A01_-_PWS_Technical_Exhibit_I.docx
DOCX document 20 KB Posted
- Attached to
- Repair/Replace Fire Hydrants and Shut-Off Valves Federal contract opportunity
- Solicitation number
- W911QX-17-T-0122
About this file
PWS Technical Exhibit I
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| A02_-_Combination_Synopsis-Solicitation_for_Commercial_Purchases.docx | DOCX document | |
| A07_-_Evaluation_Criteria_(LPTA).doc | DOC document | |
| A01_-_PWS_Technical_Exhibit_II.docx | DOCX document | |
| A02_-_Provisions_and_Clauses_Full-Text_Attachment.doc | DOC document | |
| A01_-_PWS.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Exhibit I Fire Hydrant List at the Adelphi Laboratory Center
The equipment listed in Technical Exhibit one must be returned to full functionality during the base year of this contract.
Figure 1 Replace fire hydrant, mechanical joint gate valve includes valve box and cover with the option of Value Engineering Change Proposals (VECPs)
| Hydrant Type |
| Location |
| Building Side |
| Hydrant Number |
| Static Pressure |
| Residual Pressure |
| GPM |
| Remarks |
| Mueller |
| 100 Area |
| 101 SW |
| 7 |
| 82 |
| 54 |
| 825 |
| Lower hydrant mounting flange is leaking on the left side |
| Mueller |
| 200 Area |
| 203E |
| 19 |
Hydrant failed does not close
| Mueller |
| 400 Area |
| Kuester-Floral |
| 21 |
| 100 |
| 76 |
| 764 |
| All gaskets leak weeps while open |
| Mueller |
| 500 Area |
| 601 |
| 31 |
Safety clevis is broken, had to close street valve UNUSEABLE.
Figure 2 Repair or replace new valve box with proper elevation and alignment
| Hydrant Type |
| Location |
| Building Side |
| Hydrant Number |
| Static Pressure |
| Residual Pressure |
| GPM |
| Remarks |
| Kennedy |
| 500 Area |
| 500W |
| 28 |
| 103 |
| 70 |
| 896 |
| Street valve very stiff almost unturnable |
Figure 3 Repair six-inch domestic water valve located in building 106
| Domestic Water Valve Description |
| Location |
| Building Side |
| 6” Building Isolation Valve |
| 100 Area |
| Building 106 |
File details come from the government source that posted it. Updated .