PWS Technical Exhibit I

View the file

Other files for this federal contract opportunity

Other files attached to Repair/Replace Fire Hydrants and Shut-Off Valves, newest first.
File Type Posted
A02_-_Combination_Synopsis-Solicitation_for_Commercial_Purchases.docx DOCX document
A07_-_Evaluation_Criteria_(LPTA).doc DOC document
A01_-_PWS_Technical_Exhibit_II.docx DOCX document
A02_-_Provisions_and_Clauses_Full-Text_Attachment.doc DOC document
A01_-_PWS.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Technical Exhibit I Fire Hydrant List at the Adelphi Laboratory Center

The equipment listed in Technical Exhibit one must be returned to full functionality during the base year of this contract.

Figure 1 Replace fire hydrant, mechanical joint gate valve includes valve box and cover with the option of Value Engineering Change Proposals (VECPs)

Hydrant Type
Location
Building Side
Hydrant Number
Static Pressure
Residual Pressure
GPM
Remarks
Mueller
100 Area
101 SW
7
82
54
825
Lower hydrant mounting flange is leaking on the left side
Mueller
200 Area
203E
19

Hydrant failed does not close

Mueller
400 Area
Kuester-Floral
21
100
76
764
All gaskets leak weeps while open
Mueller
500 Area
601
31

Safety clevis is broken, had to close street valve UNUSEABLE.

Figure 2 Repair or replace new valve box with proper elevation and alignment

Hydrant Type
Location
Building Side
Hydrant Number
Static Pressure
Residual Pressure
GPM
Remarks
Kennedy
500 Area
500W
28
103
70
896
Street valve very stiff almost unturnable

Figure 3 Repair six-inch domestic water valve located in building 106

Domestic Water Valve Description
Location
Building Side
6” Building Isolation Valve
100 Area
Building 106