Technical Exhibit II Fire Hydrant List at the Adelphi Laboratory Center
The equipment listed in Technical Exhibit two must be returned to full functionality during option year I.
Figure 4 Replace fire hydrant, mechanical joint gate valve includes valve box and cover with the option of Value Engineering Change Proposals (VECPs)
| Hydrant Type |
| Location |
| Building Side |
| Hydrant Number |
| Static Pressure |
| Residual Pressure |
| GPM |
| Remarks |
Hydrant failed 5” opening leaks at threaded boss
Figure 5 Repair or replace new valve box with proper elevation and alignment
| Hydrant Type |
| Location |
| Building Side |
| Hydrant Number |
| Static Pressure |
| Residual Pressure |
| GPM |
| Remarks |
| Mueller |
| 100 Area |
| 103NW |
| 3 |
| 92 |
| 64 |
| 825 |
| Street valve is missing the operating nut |
| Mueller |
| 200 Area |
| 203SE |
| 17 |
| 86 |
| 56 |
| 854 |
| Street valve full of debris requires cleaning hydrant operating nut |
| Mueller |
| 200 Area |
| 203SE |
| 18 |
| 90 |
| 57 |
| 896 |
| Street valve full of debris |
| Mueller |
| 400 Area |
| 403 |
| 23 |
| 115 |
| 82 |
| 896 |
| Street valve has shifted inaccessible |
| Mueller |
| 500 Area |
| 505 |
| 24 |
| 102 |
| 69 |
| 896 |
| Street valve full of debris requires cleaning |
| Mueller |
| Floral Drive |
| Ent. To 601 |
| 33 |
| 103 |
| 73 |
| 854 |
| Hydrant too low |