W911SA22B2014 Attachment 3 DRAWINGS.pdf
PDF 14 MB Posted
- Attached to
- Replace Airfield Fire Pump, Fort McCoy WI Federal contract opportunity
- Solicitation number
- W911SA22B2014
About this file
This document provides details for a federal contract solicitation to replace an airfield fire pump at Fort McCoy in Wisconsin. The solicitation seeks to procure all parts, labor, tools, equipment, materials and transportation necessary to replace the deluge fire suppression system building 6062 in accordance with provided specifications, drawings and contract documents. This is a 100% small business set-aside contract under NAICS code 237110 with a size standard of $36.5 million. The solicitation was issued by the Department of the Army Materiel Command Mission and Installation Contracting Command at Fort McCoy. Responses are due by the date specified on the solicitation.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W911SA22B2014 Bid Abstract Page 2.pdf | ||
| W911SA22B2014 Bid Abstract page 1.pdf | ||
| W911S22B2014 Attachement 6 Site Photos.pdf | ||
| W911SA22B2014 AMENDMENT 3.pdf | ||
| W911SA22B2014 AMENDMENT 2.pdf | ||
| Attachment 2 Specifications (revised 7192022).pdf | ||
| W911SA22B2014 SOLICIATION AMENDMENT.pdf | ||
| W911SA22B2014 SOLICIATION.pdf | ||
| W911SA22B2014 Attachment 1 ATOPSEC.pdf | ||
| W911SA22B2014 Attachment 2 SPECIFICATIONS.pdf | ||
| W911SA22B2014 Attachment 4 Wage Determination.docx | DOCX document |
Show all 11
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SHEET INDEX
E0.1 ELECTRICAL SYMBOLS AND ABBREVIATIONS
E1.1 ELECTRICAL DEMOLITION AND REMODEL PLANS - PUMP BUILDING
E1.2 ELECTRICAL DEMOLITION AND REMODEL PLANS - WELL HOUSE
E2.1 RISER DIAGRAMS
A AMBER, AMPERE, ALARM
AC ALTERNATING CURRENT
AFF ABOVE FINISHED FLOOR
AM AMMETER
ANN ANNUNCIATOR
AR ALARM RELAY
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BC BATTERY CHARGER
BLDG BUILDING
C CLOSE, COUNTER OR CONTACTOR
CAP CAPACITOR
CB CIRCUIT BREAKER
CD CONTROL DAMPER
CGD COMBUSTIBLE GAS DETECTOR
CKT CIRCUIT
CL2 CHLORINE
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CR CURRENT OR CONTROL RELAY
CS CONTROL STATION
CT CYCLE TIMER OR CURRENT
TRANSFORMER
CV CONTROL VALVE
2/C 2 CONDUCTOR
4"C 4" CONDUIT
DC DIRECT CURRENT
DI DOOR INTERLOCK
DM DAMPER MOTOR OR DEMAND METER
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DP DIFFERENTIAL PRESSURE
DPS DIFFERENTIAL PRESSURE SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
E EMERGENCY OR DAMPER OPERATOR
EC EMPTY CONDUIT
ECP EQUIPMENT CONTROL PANEL
EG ENGINE GENERATOR
EL ELEVATION OR EMERGENCY LIGHT
EMH ELECTRICAL MANHOLE
ES END SWITCH
ETM ELAPSED TIME METER
EUH ELECTRICAL UNIT HEATER
EVS EMERGENCY VENTILATION SHUTOFF
EXIST EXISTING
F FORWARD
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FDR FEEDER
FE FLOW ELEMENT
FIT FLOW INDICATING TRANSMITTER
FO FIBER OPTIC
FS FLOW SWITCH
FPSP FIRE PROTECTION SIGNALING PANEL
G GREEN OR GROUND OR GENERATOR
GD GROUND DETECTOR OR GAS
DETECTOR
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
GFCI GROUND FAULT CKT INTERRUPTER
GND GROUND
GUH GAS UNIT HEATER
H HIGH OR HUMIDISTAT
HH HANDHOLE
HOA HAND-OFF-AUTO
HP HORSEPOWER
HTR HEATER
HVMH HIGH VOLTAGE ELECTRIC MANHOLE
HZ HERTZ (CYLES PER SECOND)
I/O INPUT/OUTPUT
INST INSTANTANEOUS
IS INTRINSICALLY SAFE
ISO ISOLATION
J JUNCTION BOX
K KEY INTERLOCK
KAIC KILOAMPERE
KCMIL THOUSAND CIRCULAR MILS
KV KILIVOLT
KVA KILIVOLT AMPERE
KVAR KILOVAR
KW KILOWATT
KWH KILOWATT HOUR
L LOW, LEVEL
LA LIGHTNING ARRESTER
LAN LOCAL AREA NETWORK
LC LIGHTING CONTACTOR
LE LEVEL ELEMENT
LIT LEVEL INDICATING TRANSMITTER
LP LIGHTING PANEL
LS LIMIT OR LEVEL SWITCH
LTG LIGHTING
LWCO LOW WATER CUTOFF
M MAGNETIC MOTOR STARTER
MA MILLIAMPERE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MD MOISTURE DETECTOR
MFR MANUFACTURER
MH MANHOLE OR MOUNTING HEIGHT
MOV MOTOR OPERATED VALVE
MS MANUAL MOTOR STARTER
MSH MOTOR SPACE HEATER
MTR MOTOR
MTS MANUAL TRANSFER SWITCH
MV MILLIVOLT, MEDIUM VOLTAGE
MVA MEGA VOLT AMPERE
N NEUTRAL
NC NORMALLY CLOSED
NEC MOST RECENT EDITION OF NFPA 70
NATIONAL ELECTRIC CODE
NO NORMALLY OPEN
O OPEN
OL OVERLOAD
OOA ON-OFF-AUTO
OOR ON-OFF-REMOTE
OH OVERHEAD
P PRIMARY
PB PUSHBUTTON OR PULL BOX
PLC PROGRAMMABLE LOGIC CONTROLLER
PF POWER FACTOR
PFCC POWER FACTOR CORRECTION
CAPACITOR
PH PHASE, CHEMICAL TERM
PRS PROXIMITY SWITCH
PRV POWER ROOF VENTILATOR
PS PRESSURE SWITCH OR PUMP STATION
PT POTENTIAL TRANSFORMER OR
PROGRAM TIMER
2P 2 POLE
R RED, RAISE RELAY OR REVERSE
RECP RECEPTACLE
RGS RIGID GALVANIZED STEEL
RTD RESISTANCE TYPE TEMP DETECTOR
RTU REMOTE TERMINAL UNIT
SA SURGE SUPPRESSOR
SCC SHORT CIRCUIT CURRENT
SCADA SUPERVISORY CONTROL AND
DATA ACQUISITION
S2 SIZE 2 STARTER
SN SOLID NEUTRAL
SP SINGLE POLE
SPD SURGE PROTECTOR
SPDT SINGLE POLE DOUBLE THROW
SPST SINGLE POLE SINGLE THROW
SS SELECTOR SWITCH
S.S. STAINLESS STEEL
SSRV SOLID STATE REDUCED VOLTAGE
STARTER
SV SOLENOID VALVE
SWBD SWITCHBOARD
SWGR SWITCHGEAR
T THERMOSTAT, TIMER OR TOTALIZER
TB TERMINAL BLOCK
TCP TEMPERATURE CONTROL PANEL
TD TIME DELAY RELAY
TEMP TEMPERATURE
TQ TORQUE
TTB TELEPHONE TERMINAL BOX
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSOR
UG UNDERGROUND
UPS UNINTERRUPTIBLE POWER SUPPLY
UV UNDER VOLTAGE OR ULTRAVIOLET
V VOLTS
VA VOLT AMPERE
VAR VOLTAMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VM VOLTMETER
W WHITE OR WATTS
WE WEIGHT ELEMENT
WIT WEIGHT INDICATING TRANSMITTER
WP WEATHERPROOF
WPI WEATHERPROOF IN-USE RECEPTACLE
COVER
XFMR TRANSFORMER
THE TERMS LISTED BELOW ARE
DEFINED AS FOLLOWED:
1. FURNISH: OBTAIN, COORDINATE,
DELIVER TO THE JOB SITE AND
GUARANTEE.
2. INSTALL: FURNISHED BY OTHERS,
RECEIVE ON SITE, UNLOAD, STORE,
SET IN PLACE, CONNECT, PLACE IN
OPERATION AND GUARANTEE
WORKMANSHIP OF INSTALLATION.
3. PROVIDE: FURNISH AND INSTALL.
4. CONNECT: BRING SERVICE TO THE
EQUIPMENT AND MAKE FINAL
ATTACHMENTS, INCLUDING
NECESSARY DISCONNECT
SWITCHES, CONTROL SWITCHES,
OUTLETS, ETC.
5. CONDUIT: IN ADDITION TO CONDUIT
INCLUDES FITTINGS, HANGERS,
PULLBOXES, SUPPORTS, ETC. AS
REQUIRED FOR A COMPLETE AND
PROPER INSTALLATION.
6. CONCEALED: HIDDEN FROM SIGHT
IN WALLS, CEILINGS OR FLOORS..
7. EXPOSED: SURFACE MOUNTED,
NOT HIDDEN FROM SITE.
8. BUILDING STRUCTURE: COLUMNS
BEAMS, JOIST BRIDGING SHALL NOT
BE USED FOR SUPPORTING
ELECTRICAL EQUIPMENT.
9. RELOCATE: EXISTING EQUIPMENT
TO BE RELOCATED TO NEW
LOCATION AND EXISTING CONDUIT
AND BRANCH CIRCUITRY TO BE
EXTENDED TO NEW LOCATION AND
RECONNECTED.
10. CIRCUITRY: CONDUIT,
CONDUCTORS AND CONNECTIONS
FOR A COMPLETE OPERATIONAL
SYSTEM.
DEFINITIONSELECTRICAL ABBREVIATIONS
NOTES
GENERAL WIRING METHODS:
1. USE NO. 10 AWG CONDUCTOR FOR
20 AMPERE, 120-VOLT BRANCH
CIRCUIT HOME RUNS LONGER THAN
75 FEET; AND FOR 20 AMPERE,
240-VOLT BRANCH CIRCUIT HOME
RUNS LONGER THAN 150 FEET.
GROUND
MOTOR- NUMBER DENOTES HORSEPOWER
FIRE ALARM HEAT DETECTOR
FACP - FIRE ALARM CONTROL PANEL
H
FIRE ALARM STROBE
FIRE SMOKE DAMPER
FIRE ALARM FLOW SWITCH
FAAP - FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM TAMPER SWITCH
T
F
SMOKE DAMPER
F
S
S
D
S
FIRE ALARM SMOKE DETECTOR:
D = DUCT, I = IONIZATION, PH = PHOTOELECTRIC
3/4"C., 2#12, #12G
CONDUIT TURNING UP
CONDUIT CONCEALED
CONDUIT EXPOSED
CONDUIT CAPPED
BRANCH CIRCUIT HOME RUN TO PANELBOARD, PANEL
NAME SHOWN ABOVE CIRCUIT NUMBER(S) AND TAGGED TO
INDICATE CONDUIT AND CONDUCTOR SIZES. CIRCUITING
SIZES NOT SHOWN SHALL BE MINIMUM 3/4"C. WITH #12
AWG. CONDUCTORS AND SIZED PER NEC REQUIREMENTS.
UNDERGROUND CONCRETE ENCASED ELECTRICAL DUCT BANK
OVERHEAD ELECTRICAL LINE
UNDERGROUND CONCRETE ENCASED ELECTRICAL BANK
ROUTED BENEATH SLAB-ON-GRADE
DIRECT BURIED CONDUIT
GROUND CONDUCTOR
LP-1
1,3
INDICATES THAT ALL OR PART OF CIRCUIT MAY BE ROUTED IN
DUCT BANK OR UNDERGROUND. CONDUIT SIZE SHOWN ON
ONE-LINE IS ABOVE GROUND AND/OR INSIDE OF STRUCTURE.
SEE DUCT BANK SCHEDULE AND SECTIONS FOR CONDUIT SIZE
OF UNDERGROUND PORTION OF CIRCUIT.
WALL MOUNTED BATTERY PACK EMERGENCY LIGHT
SPECIAL PURPOSE RECEPTACLE
MOTOR AND MOTOR SWITCH
DOUBLE DUPLEX RECEPTACLE
DUPLEX CEILING RECEPTACLE
POWER OR LIGHTING PANELBOARD
POWER OR DISTRIBUTION CABINET
MOTOR STARTER
DISCONNECT
TRANSFORMER
COMBINATION STARTER/DISCONNECT
DUPLEX WALL RECEPTACLE
SINGLE WALL RECEPTACLE
RELAY
R
METER
PHOTOCELL
4' INDUSTRIAL LIGHT FIXTURE
SHADED FIXTURE = EMERGENCY LIGHT
RECESSED LIGHT FIXTURE
SURFACE MOUNTED LIGHT FIXTURE
WALL MOUNTED LIGHT FIXTURE
1X4 LIGHT FIXTURE
2X2 LIGHT FIXTURE
COMBINATION VOICE/DATA OUTLET
TELEPHONE OUTLET
BUZZER
T
DATA OUTLET
THERMOSTAT
FLOOR BOX, POKE-THROUGH OR GROUND ROD AS NOTED
WALL MOUNTED JUNCTION BOX
a
S
M
T
2X4 LIGHT FIXTURE
UPPER CASE INDICATES FIXTURE TYPE
NUMBER INDICATES CIRCUIT LOWER CASE
INDICATES SWITCH DESIGNATION
SWITCH SYMBOL:
SINGLE POLE (IF BLANK)
2 = DOUBLE POLE
3 = THREE-WAY
4 = FOUR-WAY
D = DIMMER
K = KEY OPERATED
LV = LOW VOLTAGE
MS = MANUAL MOTOR STARTER
OS = OCCUPANCY SENSOR
P = WITH PILOT LIGHT
WP = WEATHERPROOF
x = SMALL LETTER INDICATES LUMINARIES CONTROLLED
XP = EXPLOSION PROOF
MC = MOMENTARY CONTACT
EXIT LIGHT (WITH FACES & DIRECTION
ARROWS INDICATED)
POLE MOUNTED LUMINAIRE
WALL MOUNTED EXIT LIGHT (WITH FACES & DIRECTION
ARROWS INDICATED)
D a
EMERGENCY RECEPTACLE
CCTV (CLOSED CIRCUIT TV CAMERA)
FIRE ALARM HORN/STROBE
FIRE ALARM MANUAL PULL STATIONF
HANDRAIL MOUNTED LUMINAIRE
JUNCTION BOX
PUSHBUTTON STATION
POWER & LIGHTING SYMBOLS
J
A1
OS
OS
OCCUPANCY SENSOR, CEIL MOUNT
OCCUPANCY SENSOR, WALL MOUNT
P
F
F
J T
M
B D
M
E L E
C T
R I C
A L
S
Y M
B O
L S
A
N D
B B
R E
V I A
T I O
N S
B D
M
J T
M
E L E
C T
R I C
A L
S
Y M
B O
L
B B
R E
V I A
T I O
N S
E0.1
AutoCAD SHX Text S
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text FORT McCOY
AutoCAD SHX Text
2171 SOUTH 8TH AVE.
AutoCAD SHX Text
FORT MC COY, WI 54656
AutoCAD SHX Text
DIRECTORATE OF PUBLIC WORKS
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text Dwn by:
AutoCAD SHX Text Designed by:
AutoCAD SHX Text Reviewed by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Ckd by:
AutoCAD SHX Text Submitted by:
AutoCAD SHX Text Work Order No
AutoCAD SHX Text Project Number
AutoCAD SHX Text Plot date:
AutoCAD SHX Text
MARK
AutoCAD SHX Text
MOD REQUEST # - DESCRIPTION
AutoCAD SHX Text
MOD #
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DPW FORT MCCOY, WI
AutoCAD SHX Text SHEET of
AutoCAD SHX Text
DPW
AutoCAD SHX Text Rev.
AutoCAD SHX Text FORT McCOY, WISCONSIN
AutoCAD SHX Text
REPAIR AIRFIELD FIRE PUMP SYSTEM
E1.1
E L E
C T
R I C
A L
D
E M
O L I T
I O
N
A
R
M
O D
E L
P L A
P
U M
P
B
U I L D
I N
G
S E
H
B D
M
J T
M
AutoCAD SHX Text
CT CABINET
AutoCAD SHX Text
SERVICE DISCONNECT
AutoCAD SHX Text
MDP
AutoCAD SHX Text
ATS
AutoCAD SHX Text
GEN MCB
AutoCAD SHX Text
CUSTOMER METER
AutoCAD SHX Text
FAN
AutoCAD SHX Text
FIRE PUMP CONTROLLER
AutoCAD SHX Text
STARTER
AutoCAD SHX Text
CONTROL WIRING BOX
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
METER CONTROLLER/RADIO ENCLOSURE
AutoCAD SHX Text
BOILER
AutoCAD SHX Text
FACP AND TRANSMITTER
AutoCAD SHX Text
EDWARDS QUICKSART FIRE LARM (NOT IN SERVICE)
AutoCAD SHX Text
EST CABINET (NOT IN SERVICE)
AutoCAD SHX Text
EMERGENCY GENERATOR
AutoCAD SHX Text
DIESEL MOTOR
AutoCAD SHX Text
DIESEL PUMP #2
AutoCAD SHX Text
DIESEL PUMP #3
AutoCAD SHX Text
ELEC PUMP #1
AutoCAD SHX Text
PANEL B
AutoCAD SHX Text
PANEL A
AutoCAD SHX Text
WATER LVL CONTROLLER
AutoCAD SHX Text
JOCKEY PUMP CONTROLLER
AutoCAD SHX Text
CT CABINET
AutoCAD SHX Text
SERVICE DISCONNECT
AutoCAD SHX Text
MDP
AutoCAD SHX Text
ATS
AutoCAD SHX Text
GEN MCB
AutoCAD SHX Text
FAN
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
EMERGENCY GENERATOR
AutoCAD SHX Text
DIESEL MOTOR
AutoCAD SHX Text
PUMP #2
AutoCAD SHX Text
PUMP #3
AutoCAD SHX Text
ELEC PUMP #1
AutoCAD SHX Text
FIRE PUMP SERVICE DISCONNECT
AutoCAD SHX Text
CUSTOMER METER
AutoCAD SHX Text
WATER LVL CONTROLLER
AutoCAD SHX Text
JOCKEY PUMP CONTROLLER
AutoCAD SHX Text
STARTER
AutoCAD SHX Text
CONTROL WIRING BOX
AutoCAD SHX Text
METER CONTROLLER/RADIO ENCLOSURE
AutoCAD SHX Text
BOILER
AutoCAD SHX Text
FACP AND TRANSMITTER
AutoCAD SHX Text
EDWARDS QUICKSART FIRE LARM (NOT IN SERVICE)
AutoCAD SHX Text
EST CABINET (NOT IN SERVICE)
AutoCAD SHX Text
PANEL B
AutoCAD SHX Text
PANEL A
AutoCAD SHX Text Scale: 1/4" = 1'-0"
AutoCAD SHX Text
ELECTRICAL DEMOLITION FLOOR PLAN
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text FORT McCOY
AutoCAD SHX Text
2171 SOUTH 8TH AVE.
AutoCAD SHX Text
FORT MC COY, WI 54656
AutoCAD SHX Text
DIRECTORATE OF PUBLIC WORKS
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text Dwn by:
AutoCAD SHX Text Designed by:
AutoCAD SHX Text Reviewed by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Ckd by:
AutoCAD SHX Text Submitted by:
AutoCAD SHX Text Work Order No
AutoCAD SHX Text Project Number
AutoCAD SHX Text Plot date:
AutoCAD SHX Text
MARK
AutoCAD SHX Text
MOD REQUEST # - DESCRIPTION
AutoCAD SHX Text
MOD #
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DPW FORT MCCOY, WI
AutoCAD SHX Text SHEET of
AutoCAD SHX Text
DPW
AutoCAD SHX Text Rev.
AutoCAD SHX Text FORT McCOY, WISCONSIN
AutoCAD SHX Text
REPAIR AIRFIELD FIRE PUMP SYSTEM
AutoCAD SHX Text
1. DISCONNECT ELECTRICAL CONNECTIONS DISCONNECT ELECTRICAL CONNECTIONS TO DIESEL PUMP AND MOTOR TO BE REPLACED. DEMOLISH ELECTRICAL WIRING AND CONDUIT BACK TO THE FIRE PUMP CONTROLLER. 2. DISCONNECT ELECTRICAL CONNECTIONS DISCONNECT ELECTRICAL CONNECTIONS TO FIRE PUMP CONTROLLER TO BE REPLACED. DEMOLISH ELECTRICAL WIRING AND CONDUIT BACK TO THE SOURCE. 3. LOCATION OF EXISTING ELECTRICAL LOCATION OF EXISTING ELECTRICAL DISTRIBUTION PANEL SERVING THE ELECTRIC FIRE PUMP CONTROLLER. EXISTING CIRCUIT BREAKER SERVING FIRE PUMP SHALL BE ABANDONED IN PLACE. RE-LABEL AS 'SPARE'. 4. PROVIDE FUSED SWITCH IN NEMA 3R PROVIDE FUSED SWITCH IN NEMA 3R ENCLOSURE ON EXTERIOR OF BUILDING NEXT TO EXISTING CT CABINET. 5. MAKE ELECTRICAL CONNECTIONS TO MAKE ELECTRICAL CONNECTIONS TO NEW FIRE PUMP CONTROLLER INSTALLED IN SAME LOCATION AS EXISTING. 6. MAKE ELECTRICAL CONNECTIONS TO MAKE ELECTRICAL CONNECTIONS TO NEW PUMPS AND MOTORS AND PROVIDE CONTROL AND ALARM WIRING AS REQUIRED. 7. NOT USED NOT USED 8. NOT USED NOT USED 9. MAINTAIN EXISTING FIRE PUMP CONTROL MAINTAIN EXISTING FIRE PUMP CONTROL SYSTEMS FOR RECONNECTION TO NEW FIRE PUMPS AND MODIFY AS REQUIRED. SEQUENCE OF OPERATION OF NEW PUMPS SHALL MATCH EXISTING: (FIELD VERIFY): JOCKEY PUMP: ON-125 PSI, OFF-135 PSI. ELECTRIC PUMP #1: ON-118 PSI, NO DELAY. DIESEL PUMP#2: ON AT 118 PSI WITH A 10 SECOND DELAY. DIESEL PUMP #3: ON AT 118 PSI WITH A 20 SECOND DELAY. ALL PUMPS-MANUALLY STOPPED. CONNECT DIESEL FIRE PUMP CONTROLLERS TO MOTORIZED VENTILLATION LOUVER. 10. MAINTAIN EXISTING FIRE PUMP ALARM MAINTAIN EXISTING FIRE PUMP ALARM SYSTEMS FOR RECONNECTION TO NEW FIRE PUMPS AND MODIFY AS REQUIRED. ALARMS SHALL BE TRANSMITTED TO CALL CENTER FOR THE FOLLOWING CONDITIONS: ENGINE RUNNING, ENGINE TROUBLE, MAIN SWITCH MIS-SET, LOW FUEL. 11. PROVIDE STROBE LIGHT ON OUTSIDE OF PROVIDE STROBE LIGHT ON OUTSIDE OF BUILDING AND CONNECT TO ILLUMINATE WHEN EITHER DIESEL FIRE PUMP IS RUNNING. STROBE LIGHT SHALL BE AMBER, EDWARDS #105XBRMA120A OR APPROVED EQUAL WITH WALL MOUNTING BRACKET. 12. PROGRAM AND COMMISSION FIRE ALARM PROGRAM AND COMMISSION FIRE ALARM AND FIRE PUMP CONTROLS SYSTEMS IN THE PRESENCE OF THE FIRE DEPARTMENT AHJ. 13. PANEL 'A' SERVES WELLHOUSE PUMP. PANEL 'A' SERVES WELLHOUSE PUMP. 30A/P BREAKER TO BE REUSED. NOTED FOR REFERENCE.
AutoCAD SHX Text
FLOOR PLAN KEY NOTES:
AutoCAD SHX Text Scale: 1/4" = 1'-0"
AutoCAD SHX Text
ELECTRICAL REMODEL FLOOR PLAN
AutoCAD SHX Text
GENERAL NOTES: A. HATCHED OR SHADED AREA DESIGNATES HATCHED OR SHADED AREA DESIGNATES DEMOLITION. B. CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN EXISTING BRANCH CIRCUITS, AND CONTINUITY FOR EXISTING EQUIPMENT TO REMAIN. C. COORDINATE ELECTRICAL DEMOLITION AND SERVICE COORDINATE ELECTRICAL DEMOLITION AND SERVICE INTERRUPTION WITH COR AND OTHER TRADES. D. WHERE POSSIBLE, MINIMIZE DOWNTIME BY PLACING WHERE POSSIBLE, MINIMIZE DOWNTIME BY PLACING NEW EQUIPMENT AND CIRCUITRY PRIOR TO DISCONNECTING EXISTING EQUIPMENT. E. ANY ELECTRICAL DEVICES, EQUIPMENT OR ANY ELECTRICAL DEVICES, EQUIPMENT OR MATERIALS REMOVED DURING DEMOLITION THAT WILL NOT BE REUSED, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND REMOVED FROM THE SITE. F. FIELD VERIFY SOURCE PANELS FOR EXISTING FIELD VERIFY SOURCE PANELS FOR EXISTING CIRCUITS TO BE REMOVED. G. ALL EQUIPMENT SHOWN IS EXISTING TO REMAIN ALL EQUIPMENT SHOWN IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED. H. ALL ELECTRICAL WORK SHALL BE ALL ELECTRICAL WORK SHALL BE PERFORMED IN COMPLIANCE WITH THE MOST RECENT EDITION OF NFPA 70 NATIONAL ELECTRICAL CODE, AND FEDERAL, STATE, COUNTY AND MUNICIPAL LAWS, REGULATIONS , STATUTES AND ORDINANCES. NOTIFY THE COR OF ANY DISCREPANCIES PRIOR TO ORDERING EQUIPMENT AND PRIOR TO THE START OF CONSTRUCTION. ALL ELECTRICAL WORK MUST BE PERFORMED UNDER THE SUPERVISION OF A CURRENTLY LICENSED MASTER ELECTRICIAN. I. PROVIDE WORK, EQUIPMENT, LABOR AND PROVIDE WORK, EQUIPMENT, LABOR AND MATERIALS FOR COMPLETE, FULLY OPERATIONAL SYSTEMS IN COMPLIANCE WITH PLANS AND SPECIFICATIONS, AND IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA AND RECOMMENDATIONS. J. EQUIPMENT AND MATERIALS SHALL BE NEW, EQUIPMENT AND MATERIALS SHALL BE NEW, UL LISTED AND APPROVED FOR THE PURPOSE. K. CONTRACTOR IS RESPONSIBLE TO PROVIDE CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL REQUIRED PERMITS, LICENSES AND INSPECTION FEES AT CONTRACTOR'S EXPENSE. PROVIDE COORDINATION WITH UTILITIES AND AUTHORITY HAVING JURISDICTION. L. INTERIOR CONDUIT SHALL BE ELECTRICAL INTERIOR CONDUIT SHALL BE ELECTRICAL METALLIC TUBING (EMT). M. PROVIDE NEW CONDUCTORS IN PROVIDE NEW CONDUCTORS IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA AND RECOMMENDATIONS. NEW CONDUCTORS SHALL BE TYPE XHHW OR THWN/THHN STRANDED COPPER. N. VERIFY THAT EXISTING EQUIPMENT IS VERIFY THAT EXISTING EQUIPMENT IS PROPERLY GROUNDED AND CORRECT EXISTING CODE VIOLATIONS.
E1.2
L E
C T
R I C
A L
D
E M
O L I T
O
R
M
O D
E L
P L A
W
E L L
H
O U
S E
S E
H
B D
M
J T
M
AutoCAD SHX Text
WELL PUMP
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
DIESEL MOTOR
AutoCAD SHX Text
STARTER
AutoCAD SHX Text
WELL PUMP
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
DIESEL MOTOR
AutoCAD SHX Text
STARTER
AutoCAD SHX Text Scale: 1/4" = 1'-0"
AutoCAD SHX Text
ELECTRICAL DEMOLITION FLOOR PLAN - WELL HOUSE
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text FORT McCOY
AutoCAD SHX Text
2171 SOUTH 8TH AVE.
AutoCAD SHX Text
FORT MC COY, WI 54656
AutoCAD SHX Text
DIRECTORATE OF PUBLIC WORKS
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text Dwn by:
AutoCAD SHX Text Designed by:
AutoCAD SHX Text Reviewed by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Ckd by:
AutoCAD SHX Text Submitted by:
AutoCAD SHX Text Work Order No
AutoCAD SHX Text Project Number
AutoCAD SHX Text Plot date:
AutoCAD SHX Text
MARK
AutoCAD SHX Text
MOD REQUEST # - DESCRIPTION
AutoCAD SHX Text
MOD #
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DPW FORT MCCOY, WI
AutoCAD SHX Text SHEET of
AutoCAD SHX Text
DPW
AutoCAD SHX Text Rev.
AutoCAD SHX Text FORT McCOY, WISCONSIN
AutoCAD SHX Text
REPAIR AIRFIELD FIRE PUMP SYSTEM
AutoCAD SHX Text Scale: 1/4" = 1'-0"
AutoCAD SHX Text
ELECTRICAL REMODEL FLOOR PLAN - WELL HOUSE
AutoCAD SHX Text
AutoCAD SHX Text
1. DISCONNECT ELECTRICAL CONNECTIONS DISCONNECT ELECTRICAL CONNECTIONS TO DIESEL PUMP AND MOTOR TO BE REPLACED. DEMOLISH ELECTRICAL WIRING AND CONDUIT BACK TO THE FIRE PUMP CONTROLLER. 2. DISCONNECT ELECTRICAL CONNECTIONS DISCONNECT ELECTRICAL CONNECTIONS TO FIRE PUMP CONTROLLER TO BE REPLACED. DEMOLISH ELECTRICAL WIRING AND CONDUIT BACK TO THE SOURCE. 3. MAKE ELECTRICAL CONNECTIONS TO MAKE ELECTRICAL CONNECTIONS TO NEW FIRE PUMP CONTROLLER INSTALLED IN SAME LOCATION AS EXISTING. 4. MAKE ELECTRICAL CONNECTIONS TO MAKE ELECTRICAL CONNECTIONS TO NEW PUMPS AND MOTORS AND PROVIDE CONTROL AND ALARM WIRING AS REQUIRED. 5. DISCONNECT ELECTRICAL CONNECTION DISCONNECT ELECTRICAL CONNECTION TO STARTER/DISCONNECT TO BE REPLACED. DEMOLISH ELECTRICAL WIRING BACK TO TRANSFORER IN THIS ROOM. 6. MAKE ELECTRICAL CONNECTION TO NEW MAKE ELECTRICAL CONNECTION TO NEW STARTER/DISCONNECT. PROVIDE CONTROL WIRING AS NECESSARY.
AutoCAD SHX Text
FLOOR PLAN KEY NOTES:
GENERAL NOTES: A. HATCHED OR SHADED AREA DESIGNATES HATCHED OR SHADED AREA DESIGNATES DEMOLITION. B. CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN EXISTING BRANCH CIRCUITS, AND CONTINUITY FOR EXISTING EQUIPMENT TO REMAIN. C. COORDINATE ELECTRICAL DEMOLITION AND SERVICE COORDINATE ELECTRICAL DEMOLITION AND SERVICE INTERRUPTION WITH OWNER AND OTHER TRADES. D. WHERE POSSIBLE, MINIMIZE DOWNTIME BY PLACING WHERE POSSIBLE, MINIMIZE DOWNTIME BY PLACING NEW EQUIPMENT AND CIRCUITRY PRIOR TO DISCONNECTING EXISTING EQUIPMENT. E. ANY ELECTRICAL DEVICES, EQUIPMENT OR ANY ELECTRICAL DEVICES, EQUIPMENT OR MATERIALS REMOVED DURING DEMOLITION THAT WILL NOT BE REUSED, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND REMOVED FROM THE SITE. F. FIELD VERIFY SOURCE PANELS FOR EXISTING FIELD VERIFY SOURCE PANELS FOR EXISTING CIRCUITS TO BE REMOVED. G. ALL EQUIPMENT SHOWN IS EXISTING TO REMAIN ALL EQUIPMENT SHOWN IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED. H. ALL ELECTRICAL WORK SHALL BE ALL ELECTRICAL WORK SHALL BE PERFORMED IN COMPLIANCE WITH THE MOST RECENT EDITION OF NFPA 70 NATIONAL ELECTRICAL CODE, AND FEDERAL, STATE, COUNTY AND MUNICIPAL LAWS, REGULATIONS , STATUTES AND ORDINANCES. NOTIFY THE COR OF ANY DISCREPANCIES PRIOR TO ORDERING EQUIPMENT AND PRIOR TO THE START OF CONSTRUCTION. ALL ELECTRICAL WORK MUST BE PERFORMED UNDER THE SUPERVISION OF A CURRENTLY LICENSED MASTER ELECTRICIAN. I. PROVIDE WORK, EQUIPMENT, LABOR AND PROVIDE WORK, EQUIPMENT, LABOR AND MATERIALS FOR COMPLETE, FULLY OPERATIONAL SYSTEMS IN COMPLIANCE WITH PLANS AND SPECIFICATIONS, AND IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA AND RECOMMENDATIONS. J. EQUIPMENT AND MATERIALS SHALL BE NEW, EQUIPMENT AND MATERIALS SHALL BE NEW, UL LISTED AND APPROVED FOR THE PURPOSE. K. CONTRACTOR IS RESPONSIBLE TO PROVIDE CONTRACTOR IS RESPONSIBLE TO PROVIDE ALL REQUIRED PERMITS, LICENSES AND INSPECTION FEES AT CONTRACTOR'S EXPENSE. PROVIDE COORDINATION WITH UTILITIES AND AUTHORITY HAVING JURISDICTION. L. INTERIOR CONDUIT SHALL BE ELECTRICAL INTERIOR CONDUIT SHALL BE ELECTRICAL METALLIC TUBING (EMT). M. PROVIDE NEW CONDUCTORS IN PROVIDE NEW CONDUCTORS IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED DATA AND RECOMMENDATIONS. NEW CONDUCTORS SHALL BE TYPE XHHW OR THWN/THHN STRANDED COPPER. N. VERIFY THAT EXISTING EQUIPMENT IS VERIFY THAT EXISTING EQUIPMENT IS PROPERLY GROUNDED AND CORRECT EXISTING CODE VIOLATIONS.
MAIN
SERVICE
DISCONNECT
N
G
UFER GROUND
KEYNOTES:
1. SIZE MAIN GROUNDING CONDUCTOR PER NEC OR 12.5%
OF TOTAL CROSS SECTIONAL AREA OF MAIN SERVICE
CONDUCTORS PER PHASE.
2. BONDING CONDUCTOR TO EXPOSED PIPE, BUILDING
STEEL AND CONCRETE STEEL REINFORCING PER NEC
FOR CONNECTION OF ALL OTHER AREAS REQUIRED TO
BE BONDED TO GROUNDING.
3. 3/4"x10' COPPER CLAD STEEL GROUND ROD. GROUND
RODS SHALL BE SPACED A MINIMUM OF 10 FEET APART.
EXOTHERMIC WELD ALL CONNECTIONS OF CONDUCTORS
TO GROUND RODS.
4. CONDUCTOR CONNECTING THE GROUND RODS SHALL BE
A MINIMUM OF #2/0 AWG BARE CU.
(3 TYP)
E2.1
L E
C T
R I C
A L
R
E M
O D
E L
P
L A
N
S E
H
B D
M
J T
M
AutoCAD SHX Text
MDP
AutoCAD SHX Text
EXISTING FIRE PUMP CONTROLLER
AutoCAD SHX Text
PUMP #1
AutoCAD SHX Text
PUMP #2 DIESEL
AutoCAD SHX Text
PUMP #3 DIESEL
AutoCAD SHX Text
PUMP ROOM
AutoCAD SHX Text
PANEL A
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
PANEL B
AutoCAD SHX Text
EXISTING FIRE PUMP CONTROLLER
AutoCAD SHX Text
EXISTING FIRE PUMP CONTROLLER
AutoCAD SHX Text
EXISTING SERVICE DROP
AutoCAD SHX Text EXISTING 300 KVA POLE-MOUNTED TRANSFORMER BANK 480/277V, 3 PHASE, 4-WIRE SECONDARY
AutoCAD SHX Text
400A, 3P, FUSED SERVICE DISCNNECT NEMA 3R (EXTERIOR)
AutoCAD SHX Text
600A, NEMA 3R CT CABINET (EXTERIOR)
AutoCAD SHX Text
WELL PUMP HOUSE
AutoCAD SHX Text
WELL PUMP DIESEL
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
EXISTING FIRE PUMP CONTROLLER
AutoCAD SHX Text
MAIN DISC.
AutoCAD SHX Text
STARTER/ DISC.
AutoCAD SHX Text
400A, 3P, FUSED SERVICE DISCNNECT NEMA 3R (EXTERIOR)
AutoCAD SHX Text
600A, NEMA 3R CT CABINET (EXTERIOR)
AutoCAD SHX Text
MDP
AutoCAD SHX Text
PUMP ROOM
AutoCAD SHX Text
NEW ENCLOSED MCB 1000A NEMA 3R (EXTERIOR)
AutoCAD SHX Text
2-1/2'' RMC-4#4/0
AutoCAD SHX Text
2-1/2'' RMC-3#4/0+1#2GND
AutoCAD SHX Text
EXISTING SERVICE DROP
AutoCAD SHX Text EXISTING 300 KVA POLE-MOUNTED TRANSFORMER BANK 480/277V, 3 PHASE, 4-WIRE SECONDARY
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER
AutoCAD SHX Text
PUMP #1
AutoCAD SHX Text
PUMP #2 DIESEL
AutoCAD SHX Text
PUMP #3 DIESEL
AutoCAD SHX Text
PANEL A
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
PANEL B
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER
AutoCAD SHX Text
3/4"-3#12, 1 #12 GND
AutoCAD SHX Text
3/4"-3#12, 1 #12 GND
AutoCAD SHX Text 1''C
AutoCAD SHX Text
2-1/2'' RMC-3#4/0+1#2GND
AutoCAD SHX Text
1-1/2'', 20#10, 1#10 GND
AutoCAD SHX Text
1-1/2'', 20#10, 1#10 GND
AutoCAD SHX Text
WELL PUMP HOUSE
AutoCAD SHX Text
WELL PUMP DIESEL
AutoCAD SHX Text
XFMR
AutoCAD SHX Text
NEW FIRE PUMP CONTROLLER
AutoCAD SHX Text
MAIN DISC.
AutoCAD SHX Text
NEW STARTER/ DISC.
AutoCAD SHX Text
1-1/2'', 20#10, 1#10 GND
AutoCAD SHX Text
3/4'', 3#10, 1#10 GND
AutoCAD SHX Text
3/4'', 3#10 1#10 GND
AutoCAD SHX Text Scale: NTS
AutoCAD SHX Text
ELECTRICAL RISER DIAGRAM - REMOVAL
AutoCAD SHX Text
AutoCAD SHX Text H
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text R
AutoCAD SHX Text H
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text FORT McCOY
AutoCAD SHX Text
2171 SOUTH 8TH AVE.
AutoCAD SHX Text
FORT MC COY, WI 54656
AutoCAD SHX Text
DIRECTORATE OF PUBLIC WORKS
AutoCAD SHX Text
SHEET NUMBER:
AutoCAD SHX Text Dwn by:
AutoCAD SHX Text Designed by:
AutoCAD SHX Text Reviewed by:
AutoCAD SHX Text Date:
AutoCAD SHX Text Ckd by:
AutoCAD SHX Text Submitted by:
AutoCAD SHX Text Work Order No
AutoCAD SHX Text Project Number
AutoCAD SHX Text Plot date:
AutoCAD SHX Text
MARK
AutoCAD SHX Text
MOD REQUEST # - DESCRIPTION
AutoCAD SHX Text
MOD #
AutoCAD SHX Text
DATE
AutoCAD SHX Text
DPW FORT MCCOY, WI
AutoCAD SHX Text SHEET of
AutoCAD SHX Text
DPW
AutoCAD SHX Text Rev.
AutoCAD SHX Text FORT McCOY, WISCONSIN
AutoCAD SHX Text
REPAIR AIRFIELD FIRE PUMP SYSTEM
AutoCAD SHX Text Scale: NTS
AutoCAD SHX Text
ELECTRICAL RISER DIAGRAM - REWORK
AutoCAD SHX Text
AutoCAD SHX Text
1. MAKE PROVISIONS FOR MAKE PROVISIONS FOR CUSTOMER METERING ON LINE SIDE OF FIRE PUMP FEEDER. 2. 1000 AMP, 480/277V, 3 POLE, 1000 AMP, 480/277V, 3 POLE, 4 WIRE SWITCH FUSED AT 1000 AMPS. SWITCH SHALL BE SERVICE ENTRANCE LISTED. 3. LABEL DISCONNECT AS 'MAIN LABEL DISCONNECT AS 'MAIN SERVICE DISCONNECT 1 OF 2. 4. LABEL DISCONNECT AS 'MAIN LABEL DISCONNECT AS 'MAIN SERVICE DISCONNECT 1 OF 2. 5. MAKE CONNECTION ON LOAD MAKE CONNECTION ON LOAD SIDE OF CT CABINET FOR NEW FIRE PUMP. FIELD VERIFY EXISTING CONDITIONS AND PROVIDE LUGS, CONDUCTORS, ENCLOSURES, AND ACCESORIES REQUIRED FOR CONNECTIONS. 6. GROUND NEW SERVICE GROUND NEW SERVICE DISCONNECT PER NEC. SEE GROUNDING DETAIL. 7. PROVIDE METER BASE PER PROVIDE METER BASE PER UTILITY REQUIREMENTS.
AutoCAD SHX Text
RISER DIAGRAM KEY NOTES:
AutoCAD SHX Text GENERAL NOTES: 1. ALL EQUIPMENT SHOWN IS ALL EQUIPMENT SHOWN IS EXISTING UNLESS NOTED OTHERWISE. 2. CONNECT NEW FIRE PUMPS TO CONNECT NEW FIRE PUMPS TO NEW FIRE PUMP CONTROLLERS PER MANUFACTURER'S WIRING DIAGRAMS. VERIFY QUANTITIES AND SIZES OF REQUIRED CONDUIT AND CONDUCTORS WITH MANUFACTURER.
AutoCAD SHX Text Scale: NTS
AutoCAD SHX Text
MAIN SERVICE DISCONNECT GROUNDING DETAIL
File details come from the government source that posted it. Updated .