCRIBED IN AWS D1.1 SECTION 4. THE SCHEDULE SHALL PROVIDE

DETAILED PROCEDURE SPECIFICATIONS AND TABLES OR DIAGRAMS SHOWING

THE PROCEDURES TO BE USED FOR EACH REQUIRED JOINT. WELDING

PROCEDURES MUST INCLUDE FILLER METAL, PREHEAT, AND INTERPASS

TEMPERATURE REQUIREMENTS. EACH WELDING PROCEDURE SHALL BE CLEARLY

IDENTIFIED AS BEING PREQUALIFIED OR REQUIRED TO BE QUALIFIED BY

TESTS. WELDING PROCEDURES MUST SHOW TYPES AND LOCATIONS OF WELDS

DESIGNATED OR IN THE SPECIFICATIONS TO RECEIVE NONDESTRUCTIVE

EXAMINATION.

2. WELDING PROCESS - WELDING OF STRUCTURAL STEEL SHALL BE BY AN

ELECTRIC ARC WELDING PROCESS USING A METHOD WHICH EXCLUDES THE

ATMOSPHERE FROM THE MOLTEN METAL AND SHALL CONFORM TO THE

MINIMIZE RESIDUAL STRESSES, DISTORTION AND SHRINKAGE.

A. FILLER METAL - THE ELECTRODE, ELECTRODE-FLUX COMBINATION AND

GRADE OF WELD METAL SHALL CONFORM TO THE APPROPRIATE AWS

SPECIFICATION FOR THE BASE METAL AND WELDING PROCESS BEING

USED OR SHALL BE AS SHOWN WHERE A SPECIFIC CHOICE OF AWS

SPECIFICATION ALLOWABLES IS REQUIRED. THE AWS DESIGNATION

OF THE ELECTRODES TO BE USED SHALL BE INCLUDED IN THE

SHALL BE USED FOR MANUAL SHIELDED METAL-ARC WELDING

TEMPERATURE STORAGE OVEN SHALL BE USED AT THE JOB SITE AS

MOISTURE OF LOW HYDROGEN ELECTRODES.

B. PREHEAT AND INTERPASS TEMPERATURE - PREHEATING SHALL BE

5.6 OR AS OTHERWISE SPECIFIED EXCEPT THAT THE TEMPERATURE

OF THE BASE METAL SHALL BE AT LEAST 70 DEGREES F. THE

WELDMENTS TO BE PREHEATED SHALL BE SLOWLY AND UNIFORMLY

HEATED BY APPROVED MEANS TO THE PRESCRIBED TEMPERATURE,

HELD AT THAT TEMPERATURE UNTIL THE WELDING IS COMPLETED AND

THEN PERMITTED TO COOL SLOWLY IN STILL AIR.

4. WORKMANSHIP - WORKMANSHIP FOR WELDING SHALL BE IN ACCORDANCE

OF THESE REQUIREMENTS.

A. PREPARATION OF BASE METAL - PRIOR TO WELDING THE CONTRACTOR

SHALL INSPECT SURFACES TO BE WELDED TO ASSURE COMPLIANCE

AND ERECTION SHALL BE MADE UNDER THE CONTROLLED CONDITIONS

MADE USING LOW-HYDROGEN WELDING ELECTRODES AND BY WELDERS

QUALIFIED FOR PERMANENT WORK AS SPECIFIED IN THESE

SPECIFICATIONS. PREHEATING FOR TEMPORARY WELDS SHALL BE AS

REQUIRED BY AWS D1.1 FOR PERMANENT WELDS EXCEPT THAT THE

MINIMUM TEMPERATURE SHALL BE 120 DEGREES F IN ANY CASE.

IN MAKING TEMPORARY WELDS ARCS SHALL NOT BE STRUCK IN

OTHER THAN WELD LOCATIONS. EACH TEMPORARY WELD SHALL BE

REMOVED AND GROUND FLUSH WITH ADJACENT SURFACES AFTER

SERVING ITS PURPOSE.

THE PERMANENT WORK SHALL BE SUBJECT TO THE SAME QUALITY

REQUIREMENTS AS THE PERMANENT WELDS AND SHALL BE CLEANED

AND THOROUGHLY FUSED WITH PERMANENT WELDS. PREHEATING

SHALL BE PERFORMED AS SPECIFIED ABOVE FOR TEMPORARY WELDS.

MULTIPLE-PASS TACK WELDS SHALL HAVE CASCADED ENDS.

DEFECTIVE TACK WELDS SHALL BE REMOVED BEFORE

PERMANENT WELDING.

A. SUBMIT WRITTEN RECORDS TO INDICATE THE LOCATION OF WELDS

MADE BY EACH WELDER, WELDING OPERATOR, OR TACKER.

OPERATOR, OR TACKER WITH AN ASSIGNED NUMBER, LETTER, OR

SYMBOL TO IDENTIFY WELDS MADE BY THAT INDIVIDUAL. THE

CONTRACTING OFFICER MAY REQUIRE WELDERS, WELDING OPERATORS,

AND TACKERS TO APPLY THEIR SYMBOL NEXT TO THE WELD BY MEANS

OF RUBBER STAMP, FELT-TIPPED MARKER WITH WATERPROOF INK, OR

OTHER METHODS THAT DO NOT CAUSE AN INDENTATION IN THE METAL.

PLACE THE IDENTIFICATION MARK FOR SEAM WELDS ADJACENT TO THE

WELD AT 3 FOOT INTERVALS. IDENTIFICATION WITH DIE STAMPS OR

ELECTRIC ETCHERS IS NOT ALLOWED.

TESTS. WHEN MATERIALS OR WORKMANSHIP DO NOT CONFORM TO THE SPECIFICATION

TECHNICAL CONSULTANT; OR IF APPROVED, THE CONTRACTOR’S INSPECTION AND

TESTING PERSONNEL MAY BE USED INSTEAD OF THE COMMERCIAL INSPECTION OR

TESTING LABORATORY OR TECHNICAL CONSULTANT.

WELDS SHALL BE CLEANED AND CAREFULLY EXAMINED FOR INSUFFICIENT THROAT

OR LEG SIZES, CRACKS, UNDERCUTTING, OVERLAP, EXCESSIVE CONVEXITY OR

REINFORCEMENT AND OTHER SURFACE DEFECTS TO ENSURE COMPLIANCE WITH THE

THE CONTRACT DRAWINGS TO DETERMINE CONFORMANCE WITH PARAGRAPH STANDARDS

DETAILS OF WELDS, AND QUALITY OF WELDS WITH THE APPLICABLE REQUIREMENTS

TESTS PERFORMED BY THE CONTRACTOR FOR QUALITY CONTROL, THE GOVERNMENT MAY

PERFORM INSPECTION AND TESTING FOR ACCEPTANCE TO THE EXTENT DETERMINED BY

THE CONTRACTING OFFICER. THE COSTS OF SUCH INSPECTION AND TESTING WILL BE

GOVERNMENT IF THE WELDS ARE SATISFACTORY. THE WORK MAY BE PERFORMED BY THE

TESTING. THE GOVERNMENT RESERVES THE RIGHT TO PERFORM SUPPLEMENTAL

STANDARDS OF ACCEPTANCE.

IN THE WELD JOINTS, REPAIR DEFECTIVE WELDS USING A QUALIFIED WELDER OR

WELDING OPERATOR AS APPLICABLE. CONDUCT CORRECTIONS IN ACCORDANCE WITH

AWS D1.1 AND THE PROVISIONS OF THESE REQUIREMENTS. REPAIR ALL DEFECTS

AND REPAIR BY WELDING IS NOT REQUIRED, BLEND THE AFFECTED AREA INTO THE

SURROUNDING SURFACE TO ELIMINATE SHARP NOTCHES, CREVICES, OR CORNERS. AFTER

REPAIRED WELDS SHALL MEET THE INSPECTION REQUIREMENTS FOR THE ORIGINAL

RE-EVALUATION BY NONDESTRUCTIVE METHODS OR BY SURFACE CONDITIONING SHOWS

WORKMANSHIP OR BOTH AT ANY TIME BEFORE FINAL ACCEPTANCE OF THE STRUCTURE

CONTAINING THE WELDMENT.

2. THERE IS SPECIFIC REASON TO QUESTION THE WELDER OR WELDING

1. WELDING PROCEDURES FOR STRUCTURAL STEEL - WELDING PROCEDURES FOR

3. WELDING TECHNIQUE

B. TEMPORARY WELDS - TEMPORARY WELDS REQUIRED FOR FABRICATION

C. TACK WELDS - TACKS WELDS THAT ARE TO BE INCORPORATED INTO

5. IDENTIFICATION - IDENTIFY ALL WELDS IN ONE OF THE FOLLOWING WAYS:

B. IDENTIFY ALL WORK PERFORMED BY EACH WELDER, WELDING

A. NONDESTRUCTIVE EXAMINATION - THE WELDING IS SUBJECT TO INSPECTION AND

B. PERFORM TESTING USING AN APPROVED INSPECTION OR TESTING LABORATORY OR

D. MAGNETIC PARTICLE INSPECTION OF THE WELDS AND EXTENT IDENTIFIED ON

C. PERFORM 100% VISUAL INSPECTION OF ALL COMPLETED WELDS. ALL COMPLETED

GENERAL REQUIREMENTS

A. WELDING OF STRUCTURAL STEEL

SHALL CONFORM TO THE REQUIREMENTS SPECIFIED IN THE PROVISIONS

AWS D1.1, SUBSECTION 4.1 OR SHALL BE QUALIFIED BY TESTS AS

BE REMOVED, REWELDED AND RETESTED TO ENSURE CONFORMANCE.

E. ULTRASONIC TESTING - MAKING, EVALUATING AND REPORTING ULTRASONIC TESTING

OF WELDS SHALL CONFORM TO THE REQUIREMENTS OF AWS D1.1, SECTION 6, PART C.

THE ULTRASONIC EQUIPMENT SHALL BE CAPABLE OF MAKING A PERMANENT RECORD

OF THE TEST INDICATIONS. A RECORD SHALL BE MADE OF EACH WELD TESTED.

SHALL NOT BE REPRODUCTIONS OF CONTRACT DRAWINGS. INCLUDE COMPLETE

INFORMATION FOR THE FABRICATION AND ERECTION OF THE STRUCTURE’S COMPONENTS,

INCLUDING THE LOCATION, TYPE, AND SIZE OF BOLTS, WELDS, MEMBER SIZES AND

LENGTHS, CONNECTION DETAILS, BLOCKS, COPES, AND CUTS. USE AWS A2.4 STANDARD

WELDING SYMBOLS. MEMBER SUBSTITUTIONS OF DETAILS SHOWN ON THE CONTRACT

DRAWINGS SHALL BE CLEARLY HIGHLIGHTED ON THE FABRICATION DRAWINGS. EXPLAIN

THE REASONS FOR ANY DEVIATIONS FROM THE CONTRACT DRAWINGS.

ORDERS, MILL ORDERS, SHOP ORDERS AND WORK ORDERS FOR ALL MATERIALS ORDERS

AND ITEMS USED IN THE WORK. WHERE MILL TESTS ARE REQUIRED PURCHASE ORDERS

SHALL CONTAIN THE TEST SITE ADDRESS AND THE NAME OF THE TESTING AGENCY.

SHAPE, ETC.) TO BE SUPPLIED TO THE FABRICATOR, THE HEAT NUMBER AND THE

BE MADE.

A. STRUCTURAL FABRICATION - MATERIAL MUST BE STRAIGHT BEFORE BEING LAID

OFF OR WORKED. IF STRAIGHTENING IS NECESSARY IT SHALL BE DONE BY

METHODS THAT WILL NOT IMPAIR THE METAL. SHARP KINKS OR BENDS SHALL

BE ACCEPTED EXCEPT WHERE WELDING IS DEFINITELY SPECIFIED, INDICATED

OR OTHERWISE APPROVED. WHERE HEATING IS REQUIRED, PRECAUTIONS SHALL

BE TAKEN TO AVOID OVERHEATING THE METAL AND IT SHALL BE ALLOWED TO

COOL IN A MANNER THAT WILL NOT IMPAIR THE ORIGINAL PROPERTIES OF THE

METAL. SHEARING SHALL BE ACCURATE AND ALL PORTIONS OF THE WORK SHALL

BE NEATLY FINISHED. CORNERS SHALL BE SQUARE AND TRUE UNLESS

OTHERWISE SHOWN. RE-ENTRANT CUTS SHALL BE FILLETED TO A MINIMUM

RADIUS OF 3/4 INCH UNLESS OTHERWISE APPROVED. FINISHED MEMBERS SHALL

BE FREE OF TWISTS, BENDS AND OPEN JOINTS.

MEASURED BY AN APPROVED CALIBRATED STEEL TAPE OF APPROXIMATELY THE

SAME TEMPERATURE AS THE MATERIAL BEING MEASURED. THE OVERALL

DIMENSIONS OF AN ASSEMBLED STRUCTURAL UNIT SHALL BE WITHIN AN

MECHANICALLY GUIDED OR HAND-GUIDED TORCHES, PROVIDED AN ACCURATE

PROFILE WITH A SURFACE THAT IS SMOOTH AND FREE FROM CRACKS AND

NOTCHES IS OBTAINED. SURFACES AND EDGES TO BE WELDED SHALL BE

PREPARED IN ACCORDANCE WITH AWS D1.1, SUBSECTION 5.15. WHERE

STRUCTURAL STEEL IS NOT TO BE WELDED, CHIPPING OR GRINDING WILL

NOT BE REQUIRED EXCEPT AS NECESSARY TO REMOVE SLAG AND SHARP EDGES

OF MECHANICALLY GUIDED OR HAND-GUIDED CUTS NOT EXPOSED TO VIEW.

HAND-GUIDED CUTS WHICH ARE TO BE EXPOSED OR VISIBLE SHALL BE

CHIPPED, GROUND OR MACHINED TO SOUND METAL.

NONDESTRUCTIVE TESTING PERSONNEL, WELDERS, WELDING OPERATORS, AND

TACKERS HAVE BEEN QUALIFIED AND THE SUBMITTALS APPROVED BY THE

CONTRACT MUST BE QUALIFIED IN ACCORDANCE WITH THE APPLICABLE

REQUIREMENTS OF AWS D1.1. WELDERS, WELDING OPERATORS, AND TACKERS

CONSIDERED QUALIFIED FOR THE WELDING PROCEDURE USED.

CONTRACTING OFFICER, WELDERS, WELDING OPERATORS, AND TACKERS

QUALIFIED BY TEST WITHIN THE PREVIOUS 6 MONTHS MAY BE ACCEPTED FOR

THIS CONTRACT WITHOUT RE-QUALIFICATION IF ALL THE FOLLOWING

CONDITIONS ARE MET:

1. COPIES OF THE WELDING PROCEDURE SPECIFICATIONS, THE PROCEDURE

QUALIFICATION TEST RECORDS, AND THE WELDER, WELDING OPERATOR,

AND TACKER QUALIFICATION TEST RECORDS ARE SUBMITTED AND APPROVED

IN ACCORDANCE WITH THE SPECIFIED REQUIREMENTS FOR DETAIL DRAWINGS.

2. TESTING WAS PERFORMED BY AN APPROVED TESTING LABORATORY,

TECHNICAL CONSULTANT, OR THE CONTRACTOR’S APPROVED QUALITY

CONTROL ORGANIZATION.

REQUIREMENTS OF THIS SPECIFICATION AND IS APPLICABLE TO WELDING

CONDITIONS ENCOUNTERED UNDER THIS CONTRACT.

CONFORM TO THE REQUIREMENTS OF THIS SPECIFICATION AND ARE

APPLICABLE TO WELDING CONDITIONS ENCOUNTERED UNDER THIS CONTRACT.

TACKER TO WORK UNDER THIS CONTRACT, SUBMIT THE NAMES OF THE WELDERS,

WELDING OPERATORS, AND TACKERS TO BE EMPLOYED, AND CERTIFICATION THAT

EACH INDIVIDUAL IS QUALIFIED AS SPECIFIED. THE CERTIFICATION MUST

STATE THE TYPE OF WELDING AND POSITIONS FOR WHICH THE WELDER, WELDING

OPERATOR, OR TACKER IS QUALIFIED, THE CODE AND PROCEDURE UNDER WHICH

THE INDIVIDUAL IS QUALIFIED, THE DATE QUALIFIED, AND THE NAME OF THE

FIRM AND PERSON CERTIFYING THE QUALIFICATION TESTS. KEEP THE

CERTIFICATION CURRENT, ON FILE, AND FURNISH 3 COPIES.

C. CERTIFICATES - BEFORE ASSIGNING ANY WELDER, WELDING OPERATOR, OR

3. THE PREVIOUSLY QUALIFIED WELDING PROCEDURE CONFORMS TO THE

4. THE WELDER, WELDING OPERATOR, AND TACKER QUALIFICATION TESTS

B. PREVIOUS PERSONNEL QUALIFICATIONS - AT THE DISCRETION OF THE

C. STRUCTURAL STEEL FABRICATION - STRUCTURAL STEEL MAY BE CUT BY

B. DIMENSIONAL TOLERANCES FOR STRUCTURAL WORK - DIMENSIONS SHALL BE

PROCEDURES" IN SPECIFICATION SECTION 09 97 02, "PAINTING: HYDRAULIC STRUCTURES".

SPECIFICATION SECTION 09 97 02, "PAINTING: HYDRAULIC STRUCTURE".

PREPARED IN ACCORDANCE WITH AISC 326, AISC 316 AND AISC 317. FABRICATION DRAWINGS

SUBMIT FABRICATION DRAWINGS, ANSI "D" SIZE, FOR APPROVAL PRIOR TO FABRICATION.

1. ALL SUBMITTALS SHALL BE SUBMITTED IN ACCORDANCE WITH PARAGRAPH "SUBMITTAL

2. THE COMPLETED STRUCTURES SHALL BE CLEANED AND PAINTIED IN ACCORDANCE WITH

ALLOWABLE VARIATION OF 3/32 INCH.

BE CAUSE FOR REJECTION OF THE MATERIAL. MATERIAL WITH WELDS WILL NOT

CONTRACT FOR LEVELS I OR II IN THE APPLICABLE NON-DESTRUCTIVE TESTING

CONTRACTING OFFICER AND THE DESIGN ENGINEER OF RECORD.

WHO MAKE ACCEPTABLE PROCEDURE QUALIFICATION TEST WELDS WILL BE

THE APPLICABLE REQUIREMENTS OF AWS D1.5.

A CERTIFICATE FROM THE MILL STATING, FOR EACH ARTICLE (SHEET, PLATE, BAR,

SPECIFIC REASON TO QUESTION THE TACKER’S ABILITY. IN SUCH A CASE,

REQUIREMENTS, THE GOVERNMENT RESERVES THE RIGHT TO REJECT MATERIAL OR

NONDESTRUCTIVE AND DESTRUCTIVE TESTS TO DETERMINE COMPLIANCE WITH PARAGRAPH

CHEMICAL AND PHYSICAL PROPERTIES OF THE METAL FROM WHICH THE ARTICLE IS TO

A. EACH WELDER, WELDING OPERATOR, AND TACKER ASSIGNED TO WORK ON THIS

THE REQUIREMENTS OF AWS D1.5.

APPLICABLE REQUIREMENTS OF AWS D1.1 AND ASTM E 709.

THE AREA BY SUITABLE METHODS TO ENSURE THAT THE DEFECT HAS BEEN ELIMINATED.

3.

4. DRAWING REQUIREMENTS

5. MATERIAL ORDERS - THE CONTRACTOR SHALL FURNISH FOUR COPIES OF PURCHASE

6. REPORTS OF MATERIAL - THE CONTRACTOR SHALL FURNISH THE CONTRACTING OFFICER

7. FABRICATION

8. DO NOT COMMENCE WELDING UNTIL WELDING PROCEDURES, INSPECTORS,

9. WELDER, WELDING OPERATOR, AND TACKER QUALIFICATION

10. INSPECTOR QUALIFICATION

11. SAFETY

12. WELDING EQUIPMENT AND MATERIALS - ALL WELDING EQUIPMENT, ELECTRODES,

13. WELDING OPERATIONS

14. QUALITY CONTROL

15. STANDARDS OF ACCEPTANCE - DIMENSIONAL TOLERANCES FOR WELDED CONSTRUCTION,

16. GOVERNMENT INSPECTION AND TESTING - IN ADDITION TO THE INSPECTION AND

17. CORRECTIONS AND REPAIRS - IF INSPECTION OR TESTING INDICATES DEFECTS

BORNE BY THE CONTRACTOR IF UNSATISFACTORY WELDS ARE DISCOVERED, OR BY THE

STRUCTURAL STEEL SHALL BE PREQUALIFIED AS DESCRIBED IN AWS D1.1.

GOVERNMENT’S OWN FORCES OR UNDER A SEPARATE CONTRACT FOR INSPECTION AND

APPLICABLE PROVISIONS OF AWS D1.1. WELDING SHALL BE SUCH AS TO

PRESCRIBED BY AWS D1.1, SUBSECTION 5.3 TO MAINTAIN LOW

SCHEDULE OF WELDING PROCEDURES. ONLY LOW HYDROGEN ELECTRODES

REGARDLESS OF THE THICKNESS OF THE STEEL. A CONTROLLED

PERFORMED AS REQUIRED BY AWS D1.1/D1.1M, SUBSECTION 3.5 AND

WITH AWS D1.1, SECTION 5 AND OTHER APPLICABLE PROVISIONS

WITH AWS D1.1, SUBSECTION 5.15.

PRESCRIBED FOR PERMANENT WORK. TEMPORARY WELDS SHALL BE

REQUIREMENTS OF AWS D1.1, SECTION 6.

OF ACCEPTANCE. CONFORM PROCEDURES AND TECHNIQUES FOR INSPECTION WITH

OF AWS D1.1 AND THE CONTRACT DRAWINGS. WELDS NOT PASSING SHALL

ALL OTHER SHAPES - ASTM A36

W SHAPES - ASTM A992, GR 50.

ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING, UNLESS NOTED OTHERWISE:

THAT NO UNACCEPTABLE DEFECT IS PRESENT.

A DEFECT IS THOUGHT TO HAVE BEEN REMOVED, AND BEFORE RE-WELDING, EXAMINE

IN ACCORDANCE WITH THE APPROVED PROCEDURES. WHEREVER A DEFECT IS REMOVED

TO THE CONTRACTING OFFICER FOR APPROVAL.

18. ANY MODIFICATIONS OR ADDITIONS TO THE CONTRACT PLANS SHALL BE SUBMITTED

S-201

T A

IN

T E

R G

A T

E R

E H

A B

J O

H N W F

L A

N N

IG

A N

H A

Y S I, V

A

P O

U N

D R

IV

E R

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

H U

N T

IN

G T

O N D

IS

T R

IC

T

H U

N T

IN

G T

O N

W E

S T V

IR

G

IN

IA

1 4

C L

C

J J

K

N O

T E

S

WELDS. ANY INDICATION OF A DEFECT IS REGARDED AS A DEFECT, UNLESS

STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS, JUNE 30, 2004" (RCSC).

IN SECTION 8.1 OF THE "RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS, SPECIFICATION FOR AND SHALL BE HOT-DIPPED GALVANIZED. ALL BOLTS SHALL BE INSTALLED ’SNUG TIGHT’ AS SPECIFIED

19. BOLTS - ALL BOLTS SHALL MEET THE REQUIREMENTS OF ASTM A325, UNLESS OTHERWISE NOTED, M A

R C

H

P J L

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

IDENTIFICATION

SHEET

D A

T E

A P

P R

SHEET OF

fiof Engineers

US Army Corps

Huntington District

46’-0" 50’-0" 50’-0" 50’-0" 50’-0" 46’-0"

6 GATES @ 42’-0" AND 5 PIERS @ 8’-0" = 292’-0"

FACE OF LEFT ABUTMENT FACE OF RIGHT ABUTMENT

CREST EL. 1410.00

EL. 1400.00

MATCH C OF

EXIST’G VERTICAL

MATCH C OF

EXIST’G VERTICAL

21’-0" (FIELD VERIFY)

0"

FI

ELD

V

ERI

FY

BRACE FRAME

INSTALL NEW

EXISTING STRUT

ARM TYP.

INSTALL NEW

BRACE FRAME

TYP. ALL ARMS

INSTALL COVER P

TOP GIRDER ONLY

INSTALL COVER P

(BOTH SIDES)

INSTALL COVER P’S

SCALE: �"=1’-0"

GATE NO. 1 GATE NO. 2 GATE NO. 3 GATE NO. 4 GATE NO. 5 GATE NO. 6

L

L

L

SCALE: �"=1’-0"

C

SECTION

SCALE: �"=1’-0"

L

NOTES:

P L

A N

.d g n

2 4

IP

P

W P :d m s \P

L A

N .d g n

H E

D X J J

K

:1

/1

/2

L

R H -A

P -E

C -C

A E \A

P P

S \L

R H

W o rk s p a c e \W o rk s p a c e \P ro je c tW is e I n te rP lo t

O rg a n iz e r\ m is c \d e s ig n s c ri p t\ s td v .p e n d e fa u lt a tt a c h e d f ro m d ia lo g

-A

U G -2

:0

P O

U N

D R

IV

E R

J O

H N W F

L A

N N

A G

A N L

A K

E

H A

Y S I, V

A

T A

IN

T E

R G

A T

E R

E H

A B

H

N T

IN

G T

O N D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

S

N T

IN

G T

O N

W E

S T V

IR

G

IN

IA

S-701

J J

K

C L

C

S-701

S-702

B

S-702

A

S-701

C

S-702

L

SPILLWAY TAINTER GATE

TYPICAL PLAN VIEW

UPSTREAM ELEVATION

SPILLWAY

SHALL MATCH THE COLOR OF EXISTING STRUCTURE AFTER MODIFICATIONS ARE COMPLETE.

7. ALL UNCOATED SURFACES SHALL BE PAINTED WITH A TWO-PART EPOXY PAINT AND

6. ALL SURFACES TO BE WELDED SHALL BE FREE OF PAINT AND OTHER FOREIGN DEBRIS.

5. ALL BOLT HOLES SHALL BE �" DIAMETER UNLESS NOTED OTHERWISE.

SPECIFIED IN DRAWINGS.

HOT DIP GALVANIZED, UNLESS NOTED OTHERWISE. BOLT LENGTH TO BE AS

4. ALL BOLTS SHALL BE ASTM A325, �" DIA. HEAVY HEX HEAD WITH WASHER AND NUT,

3. ALL WELDS SHALL BE MADE USING E70XX ELECTRODES.

TO BE REHABILITATED.

2. DRAWING AND QUANTITIES SHOWN ARE FOR ONE (1) GATE. ALL SIX (6) GATES ARE

OF THE NEW CROSS-BRACE FRAME SHOWN IN THESE PLANS.

1. ALL DIMENTIONS SHALL BE FIELD VERIFIED PRIOR TO FABRICATION

G E

N E

R A

L V

IE

W S

P J L

/1

/2

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

IDENTIFICATION

SHEET

D A

T E

A P

P R

SHEET OF

fiof Engineers

13’-10"

27’-8"

13’-10"FIELD VERIFY

ARM TYPICAL

EXISTING STRUT

TYP.

�"X9" P

ARM TYP.

EXISTING STRUT

SPLICE AS NECESSARY

�"X9" COVER P

ARM TYPICAL

EXISTING STRUT

W10X33

4"

�" ATTACHMENT LUGS

WORKING LINE

BRACE FRAME

INSTALLATION OF NEW

TO FACILITATE

L3X3X�" BEAM SEAT

OPTIONAL

THIS SHEET

SEE SPLICE DETAIL

EACH SIDE OF ARM

�"X9" COVER P TYP.

ALL COVER P CORNERS

�" RADIUS TYP. ON

1" MAX. TYP.

1" MAX. TYP.

BRACE

C OF EXIST.

BRACE

C OF EXIST.

BRACE

C OF EXIST.

�"X9"X16’-6" P FIELD CUT TO LENGTH TYP. EACH SIDE EACH ARM

�" P

EXISTING GUSSETT P

BRACE FRAME

SCALE: �"=1’-0"

SECTION

L

SCALE: 1�"=1’-0"

SECTION

p la n .d g n

3 4

IP

P

W P :d m s \p la n .d g n

H E

D X J J

K

.6

:1

/1

/2

L

R H -A

P -E

C -C

A E \A

P P

S \L

R H

W o rk s p a c e \W o rk s p a c e \P ro je c tW is e I n te rP lo t

O rg a n iz e r\ m is c \d e s ig n s c ri p t\ s td v .p e n d e fa u lt a tt a c h e d f ro m d ia lo g

-A

U G -2

U N

D R

IV

E R

J O

H N W F

L A

N N

A G

A N L

A K

E

H A

Y S I, V

A

T A

IN

T E

R G

A T

E R

E H

N T

IN

G T

O N D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

N T

IN

G T

O N

W E

S T V

IR

G

S-702

J

K

C L

C

S-702

E

S-703

S-703

S-701

A

L

SCALE: 1�"=1’-0"

COVER PLATE

SPLICE DETAIL

L

SCALE: �"=1’-0"

DETAIL

E

S-7

S-701

L

TYP.

SHEET S-703

SEE SEC. D

CUT TO LENGTH

25% P.T.

TYP.

SCALE: 1�"=1’-0"

DETAIL

S-702

S-702

L

100% M.T.

100% U.T.

B.G.

CONTRACTOR SHALL VERIFY

ORIGINAL SHOP DWGS.

SLOPES AS GIVEN ON *

D E

T A

IL

S

L

L

L

P J L

/1

/2

12’-0"

2" TYP.

R

HORIZONTAL GIRDER

C EXISTING WF33X118

L

L

L

SCALE: 1�"=1’-0"S-701

B VIEW

100% P.T.

TYP.

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

IDENTIFICATION

SHEET

D A

T E

A P

P R

SHEET OF

fiof Engineers

�" P TYP.

13’-10" 13’-10"

27’-8"

W10X33

W10X33

CUT TO FIT TYP.

FIELD MEASURE

W10X33

FIELD VERIFY

CUT TO LENGTH

9"X�" P

FIELD CUT

TYP

1�"

2�"

8"

EXISTING

STRUT ARM

W10X33

FIELD VERIFY

CUT TO LENGTH

EXISTING

STRUT ARM

�" P

TYP

W10X33 TYP.

INSTALL �"

STIFF. P TYP.

INSTALL �"

STIFF. P TYP.�" P

TYP

3�" LONG BOLT

FIELD DRILL FOR

2’-9" TYP.

8" TYP.

5�"

1"1" 1�" 1�"

TYP.

MIN. 1" EDGE DIST.

2" C. TO C.

LONG BOLTS

INSTALL 2-2�"

ALLOW �" TYP.

SHIM AS NEEDED

W10X33

(TYP. ALL 3 GIRDERS)

2" DIA. DRAIN HOLES

3’-6"6’-10"7’-0"6’-10"3’-6"

TYPICAL

L 4X3X�"

W10X33

GUSSET P

1’-1�"X8�"X�"

GUSSET P

2’-0"X8�"X�"

GUSSET P

9"X6"X�"

GUSSET P

2’-0"X6�"X�"

GUSSET P

1’-1�"X8�"X�"

GUSSET P

2’-0"X8�"X�"

GUSSET P

2’-0"X8�"X�"

GUSSET P

9"X6"X�"

GUSSET P

9"X6"X�" GUSSET P

2’-0"X6�"X�"

GUSSET P

2’-0"X6�"X�"

TYP.

W10X33

GUSSET P

@ C/L ALL

�" STIFF. TYP.

T

Y P

TYPICAL

L4X3X�"

GUSSET P

1’-1�"X6�"X�"

GUSSET P

1’-1�"X6�"X�"

33’-2"

1�" TYP.

5’-11"

7’-11"

13’-2�"

13’-11�"

W10X33

6’-11"

WEB STIFF. TYP.

1’-0"

13’-11�" 13’-10"

W10X33

1’ 4"

1’-6�"

1’-4"

" 1’-7"

1�

1�

9�"

11"

SECTION

SCALE: 3"=1’-0"

L

SCALE: �"=1’-0"

C

L

L

L

T Y

P

TYP

SECTION

SCALE: 3"=1’-0"

D

SCALE: 3"=1’-0"

DETAIL

L

T Y

P

LL

P L

A N

.d g n

4 4

IP

P

W P :d m s \P

L A

N .d g n

H E

D X J J

K

:1

/1

/2

L

R H -A

P -E

C -C

A E \A

P P

S \L

R H

W o rk s p a c e \W o rk s p a c e \P ro je c tW is e I n te rP lo t

O rg a n iz e r\ m is c \d e s ig n s c ri p t\ s td v .p e n d e fa u lt a tt a c h e d f ro m d ia lo g

-A

U G -2

U N

D R

IV

E R

J O

H N W F

L A

N N

A G

A N L

A K

E

H A

Y S I, V

A

T A

IN

T E

R G

A T

E R

E H

N T

IN

G T

O N D

IS

T R

IC

T

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

N T

IN

G T

O N

W E

S T V

IR

G

S-703

J

K

C L

C

S-703

S-702

2 S-703

C

S-703

D

S-702

S-703

MAKE SIX (6)

L

NOT SHOWN FOR CLARITY

NOTE: �"X9" COVER P

S-702 FOR SLOPE

-SEE SECTION A,*

SCALE: 6"=1’-0"

SHIM PACK DETAIL

DETAIL - BRACE FRAME

L

D E

T A

IL

S

PROVIDE �", �", �" THICK

AS SHOWN TWELVE (12) EACH PER GATE

A

S-703

SCALE: �"=1’-0"S-703

A TOP VIEW

L

L L

LL L

L

L L

LL

T Y

P

T Y

P

T Y

P

T Y

P

L

TYP

B.G.

TYP. ALL

GUSSETS

25% UT

P J L

/1

/2

G-1

G-2

G-3

WT. APPROX. 4,000 LB

ADJUST DIMENSIONS TO FIT GATE

FABRICATION OF THIS BRACE FRAME

FIELD VERIFY ALL DIMENSIONS PRIOR TO

E

S-703

E

S-703

L

C WORKING POINT

LC WEB STIFFENER

DIMENSIONS SHOWN SYMETRICAL ABOUT THE CL

SCALE: 3"=1’-0"S-703

E SECTION G-2

SCALE: 3"=1’-0"S-703

F SECTION G-1 & G-3

LC WEB STIFFENER

TYP.

TYP.

TO GUSSET PL

ANGLE MEMBERS

SPACING FOR

BOLT HOLE

TYPICAL

MATERIAL: NAVAL BRASS, COPPER ALLOY C464 OR EQUAL

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N

C O

N T

R A

C T N

O

IDENTIFICATION

SHEET

D A

T E

A P

P R

SHEET OF

fiof Engineers

EXHIBIT B

LAB RESULTS

Analysis Report

Client:

Project/Test Address:

Pinnacle Env. Consultants (WV)

7469 Whitepine Rd

Telephone: 800.347.4010

Richmond, VA 23237

Environmental Hazards Services, L.L.C.

Flannigan PRC 72084030;

Client Number:

50-3547

Fax Number:

304-757-5205Laboratory Results

Analyzed Date:

Client Sample Number

Lab Sample Number

Pb (ug/g) ppm

Lead Paint Chip

07/31/2017

07/31/2017

17-07-04258

Reported Date:

Received Date:

Report Number:

400 D Prestige Park Hurricane, WV 25526

Narrative

ID

07/31/2017

Collection Location % Pb by Wt.

07/27/2017Collection Date:

117-07-04258-001 51000 5.1

Missy Kanode

QA/QC Clerk

Analysis Method: EPA SW846 7000B

The HUD lead guidelines for lead paint chips are 0.50% by Weight, 5000 ppm, or 1.0 mg/cm². The Reporting Limit (RL) for samples prepared by ASTM E-1979-12 is 10.0 ug Total Pb. The RL for samples prepared by EPA SW846 3050B is 25.0 ug Total Pb. Paint chip area and results are calculated based on area measurements determined by the client. All internal quality control requirements associated with this batch were met, unless otherwise noted.

LEGEND Pb= lead ug = microgram ppm = parts per million ug/g = micrograms per gram Wt. = weight

Reviewed By Authorized Signatory:

Preparation Method: ASTM E-1979-12

The condition of the samples analyzed was acceptable upon receipt per laboratory protocol unless otherwise noted on this report. Results represent the analysis of samples submitted by the client. Sample location, description, area, etc., was provided by the client. Results reported above in mg/cm3 are calculated based on area supplied by client. This report shall not be reproduced except in full, without the written consent of the Environmental Hazards Service, L.L.C. California Certification #2319 NY ELAP #11714.

Page 1of1

EXHIBIT C

PHOTOS

Fig. 1 Upstream view of spillway gates from parking area

Fig. 2 Downstream view of spillway gates from concrete apron

Fig. 3 Downstream view of work area

Fig. 4 Downstream view of work area

Fig. 5 Close up view of gate

Fig. 6 Close up view of gate strut arm

Blank Page