Drawings.pdf

PDF 46 MB Posted

Attached to
Pike Island - Motor Control Center Upgrade Federal contract opportunity
Solicitation number
W911WN-16-B-8002
Issued by
Department of the Army Corps of Engineers Engineering District Pittsburgh

View the file

Other files for this federal contract opportunity

Other files attached to Pike Island - Motor Control Center Upgrade, newest first.
File Type Posted
Bid_Results.doc DOC document
Amendment_0003.pdf PDF
Questions_-_Updated.pdf PDF
Amendment_0003.pdf PDF
Questions_-_Updated.pdf PDF
Revised_Specifications_-_18_May_2016.pdf PDF
Contractor_Questions_18_May_2016.pdf PDF
Drawings.pdf PDF
SOLICITATION_-_AMENDMENT_18_May_2016.doc DOC document
UPDATED.pdf PDF
Site_Visit.pdf PDF
SOLICITATION.pdf PDF
Certified_Final_RTA_-_Revised.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WEST VIRGINIA

OHIO COUNTY

PIKE ISLAND LOCKS AND DAM

OHIO RIVER

PITTSBURGH DISTRICT

OF ENGINEERS

US ARMY CORPS

MIDDLE WALL MCC REPLACEMENT

PIKE ISLAND LOCKS AND DAM

W911WN-16-C-0000

W911WN-16-B-8002RFP NO.:

CERTIFIED FINAL DOCUMENTS

MARCH 2016

PER A/E/C CADD STANDARDS

SHEET TYPE DESIGNATOR AS

DRAWING NUMBER

A/E/C CADD STANDARDS

DISCIPLINE DESIGNATOR AS PER

AND APPROVAL OF ALL DRAWINGS LISTED ON THE INDEX SHEET.

SIGNATURES AFFIXED BELOW INDICATE OFFICIAL RECOMMENDATION

SUBMITTED BY:

SECTION CHIEF

APPROVAL RECOMMENDED BY:

BRANCH CHIEF

APPROVED BY:

CONSTRUCTION DIVISION

CHIEF, ENGINEERING AND

DATE

DATE

DATE

THEIR EMPLOYMENT AS REQUIRED BY ER 1110-1-8152.

APPEAR ON THESE PROJECT DOCUMENTS WITHIN THE SCOPE OF

DESIGNATIONS OF U.S. ARMY CORPS OF ENGINEERS INDIVIDUALS

THIS SHEET. THE INITIALS OR SIGNATURES AND REGISTRATION

U.S. ARMY CORPS OF ENGINEERS AND THE A/E FIRMS IDENTIFIED ON

THIS PROJECT WAS DESIGNED BY THE PITTSBURGH DISTRICT OF THE

SHEET INDENTIFICATION KEY:

SHEET ID (DRAWING NUMBER, DWG. NO.) A-NNNN

INDEX DRAWINGSCONTRACT

NAMEFILE

DWG SHEET

TITLE

CODE NO.ID

INDEXESGENERAL

COVERSHEET SHEETCOVER

LPIO_100_G-0023 100 G-0023 SHEET SIGNATURE & INDEX DRAWINGS REFERENCE INDEX, DRAWINGSCONTRACT

GENERAL

LPIO_203_G-1024 203 G-1024 PLAN SITE GENERAL & MAP, VICINITY MAP, LOCATIONPROJECT

STRUCTURAL

LPIO_770_S-1030 770 S-1030 DETAILS & PLANS STRUCTURAL BUILDING OPERATIONS WALLMIDDLE

ELECTRICAL

LPIO_770_E-0060 770 E-0060 ABBREVIATIONS & SYMBOLSELECTRICAL

LPIO_770_E-1061 770 E-1061 SECTION & PLANS FLOORS SECOND & FIRST BUILDING OPERATIONS WALLMIDDLE

LPIO_770_E-2062 770 E-2062 (MW-MCC) CENTER CONTROL MOTOR WALLMIDDLE

LPIO_770_E-6063 770 E-6063 3 OF 1 SHEET - DIAGRAMONE-LINE

LPIO_770_E-6064 770 E-6064 3 OF 2 SHEET - DIAGRAMONE-LINE

LPIO_770_E-6065 770 E-6065 3 OF 3 SHEET - DIAGRAMONE-LINE

LPIO_770_E-6066 770 E-6066 DIAGRAM WIRING SIGNAL TRAFFIC - CHAMBERLAND

LPIO_770_E-6067 770 E-6067 DIAGRAM WIRING SIGNAL TRAFFIC - CHAMBERRIVER

LPIO_770_E-6068 770 E-6068 SCHEDULES LPC & LPL PANELSLIGHTING

18 MARCH 2016

/s/ JEANINE HOEY, P.E.

/s/ JOHN E. NITES, P.E.

/s/ JOHN E. NITES, P.E. 17 MARCH 2016

18 MARCH 2016

IP

P W

P :d m s

L P

IO

G .d g n h e c n e r l

M A

R

:0

L P

IO

G .d g n

.0

:1

G-0023

S

IG

N A

T U

R E S

H E

E T

C O

N T

R A

C T D

R A

W

IN

G S I

N D

E X

R E

F E

R E

N C

E D

R A

W

IN

G I

N D

E X

E

L E

IS

U R

E

E

L E

IS

U R

E

M A

R C

H s

J

O

N

E

N

IT

E S

P .E

R

G A

D O

M S

K I

INDEX DRAWINGSREFERENCE

NAMEFILE TITLE

O-LPI-20_2.6 END UPPER - PLAN WALLSLOCK

O-LPI-20_3.4 END LOWER - PLAN WALLSLOCK

O-LPI-20_4.5 END UPPER - ELEVATIONS WALLSLOCK

O-LPI-20_5.3 END LOWER - ELEVATIONS WALLSLOCK

O-LPI-20_7.3 END LOWER - SECTIONS WALLSLOCK

O-LPI-20_8.2 DETAILS & SECTIONS PLANS, ROOM CABLE & GALLERY PIPE WALLSLOCK

O-LPI-20_9.3 DETAILS & SECTIONS PLANS, TRENCHES CABLE & PIPE WALLSLOCK

O-LPI-20_15.2 DETAILS & SECTIONS PLANS, RECESSES GATE WALLSLOCK

O-LPI-20_16.1 DETAILS & SECTIONS PLANS, RECESSES VALVE WALLSLOCK

O-LPI-21_1.4 OUTLINE RECESS & LEAF - GATES LOWER & UPPER - GATESLOCK

O-LPI-22_1.2 ASSEMBLY MACHINERY OPERATING GATE -LOCKS

O-LPI-22_3.1 DETAILS & COVER ROD PISTON ARM, SECTOR SECTOR, - MACHINERY OPERATING GATE -LOCKS

O-LPI-22_6.2 LIST BOLT & DETAILS SUPPORT, TOP SECTOR BASE, SECTOR - MACHINERY OPERATING GATE -LOCKS

O-LPI-27_1.1 DIAGRAM CIRCUIT SCHEMATIC PIPING SYSTEMHYDRAULIC

O-LPI-28_1.1 ASSEMBLY MACHINERY OPERATING VALVE -LOCKS

O-LPI-29_1.3 DIAGRAM WIRING LINE ONE - SYSTEMELECTRICAL

O-LPI-29_2.1 DIAGRAM WIRING SWITCHBOARD MAIN - SYSTEMELECTRICAL

O-LPI-29_5.3 DETAILS & PLANS WALLS GUIDE & LAND - SYSTEMELECTRICAL

O-LPI-29_6.3 ELEVATIONS & PLANS WALL MIDDLE - SYSTEMELECTRICAL

O-LPI-29_7.2 DETAILS & ELEVATION PLAN, WALL MIDDLE LOWER - SYSTEMELECTRICAL

O-LPI-29_8.2 DETAILS & ELEVATION PLANS, WALLS GUARD & RIVER - SYSTEMELECTRICAL

O-LPI-29_9.2 DETAILS LIGHTING - WALLS LOCK - SYSTEMELECTRICAL

O-LPI-29_10.1 DETAILS INSTALLATION SWITCH LIMIT - SYSTEMELECTRICAL

O-LPI-29_11.1 DIAGRAMS SCHEMATIC CONTROL VALVE CULVERT - SYSTEMELECTRICAL

O-LPI-29_12.1 DIAGRAMS CONNECTION STATIONS CONTROL VALVE CULVERT - SYSTEMELECTRICAL

O-LPI-29_13.1 DETAILS STATIONS CONTROL VALVE CULVERT - SYSTEMELECTRICAL

O-LPI-29_15.1 PLAN, LOCK SYSTEM SIGNAL TRAFFIC VISUAL - SYSTEMELECTRICAL

EQUIPMENT CONTROL & DIAGRAMSWIRING

O-LPI-29_16.2 SCHEDULE CABLE & TABLE REFERENCE - SYSTEMELECTRICAL

O-LPI-29_17.1 BUILDING OPERATION - SYSTEMELECTRICAL

O-LPI-70_1.1 SCHEDULE ROOM & PLANS FLOOR - BUILDINGOPERATION

O-LPI-70_3.1 DETAILS MISCELLANEOUS SCHEDULES, WINDOW & DOOR SECTIONS, - BUILDINGOPERATION

O-LPI-70_4.2 DETAILS MISCELLANEOUS & STAIRS WINDOW, DOOR, - BUILDINGOPERATION

O-LPI-70_5.1 DETAILS & SECTIONS ELEVATIONS, PLANS, REINFORCING & STEEL STRUCTURAL - BUILDINGOPERATION

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IC

T

PITTSBURGH DISTRICT

P

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

UPPER GUARD WALL

SERVICE BRIDGE

UPPER GUIDE WALL

GARAGE & WORKSHOP

SERVICE BUILDING

AND STORAGE AREA

CONTRACTOR'S WORK LIMITS

OPERATIONS BUILDING

MAIN ENTRANCE

P W

P :d m s

L P

IO

G .d g n h e c n e r l

M A

R

:5

L P

IO

G .d g n

.0

:1

P R

O J E

C T L

O C

A T

IO

N M

A P

G-1024

V

IC

IN

IT

Y M

A P

G E

N E

R A

L S

IT

E P

L A

N

E

L E

IS

U R

E

E

L E

IS

U R

E R

G A

D O

M S

K I

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

CERTIFIED FINAL DOCUMENTS

OHIO RIVER

NN

S T

A

.0

B

S

A

.0

A

.0

B

S T

A

.2

FLOW

PARKING

RIVER WALL

LAND WALLESPLANADE

MIDDLE WALL

LOCK CHAMBER - 110' x 1200'

LOCK CHAMBER - 110' x 600'

W VA ROUTE NO. 2

LOCATION

PROJECT

N.T.S.

PROJECT LOCATION MAP

N.T.S.

PROJECT VICINITY MAP

N.T.S.

GENERAL PLAN

LOCKS AND DAM

PIKE ISLAND

N.T.S.

PIKE ISLAND LOCKS AND DAM

(TYP)

MCC CURB

REMOVE EXIST.

CURB (TYP)

TO SLAB BELOW

MINIMIZE DAMAGE

TAKE CARE TO

COUNTERSUNK BOLTS

DRILL HOLES IN P TO ACCEPT

‚" CHK'D P W/BEVELED EDGES,

L

R

OPENING WIDTH

3"

1" (TYP)

X

T O

P P

IN

G

11'-1"±11'-2"±

8"±

IN

6" MIN

(TYP)

HOLE

3" CORE

6" MIN

8"±

11'-1"±11'-2"±

7'-5"± 7'-5"± 7'-5"±

3" TYP

EQ EQ EQ

EX. 8WF20 EX. 8WF20

P

‚" CHK'D

(TYP)

ANCHOR

MCC

PROPOSED

SEE DETAIL 1

HOLES (TYP) (TYP)

EX. 8WF31 COL.

T&B

#6@10±

T&B

#6@18"±

MCC CURB

REMOVE EX.

T O

P P

IN

G

OF CURB (TYP)

SMOOTH AFTER REMOVAL

GRIND CONCRETE SURFACE

REINF (TYP)

CONCRETE SLAB

+2" TOPPING

CONCRETE SLAB

EXIST. 8"

REBAR T&B

1" CLR TO

+2" TOPPING

EX. 8" CONCRETE

FOR REINF.

SEE PLAN

+2" TOPPING

CONCRERE SLAB

EXIST. 8"

SEE PLAN FOR LOCATIONS

KWIK BOLT 3 ANCHOR BY HILTI,

…"Ø X 4" LONG COUNTERSUNK

1' 2'0 6"

SCALE: 1•"=1'

4' 8'0 2'

SCALE: ‚"=1'

2' 4'0 1'

SCALE: •"=1'

A

SECTION

SCALE: 1•"=1'-0"

S L

A B

E X

C O

N C

L

L

T

B

T

Y P

TO SIZE CHK'D P

DETERMINE IN FIELD

L

B

SECTION

SCALE: 1•"=1'-0"

S L

A B

E X

C O

N C

SCALE: ‚"=1'-0"

DEMOLITION - SECOND FLOOR PLAN

SCALE: ‚"=1'-0"

PARTIAL - SECOND FLOOR PLAN

DETAIL

SCALE: •"=1'-0"

A

E X

W

F E

X

W

FEX. 12WF

E X

W F

E X

W

F

EX. 16WF40 EX. 16WF40

E X

W F

E

X

W F

E X

W F

E X

W F

E X

W

F

E X

W

F

E X

W F

EX. 12WF40 EX. 12WF40

L

B

EX. 16WF40EX. 16WF40

E X

W F

EX. 12WF40EX. 12WF40

E X

W

F

E X

W

F

E X

W F

WORK THIS DWG WITH E-1061.6.

AND 70/5.1.

SEE REFERENCE DWG'S 70/1.1, 70/3.15.

CORE HOLES MUST NOT BE STAGGERED.4.

AS SHOWN.

10 IN 2 LINES BETWEEN STEEL BEAMS

MAXIMUM NUMBER OF CORES ARE TO BE3.

FRAMING.

CONCRETE SLAB REINFORCING OR STEEL

CORES SHALL NOT CUT THRU EXISTING2.

MAXIMUM DIAMETER OF 3".

WITH DIAMOND TIP CORE DRILL WITH A

ALL CONDUIT HOLES MUST BE DRILLED1.

NOTES:

L

VERIFY IN FIELDV.I.F.

TYPICALTYP

TOP AND BOTTOMT&B

REINFORCINGREINF.

PLATEP

MINIMUMMIN.

EXISTINGEXIST.

EXISTINGEX.

EQUALEQ.

DRAWINGDWG

DETAILDTL.

COLUMNCOL.

CLEARCLR

CHECKEREDCHK'D

APPROXIMATE(LY)APPROX.

ABBREVIATIONS:

P W

P :d m s

L P

IO

S .d g n h e c n e r l

M A

R

:5

L P

IO

S .d g n

.0

:1

M

ID

D L E W

A L L O

P E

R A

T

IO

N S B

U

IL

D

IN

G

S-1030

S T

R U

C T

U R

A L P

L A

N S D

E T

A

IL

S

V

IN

C E

D E

C A

R L

O

P .E

E

L E

IS

U R

E T

O L

O U

G H

L

IN

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

THE DRAWING SET.

ADDITIONAL SYMBOLS MAY BE IDENTIFIED WITHIN1.

NOTES:

CURRENT TRANSFORMER

TRANSFORMER

LPC-1 3#12, ƒ"C UNLESS OTHERWISE NOTED

HOME RUN TO LIGHTING PANEL C, CIRCUIT #1

3/C

MAY NOT BE INCLUDED.

SINGLE CABLE WITH 3 CONDUCTORS, GROUND WIRE

3#12 3 SINGLE CONDUCTORS, #12AWG

4#12, ƒ"C FOUR CABLES, SINGLE-CONDUCTOR #12AWG, IN ƒ" CONDUIT

3/C#12 W/GRD SINGLE CABLE WITH 3 CONDUCTORS, #12AWG, AND GROUND WIRE

CONNECTOR

RECEPTACLE - SPECIAL PURPOSE

PUSH BUTTON - NORMALLY CLOSED, NORMALLY OPEN

TERMINAL BLOCK (1, 2, 3 = TERMINAL NUMBER (TYP))

P1 CABLE NAMETAG

R

A-AMBER. BOTH SYMBOLS INDICATE PUSH-TO TEST LIGHTS

LIGHT - INDICATOR (PILOT), R-RED, G-GREEN, W-WHITE,

R A-AMBER. BOTH SYMBOLS INDICATE PUSH-TO TEST LIGHTS

LIGHT - INDICATOR (PILOT), R-RED, G-GREEN, W-WHITE,

G COPPER GROUND WIRE

GROUND CONNECTION

OR DUAL ELEMENT FUSE - CARTRIDGE TYPE

NON-FUSIBLE DISCONNECT SWITCH

CONDUIT EMBEDDED OR BELOW FLOOR

UNLESS OTHERWISE NOTED

EXPOSED GALVANIZED RIGID STEEL

CONDUITS:

N.C. NORMALLY CLOSED CONTACTOR

NORMALLY OPEN CONTACTOR

CONTACTS:

N.O.

CR

MOTOR STARTER-MS, SOLENOID VALVE-SV

CONTROL RELAY-CR, MAGNETIC CONTACTOR-MC,

AF

AT (AF = FRAME SIZE, AT = TRIP SIZE)

CIRCUIT BREAKER - THERMAL MAGNETIC

(NUMBER DENOTES NEMA SIZE 2)

NON-REVERSIBLE STARTER W/OVERLOAD (SSOL)

SSOL2

ELECTRICAL SYMBOLS

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E-0060

E L E

C T

R

IC

A L S

Y S

T E

M S

E L E

C T

R

IC

A L S

Y M

B O

L S A

B B

R E

V

IA

T

IO

L E

IS

U R

E

E

L E

IS

U R

E R

G A

D O

M S

K I

R s

J

O

N

IT

E S

P .E

ABBREVIATIONS

3W WIRETHREE

A AMPERE PVC CHLORIDEPOLYVINYL

AC CURRENTALTERNATING PWR TERMINALPOWER

AF RATING FRAMEAMP, RC CHAMBERRIVER

AIC CAPACITY INTERRUPTINGAMPERE RGS CONDUIT STEEL GALVANIZEDRIGID

AT RATING TRIPAMP, R.W ORR/W WALLRIVER

AWG GAUGE WIREAMERICAN SHLDSH, SHIELDED

C CONDUIT SSOL OVERLOAD STATESOLID

CB BREAKERCIRCUIT STD DELAY TIMESHORT

CC CONTACTORCOMBINATION STPU PICKUP TIMESHORT

CKT CIRCUIT SW SWITCH

CP PANELCONTROL XFMRT, TRANSFORMER

CU COPPER TB BLOCKTERMINAL

DC CURRENTDIRECT TVSS SUPPRESSOR SURGE VOLTAGETRANSIENT

DIA DIAMETER TYP TYPICAL

D.S. ORD/S DOWNSTREAM UL LABORATORIESUNDERWRITERS

D.S.L.W. WALL LANDDOWNSTREAM U.S. ORU/S UPSTREAM

D.S.R.W. WALL RIVERDOWNSTREAM U.S.L.W. WALL LANDUPSTREAM

DWG DRAWING U.S.R.W. WALL RIVERUPSTREAM

EL ELEVATION V VOLTS

FL FLOOR VAC CURRENT ALTERNATINGVOLTS

FT FOOT VDC CURRENT DIRECTVOLTS

FU FUSE 1P BREAKER CIRCUIT POLESINGLE

GALV GALVANIZED 2P BREAKER CIRCUIT POLEDOUBLE

GEN GENERATOR 3P BREAKER CIRCUIT POLETHREE

G/GND/GRD GROUND

GF FAULTGROUND

GFD DELAY FAULTGROUND

HP HORSEPOWER

ICP PANEL CONTROLINTERLOCK

IN INCH

INST INSTANTANEOUS

JB BOXJUNCTION

KVA AMPSKILOVOLT

KW KILOWATT

L POWERLINE,

LC CHAMBERLAND

LP PANELBOARDLIGHTING

LPB "B" PANELLIGHTING

LPC "C" PANELLIGHTING

LPL "L" PANELLIGHTING

LTD DELAY TIMELONG

LTG LIGHTING

LTPU PICKUP TIMELONG

L/W OR L.W. WALLLAND

M/W OR M.W. WALLMIDDLE

MC CLADMETAL

MCC CENTER CONTROLMOTOR

MFR MANUFACTURER

MIN MINIMUM

MLO ONLY LUGMAIN

NEUN, NEUTRAL

NONC, OPEN NORMALLY CLOSED,NORMALLY

NO. NUMBER

NTS OR N.T.S. SCALE TONOT

OL OVERLOAD

P POLE

PC COMPUTERPERSONAL

PH PHASE

PNL PANEL

PR PAIR

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

RC-ICP AND LC-ICP

CONTROL PANELS

EXISTING INTERLOCK

SWITCHBOARD

EXISTING MAIN

PUMP (TYP)

HYDRAULIC

CENTER

CONTROL

NEW MOTOR

1PH, 60HZ

LPC, 125A, 120/240V,

NEW LIGHTING PANEL

(EXIST)

PANEL "B"

LIGHTING

BELOW SWITCHBOARD (TYP)

EXISTING SLOT IN FLOOR

IN FIRST FLOOR

CONCRETE WALL

480-120/208V XFMR

NEW 75KVA, 3PH, 4W

J. BOX

12"X12"X6"

BEAM (TYP)

SUPPORTING

SECOND FLOOR

CEILING

ABOVE DROP

CABLE TRAY

EXISTING

(TYP)

TO CROSSOVER

EXISTING CONDUIT

DROP CEILING

BEAM (TYP)

SUPPORTING

SECOND FLOOR

RC-ICP AND LC-ICP

CONTROL PANELS

EXISTING INTERLOCK

CENTER (MW-MCC)

MOTOR CONTROL

NEW MIDDLE WALL

(LPC)

LIGHTING PANEL

FLOOR MOUNT

25KVA TRANSFORMER

BOX WALL MOUNT AND

12"X12"X6" JUNCTION

EXISTING SLOT THRU WALL

3" DIA BELOW NEW MCC

CORE DRILL HOLES THRU FLOOR

WIRING TO TRANSFORMER

(2)-2•"C TO J. BOX AND

3" DIA EACH FOR CONNECTING

A HOLE BELOW TRANSFORMER

FLOOR BELOW J.BOX AND

CORE DRILL 2 HOLES THRU

XFMR

480-120/240V

NEW 25KVA, 1PH

MCC

REMOVE EXISTING

EXISTING MCC

COVER SLOTS BELOW

FLOW

MAIN OFFICE

OIL TANK

HYDRAULIC

PUMP ROOM

HYDRAULIC

E

X

IS

T

IN

G

G E

N E

R A

T O

R

S T

A N

D

B Y

EL. 670.75

SECOND FLOOR

D O

W N

EL. 657.42

FIRST FLOOR

SCALE: ‚"=1'-0"

M/W OPERATIONS BUILDING

D O

W N

SUB-OFFICE

4' 8'0 2'

SCALE: ‚"=1'

A

A

OIL TANK

HYDRAULIC

SECOND FLOOR

FIRST FLOOR

G A

L L

E R

Y

RECEIVER

AIR

A

SECTION

SCALE: ‚"=1'-0"

75KVA AND 25KVA TRANSFORMERS SHALL BE PROPERLY GROUNDED AND BONDED.10.

CORE DRILL 3" DIA HOLES THRU FLOOR FOR CABLE PENETRATION. MAXIMUM NUMBER OF HOLES SHOWN.9.

SEE DWG S-1030 FOR STRUCTURAL PLANS AND DETAILS.8.

PARAGRAPH 3.1.

FOR THE EXISTING MAIN SWITCHBOARD DEMOLITION REQUIREMENT, SEE SPECIFICATION 02 41 007.

PANEL LPC IF THESE CABLES ARE SHORT IN LENGTH.

FOR SPLICING EXISTING CABLES TRANSFERRED FROM EXISTING SWITCHBOARD TO NEW LIGHTING

PROVIDE AND INSTALL A JUNCTION BOX, 12"x12"x6" NEMA 12, CAT. HOFFMAN #A1212CH WALL MOUNT6.

DISPOSE OF BY THE CONTRACTOR.

REMOVE THREE EXISTING 15KVA TRANSFORMERS IN RESTROOM AND ASSOCIATED WIRING AND5.

75KVA TRANSFORMER SHALL HAVE BOTTOM ENTRY FOR CONDUITS.

ON A 2-INCH CONCRETE PAD. CORE DRILL HOLES THRU FLOOR FOR WIRING CABLES TO MW-MCC.

PROVIDE AND INSTALL A LIGHTING TRANSFORMER, 75KVA, 480-120/208V, 3PH, 60HZ, FLOOR MOUNT4.

TO AVOID SEATING ON TOP OF NEW MCC.

RELOCATE TWO EXISTING FLUORESCENT FIXTURES, CEILING MOUNT, ABOUT 36 INCHES OUTWARD3.

REFERENCE DWG E-7021.

29/16.2. FOR INTERLOCK SYSTEM RELATED TO MAIN SWITCHBOARD INFORMATION, SEE

SWITCHBOARD AND CABLE SCHEDULE, SEE REFERENCE DWG'S 29/1.3, 29/2.1, 29/15.1 AND

AND SPLICED IN AN APPROPRIATELY SIZED APPROVED JUNCTION BOX. FOR EXISTING MAIN

CABLE EXTENSION SHOULD BE PROVIDED WITH THE SAME TYPE AND SIZE OF EXISTING CABLE

IN NEW ONE-LINE DIAGRAM. IF THE EXISTING CABLE WOULD NOT BE LONG ENOUGH, THEN THE

CONTROL CENTER SHALL BE RECONNECTED TO NEW ASSOCIATED CIRCUIT BREAKERS AS SHOWN

EXISTING CIRCUIT CABLES TRANSFERRED FROM EXISTING MAIN SWITCHBOARD TO NEW MOTOR2.

ARE CONNECTED TO THE NEW MOTOR CONTROL CENTER.

REMOVE EXISTING MAIN SWITCHBOARD AND CONCRETE PAD COMPLETELY AFTER ALL CIRCUITS1.

NOTES:

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-1061

M

ID

D L E W

A L L O

P E

R A

T

IO

N S B

U

IL

D

IN

G

F

IR

S T S

E C

O N

D F

L O

O R

S P

L A

N S S

E C

T

IO

N

D A

N

IE

N G

U Y

E N

E

L E

IS

U R

E R

G A

D O

M S

K I

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

145"

25" 20" 20" 20" 20" 20" 20"

RECOMMENDATIONS

4" CURB PER MANUFACTURER'S

FOR EXISTING MCC WIRING, SEE REFERENCE DRAWING O-LPI-29/2.3.

BE ARRANGED TO UTILIZE EXISTING CABLES WITHOUT SPLICES.

ACTUAL MCC ARRANGEMENT MAY BE DIFFERENT. THE MCC SHALL2.

SEE DRAWING E-6063, E-6064, AND E-6065 FOR WIRING DIAGRAM.1.

NOTES:

0 1" 2"

SCALE: 1"=1"

SCALE: 1"=1'-0"

(LOCATED IN OPERATIONS BUILDING, SECOND FLOOR)

MIDDLE WALL MOTOR CONTROL CENTER LAYOUT (MW-MCC)

FOR WIRING DETAILS.

BE 30.5MM, TYPE 4/13. SEE DRAWING E-6066 AND E-6067

LED PILOT LIGHTS. ALL PUSHBUTTONS AND INDICATORS SHALL

PUSHBUTTONS AND RED, AMBER AND GREEN PUSH-TO-TEST

TRAFFIC SIGNAL CONTROLS SHALL CONSIST OF START/STOP2.

TURNED ON SIMULTANEOUSLY.

KIRKKEY TO PREVENT BOTH CIRCUIT BREAKERS FROM BEING

GENERATOR CIRCUIT BREAKER SHALL BE INTERLOCKED VIA A

THE 400A MAIN CIRCUIT BREAKER AND THE 300A MIDDLE WALL1.

NOTES:

NO. 1

SECTION

NO. 2

SECTION

NO. 3

SECTION

NO. 4

SECTION

NO. 5

SECTION

NO. 6

SECTION

NO. 7

SECTION

A

B

C

D

E

F

G

H

J

K

L

M

1A 2A

2C

2L

2M

3A

3C

3E

3H

3J

3K

3L

3M

4A

4C

4E

4H

4J

4K

4L

4M

5A

5C

5E

5H

5K

6A

6E

6G

6K

7A

7C

7E

7G

7J

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-2062

M

ID

D L E W

A L L M

O T

O R C

O N

T R

O L C

E N

T E

R

(M W -M

C C

R O

N A

D

R

G A

D O

M S

K I

E

L E

IS

U R

E D

N G

U Y

E N

R s

J

O

N

IT

E S

P .E

(MW-MCC) - SCHEDULE NAMEPLATE ANDCIRCUIT

SECTION

LINEFIRST LINESECOND LINETHRID

PLATELEGEND

BREAKER

CIRCUIT

H.P.

MOTOR

1A AND WALLLAND WALLRIVER SIGNALTRAFFIC

2A CLOCKTIME LIGHTSNAVIGATION

2C LPL PANELLIGHTING 4W 3PH,120/280V,

2L 480-120/208V PHASETHREE TRANSFORMER LPL 125A

2M 480-120/240V PHASESINGLE TRANSFORMER LPC 80A

3A CONTACTORLIGHTING LIGHTING WALLLAND OFF ON, OFF,ON, 20A

3C CONTACTORLIGHTING LIGHTING WALL GUARDUPPER OFF ON, OFF,ON, 20A

3E 1 NO. PUMPOIL OFF ON, STOP,START, 175A 50

3H TRANSFORMER SHELTER 2 NO.STATION 20A

3J TRANSFORMER SHELTER 3 NO.STATION 20A

3K WALL RIVERLOWER RECEPTACLE CRANEJIB 90A

3L SPARE 20A

3M SPARE 20A

4A CONTACTORLIGHTING LIGHTING WALLMIDDLE OFF ON, OFF,ON, 20A

4C CONTACTORLIGHTING LIGHTING WALL GUIDEUPPER OFF ON, OFF,ON, 20A

4E 2 NO. PUMPOIL OFF ON, STOP,START, 175A 50

4H POWERSHORE RECEPTACLE 1 NO. WALLLAND 70A

4J POWERSHORE RECEPTACLE 2 NO. WALLLAND 90A

4K POWERSHORE RECEPTACLE 3 NO. WALLMIDDLE 90A

4L POWERSHORE RECEPTACLE 4 NO. WALLMIDDLE 70A

4M SPARE 20A

5A CONTACTORLIGHTING LIGHTING WALLRIVER OFF ON, OFF,ON, 20A

5C CONTACTORLIGHTING LIGHTING WALL GUARDLOWER OFF ON, OFF,ON, 20A

5E 3 NO. PUMPOIL OFF ON, STOP,START, 175A 50

5H PUMP PRESSUREOIL OFF ON, STOP,START, 60A 15

5K SERVICEGENERAL PUMPWATER OFF ON, STOP,START, 150A 40

6A GENERATORM/W POWERSTANDBY 300A

6E

6G 1 NO. FEEDERDAM BRIDGESERVICE 200A

6K 2 NO. FEEDERDAM BRIDGESERVICE 200A

7A CONTACTORLIGHTING LIGHTING BITMOORING CHAMBER1200FT OFF ON, OFF,ON,

7C CONTACTORLIGHTING LIGHTING BITMOORING CHAMBER600FT OFF ON, OFF,ON,

7E MONITORPOWER

7G TVSS 30A

7J 400A - CBMAIN 400A

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

CERTIFIED FINAL DOCUMENTS

G

A

R

G

REFERENCE DWG E-7001

BUILDING ELECTRICAL ROOM, SEE

LOCATED IN LAND WALL SERVICE

CIRCUIT BREAKER IN EXISTING LW-MCC

2-3"C

3 #350KCMIL, #2 GRD,

EXISTING 2 SETS OF

ELECTRICAL ROOM

SERVICE BUILDING

LOCATED IN LAND WALL

EXISTING JUNCTION BOX

FEEDERS

EXISTING GENERATOR

(LOCATED IN M/W BUILDING)

190KW, 480V, 3PH

EXISTING M/W GENERATOR

EXISTING EXISTING EXISTING EXISTING

(TYP)

AND CONTROL

PUMP STARTER

(3) #10, #10 GRD IN EXISTING CONDUIT

(3) #4, #6 GRD IN EXISTING CONDUIT

3#350KCMIL, #2 GRD

EXISTING PARALLEL FEEDERS

SCALE: N.T.S.

ONE-LINE DIAGRAM - SHEET 1 OF 3

LW-MCC

600AF

400AT

3P

300A/3P

G

3P

400AT

600AF

3P

300AT

400AF

FU

PT

30AT

150AF

3P 3P 3P 3P 3P 3P 3P 3P 3P

175AT

225AF

175AT

225AF

175AT

225AF

60AT

150AF

70AT

150AF

90AT

150AF

90AT

150AF

70AT

150AF

G

METER TVSS

3 3 3 2

S

W

G

M A

T

HP1 HP2 HP3 HDP X X X X 4 5 (TYP)

GATE AND GARAGE

ABOVE 600FT

NO. 1

RECEPTACLE

POWER

L/W SHORE

EXISTING

GATE

LOWER 600FT

NO. 2

RECEPTACLE

POWER

L/W SHORE

EXISTING

NO. 3

RECEPTACLE

POWER

M/W SHORE

EXISTING

LOWER END

NO. 4

RECEPTACLE

POWER

M/W SHORE

EXISTING

HP

HP

HP

HP

NO. 1

OIL PUMP

EXISTING

NO. 2

OIL PUMP

EXISTING

NO. 3

OIL PUMP

EXISTING

HOLDING PUMP

OIL PRESSURE

EXISTING

SUPPRESSOR

VOLTAGE SURGE

MONITOR

POWER

METERING

SOLID STATE

CIRCUIT BREAKER

STAND-BY POWER

MIDDLE WALL

CIRCUIT BREAKER

MCC MAIN

MAIN BUS - 600A, 42000 A.I.C. BRACING, 480V, 3PH, 3W

NEW MOTOR CONTROL CENTER IN MIDDLE WALL BUILDING - MW-MCC

SSOL

ENSURE THE MCC GROUND IS IN COMPLIANCE WITH THE NEC.

THE CONTRACTOR SHALL CONDUCT A GROUND RESISTANCE TEST TO5.

PROVIDE APPROPRIATELY APPROVED JUNCTION BOX FOR SPLICING.

MCC. THE EXTENSION SHALL BE THE SAME TYPE OF THE EXISTING.

ENOUGH WHEN THE ASSOCIATED CIRCUIT TRANSFERRED TO NEW

THE CONTRACTOR SHALL EXTEND EXISTING CABLES NOT LONG4.

SEE DRAWING E-2062 FOR NEW MCC LAYOUT.3.

LENGTH FROM SOURCE TO EQUIPMENT UNLESS OTHERWISE NOTED.

ALL NEW FEEDER CABLES SHALL BE PROVIDED IN CONTINUOUS2.

REMAIN UNLESS OTHERWISE SPECIFIED.

EXISTING ELECTRICAL EQUIPMENT IN M/W OPERATION BUILDING TO1.

GENERAL NOTES:

INST, GF, AND GFD SETTINGS.

PROVIDE ELECTRONIC TRIP UNIT WITH LTPU, LTD, STPU, STD,6.

OTHERWISE NOTED.

ALL WIRING CABLES AND CONDUITS ARE EXISTING, UNLESS5.

SHALL BE AS SHOWN ON THE DRAWINGS.

CENTER, KEEPING EXISTING NAMES. CABLE WITH NEW NAME

PROVIDE NAME TAGS ON ALL CABLES IN NEW MOTOR CONTROL4.

THE NEW STARTER PANELS.

EXISTING EXTERNAL CONTROLS SHALL BE RE-CONNECTED TO

ADDITIONAL N.O. OR N.C. CONTACTS MAY BE REQUIRED. ALL3.

PUSHBUTTONS AND INDICATORS SHALL BE 30.5 MM, TYPE 4/13.

CONTROL WIRING SHALL BE 16AWG, COPPER TYPE MTW. ALL

OVERLOAD RELAYS SHALL HAVE ADJUSTABLE TRIP SETTINGS. ALL

CONTROL TRANSFORMER WITH PRIMARY AND SECONDARY FUSING.

ON/OFF PUSH-TO-TEST LED PILOT LIGHTS (RED/GREEN) AND

PUMP CONTROLS SHALL CONSIST OF START/STOP PUSHBUTTONS,2.

SIMULTANEOUSLY.

CIRCUIT BREAKER TO AVOID TURNING ON BOTH BREAKERS

ON BOTH MCC MAIN CIRCUIT BREAKER AND M/W GENERATOR

PROVIDE MECHANICAL INTERLOCK WITH KIRK KEY SCHEME 35A1.

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-6063

O N

E -L

IN

E D

IA

G R

A M

S H

E E

T O

F

R O

N A

G A

D O

M S

K I

E

L E

IS

U R

E J

O S

T R

O S

K Y

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

CERTIFIED FINAL DOCUMENTS

X GEN

EXISTING EXISTING EXISTING EXISTING EXISTING

(4) 4/0, #4GRD, 2•"C (3) #1, #6GRD, 1‚"C

(3) #2AWG, #6GRD, 1•"C (2) #2, #8GRD, 1•"C

SCALE: N.T.S.

ONE-LINE DIAGRAM - SHEET 2 OF 3

S

M A

T

125AT

150AF

90AT

150AF

200AT

225AF

200AT

225AF

20AT

150AF

20AT

150AF

20AT

150AF

20AT

150AF

80AT

150AF

3P 3P 3P 3P 3P 3P 3P 3P 2P

S

M A

T

LPL X X X

RECEPTACLE

JIB CRANE

POWER

R/W SHORE

EXISTING

NO. 1

DAM FEEDER

EXISTING

NO. 2

DAM FEEDER

EXISTING

CS2

STATION NO. 2

CONTROL

TRANSFORMER

EXISTING

CS3

STATION NO. 3

CONTROL

TRANSFORMER

EXISTING

FLOOR MOUNT

120/240VAC

25kVA, 1PH, 480VAC

TRANSFORMER

NEW DRY TYPE

SPARE SPARE

1PH, 3W

120/240V

125A

LPC

IN M/W BUILDING

30 SPACES

1PH, 3W, 60HZ

MAIN CB 125A, 120/240V

LIGHTING PANEL "C"

NEW

FLOOR MOUNT

480-120/208VAC, 60HZ

75kVA, 3PH, 4W

TRANSFORMER

NEW DRY TYPE

IN MCC

42 SPACES

3PH, 4W, 60HZ

MAIN CB 225A, 120/208V

LIGHTING PANEL "L"

NEW

3PH

120/208V

225A

LPL

3PH

120/208V

100A

LPB

IN M/W BUILDING

3PH, 4W, 60HZ

100A, 120/208VAC

LIGHTING PANEL "B"

EXISTING

LPC (TYP)1DF1 DF2

MAIN BUS - 600A, 42000A.I.C. BRACING, 480V, 3PH, 3W

NEW MOTOR CONTROL CENTER IN MIDDLE WALL BUILDING - MW-MCC

2 2

INST, GF, AND GFD SETTINGS.

PROVIDE ELECTRONIC TRIP UNIT WITH LTPU, LTD, STPU, STD,2.

NAMES SHALL BE AS SHOWN ON THE DRAWINGS.

CENTER, KEEPING EXISTING NAMES. THE CABLES WITH NEW

PROVIDE NAME TAGS ON ALL CABLES IN NEW MOTOR CONTROL1.

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-6064

O N

E -L

IN

E D

IA

G R

A M

S H

E E

T O

F

R O

N A

G A

D O

M S

K I

E

L E

IS

U R

E J

O S

T R

O S

K Y

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

EXISTING

(TYP)

CONTACTOR

LIGHTING

EXISTING

EXISTING CONDUIT

3/C#4 W/GRD IN EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING

FOR POWER

TO LPL CKT #2

FOR POWER

TO LPL CKT #3

EXISTING ASSOCIATED CIRCUIT.

NEW CABLE SHALL BE OF THE SAME SIZE AND TYPE AS THE4.

PUSHBUTTONS AND INDICATORS SHALL BE 30.5 MM, TYPE 4/13.

CONTROL WIRING SHALL BE 16AWG, COPPER TYPE MTW. ALL

OVERLOAD RELAYS SHALL HAVE ADJUSTABLE TRIP SETTINGS, ALL

CONTROL TRANSFORMER WITH PRIMARY AND SECONDARY FUSING.

ON/OFF PUSH-TO-TEST LED PILOT LIGHTS (RED/GREEN) AND

PUMP CONTROLS SHALL CONSIST OF START/STOP PUSHBUTTONS,3.

LIGHTING CONTROLS SHALL CONSIST OF ON/OFF PUSHBUTTONS.2.

NAMES SHALL BE AS SHOWN ON THE DRAWINGS.

CENTER, KEEPING EXISTING NAMES. THE CABLES WITH NEW

PROVIDE NAME TAGS ON ALL CABLES IN NEW MOTOR CONTROL1.

NOTES:

SCALE: N.T.S

ONE-LINE DIAGRAM - SHEET 3 OF 3

S

M A

T

LPL2 X LPL3 X X X X X X X X

150AT

150AF

20AT

150AF

20AT

30AF

20AT

30AF

20AT

30AF

20AT

30AF

20AT

30AF

20AT

30AF

3P 3P 2P 2P 2P 2P 2P 2P

SPARE

(TYP)1

4 4

HP

WATER PUMP

SERVICE

GENERAL

EXISTING

11111111

1200FT CHAMBER

MOORING BIT LIGHTING

EXISTING

600FT CHAMBER

MOORING BIT LIGHTING

EXISTING

RIVER WALL

LIGHTING

EXISTING

LAND WALL

LIGHTING

EXISTING

MIDDLE WALL

LIGHTING

EXISTING

WALL

UPPER GUIDE

LIGHTING

EXISTING

WALL

UPPER GUARD

LIGHTING

EXISTING

WALL

LOWER GUARD

LIGHTING

EXISTING

MAIN BUS - 600A, 42000A.I.C. BRACING, 480V, 3PH, 3W

NEW MOTOR CONTROL CENTER IN MIDDLE WALL BUILDING - MW-MCC

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-6065

O N

E -L

IN

E D

IA

G R

A M

S H

E E

T O

F

R O

N A

G A

D O

M S

K I

E

L E

IS

U R

E J

O S

T R

O S

K Y

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-6066

L A

N D C

H A

M B

E R

T R

A F F

IC

S

IG

N A

L W

IR

IN

G D

IA

G R

A M

R O

N A

G A

D O

M S

K I

E

L E

IS

U R

E J

O S

T R

O S

K Y

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

CERTIFIED FINAL DOCUMENTS

L

N

2 3

THE THREE STOP BUTTONS.

RED SIGNAL LIGHT WILL FLASH. THE SYSTEM CAN BE DE-ENERGIZED BY PRESSING ONE OF

AND AMBER SIGNAL LIGHTS TO FLASH FOR A PREDETERMINED PERIOD FOLLOWING WHICH THE

THE AMBER-GREEN BUTTON AT THE ADJACENT CONTROL STATION. THIS CAUSES THE GREEN

PLACED WITHIN THEIR RESPECTIVE RECESSES A COMBINATION SIGNAL IS GIVEN, BY PRESSING

OUT AND THE RED SIGNAL LIGHT WILL FLASH. IF BOTH GATE LEAVES CANNOT BE FULLY

OPEN, WHILE THE GREEN SIGNAL LIGHT IS FLASHING, THE GREEN SIGNAL LIGHT WILL GO

GO OUT AND THE GREEN SIGNAL LIGHT WILL FLASH. SHOULD ONE OR BOTH GATE SWITCHES

BOTH GATE LIMIT SWITCHES TO CLOSE, FOLLOWING WHICH THE AMBER SIGNAL LIGHT WILL

FLASH UNTIL BOTH GATE LEAVES ARE FULLY WITHIN THEIR RESPECTIVE RECESSES, CAUSING

ADJACENT CONTROL STATION IS PRESSED. THE AMBER SIGNAL LIGHT WILL CONTINUE TO

GREEN SIGNAL, WITH THE AMBER SIGNAL LIGHT FLASHING, THE GREEN BUTTON AT THE

LIGHT AT THE OTHER END OF THE LOCK CONTINUES TO FLASH. TO SET UP FOR A

STATION TO GO OUT AND THE CORRESPONDING AMBER SIGNAL TO FLASH. THE RED SIGNAL

EITHER CONTROL STATION IS PRESSED CAUSING THE RED SIGNAL LIGHT AT THE SELECTED

AMBER SIGNAL, AT EITHER END OF THE LOCK, THE CORRESPONDING AMBER BUTTON, AT

THE RED SIGNAL LIGHTS AT BOTH ENDS OF THE LOCK TO FLASH. TO CHANGE TO AN

THE SYSTEM IS ENERGIZED BY PRESSING ONE OF THE THREE START BUTTONS CAUSING

DESCRIPTION OF OPERATION:

1766-L32AWA

CONTROLLER

MICROLOGIX 1400

ALLEN-BRADLEY

PLC

IN MW-MCC

PANEL "LPL-1"

LIGHTING

120VAC FROM

EQUAL TO GE LIGHTING SOLUTIONS GTX SERIES.

TRAFFIC SIGNALS OR TRAFFIC SIGNAL LED MODULES SIMILIAR OR

REPLACED WITH EQUIVALENT WATTAGE LED BULBS SUITABLE FOR

EXISTING TRAFFIC SIGNAL INCANDESCENT LIGHT BULBS SHALL BE8.

ALL RELAY COILS SHALL HAVE SURGE SUPPRESSORS INSTALLED.7.

PUSH-TO-TEST WIRING NOT SHOWN FOR CLARITY.

SERIES. INDICATORS SHALL BE PUSH-TO-TEST LED TYPE. REQUIRED

WATERTIGHT/OILTIGHT SIMILAR OR EQUAL TO ALLEN-BRADLEY 800T

ALL INDICATORS AND PUSHBUTTONS SHALL BE 30.5mm, NEMA 4/136.

APPLIED.

BE LABELED AND ALL CONDUCTORS SHALL HAVE WIRE MARKERS

ALL TERMINAL BLOCKS, RELAYS, SWITCHES AND INDICATORS SHALL5.

TERMINATED TO TERMINAL BLOCKS AND IDENTIFIED.

ALL CABLES ENTERING/EXITING THE ENCLOSURE SHALL BE4.

BACKUP MODULE AND BACKUP MEMORY MODULE.

THE MICROLOGIX 1400 PLC SHALL BE PROVIDED WITH A BATTERY3.

OF 20 DIGITAL INPUTS AND 12 DIGITAL OUTPUTS

MICROLOGIX 1400 CONTROLLER 1766-L32AWA WITH A MINIMUM

THE PLC SHALL BE SIMILAR OR EQUAL TO AN ALLEN-BRADLEY2.

SHALL BE LOCATED IN MIDDLE WALL MCC.

DRAWINGS FOR EXISTING WIRING. THE TRAFFIC SIGNAL CONTROL

MANNER AS THE EXISTING CONTROLS. CONSULT REFERENCE

THE TRAFFIC SIGNAL CONTROLS SHALL OPERATE IN THE SAME1.

NOTES:

S

S

S

N

TRAFFIC SIGNAL CONTROLS

EXISTING UPSTREAM CONTROL STATION

UPPER POOL

A GR

11 12 13

NNN

8 5X6 5X2 5X

START AMBER

UPPER

GREEN

UPPER

9 5X

3 5X

AMBER-GREEN

UPPER

STOP

5 5X

LOWER POOL

AR

19 20

NN

AMBER

LOWER

TB

TM

A

G

R

TRAFFIC SIGNAL

UPSTREAM

EXISTING

N

N

N

STATION

CONTROL

UPSTREAM

CABLE TO

CONTROL

EXISTING

LIMIT SWITCH

GATE RECESS

U/S M/W

EXISTING

STATION

CONTROL

UPSTREAM

CABLE TO

CONTROL

EXISTING

MW-MCC

CABLE TO

CONTROL

EXISTING

S

S

S

N

UPPER POOL

AR

11 12

NN

6 5X

AMBER

UPPER

LOWER POOL

AR

19 20

N

TA

TM

A

G

R

N

N

N

LIMIT SWITCH

GATE RECESS

D/S M/W

EXISTING

T3

MW-MCC

CABLE TO

CONTROL

EXISTING

TRAFFIC SIGNAL

DOWNSTREAM

EXISTING

STATION

CONTROL

DOWNSTREAM

CABLE TO

CONTROL

EXISTING

STATION

CONTROL

DOWNSTREAM

CABLE TO

CONTROL

EXISTING

TRAFFIC SIGNAL CONTROLS

EXISTING DOWNSTREAM CONTROL STATION

G

5X

AMBER

LOWER

GREEN

LOWER

5X

5X

AMBER-GREEN

LOWER

2 5X

START

4 5X

STOP

5 5X

UPPER POOL

A GR

11 12 13

N

LOWER POOL

A GR

19 20 21

5X

N N

N N N N N

TJ

LIMIT SWITCH

GATE RECESS

U/S L/W

EXISTING

TL

LIMIT SWITCH

GATE RECESS

D/S L/W

EXISTING

MCC

CABLE TO

CONTROL

EXISTING

MCC

CABLE TO

CONTROL

EXISTING

S

S

S

N

L

N

L

L

L

T2

DI:1/0

DI:1/9

DI:1/8

DI:1/7

DI:1/6

DI:1/5

DI:1/4

DI:1/3

DI:1/2

DI:1/1

DI:1/10

DI:1/11

6A

6A

5 5X 6A

5X

START

3 5X

STOP

L

CR1

N

DO:1/0

DO:1/1

DO:1/2

DO:1/3

DO:1/4

DO:1/5

CR2

CR3

CR4

CR5

CR6

LOWER AMBER LIGHT

LOWER GREEN LIGHT

UPPER GREEN LIGHT

UPPER AMBER LIGHT

UPPER RED LIGHT

LOWER RED LIGHT

CR3

3A

CR5

3A

CR6

3A

CR4

3A

CR2

3A

CR1

3A

FUSE

FUSE

FUSE

AUXILIARY (600 FT.) CHAMBER

MW-MCC TRAFFIC CONTROL PANEL

SCALE: N.T.S.

LAND CHAMBER - 600FT. (MW-MCC)

TRAFFIC SIGNAL WIRING DIAGRAM

LOWER POOL SIGNAL - GREENDO:1/5

LOWER POOL SIGNAL - AMBERDO:1/4

LOWER POOL SIGNAL - REDDO:1/3

UPPER POOL SIGNAL - GREEND0:1/2

UPPER POOL SIGNAL - AMBERDO:1/1

UPPER POOL SIGNAL - REDDO:1/0

D/S L/W GATE RECESS LIMIT SWITCHDI:1/11

LOWER AMBER-GREEN PUSHBUTTONDI:1/10

LOWER GREEN PUSHBUTTONDI:1/9

D/S M/W GATE RECESS LIMIT SWITCHDI:1/8

LOWER AMBER PUSHBUTTONDI:1/7

U/S L/W GATE RECESS LIMIT SWITCHDI:1/6

UPPER AMBER-GREEN PUSHBUTTONDI:1/5

UPPER GREEN PUSHBUTTONDI:1/4

U/S M/W GATE RECESS LIMIT SWITCHDI:1/3

UPPER AMBER PUSHBUTTONDI:1/2

STOP PUSHBUTTONDI:1/1

START PUSHBUTTONDI:1/0

PLC I/O ASSIGNMENTS:

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-6067

R

IV

E R C

H A

M B

E R

T R

A F F

IC

S

IG

N A

L W

IR

IN

G D

IA

G R

A M

R O

N A

G A

D O

M S

K I

E

L E

IS

U R

E J

O S

T R

O S

K Y

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

CERTIFIED FINAL DOCUMENTS

L

N

2 3

THE THREE STOP BUTTONS.

RED SIGNAL LIGHT WILL FLASH. THE SYSTEM CAN BE DE-ENERGIZED BY PRESSING ONE OF

AND AMBER SIGNAL LIGHTS TO FLASH FOR A PREDETERMINED PERIOD FOLLOWING WHICH THE

THE AMBER-GREEN BUTTON AT THE ADJACENT CONTROL STATION. THIS CAUSES THE GREEN

PLACED WITHIN THEIR RESPECTIVE RECESSES A COMBINATION SIGNAL IS GIVEN, BY PRESSING

OUT AND THE RED SIGNAL LIGHT WILL FLASH. IF BOTH GATE LEAVES CANNOT BE FULLY

OPEN, WHILE THE GREEN SIGNAL LIGHT IS FLASHING, THE GREEN SIGNAL LIGHT WILL GO

GO OUT AND THE GREEN SIGNAL LIGHT WILL FLASH. SHOULD ONE OR BOTH GATE SWITCHES

BOTH GATE LIMIT SWITCHES TO CLOSE, FOLLOWING WHICH THE AMBER SIGNAL LIGHT WILL

FLASH UNTIL BOTH GATE LEAVES ARE FULLY WITHIN THEIR RESPECTIVE RECESSES, CAUSING

ADJACENT CONTROL STATION IS PRESSED. THE AMBER SIGNAL LIGHT WILL CONTINUE TO

GREEN SIGNAL, WITH THE AMBER SIGNAL LIGHT FLASHING, THE GREEN BUTTON AT THE

LIGHT AT THE OTHER END OF THE LOCK CONTINUES TO FLASH. TO SET UP FOR A

STATION TO GO OUT AND THE CORRESPONDING AMBER SIGNAL TO FLASH. THE RED SIGNAL

EITHER CONTROL STATION IS PRESSED CAUSING THE RED SIGNAL LIGHT AT THE SELECTED

AMBER SIGNAL, AT EITHER END OF THE LOCK, THE CORRESPONDING AMBER BUTTON, AT

THE RED SIGNAL LIGHTS AT BOTH ENDS OF THE LOCK TO FLASH. TO CHANGE TO AN

THE SYSTEM IS ENERGIZED BY PRESSING ONE OF THE THREE START BUTTONS CAUSING

DESCRIPTION OF OPERATION:

SCALE: N.T.S.

RIVER CHAMBER - 1200FT. (MW-MCC)

TRAFFIC SIGNAL WIRING DIAGRAM

LOWER POOL SIGNAL - GREENDO:1/5

LOWER POOL SIGNAL - AMBERDO:1/4

LOWER POOL SIGNAL - REDDO:1/3

UPPER POOL SIGNAL - GREEND0:1/2

UPPER POOL SIGNAL - AMBERDO:1/1

UPPER POOL SIGNAL - REDDO:1/0

D/S L/W GATE RECESS LIMIT SWITCHDI:1/11

LOWER AMBER-GREEN PUSHBUTTONDI:1/10

LOWER GREEN PUSHBUTTONDI:1/9

D/S M/W GATE RECESS LIMIT SWITCHDI:1/8

LOWER AMBER PUSHBUTTONDI:1/7

U/S L/W GATE RECESS LIMIT SWITCHDI:1/6

UPPER AMBER-GREEN PUSHBUTTONDI:1/5

UPPER GREEN PUSHBUTTONDI:1/4

U/S M/W GATE RECESS LIMIT SWITCHDI:1/3

UPPER AMBER PUSHBUTTONDI:1/2

STOP PUSHBUTTONDI:1/1

START PUSHBUTTONDI:1/0

PLC I/O ASSIGNMENTS:

1766-L32AWA

CONTROLLER

MICROLOGIX 1400

ALLEN-BRADLEY

PLC

IN MW-MCC

PANEL "LPL-5"

LIGHTING

120VAC FROM

EQUAL TO GE LIGHTING SOLUTIONS GTX SERIES.

TRAFFIC SIGNALS OR TRAFFIC SIGNAL LED MODULES SIMILIAR OR

REPLACED WITH EQUIVALENT WATTAGE LED BULBS SUITABLE FOR

EXISTING TRAFFIC SIGNAL INCANDESCENT LIGHT BULBS SHALL BE8.

ALL RELAY COILS SHALL HAVE SURGE SUPPRESSORS INSTALLED.7.

PUSH-TO-TEST WIRING NOT SHOWN FOR CLARITY.

SERIES. INDICATORS SHALL BE PUSH-TO-TEST LED TYPE. REQUIRED

WATERTIGHT/OILTIGHT SIMILAR OR EQUAL TO ALLEN-BRADLEY 800T

ALL INDICATORS AND PUSHBUTTONS SHALL BE 30.5mm, NEMA 4/136.

APPLIED.

BE LABELED AND ALL CONDUCTORS SHALL HAVE WIRE MARKERS

ALL TERMINAL BLOCKS, RELAYS, SWITCHES AND INDICATORS SHALL5.

TERMINATED TO TERMINAL BLOCKS AND IDENTIFIED.

ALL CABLES ENTERING/EXITING THE ENCLOSURE SHALL BE4.

BACKUP MODULE AND BACKUP MEMORY MODULE.

THE MICROLOGIX 1400 PLC SHALL BE PROVIDED WITH A BATTERY3.

OF 20 DIGITAL INPUTS AND 12 DIGITAL OUTPUTS

MICROLOGIX 1400 CONTROLLER 1766-L32AWA WITH A MINIMUM

THE PLC SHALL BE SIMILAR OR EQUAL TO AN ALLEN-BRADLEY2.

SHALL BE LOCATED IN MIDDLE WALL MCC.

DRAWINGS FOR EXISTING WIRING. THE TRAFFIC SIGNAL CONTROL

MANNER AS THE EXISTING CONTROLS. CONSULT REFERENCE

THE TRAFFIC SIGNAL CONTROLS SHALL OPERATE IN THE SAME1.

NOTES:

S

S

S

N

TRAFFIC SIGNAL CONTROLS

EXISTING UPSTREAM CONTROL STATION

UPPER POOL

A GR

11 12 13

NNN

8 5X6 5X2 5X

START AMBER

UPPER

GREEN

UPPER

9 5X

3 5X

AMBER-GREEN

UPPER

STOP

5 5X

LOWER POOL

AR

19 20

NN

AMBER

LOWER

TC

TM

A

G

R

TRAFFIC SIGNAL

UPSTREAM

EXISTING

N

N

N

STATION

CONTROL

UPSTREAM

CABLE TO

CONTROL

EXISTING

LIMIT SWITCH

GATE RECESS

U/S M/W

EXISTING

STATION

CONTROL

UPSTREAM

CABLE TO

CONTROL

EXISTING

MW-MCC

CABLE TO

CONTROL

EXISTING

S

S

S

N

UPPER POOL

AR

11 12

NN

6 5X

AMBER

UPPER

LOWER POOL

AR

19 20

N

TC

TM

A

G

R

N

N

N

LIMIT SWITCH

GATE RECESS

D/S M/W

EXISTING

T4

MW-MCC

CABLE TO

CONTROL

EXISTING

TRAFFIC SIGNAL

DOWNSTREAM

EXISTING

STATION

CONTROL

DOWNSTREAM

CABLE TO

CONTROL

EXISTING

STATION

CONTROL

DOWNSTREAM

CABLE TO

CONTROL

EXISTING

TRAFFIC SIGNAL CONTROLS

EXISTING DOWNSTREAM CONTROL STATION

G

5X

AMBER

LOWER

GREEN

LOWER

5X

5X

AMBER-GREEN

LOWER

2 5X

START

4 5X

STOP

5 5X

UPPER POOL

A GR

11 12 13

N

LOWER POOL

A GR

19 20 21

5X

N N

N N N N N

TG

LIMIT SWITCH

GATE RECESS

U/S L/W

EXISTING

TR

LIMIT SWITCH

GATE RECESS

D/S L/W

EXISTING

MCC

CABLE TO

CONTROL

EXISTING

MCC

CABLE TO

CONTROL

EXISTING

S

S

S

N

L

N

L

L

L

T1

DI:1/0

DI:1/9

DI:1/8

DI:1/7

DI:1/6

DI:1/5

DI:1/4

DI:1/3

DI:1/2

DI:1/1

DI:1/10

DI:1/11

6A

6A

5 5X 3A

5X

START

3 5X

STOP

L

CR1

N

DO:1/0

DO:1/1

DO:1/2

DO:1/3

DO:1/4

DO:1/5

CR2

CR3

CR4

CR5

CR6

LOWER AMBER LIGHT

LOWER GREEN LIGHT

UPPER GREEN LIGHT

UPPER AMBER LIGHT

UPPER RED LIGHT

LOWER RED LIGHT

MAIN (1200 FT.) CHAMBER

MW-MCC TRAFFIC CONTROL PANEL

CR3

3A

CR5

3A

CR6

3A

CR4

3A

CR2

3A

CR1

3A

FUSE

FUSE

FUSE

SURGE PROTECTION.

ALL PANELS TO BE PROVIDED WITH INTERNAL PLUG-ON2.

THE EXISTING. PROVIDE APPROPRIATE JUNCTION BOX FOR SPLICING.

NEW EXTENSION SHALL BE OF THE SAME TYPE AND SIZE AS

EXTEND THE EXISTING CABLE TO NEW PANEL AS NECESSARY.1.

NOTES:

LPL PANELLIGHTING

225A RATING:MAIN 4W 3PH, 120/208V,VOLTAGE: 12NEMA ENCLOSURE: MCC INMOUNTING:

250A RATING: BUSMAIN 22,000 RATING:A.I.C. 42POLES: X NO.:CATALOG

DESCRIPTION

BREAKERCKT. kVA -LOAD kVA -LOAD BREAKERCKT.

DESCRIPTION

NO. AMP POLE Ø A Ø B Ø C Ø A Ø B Ø C POLE AMP NO.

SIGNALS TRAFFIC600' 1 20 1 1 20 2 LIGHTS BIT MOORING1200'

LIGHTS BIT MOORING600' 3 20 1 1 20 4 END LOWER LIGHTS,GALLERY

LIGHTS TRAFFIC1200' 5 20 1 1 20 6 END UPPER LIGHTS,GALLERY

CKT HOLDING STREET & LIGHTS BIT 1200' &600' 7 20 1 1 20 8 CONTROL VALVE1200'

HORN BOAT & LIGHTS HEEL WALLRIVER 9 20 1 1 20 10 CONTROL VALVE600'

SB 1200' LOWERCONSOL, 11 20 1 1 20 12 LIGHTS HEEL WALLLAND

REFRIGERATOR 13 20 1 1 20 14 LIGHTS FLOOD 1200' & BUILDING SHELTER1200'

SB 1200' UPPERCONSOL, 15 20 1 1 20 16 LIGHTS FLOOR 1200' & BUILDINGS SHELTER 600' BOTHCONSOL, LIGHTSNAVIGATION 17 20 1 1 20 18 STRIP RECEPTACLE RIGHTSUB-OFFICE

LIGHTS HEEL WALL MIDDLE 600' & BUILDING SHELTER600' 19 20 1

3 60

FEEDER LPB PANELLIGHTING CONDITIONERAIR 21 20 1 22

STRIP RECEPTACLE LEFTSUB-OFICE 23 20 1 24

POT COFFEE & VCRTV, 25 20 1 1 20 26 RECEPTACLE SYSTEMPHONE

MICROWAVE 27 20

1 20 28 MACHINEPOP

SPARE 29 20 1 20 30 STRIP RECEPTACLE MIDDLESUB-OFFICE

SPARE

20 2 2 20

SPARE

33 34

SPARE 35 20 1 1 20 36 SPARE

SPACE 37 38 SPACE

SPACE 39 40 SPACE

SPACE 41 42 SPACE

TOTAL:

BUILDING WALL MIDDLELOCATION: Ø: A CABLES EXISTING ARE 30 THRU 1 CKTNOTES:

Ø: B

Ø: C

TOTAL:

LPC PANELLIGHTING

125A/2P RATING:MAIN 3W 1PH, - 120/240VVOLTAGE: 12NEMA ENCLOSURE: SURFACE MOUNTING:

125A RATING: BUSMAIN 22,000 RATING:A.I.C. 30 POLES: NDOQ DSQUARE NO.:CATALOG

DESCRIPTION

BREAKERCKT. kVA -LOAD kVA -LOAD BREAKERCKT.

DESCRIPTION

NO. AMP POLE Ø A Ø B Ø A Ø B POLE AMP NO.

PUMPGRINDER

30 2 2 30

LIGHTSHOUSE

3 4

STOVE/OVER

50 2 2 30

HEATERCC7

7 8

HEATER ROOMLUNCH

20 2 2 20

FANVENT

11 12

SPARE

20 2 2 30

SPARE

15 16

SPARE

20 2 2 20

SPARE

19 20

SPARE 21 20 1 1 20 22 SPARE

SPARE 23 20 1 1 20 24 SPARE

SPACE 25 26 SPACE

SPACE 27 28 SPACE

SPACE 29 30 SPACE

TOTAL:

BUILDING WALL MIDDLELOCATION: Ø: A CABLES EXISTING ARE 16 & 14, 12, THRU 1 CKTNOTES:

Ø: B

TOTAL:

P W

P :d m s

L P

IO

E .d g n h e c n e r l

M A

R

:5

L P

IO

E .d g n

.0

:1

E L E

C T

R

IC

A L S

Y S

T E

M S

E-6068

L

IG

H T

IN

G P

A N

E L S L

P L L

P C

S C

H E

D U

L E

S

D A

N

IE

N G

U Y

E N

E

L E

IS

U R

E R

G A

D O

M S

K I

R s

J

O

N

IT

E S

P .E

S O

L

IC

IT

A T

IO

N N

O

F

IL

E N

A M

E

D W

N B

Y

C K

D B

Y

D E

S

IG

N E

D B

Y

D E

S C

R

IP

T

IO

N

D

2 3

C

4 5

A

B

M A

R K

A P

P R

NUMBER

IDENTIFICATION

SHEET

OF ENGINEERS

US ARMY CORPS

D A

T E

F

IL

E N

U M

B E

R

S

IZ

E

S U

B M

IT

T E

D B

Y

P L

O T S

C A

L E

P L

O T D

A T

E

D A

T E

M A

R K

D E

S C

R

IP

T

IO

N A

P P

R

D A

T E

C O

N T

R A

C T N

O

C O

R P

S O

F E

N G

IN

E E

R S

U S

A R

M Y E

N G

IN

E E

R D

IS

T R

IT

T S

B U

R G

H P

A

O H

IO

R

IV

E R

A N

S I D

M

ID

D L E W

A L L M

C C R

E P

L A

C E

M E

N T

W E

S T V

IR

G

IN

IA

P

IK

E I S

L A

N D L

O C

K S A

N D D

A M

W

W N

B

LPIO_100_G-0023
LPIO_203_G-1024
LPIO_770_S-1030
LPIO_770_E-0060
LPIO_770_E-1061
LPIO_770_E-2062
LPIO_770_E-6063
LPIO_770_E-6064
LPIO_770_E-6065
LPIO_770_E-6066
LPIO_770_E-6067
LPIO_770_E-6068
Reference Drawings
O-LPI-20_2.6
O-LPI-20_3.4
O-LPI-20_4.5
O-LPI-20_5.3
O-LPI-20_7.3
O-LPI-20_8.2
O-LPI-20_9.3
O-LPI-20_15.2
O-LPI-20_16.1
O-LPI-21_1.4
O-LPI-22_1.2
O-LPI-22_3.1
O-LPI-22_6.2
O-LPI-27_1.1
O-LPI-28_1.1
O-LPI-29_1.3
O-LPI-29_2.1
O-LPI-29_5.3
O-LPI-29_6.3
O-LPI-29_7.2
O-LPI-29_8.2
O-LPI-29_9.2
O-LPI-29_10.1
O-LPI-29_11.1
O-LPI-29_12.1
O-LPI-29_13.1
O-LPI-29_15.1
O-LPI-29_16.2
O-LPI-29_17.1
O-LPI-70_1.1
O-LPI-70_3.1
O-LPI-70_4.2
O-LPI-70_5.1

File details come from the government source that posted it. Updated .