NOT TO SCALE
VENT THRU ROOF DETAIL
ROOF PANEL
RIB OR SEAM
STANDING SEAM METAL
ROOF SYSTEM
VENT PIPE
REF. MECHANICAL
ROOF PANEL
RIB OR SEAM
PRE-MANUFACTURED
FLEXIBLE PIPE
FLASHING,
WEATHERPROOF
1" MIN.
DIAPHRAGM TYPE
EXPANSION TYPE
SEE SCHEDULE
TO SYSTEM
EXPANSION TANK PIPING
DIAGRAM
NOT TO SCALE
6"
HOUSEKEEPING
PAD
AIR VENT
SYSTEM
CONNECTION
CHARGING
VALVE CLOSURE
TEMPERATURE ADJUSTMENT
WITH RETENTION SCREW
ACCESS PANEL
ISOLATION VALVE
(TYP ALL)
NOTES:
1. B.O.D. WATTS LFMMV
2. REFER TO SPECIFICATIONS
3. REFER TO FLOOR PLANS FOR APPROXIMATE
LOCATIONS
ASSE 1070 MIXING VALVE DETAIL
NOT TO SCALE
NOT TO SCALE
PRECAST
NON-SHRINK
GROUT
"P" TRAP
SEE PLANS
FOR SIZES
FINISHED
FLOOR
FLOOR DRAIN DETAIL
FLOOR DRAIN
w/SEDIMENT BUCKET
WATERLESS TRAP PRIMER
METAL
INSULATION
SHIELD
U-BOLT
(TYPICAL)
INSULATED PIPES
PIPING TRAPEZE
NOT TO SCALE
PIPE SUPPORT DETAIL
BALANCING
VALVE (TYP.)
AQ
CHECK
VALVE
COMBINATION
VALVE ALLOWED
TIMER AND
AQUASTAT
DIAL
THERMOMETER
PUMP
DHWR FROM
OCCUPIED SPACE
BALL
VALVE
(TYP.)
DHWR TO
WH-1 DCW
SUPPLY
PIPING
NOT TO SCALE
RETURN PUMP DETAIL
NOT TO SCALE
DHWP-1 REFER TO
DETAIL ON SHEET P-502
FOR CONNECTIONS
DOMESTIC
WATER
HEATER
DOMESTIC WATER HEATER
PIPING SCHEMATIC
VACUUM RELIEF
VALVE
STRAINER
w/BLOW-OFF
AND HOSE
CONNECTION
KEYED NOTES:
TEMP. AND PRESSURE
RELIEF VALVE W/FULL
SIZE DISCHARGE ROUTE
TO FLOOR DRAIN
COLD WATER SUPPLY
HOT WATER RETURN
120^F HOT WATER
DIAPHRAGM EXPANSION
TANK ET-1
FULL PORTED BALL
VALVE w/HOSE CONN.
V
FIRESTOPPING SEE
SPECIFICATIONS
FOR FIRE RATING
SEE SPECIFICATIONS
FOR REQUIREMENT
ESCUTCHEON; (ON
FINISHED, VISIBLE
SURFACES ONLY)
BACKUP
MATERIAL;
TYPICAL
INSULATED OR
UNINSULATED PIPE
PIPE
SLEEVE
3/8"
MINERAL WOOL FULL
THICKNESS OF WALL
ESCUTCHEON (ON
FINISHED, VISIBLE
SURFACES ONLY)
INSULATED OR
UNINSULATED PIPE
NOT TO SCALE
PIPE THRU FLOOR PIPE THRU STUD WALL
NOT TO SCALE
SLEEVE WITH 26 GA
SHEET METAL
NOT TO SCALE
NUT
STEEL WASHER FLANGES
PIPE
FLANGE BOLT
STEEL WASHER
„" THICK
INSULATING
GASKET SET
SIMILAR
INSULATING BOLT SLEEVE
ˆ" MIN. WALL THICKNESS
ISOLATION FLANGE
NOTE:
CONTRACTOR SHALL COMPLY WITH THE ISOLATION
FLANGE MANUFACTURER'S RECOMMENDATIONS FOR
BOLT TORQUES AND BOLTING PATTERN. CONTRACTOR
SHALL ALSO RECHECK BOLT TORQUES 72 HOURS AFTER
SYSTEM STARTUP.
119 12
5 6
SITE
DOMESTIC
WATER
SLAB
DCW TO
FIXTURES
TO DHW
RPBP
NOTES:
1. ALL PIPING DISCHARGING TO DRAIN
SHALL HAVE AIR GAP. REFER TO
DETAIL.
2. REFER TO CONTROLS DRAWINGS
FOR SENSORS AND CONNECTIONS
TO DDC SYSTEM.
DOMESTIC COLD WATER SYSTEM
SCHEMATIC
NOT TO SCALE
M
PRIMARY METER
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 8:32:23 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
P-502
PL
UM
BI
NG
D
ET
AI
LS
K.
W
IL
LI
AM
S
P.
E.
PROJECT NAME
WATER HAMMER ARRESTOR SCHEDULE
UNIT TAG P.D.I SYMBOL FIXTURE UNITS MAX. FLUID TEMP. F CONNECTION PIPE SIZE REMARKS
WHA-A A 1 - 11 180 1/2" ALL
WHA-B B 12 - 32 180 3/4" ALL
REMARKS:
1. REFER TO SPECIFICATIONS FOR WATER HAMMER REQUIREMENTS AND DRAWINGS FOR WATER HAMMER LOCATIONS.
2. PROVIDE ACCESS PANELS TO ALLOW FOR MAINTENANCE OF WATER HAMMER ARRESTORS.
3. REFER TO DETAIL FOR CONNECTIONS.
DOMESTIC WATER HEATER SCHEDULE
UNIT TAG TYPE RECOVERY RATE/TEMPERATURE
RISE (GPH/ DEG F)
MAX INPUT
CAPACITY (KW)
ELECTRICAL
(V/PH/HZ)
REMARKS
WH-1 ELECTRIC 4
REMARKS:
1. B.O.D. AO SMITH ENT-50
20/60 208/1/60 ALL
E.W.T.
(DEG F)
PLUMBING RECIRCULATION PUMP SCHEDULE
UNIT TAG SERVICE RPM SUPPLY / RETURN
CONNECTIONS
FLOW RATE
(GPM)
HEAD
(FT WTR)
ELECTRICAL MAX. OPERATING
WEIGHT (LBS) REMARKS
HP MOTOR
V/PH/HZ
REMARKS:
1. B.O.D. TACO 006
2. REFER TO DETAIL FOR ADDITIONAL ACCESSORIES REQUIRED.
DHWP-1 DHW RECIRCULATION 5.53.6 1/40 115/1/60 103/4" / 3/4"3250 ALL
PLUMBING FIXTURE SCHEDULE
UNIT TAG DESCRIPTION COLD
WATER
HOT
WATER VENT WASTE FLOW RATE
(GPM/GPF)
REMARKS
(SEE SPECS FOR SUPPORTS)
P-1 WATER CLOSET 1" - 2" 3" 1.1/1.28 DUAL FLUSH VALVE / WALL MOUNTED
P-5 LAVATORY 1/2" 1/2" 1 1/4" 1 1/2" 0.35
P-8 SERVICE SINK 1/2" 1/2" 1 1/2" 3" 1.5
P-9 KITCHEN SINK 1/2" 1/2" 1 1/4" 2" 0.35
NFWH NON-FREEZING WALL
HYDRANT 1/2" - - -
REMARKS:
1. COMPLY WITH ASSE 1016 OR ASME A112.18.1/CSA B125.1
2. KITCHEN SINKS SHALL BE PROVIDED A WATER SAVING FAUCET AERATOR.
FD FLOOR DRAIN - - 2" 3"
P-2 URINAL 1" 1 1/4" 2" 0.125-
TANK CAPACITY
(GAL.)
EXPANSION TANK SCHEDULE
UNIT TAG SERVICE TYPE TANK VOLUME
(GALLONS)
MAX. ACCEPTANCE
VOLUME (GALLONS) REMARKS
ET-1 1,2
NOTES:
1. PRE CHARGE TO MAINTAIN 5 PSI STATIC PRESSURE AT HIGHEST SYSTEM POINT.
2. B.O.D. AMTROL ST-12C
BLADDER 6.4 3.2
SYSTEM TEMP.
(DEG. F)
MAX
PIPE SIZE
TO TANK
200 3/4"
DOMESTIC HOT
WATER SYSTEM
INITIAL
PRESSURE
(PSIG)
MAX. FINAL
PRESSURE
SANITARY SEWER DRAINAGE PIPE SLOPE SCHEDULE
SIZE (INCHES) MINIMUM SLOPE (INCH PER FOOT)
REMARKS:
1.
2.
3.
1/42 1/2 OR LESS
1/83 TO 6
1/168 OR LARGER
P-15 DRINKING FOUNTAIN 1/2" - 1 1/2" 1 1/2" 1.1
L.W.T.
(DEG F)
WIRING
NON-SIMULTANEOUS
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 8:32:39 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
P-601
PL
UM
BI
NG
S
CH
ED
UL
ES
K.
W
IL
LI
AM
S P.
2" DCW
NFWH
P-15
1/2" DCW
P-1
P-1
P-1
P-5
P-5
P-8
P-2
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DHW
1/2" DCW
1/2" DCW
1/2" DHW
1/2" DCW
3/4" DHWR
1" DHW
2" DCW
1 1/2" DCW
2" DCW
1/2" DCW
1 1/2" DHW
1 1/2" DCW
1" DCW
1" DCW
1/2" DHW
1/2" DCW
FD
FD
WH-1
FD
3/4" DCW
P-9
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 8:32:50 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
P-901
DO
M
ES
TI
C W
AT
ER
IS
O
M
ET
RI
C
K.
W
IL
LI
AM
S
P.
E.
PROJECT NAME
NTS1 DOMESTIC WATER ISOMETRIC
1 DOMESTIC WATER PIPE ENTERING BUILDING BELOW SLAB. CENTERLINE
AT -3' 0".
2 NFWH, REFER TO SPECIFICATION FOR PIPE ROUTING AND INSULATION
REQUIREMENTS. PROVIDE ISOLATION VALVE ON BRANCH PIPING AT
CONNECTION TO MAIN.
3 DOMESTIC WATER UP FROM BELOW SLAB TO 6' A.F.F.
4 ISOLATION VALVES
5 EXPANSION TANK CONNECTION LINE.
6 WATER HAMMER ARRESTOR SIZE A. SEE SHEET P-601 FOR
REQUIREMENTS.
7 WATER HAMMER ARRESTOR SIZE B. SEE SHEET P-601 FOR
REQUIREMENTS.
8 BALANCING VALVE FOR DHWR.
P-9 LEG: 0.6 GPM
OTHER LEG: 3.0 GPM
GENERAL NOTES
1. PROVIDE LABEL FOR EACH ISOLATION VALVE INDICATING THE TYPE OF
WATER SERVICE, ROOM NAME, AND FIXTURE TYPE I.E. "DCW ROOM XXX
SHOWERS".
2. ALL WATER HAMMER ARRESTORS SHALL HAVE WALL ACCESS PANELS.
REFER TO DETAILS.
3. MAXIMUM DEVELOPED LENGTH OF PIPE FROM DHW MAIN IS 50 FT.
KEYED NOTES
8 BEHIND DCW PIPING
WH-1
1 1/2" V
WCO
2" SS
3" SS
2" V
1 1/2" SS
WCO
P-5 P-8
P-5
WCO
P-1
2" V
3" SS
4" SS
P-1
P-1
4" SS
3" SS
1 1/2" SS
3" SS
FD
FD
3" SS
1 1/2" SS
P-15
FD
3" SS
1 1/4" V
2" V
1 1/4" V
P-2
1 1/2" V
3" SS
P-9
2" SS
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 8:33:11 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
P-902
W
AS
TE
A
ND
V
EN
T
IS
O
M
ET
RI
C
K.
W
IL
LI
AM
S
P.
E.
PROJECT NAME
NTS1 RESTROOM WASTE AND VENT ISOMETRIC
1 VENT THRU ROOF.
KEYED NOTES
1. SLOPE SANITARY SEWER LINES IN ACCORDANCE TO
SCHEDULE ON P-601.
GENERAL NOTES
CHANGE IN DUCT CONSTRUCTION BY
PRESSURE CLASS.
(PRESSURES IN INCHES W.G)
BD
SD
FD-1.5
FD-3
FSD
SS
G
HWS
HWR
CD
F
RS
RL
RD
WH
WCO
PRV
TPRV
HB
2 1
SA
AV
ZZ ZZ
NN NN
CHS
CHR
GENERAL ABBREVIATIONSPIPING SYSTEMS
PIPING SYMBOLS
DAMPERS GENERAL NOTES
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER
RETURN
SANITARY SEWER
VENT
NATURAL GAS
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
CONDENSATE DRAIN
REFRIGERANT SUCTION
REFRIGERANT LIQUID
ROOF DRAIN
DUCTWORK
CONTINUATION
DROP IN PIPE
VALVE IN RISER
ELBOW, 90 DEG.
ELBOW UP, 90 DEG.
ELBOW DOWN, 90 DEG.
TEE
UNION
UNION, FLANGED
FLOOR DRAIN WITH TRAP
PIPE PITCH
DIRECTION OF FLOW
FLOOR PENETRATION
WALL HYDRANT
WALL CLEANOUT
TEE, OUTLET TURNED
DOWNWARD
TEE, OUTLET TURNED
UPWARD
PRESSURE REDUCING
VALVE
PRESSURE RELIEF VALVE
TEMP & PRESS RELIEF
THERMOMETER
BALL JOINT
ANCHOR
HOSE BIB
AFF - ABOVE FINISHED FLOOR
AHU - AIR HANDLING UNIT
BOD - BOTTOM OF DUCT ELEV.
BOP - BOTTOM OF PIPE ELEV.
CFM - CUBIC FEET PER MINUTE
CL - CENTERLINE
CLG - CEILING
COND- CONDENSATE/CONDENSER
CONN- CONNECTION/CONNECT
DB - DRY BULB TEMPERATURE
DDC - DIRECT DIGITAL CONTROL
DSS - DEDICATED SPLIT SYSTEM
DX - DIRECT EXPANSION
EA - EXHAUST AIR
EAT - ENTERING AIR TEMP.
ELEV - ELEVATION
EMCS- ENERGY MONITORING
AND CONTROL SYSTEM
ESP - EXTERNAL STATIC PRESSURE
EWT - ENTERING WATER TEMP.
FC - FAIL CLOSED
FD - FLOOR DRAIN
FLA - FULL LOAD AMPS
FO - FAIL OPEN
GA - GAUGE
HD - HUB DRAIN
IE - INVERT ELEVATION
LAT - LEAVING AIR TEMP.
LWT - LEAVING WATER TEMP.
NC - NORMALLY CLOSED
NO - NORMALLY OPEN
NPS - NOMINAL PIPE SIZE
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTSIDE AIR
OBD - OPPOSED BLADE DAMPER
OS&Y- OUTSIDE STEM AND YORK
Pa - PASCAL
PD - PRESSURE DROP
RA - RETURN AIR
RPM - REVOLUTIONS PER MINUTE
SA - SUPPLY AIR
SOG - SLAB ON GRADE
SP - STATIC PRESSURE
TOD - TOP OF DUCT ELEVATION
TOP - TOP OF PIPE ELEVATION
TOS - TOP OF SLAB/
TOP OF STEEL
TSP - TOTAL STATIC PRESSURE
VAV - VARIABLE AIR VOLUME
VP - VELOCITY PRESSURE
VTR - VENT THRU ROOF
W - WATTS
WB - WET BULB
WC - WATER COLUMN
WG - WATER GAUGE
EXPANSION LOOP
AIR VENT, AUTOMATIC
AIR VENT, MANUAL
GUIDE
EXPANSION JOINT
FLEXIBLE CONNECTOR
PRESSURE/TEMPERATURE
TEST PORT
MANUAL BALANCING DAMPER
BACKDRAFT DAMPER
SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPER
FIRE DAMPER; 1.5 HOUR RATED
FIRE DAMPER; 3 HOUR RATED
FLEXIBLE ROUND DUCT
FLEXIBLE DUCT CONNECTION
ACOUSTICALLY LINED DUCT
SOUND ATTENUATOR
BRANCH TAKEOFF
DETAIL NO.
REF: DET.NN/MZZ
DETAIL LOCATION
REFERENCE SYMBOLOGY
DETAIL LOCATION
FIRE PROTECTION
A. MECHANICAL LAYOUTS ARE SCHEMATIC. PROVIDE ANY ADDITIONAL DROPS,
RISES, OR OFFSETS REQUIRED FOR A COMPLETE INSTALLATION.
COORDINATE EXACT ROUTING OF WORK WITH ALL OTHER TRADES AND
OBSTRUCTIONS. COORDINATE EXACT LOCATIONS OF CEILING MOUNTED
WORK WITH LIGHTS, CEILING GRID, AND OTHER OBSTRUCTIONS.
B. UNLESS OTHERWISE INDICATED ROUTED, ROUTE ALL DUCTWORK AND
PIPING ABOVE CEILINGS. ROUTE ALL DUCTWORK AND PIPING AS HIGH AS
POSSIBLE IN AREAS WITHOUT CEILINGS. ROUTE ALL DUCTWORK AND PIPING
TIGHT TO STRUCTURE.
C. DUCT DIMENSIONS ARE INSIDE CLEAR DIMENSIONS. INCREASE SHEET
METAL DIMENSIONS ON LINED DUCTWORK TO MAINTAIN THE INSIDE
CLEAR DIMENSIONS INDICATED.
D. UNLESS OTHERWISE INDICATED, PROVIDE DUCT RUNOUTS TO TERMINAL
UNITS SAME SIZE AS TERMINAL UNIT INLET.
E. FLEXIBLE DUCT RUNOUTS TO TERMINAL AIR DEVICES SHALL BE SAME
SIZE AS DIFFUSER CONNECTION. LIMIT FLEX TO 5 FEET.
F. INSTALL CALIBRATED BALANCING VALVES AND VENTURIS WITH A MINIMUM
UNRESTRICTED STRAIGHT RUN OF 5 PIPE DIAMETERS UPSTREAM AND
3 PIPE DIAMETERS DOWNSTREAM.
G. SEE ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS
OF DIFFUSERS, PLENUM SLOT DIFFUSERS, REGISTERS, AND GRILLS.
H. ALL WORK INDICATED IS NEW.
I. SOME SYMBOLS INDICATED ON THIS LEGEND SHEET MAY NOT APPEAR OF
THE DRAWINGS.
K. MOUNT CO2 SENSORS AND TEMPERATURE SENSORS 48 INCHES AFF.
L. ALL PIPING LOW POINTS SHALL HAVE DRAIN VALVES WITH HOSE
CONNECTION AND CAP.
M. ALL PIPING HIGH POINTS SHALL HAVE VALVED AIR VENTS.
N. PROVIDE 1-INCH DUCT LINER ON ALL TRANSFER DUCT.
T
T
HS
H
PS
SD
GENERAL CONTROL SYMBOLOGY
THERMOSTAT
TEMPERATURE SENSOR
HUMIDITY SENSOR
HUMIDISTAT
DUCT PRESSURE SENSOR
SMOKE DETECTOR
S
A
S1 900
36x24
DIFFUSER, REGISTER AND GRILLE NOTATION
SUPPLY DIFFUSER RETURN
REGISTER OR GRILLE
BALL VALVE
GATE VALVE
PLUG VALVE
GLOBE VALVE
CHECK VALVE
BUTTERFLY VALVE
MODULATING TWO-WAY
MODULATING THREE-WAY
SUPPLY REGISTER OR
GRILLE, SIDEWALL
RETURN/EXHAUST
REGISTER OR
GRILLE, SIDEWALL
DEVICE
IDENTIFICATION
AIR
QUANTITY
(CFM)
CALIBRATED BALANCING
VALVE
AUTOMATIC FLOW CONTROL
VALVE
ARROWS INDICATE
FLOW DIRECTION
DUCT SIZE IN INCHES
(NET INSIDE DIMENSIONS)
(RECTANGULAR DUCT SHOWN)
DIA INDICATES ROUND DUCT.
DIAO. INDICATES OVAL DUCT.
FOR RECTANGULAR DUCT:
FIRST FIGURE: SIDE SHOWN
SECOND FIGURE: SIDE NOT SHOWN
CD CARBON MONOXIDE DETECTOR
W
E
ESS
N
WATER METER
ELECTRIC METER
NIGHT THERMOSTAT
EMERGENCY STOP BUTTON
NPW NON-POTABLE WATER
FD
PA
EL
PG
PT
FLOOR SINK WITH TRAPFS
ELBOW, 45 DEG.
WATER FLOW DETECTOR
WFD
DOUBLE CHECK VALVE
BACKFLOW PREVENTER
REDUCED PRESSURE
BACKFLOW PREVENTER
FIRE DEPARTMENT
CONNECTION OS&Y VALVE
T
THERMOMETER GAGE
PRESSURE GAGE WITH SHUT
OFF COCK AND SIPHON OR
PULSATION DAMPENER
CAP BLIND FLANGE
MU MAKE-UP WATERHRR HEAT RECOVERY RETURN
HRS HEAT RECOVERY SUPPLY (E) EXISTING PIPING TO REMAIN
EXISTING PIPING TO BE
REMOVED
ROOM NUMBER000
ROUND DUCTØ
EXISTING WORK TO BE REMOVED
EXISTING WORK TO REMAIN-
POINT OF CONNECTION BETWEEN
NEW AND EXISTING WORK
POINT BETWEEN WORK TO REMAIN
AND WORK TO BE REMOVED
EXHAUST
REGISTER OR GRILLE
M- ALL OR ANY PORTION OF SUBJECTS IN THE FOLLOWING
MD MECHANICAL DEMOLITION PROTECTION, TERMINATION, AND REMOVAL
MH HVAC DUCTWORK, AIR DEVICES, AND EQUIPMENT
MI INSTRUMENTATION AND CONTROLS
MP HYDRONIC PIPING - CHILLED AND HEATING WATER, STEAM
MECHANICAL SHEET NUMBERING PREFIXES
WITH LEVEL 2 DESIGNATORS (NO DASH)
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 7:57:36 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
M-001
M
EC
HA
NI
CA
L
LE
G
EN
D
K.
W
IL
LI
AM
S
P.
M-301
1 2 3 4 5
A
B
D
C
OPEN CLASSROOM
3503 SF
CORRIDOR
207 SF
SERVER
80 SF
COMM.
78 SF
ELEC.
53 SF
MECH
119 SF
MEN
161 SF
WOMEN
161 SF
JAN
27 SF
VEST
47 SF
BREAK/LACTATION
56 SF
AHU-1
AHU-2
SA 450 SA 450 SA 450 SA 450 SA 450
SA 455SA 455SA 455SA 455SA 455
EA 200
EA 200
EA 30
10"ø EA
6"x6" EA
6"x6" EA
MH401
DSS-2
T
T
L-1
L-2
12"x12" TA 12"x12" TA
TATA3 3
L-3
EF-1
24"x16" SA
24"x16" SA
24"x16" SA
24"x16" SA
10"ø SA 10"ø SA 10"ø SA 10"ø SA 10"ø SA
10"ø SA 10"ø SA 10"ø SA 10"ø SA 10"ø SA
SA 455
SA 450
SA 455
SA 450
RA 1600RA 1600
RA 1600RA 1600
10"ø SA 10"ø SA
10"ø SA 10"ø SA24"x16" RA
24"x16" RA
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
PLAN NORTH
4/25/2019 7:59:29 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
MH101
HV
AC
P
LA
N K.
W
IL
LI
AM
S P.
E.
PROJECT NAME
1/8" = 1'-0"1 OVERALL HVAC PLAN
8'4' 16'0
GENERAL NOTES
1. ALL MAIN DUCT SHALL BE STATIC PRESSURE CLASS 2, ALL BRANCH DUCT
FROM THE MAIN TO THE OUTLETS SHALL BE STATIC PRESSURE CLASS 1.
2. PROVIDE BALANCING DAMPERS IN ALL BRANCH DUCTS FROM MAINS.
3. INSULATE ALL SUPPLY AND RETURN DUCT.
4. FOR BUILDING PRESSURIZATION CONTROL, SEE HVAC CONTROLS.
5. ALL MANUAL DAMPERS SHALL BE OPERABLE FROM BELOW.
6. ALL ELBOWS ARE 1.5 RADIUS UNLESS NOTED WITH KEYED NOTE
OTHERWISE.
7. SEE SCHEDULE ON SHEET M-602 FOR DIFFUSER NECK AT DUCT SIZE.
KEYED NOTES
1 ATFP STOP BUTTON LOCATION.
2 BAROMETRIC RELIEF DAMPER. SEE SHEET M-502 FOR DETAIL
3 TRANSFER DUCT LOCATION. SEE SHEET M-502 FOR DETAIL.
4 24" x 24" CEILING ACCESS PANEL LOCATION. REFER TO SHEET A-560 FOR
DETAILS.
5 RETURN AIR PLENUM BOX.
M-301
D
C
COMM.
78 SF
ELEC.
53 SF
MECH
119 SF
BREAK/LACTATION
56 SF
SERVER
80 SF
CORRIDOR
207 SF
SA 50
AHU-1
AHU-2
DSS-4DSS-3 DSS-1
DSS-2
DSS-1DSS-4DSS-3
TATA
12"x12" TA 12"x12" TA
6" ø
SA
24"x16" SA
24"x16" SA
4 4 4
1 3
24"x16" RA
24"x16" RA
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
PLAN NORTH
4/25/2019 7:59:58 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
MH401
EN
LA
RG
ED
M
EC
HA
NI
CA
L
RO
O
M H
VA
C
PL
AN
K.
W
IL
LI
AM
S
P.
E.
PROJECT NAME
1/4" = 1'-0"1 ENLARGED MECHANICAL ROOM HVAC PLAN
GENERAL NOTES
1. ALL MAIN DUCT SHALL BE STATIC PRESSURE CLASS 2, ALL BRANCH DUCT
FROM THE MAIN TO THE OUTLETS SHALL BE STATIC PRESSURE CLASS 1.
2. PROVIDE BALANCING DAMPERS IN ALL BRANCH DUCTS FROM MAINS.
3. INSULATE ALL SUPPLY AND RETURN DUCT.
4. FOR BUILDING PRESSURIZATION CONTROL, SEE HVAC CONTROLS.
5. ALL MANUAL DAMPERS SHALL BE OPERABLE FROM BELOW.
6. ALL ELBOWS ARE 1.5 RADIUS UNLESS NOTED WITH KEYED NOTE
OTHERWISE.
7. SEE SCHEDULE ON SHEET M-602 FOR DIFFUSER NECK AT DUCT SIZE.
KEYED NOTES
1 MITER ELBOW LOCATION.
2 AHU SERVICE CLEARANCE AREA.
3 BOTTOM OF DUCT DOWN TO 1' 0" ELEVATION TO CONNECT TO AIR
HANDLING UNIT.
4 SPLIT SYSTEM MOUNTED 7' 6" AFF.
5 SPLIT SYSTEM MOUNTED 7' 0" AFF.
6 SUPPLY DUCT UNDER RETURN. SEE SHEET M-901 FOR ISOMETRIC VIEW.
7 SPACE RESERVED FOR POSTED INSTRUCTIONS AND COLOR CODING
SCHEMATICS. REFER TO 22 00 00 AND 23 00 00 SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
8 DDC PANEL LOCATION.
9 GOOSENECK FITTING.
0 2' 4' 8'
LOW ROOF
12' - 0"
HIGH ROOF
18' - 0"
FLOOR PLAN
0' - 0"
B.O. CANOPY ROOF
8' - 0"
B.O. ROOF
12' - 0"
F.F.
0' - 0"
CD
B.O. CANOPY
7' - 5"
16"x24" SA
16"x24" RA
16"x24" RA
16"x24" SA
24"x16" SA
24"x16" RA 12"x12" TA
TA
WH-1
DSS-3
DSS-3
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 7:58:04 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
M-301
M
EC
HA
NI
CA
L
RO
O
M S
EC
TI
O N
VI
EW
K.
W
IL
LI
AM
S
P.
E.
PROJECT NAME
1/2" = 1'-0"1 MECHANICAL ROOM SECTION VIEW
2'1' 4'0
GENERAL NOTES
1. ALL MAIN DUCT SHALL BE STATIC PRESSURE CLASS 2, ALL BRANCH DUCT
FROM THE MAIN TO THE OUTLETS SHALL BE STATIC PRESSURE CLASS 1.
2. PROVIDE BALANCING DAMPERS IN ALL BRANCH DUCTS FROM MAINS.
3. INSULATE ALL SUPPLY AND RETURN DUCT.
4. FOR BUILDING PRESSURIZATION CONTROL, SEE HVAC CONTROLS.
5. ALL MANUAL DAMPERS SHALL BE OPERABLE FROM BELOW.
6. ALL ELBOWS ARE 1.5 RADIUS UNLESS NOTED WITH KEYED NOTE
OTHERWISE.
7. SEE SCHEDULE ON SHEET M-602 FOR DIFFUSER NECK AT DUCT SIZE.
1 MITER ELBOW LOCATION.
2 BOTTOM OF DUCT DOWN TO 1'0" ELEVATION TO CONNECT TO AIR
HANDLING UNIT.
KEYED NOTES
NOT TO SCALE
NUT
LOCK NUT
HVAC & PIPE HANGERS
FLAT
WASHER
FLAT
WASHER
LOCK
WASHER
THREADED
RODTHREADED ROD SEATED
IN CLEVIS FIRST
NOT TO SCALE
TYPICAL ADJUSTABLE CLEVIS HANGER
HANGER
CLEVIS
SUPPORT ROD
SUSPENDED FROM
STRUCTURE
CLEVIS BOLT
CARRIER PIPE
BOLT ON 4" CENTER
WASHER
FLEXIBLE
MATERIAL
SPECIFIED
SHEET METAL AS
SPECIFIED FOR
DUCTWORK
ALTERNATE
POSITION
OF BOLT
1" FLANGE
& HEM
FLANGED
CONNECTION
ON FAN SIDE
SHEET METAL
AS SPECIFIED
FOR DUCTWORK
11/2" MIN. TO 3" MAX.
INSTALLED 6" NORMAL
W/ MATERIAL TAUT
1 1/2" POCKET SLIP
DUCTWORK
1" x 1/8" BAND IRON
NOT TO SCALE
FLEXIBLE CONNECTOR
AIRFLOW
NOT TO SCALE
SPLITTER DAMPER DETAIL
L= 0.25*W W= 100mm MIN.
L
45°
METAL BAND
SUPPORT
TIE OFF TO ROOF
STRUCTURE
SUPPLY AIR
DIFFUSER W/
ROUND NECK
& O.B.D.
FLEX DUCT WITH 2"
INSULATION VAPOR
BARRIER, MAXIMUM
LENGTH 5'-0"
NYLON
DRAW BAND
SUPPLY
DUCT
SPIN-IN TAP
FITTING W/AIR
SCOOP & DAMPER
CEILING
SUPPLY AIR DIFFUSER DETAIL
NOT TO SCALE
AIR FLOW
TYPICAL BRANCH TAKE-OFF
NOT TO SCALE
LEVER OUTSIDE
OF DUCT
SET
SCREW
DUCT PENETRATION THROUGH
METAL PANEL STUD WALL
NOT TO SCALE
INSULATION
WALL
DUCT
20 GAGE GALVANIZED
STEEL COLLAR (EXPOSED
ONLY). SECURE TO WALL
ON 6 INCH CENTERS
(MINIMUM 4 FASTENERS
PER SIDE)
1" CLEARANCE
BETWEEN
20 GAGE
GALVANIZED
STEEL SLEEVE
2"x2"x1/4"
TACK WELDED
OR RIVETED
TO SLEEVE
INLET TUBE HOLES FACE
UPSTREAM OF AIR FLOW;
TUBE LENGTH SHALL BE
SAME AS DUCT WIDTH
PROVIDE STANDOFF BRACKET
OR RUBBER GROMMET AT
WALL PENETRATION FOR
DUCTS WIDER THAN 2'-0"
INSERT RUBBER PLUG
THIS END OF INLET
TUBE
RETURN TUBE SLANT
CUT FACE ORIENTED
DOWNSTREAM OF AIR
FLOW (DO NOT
INSERT RUBBER PLUG)
DUCT
WIDTH
DUCT SMOKE DETECTOR DETAIL
NOT TO SCALE
NOTE:
PROVIDE HINGED ACCESS DOOR
IN DUCT FOR FIRE DAMPER
NOT TO SCALE
TYPICAL SQUARE ELBOW
DUCT TURNS 2-1/2" O.C.
AIR FLOW
NOT TO SCALE
TYPICAL RADIUS ELBOW
VANES SHALL
RUN ENTIRE
LENGTH OF
ELBOW W/O
EXTENDED
TAILS
THREE SPLITTER VANES
EVENLY SPACED (NOT
REQ'D WHEN W * 12"
W
R= 1.5 X W
9 10
5 6 7 8
1 2 3
DUCT PENETRATION THROUGH
CMU WALL
NOT TO SCALE
INSULATION
WALL
GROUT
DUCT
20 GAGE GALVANIZED
STEEL COLLAR (EXPOSED
ONLY). SECURE TO WALL
ON 6 INCH CENTERS
(MINIMUM 4 FASTENERS
PER SIDE)
1" CLEARANCE
BETWEEN
20 GAGE
GALVANIZED
STEEL SLEEVE
2"x2"x1/4"
TACK WELDED
OR RIVETED
TO SLEEVE
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 7:58:25 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
M-501
M
EC
HA
NI
CA
L
DE
TA
IL
S
K.
W
IL
LI
AM
S
P.
FLEXIBLE CONNECTOR (TYP.)
HANGER ROD ISOLATOR
REFER TO
SPEC
IN-LINE FAN
IN-LINE FAN SUSPENSION DETAIL
NOT TO SCALE1 NOT TO SCALE
TRANSFER AIR DETAIL
TIE OFF TO ROOF
STRUCTURE
METAL BAND
SUPPORT
METAL DUCT WITH
BALANCING DAMPER
LAY IN DIFFUSER
LESS THAN 3'
OF FLEX DUCT
INTERIOR WALL
NOT TO SCALE3
ATFP COMPLIANT LOW
LEAKAGE CONTROL DAMPER
DUCT SHALL BE
PRESSURE CLASS 3.
DAMPER
MOTOR
LINKAGE
OUTSIDE
CAULK
CAULK
EXTENDED
SILL
FRAME WALL
FRAME WALL
DUCT CONNECTED TO
TRANSFER IN
ARCHITECTURAL
CEILING
COUNTER
BALANCE RELIEF
DAMPER
RELIEF AIR LOUVERS AND DAMPERS
1-1/2" X 1-1/2" X 1/8" ALUMINUM OR STEEL
X CLIP ANGLE, 4" WITH FASTENERS
USE RA2-600 CFM DIFFUSERS
NOT TO SCALE
DUCT ACCESS DOORS
DOOR A
DOOR B
GASKET DUCT
LOCK TYPE 2
DUCT
FRAME 2
FRAME 3
HINGE POS. 3
FRAME 2
HINGE POS. 2
DUCT
BUTT HINGE 1"x1", OR PIANO HINGE
FRAME 1
HINGE POS. 1
SASH
LOCK
LOCK
TYPE 1
ACCESS
PANEL
S = SIDE OPPOSITE HINGES, T = TOP, B = BOTTOM
12" x 12" 16" x 20" 24" x 24"
12" x 12" 16" x 20" 24" x 24"
12" x 12" 16" x 20" 24" x 24"
1-S 2-S 2-S
1-S 1-S,1-T,1-B 2-S,1-T,1-B
1-S,1-T,1-B 2-S,1-T,1-B 2-S,2-T,2-B
METAL GAGE
2" W.G.
STATIC
AND LESS
3" W.G.
STATIC
4" W.G.
TO
10" W.G.
NO.
HINGES
NO.
LOCKS
DUCT
PRESSURE
CLASS FRAME DOOR BACK
DOOR
SIZE
VIEW PORT IF
SPECIFIED
PANEL IS DUCT GAGE (MIN.)
w/SCREWS AT 8" MAX. SPACING
11/4"
ANGLE IRON REINFORCING
WHERE REQUIRED
ROOF
ANGLE RIVETED
OR SPOT WELDED
AS REQUIRED
STANDARD DUCT
CONSTRUCTION
SEAMS WATERTIGHT
PREFAB.
ROOF CURB,
PER CSPE
ROOF MFR.
NOT TO SCALE
TYPICAL GOOSENECK VENT
SCREEN
BOLTS
METAL SCREEN FRAME
BIRD SCREEN
FLASHING
" M
IN
IM
U M
SPECIFIED
DUCT SIZE
DUCT
SIZE+ 25%
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 7:58:36 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
M-502
M
EC
HA
NI
CA
L
DE
TA
IL
S
K.
W
IL
LI
AM
S
P.
AIR HANDLING UNIT SCHEDULE
UNIT TAG
SUPPLY FAN COOLING SECTION
TYPE CFM
(MIN)
E.S.P (IN WG) HP V/PH/Hz ENTERING AIR
DB/WB (DEG. F)
TOTAL
CAPACITY
(MBH)
SENSIBLE
CAPACITY
(MBH)
AHU-2 PLENUM 715 1.00 1 208-230 / 3 / 60 85.0 / 70.0 113.25 90.30
REMARKS:
1. PROVIDE UNIT WITH DISCONNECT AND VARIABLE FREQUENCY DRIVE.
2. UNIT SHALL BE SIZED TO DELIVER SCHEDULED CAPACITIES AT AN ELEVATION OF 924 FEET ABOVE SEA LEVEL.
3. B.O.D. TRANE THC120F3RKA
LEAVING AIR
DB/WB (DEG. F)
60.2/ 58.8
FILTER
(MERV)
8 / 13
REMARKS
ALL
DIFFUSER SCHEDULE
UNIT TAG DESCRIPTION TYPE NECK SIZE (IN.) MAX NC MOUNTING MATERIAL REMARKS
SA1 SUPPLY DIFFUSER
SUPPLY DIFFUSER
SA1 SUPPLY DIFFUSER
SA2 SUPPLY DIFFUSER
SA2 SUPPLY DIFFUSER
SA2 SUPPLY DIFFUSER
REMARKS:
1. ALL DIFFUSERS ARE 4 WAY THROW UNLESS NOTED OTHERWISE ON HVAC PLAN.
2. B.O.D. TITUS TMS
24 x 24 24 x 24 24 x 24 24 x 24
24 x 24 24 x 24
8"
25 LAY IN ALUMINUM
SA1
10" 12"
LAY IN
LAY IN
LAY IN
SURFACE MOUNT
SURFACE MOUNT
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
FLOW RANGE (CFM)
95-200 200-350 350-600
95-200
SA2 SUPPLY DIFFUSER 24 x 24 25 SURFACE MOUNT ALUMINUM
SUPPLY DIFFUSERSA1
200-350 350-600
8" 10" 12"
25 SURFACE MOUNT ALUMINUM24 x 24
0-95
0-95
6"
6"
EA1 EXHAUST REGISTER
EXHAUST REGISTER
EA1 EXHAUST REGISTER
EA2 EXHAUST REGISTER
EA2 EXHAUST REGISTER
EA2 EXHAUST REGISTER
24 x 24 24 x 24 24 x 24 24 x 24
24 x 24 24 x 24
8"
25 LAY IN ALUMINUM
EA1
10" 12"
LAY IN
LAY IN
LAY IN
SURFACE MOUNT
SURFACE MOUNT
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
95-200 200-350 350-600
95-200
EA2 EXHAUST REGISTER 24 x 24 25 SURFACE MOUNT ALUMINUM
EXHAUST REGISTEREA1
200-350 350-600
8" 10" 12"
25 SURFACE MOUNT ALUMINUM24 x 24
0-95
0-95
6"
6"
RA1 RETURN GRILLE
RETURN GRILLE
RA1 RETURN GRILLE
RA2 RETURN GRILLE
RA2 RETURN GRILLE
RA2 RETURN GRILLE
24 x 24 24 x 24 24 x 24 24 x 24
24 x 24 24 x 24
8"
25 LAY IN ALUMINUM
RA1
10" 12"
LAY IN
LAY IN
LAY IN
SURFACE MOUNT
SURFACE MOUNT
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
ALUMINUM
95-200 200-350 350-600
95-200
RA2 RETURN GRILLE 24 x 24 25 SURFACE MOUNT ALUMINUM
RETURN GRILLERA1
200-350 350-600
8" 10" 12"
25 SURFACE MOUNT ALUMINUM24 x 24
0-95
0-95
6"
6"
TA TRANSFER GRILLE 24 x 24 NA LAY IN ALUMINUM350-600 12"
DEDICATED SPLIT SYSTEM
UNIT TAG ROOM SERVING COOLING
CAPACITY (MBH)
CONDENSER AIR
TEMP (DEG. F)
MIN
SEER
INDOOR UNIT OUTDOOR UNIT
REMARKSELECTRICAL ELECTRICAL
V/PH/HZ MCA V/PH/HZ
DSS-1 110 - COMM ROOM
DSS-2 108 - SERVER ROOM
REMARKS:
1. UNIT SHALL BE SIZED TO DELIVER SCHEDULED CAPACITIES AT AN ELEVATION OF 924 FEET ABOVE SEA LEVEL.
2. UNIT REFRIGERANT SHALL BE R-410A.
3. INDOOR AND OUTDOOR UNITS SHARE SAME TAG NUMBER.
4. INDOOR UNITS RECEIVE POWER FROM OUTDOOR UNITS THROUGH FIELD-SUPPLIED INTERCONNECTED WIRING.
5. B.O.D TRANE INDOOR MSZ-FH06NA OUTDOOR MUZ-FH06NA
6. INSTALL CONDENSATE DRAIN PER MANUFACTURE RECOMMENDATIONS.
6 104 12 208 / 1 / 60 208 / 1 / 60 1,2,3,4,5,611 6 104 12 208 / 1 / 60 208 / 1 / 60 1,2,3,4,5,611
HEATING
CAPACITY (MBH)
DSS-3 6 104 12 208 / 1 / 60 208 / 1 / 60 1,2,3,4,5,69112 - MECH ROOM
DSS-4 6 104 12 208 / 1 / 60 208 / 1 / 60 1,2,3,4,5,69111 - ELEC ROOM
LOUVER SCHEDULE
TAG CFM FUNCTION LOUVER OVERALL
SIZE (L" X H")
MAX. P.DROP
IN. WTR
LOUVER
DEPTH (IN.) REMARKSMOUNTING HEIGHT AFF
TO BOTTOM (FT. IN.)
REMARKS:
1. LOUVER IS 6063T6 EXTRUDED ALUMINUM.
2. ALL LOUVERS HAVE EXTERIOR STAINLESS STEEL BIRD SCREEN OR INSECT SCREEN AS AN UPGRADE AS NOTED.
3. B.O.D. RUSKIN EME520DD WIND DRIVEN RAIN RESISTANT STATIONARY LOUVER OR APPROVED EQUAL.
4. REFERENCE ARCH PLANS AND COORDINATE ELEVATIONS OF LOUVERS.
5. PROVIDE CONTROL / SHUT-OFF LOW LEAKAGE DAMPER ATTACHED TO REAR OF LOUVER.
6. HEIGHT IS MEASURED FROM THE FINISHED FLOOR THE LOUVER IS ON.
7. PROVIDE LOUVERS WITH A HIGH-PERFORMANCE FINISH IN ACCORDANCE WITH AAMA 2605, COLOR MUST MATCH ADJACENT EXTERIOR BUILDING
SURFACE, SUBMIT COLOR FOR APPROVAL.
L-1 L-2
24 X 20 24 X 20
5" 5"
13' 0" 13' 0"
ALLBAROMETRIC RELIEF
BAROMETRIC RELIEF
0.02
0.02 ALL
INLINE FAN SCHEDULE
UNIT TAG TYPE DESIGN AIRFLOW
(CFM)
E.S.P.
(IN WG) DRIVE
ELECTRICAL MAX. OPERATING
WEIGHT (LBS)
OPENING
REMARKS
POWER (HP) RPM V/PH/HZ HxW
EF-1
REMARKS:
1. CONTRACTOR SHALL PROVIDE UNIT MOUNTED COMBINATION STARTER/DISCONNECT.
2. UNIT SHALL BE SIZED TO DELIVER SCHEDULED CAPACITIES AT AN ELEVATION OF 924 FEET ABOVE SEA LEVEL.
3. B.O.D GREENHECK SQ 90
4. H.O.A SWITCH
5. INTERLOCK WITH ATFP EMERGENCY STOP SWITCH
EXHAUST 430 0.50 DIRECT 1/4 1725 120/1/60 41 12 X 12 ALL
HEATING SECTION
ENTERING AIR
DB (DEG. F)
TOTAL
CAPACITY
(MBH)
53 92.21
LEAVING AIR
DB (DEG. F)
79.53 2
HEATING
STAGES
MAX
LENGTH
(IN)
8.31
MAX
WIDTH
(IN)
5.27
MAX FACE
VELOCITY (FPM)
AHU-1 PLENUM 715 1.00 1 208-230 / 3 / 60 85.0 / 70.0 113.25 90.3060.2/ 58.88 / 13 ALL53 92.2179.53 2 8.31 5.27
L-3 430 22 X 12 5" 11' 0"EXHAUST 0.08 ALL500
CONDENSER AIR
TEMP (DEG. F)
MIN
SEER
104 14
CFM
(MAX)
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 7:58:53 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
M-601
M
EC
HA
NI
CA
L
SC
HE
DU
LE
S K.
W
IL
LI
AM
S P.
AHU-2
AHU-1
16"x24" SA
24"x16" RA
10"ø SA
SA 450
12"x12" TA
12"x12" TA
24"x16" SA
DSS-1
DSS-4
DSS-3
DSS-2
20"x14" OA
DSS-2
DSS-1
24"x16" RA 20"x14" OA
WH-1
24"x16" RA
24"x16" RA
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 7:59:09 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
M-901
M
EC
HA
NI
CA
L
RO
O
M H
VA
C
IS
O
M
ET
RI
C
K.
W
IL
LI
AM
S
P.
E.
PROJECT NAME
1 MECHANICAL ROOM HVAC ISOMETRIC
GENERAL NOTES
1. ALL MAIN DUCT SHALL BE STATIC PRESSURE CLASS 2, ALL BRANCH DUCT
FROM THE MAIN THE TO OUTLETS SHALL BE STATIC PRESSURE CLASS 1.
2. PROVIDE BALANCING DAMPERS IN ALL BRANCH DUCTS FROM MAINS.
3. INSULATE ALL SUPPLY AND RETURN DUCT.
4. FOR BUILDING PRESSURIZATION CONTROL, SEE HVAC CONTROLS.
5. ALL MANUAL DAMPERS SHALL BE OPERABLE FROM BELOW.
6. ALL ELBOWS ARE 1.5 RADIUS UNLESS NOTED WITH KEYED NOTE
OTHERWISE.
7. SEE SCHEDULE ON SHEET M-601 FOR DIFFUSER NECK AT DUCT SIZE.
1 OUTSIDE AIR GOOSENECK FITTING.
2 SPLIT SYSTEM CONDENSER UNIT LOCATED OUTSIDE OF BUILDING (TYP.)
KEYED NOTES
TA
TA
TA
TA
NTS
INPUT/OUTPUT
CONTROL VALVE FLOW COEFF.
LOCAL DISPLAY PANEL
LOW LIMIT
MONITORING & CONTROL
MIXED AIR
MINIMUM OUTSIDE AIR
MOTOR STARTER
NOT APPLICABLE
NORMALLY CLOSED
NETWORK CONFIGURATION
INPUT
NORMALLY OPEN
NETWORK VARIABLE
OUTSIDE AIR
OCCUPIED
ON DELAY TIMER
OPERATOR WORK STATION
PRE-
PRESSURE
PRE-COOLING
PRIMARY CHILLED WATER
PRIMARY CHILLED WATER
RETURN
PRIMARY CHILLED WATER
SUPPLY
PREHEAT
PUMP
POSITIVE POSITIONER
PLATE HEAT EXCHANGER
RELAY
RETURN AIR
REVERSE (CONTROL ACTION)
RETURN FAN
RELATIVE HUMIDITY
RELIEF AIR
ROOM
RESET
RATE
STATUS
SUPPLY AIR
SECONDARY
SUPPLY FAN
SMOKE
STANDARD NETWORK
VARIABLE TYPE
SETPOINT
START/STOP COMMAND
THERMOSTAT
SYSTEM
SCHEDULER
TEMPERATURE
TAP, PRESSURE
THERMAL STORAGE
THERMAL STORAGE CHARGE
THERMAL STORAGE DISCHARGE
THERMAL STORAGE PUMP
UNOCCUPIED
VALVE
VARIABLE AIR VOLUME
VARIABLE FREQUENCY DRIVE
WET BULB (TEMPERATURE)
INCH WATER COLUMN
ZONE
I/O Kv
LDP
LL
M&C
MA
MINOA
MS
N/A
NC
NCI
NO
NV
OA
OCC
ODT
OWS
PR
P
PC
PCW
PCWR
PCWS
PH
PMP
PP
PX
R
RA
REV
RF
RH
RLA
RM
RST
RT
S
SA
SEC
SF
SMK
SNVT
SP
SS
STAT
SYS
SCHD
T
TAP
TS
TSC
TSD
TSP
UNOCC
V
VAV
VFD
WB
WC
ZN
CHILLER
PH
PC
EH
HC
DX
C
CONTACT, PRESSURE, LOW LIMIT (LL)
SHOWN IN ACTIVATED POSITION
OPEN WHEN PRESSURE IS BELOW SETPOINT
CLOSED WHEN PRESSURE IS ABOVE SETPOINT
CONTACT, PRESSURE, LOW LIMIT (LL)
SHOWN IN INACTIVATED POSITION
OPEN WHEN PRESSURE IS BELOW SETPOINT
CLOSED WHEN PRESSURE IS ABOVE SETPOINT
PRESSURE GAGE
FILTER
XX-C
CONTACT, PRESSURE, HIGH LIMIT (HL)
SHOWN IN ACTIVATED POSITION
OPEN WHEN PRESSURE IS ABOVE SETPOINT
CLOSED WHEN PRESSURE IS BELOW SETPOINT
CONTACT, PRESSURE, HIGH LIMIT (HL)
SHOWN IN INACTIVATED POSITION
OPEN WHEN PRESSURE IS ABOVE SETPOINT
CLOSED WHEN PRESSURE IS BELOW SETPOINT
COIL, PRECOOL
COIL, PREHEAT
COIL, COOLING, DIRECT-EXPANSION
COIL, HEAT/COOL (DUAL TEMPERATURE)
COIL, COOLING
FAN
RELAY COIL CONTACT
NORMALLY CLOSED
XX = RELAY COIL NUMBER
YY = CONTACT NUMBER
RXX-YY
RELAY COIL CONTACT
NORMALLY OPEN
XX = RELAY COIL NUMBER
YY = CONTACT NUMBER
RXX-YY
AFMA
W-X-Y-Z
DDC
W-X-Y-Z
VALVE, BALANCING
AIR FLOW MEASUREMENT ARRAY, WITH FLOW
TRANSMITTER SEE "DEVICE SYMBOL, GENERIC"
ACTUATOR, ELECTRIC
RELAY COIL
MOTOR STARTER
RXX
MS-#
MAIN AIR
MOTORM#
DAMPER, PARALLEL BLADE
NORMALLY OPEN OR CLOSED AS SHOWN
## = DAMPER NUMBER AS SHOWN
IN DAMPER SCHEDULE
DAMPER, OPPOSED BLADE
NORMALLY OPEN OR CLOSED AS SHOWN
## = DAMPER NUMBER AS SHOWN
IN DAMPER SCHEDULE
D-##
D-##
DAMPER, BALANCING
GENERIC DEVICE SYMBOL:
MULTIPLE OUTPUT DEVICE WHERE AT LEAST 1
OUTPUT IS ALWAYS A SAFETY INTERLOCK
GENERIC DEVICE SYMBOL:
USED TO REPRESENT SENSORS, INSTRUMENTS
SAFETIES, AND OTHER CONTROL DEVICES
CONTACT, TEMPERATURE, LOW LIMIT (LL)
SHOWN IN ACTIVATED POSITION
OPEN WHEN TEMPERATURE IS BELOW SETPOINT
CLOSED WHEN TEMPERATURE IS BELOW SETPOINT
CONTACT, TEMPERATURE, LOW LIMIT (LL)
SHOWN IN INACTIVATED POSITION
OPEN WHEN TEMPERATURE IS BELOW SETPOINT
CLOSED WHEN TEMPERATURE IS ABOVE SETPOINT
CURRENT TRANSFORMER/SWITCH
CONTACT, TEMPERATURE, HIGH LIMIT (HL)
SHOWN IN ACTIVATED POSITION
OPEN WHEN TEMPERATURE IS ABOVE SETPOINT
CLOSED WHEN TEMPERATURE IS BELOW SETPOINT
CONTACT, TEMPERATURE, HIGH LIMIT (HL)
SHOWN IN INACTIVATED POSITION
OPEN WHEN TEMPERATURE IS ABOVE SETPOINT
VARIABLE FREQUENCY DRIVE
XX = PROCESS/DEVICE BEING CONTROLLED
SS = START/STOP COMMAND
S = STATUS FEEDBACK (ON/OFF)
C = 4-20 MA, VDC, OR SNVT CONTROL SIGNAL
XX-S
VFD
VALVE, 3-WAY MIXING
WITH SPRING RETURN FAILSAFE
NO = NORMALLY OPEN
NC = NORMALLY CLOSED
COM = COMMON PORT
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
NC
V-##
NO COM
NC
VALVE, NORMALLY CLOSED
WITH SPRING RETURN FAILSAFE
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
VALVE, NORMALLY OPEN
WITH SPRING RETURN FAILSAFE
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
VALVE, 3-WAY DIVERTING
WITH SPRING RETURN FAILSAFE
NO = NORMALLY OPEN
NC = NORMALLY CLOSED
COM = COMMON PORT
## = VALVE NUMBER AS SHOWN
IN VALVE SCHEDULE
V-##
COM NO
V-##
NO
NC
V-##
THERMOWELL IN PIPE
THERMOSTAT WITH SPECIFIED I/O FUNCTIONS
TEMPERATURE SENSOR, POINT
SEE "GENERIC DEVICE SYMBOL"
STAT
TEMPERATURE SENSOR, AVERAGING
OR TEMPERATURE LOW LIMIT / FREEZESTAT
SEE "GENERIC DEVICE SYMBOL"
TEMPERATURE GAGE
SWITCH, MANUAL
SMOKE DETECTOR, DUCT-MOUNTED
SEE "DEVICE SYMBOL, GENERIC"
RESET BUTTON FOR SAFETY RESETRST-BUT
RADIATOR
PRESSURE SWITCH, DIFFERENTIAL, WITH GAGE
H = HIGH PRESSURE TAP
L = LOW PRESSURE TAP
SEE "DEVICE SYMBOL, GENERIC"H L
PUMP
LOCAL DISPLAY PANEL
## = SEQUENTIAL NUMBER
(WHEN MORE THAN 1 LDP)##
LDP
W-X-Y-Z
HEAT EXCHANGER
CONTROL SIGNAL LINE, LOW VOLTAGE
CONTROLLER DEVICE SYMBOL:
DDC : DIRECT DIGITAL CONTROL
## : DEVICE NUMBER
DIR : DIRECT CONTROL ACTION, OR
REV : REVERSE CONTROL ACTION
TYPICAL DEVICE NOTE:
W-X-Y-Z : (SEE ABBREVIATIONS AND ACRONYMS)
GENERIC USAGE TO SHOW LOCATION OF DEVICE;
PROCESS OR DEVICE BEING MEASURED OR
CONTROLLED; SIGNAL TYPE; MODIFIERS AND
OTHER APPLICATION INFORMATION
H
COIL, HEATING
COIL, RESISTANCE HEAT
DIR
REV
MAIN
AIR
P
BOILER
XX-SS
T
P
ABBREVIATIONS AND ACRONYMSCONTROL SCHEMATIC SYMBOLS
GENERAL NOTES:
HVAC EQUIPMENT IDENTIFIER
XX = SEQUENTIAL RELAY
(SOLENOID) NUMBER
2P
ADJ
AFMA
AI
ALM
AO
B
BI
BA
BLDG
BUT
C
CD
CHLR
CLG
CO2
COM
COMP
CP
CPA
CT
CHR
CHS
CH
CW
CWR
CWS
D
DA
DB
DDC
DI
DIFF
DIR
DIS
DISP
DO
DT
DTS
DTWR
DTWS
DX
EA
ECO
EF
ENA
EP
EPS
EW
F
FAP
FLT
FN
HD
HL
HTG
HTHW
HUM
H
HW
HWR
HWS
HX
1. ALL EQUIPMENT AND SENSORS ARE LOCATED IN THE MECHANICAL ROOM UNLESS
THE LOCATION IS IDENTIFIED OTHERWISE.
2. CONTRACTOR SHALL COMPLETE ALL POINTS LISTS AND DDC NUMBERING (##) ON
RETURNED AS-BUILTS.
3. CONTRACTOR SHALL PROVIDE ALL WIRING, VALVES, ACTUATORS, DAMPERS, AND
CONTROLS HARDWARE TO OPERATE SYSTEMS AS SHOWN IN THE SEQUENCE OF
OPERATIONS.
4. ALL CONTROL WIRING IN THE MECHANICAL ROOM AND INSIDE WALLS SHALL BE IN
CONDUIT. ALL CONTROL WIRING IN THE PLENUM SHALL BE PLENUM RATED WIRE.
5. ALL PACKAGED EQUIPMENT SENSORS SHALL BE CHECKED AND CALIBRATED BY DDC
CONTRACTOR.
D
M
TWO-POSITION (CONTROL SIGNAL)
ADJUSTABLE
AIRFLOW MEASUREMENT ARRAY
ANALOG INPUT
ALARM
ANALOG OUTPUT
BOILER
BINARY INPUT
BYPASS AIR
BUILDING
BUTTON
COMMAND (MODULATING CONTROL SIGNAL)
COLD DECK
CHILLER
COOLING
CARBON DIOXIDE
COMMON
COMPARATOR
CONFIGURATION PROPERTY
CONTROL POINT ADJUSTMENT
CURRENT TRANSFORMER/SWITCH
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER
CHILLED WATER
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
DAMPER
DISCHARGE AIR
DEADBAND
DIRECT DIGITAL CONTROL(LER)
DIGITAL INPUT
DIFFERENCE
DIRECT (CONTROL ACTION)
DISABLE
DISPLAY
DIGITAL OUTPUT
DUAL TEMP
DATA TERMINAL STRIP
DUAL TEMP WATER RETURN
DUAL TEMP WATER SUPPLY
DIRECT EXPANSION (UNIT)
EXHAUST AIR
ECONOMIZER
EXHAUST FAN
ENABLE
ELECTRIC TO PNEUMATIC TRANSDUCER
ELECTRIC TO PNEUMATIC SWITCH
ENTHALPY WHEEL
FLOW
FIRE ALARM PANEL
FILTER
FINAL
HOT DECK
HIGH LIMIT
HEATING
HIGH TEMPERATURE HOT WATER
HUMIDIFIER
HUMIDITY
HOT WATER
HOT WATER RETURN
HOT WATER SUPPLY
HEAT EXCHANGER
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 8:00:12 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
MI001
C O
N
TR
O
LS
L
EG
EN
D
K.
W
IL
LI
AM
S
P.
POINT SCHEDULE INSTRUCTIONS FOR UFGS-23 09 23 CONTRACTOR
GENERAL:
1) THE CONTRACT DRAWING POINTS SCHEDULES ASSUME THAT THE ENTIRE SEQUENCE OF
OPERATION IS PERFORMED IN A SINGLE PIECE OF DDC HARDWARE. IN CASES WHERE MULTIPLE
PIECES OF DDC HARDWARE ARE USED (INCLUDING CEA-709.1 NETWORKED SENSORS AND
ACTUATORS), SEPARATE THE POINTS SCHEDULE INTO SEPARATE TABLES EACH WITH ITS OWN
HEADER INFORMATION (SEE BELOW) SO THAT EACH PIECE OF DDC HARDWARE HAS A TABLE
DEDICATED TO IT. ALL TABLES FOR A SINGLE SEQUENCE OF OPERATION SHALL BE ON A SINGLE
DRAWING WHICH MAY SPAN MULTIPLE SHEETS. SHOW COMMUNICATION BETWEEN MULTIPLE
PIECES OF DDC HARDWARE PERFORMING A COMMON SEQUENCE THROUGH THE USE OF NVI AND
NVO ENTRIES IN THE I/O COLUMN (SEE I/O COLUMN INSTRUCTIONS BELOW), ADDING ROWS TO THE
TABLE(S) AS NEEDED.
2) ENTRIES SHOWN BRACKETED AS: < ___ > ARE REQUIRED ENTRIES UNDER UFGS-23 09 23. SOME
ENTRIES WITHOUT BRACKETS MAY BE REQUIRED IN SOME INSTANCES AS DESCRIBED IN THESE
INSTRUCTIONS. SPACES WHERE NO ENTRY IS ORDINARILY REQUIRED CONTAINS A TILDE: " ~ "
(EQUIVALENT TO AN "N/A" OR NULL VALUE)
WHEN AN ENTRY APPEARS INSIDE OF BRACKETS, IT IS A RECOMMENDED ENTRY THAT MUST BE VERIFIED OR CHANGED BY THE APPROPRIATE PARTY (AS INDICATED BY THE BRACKET TYPE). WHEN EDITING THE POINT SCHEDULES, DELETE THE BRACKETS AFTER VERIFYING/PROVIDING THE ENTRY. DO NOT LEAVE CELLS BLANK, INSTEAD SHOW THE TILDE ("~") TO INDICATE A NULL VALUE OR THAT NO FURTHER ENTRY IS
REQUIRED.
HEADER INFORMATION INSTRUCTIONS:
1) DDC HARDWARE IDENTIFIER: SHOW THE IDENTIFIER FOR EACH PIECE OF DDC HARDWARE.
MAINTAIN CONSISTENCY AND UNIQUENESS OF DDC HARDWARE IDENTIFIERS BETWEEN ALL
DRAWINGS.
2) DDC HARDWARE LOCATION: SHOW THE PHYSICAL LOCATION OF THE DEVICE. LOCATION SHALL INCLUDE THE BUILDING AND ROOM NUMBER AND MAY ALSO INCLUDE FURTHER INFORMATION SUCH
AS ENCLOSURE/PANEL IDENTIFICATION.
3) NODE ADDRESS: SHOW THE DOMAIN, SUBNET AND NODE ADDRESSES FOR ALL DEVICES ON THE
NETWORK.
4) NODE ID: SHOW THE MANUFACTURER SUPPLIED NODE ID (ALSO CALLED THE NEURON ID) FOR EACH
DEVICE.
"GENERAL" COLUMNS:
1) NAME COLUMN: SHOW POINT NAMES AS NEEDED AND AS INDICATED BY BRACKETS (<___>). THE
NAME SHALL BE CONSISTENT WITH POINT NAMES SHOWN ON ALL OTHER DRAWINGS AND SHALL
USE THE ESTABLISHED POINT ABBREVIATIONS.
2) SETTING COLUMN: CONFIGURE DEVICES TO USE THE SETPOINTS AND SETTINGS SHOWN. WHEN A SETPOINT OR SETTING IS NOT SHOWN, USE VALUES IN ACCORDANCE WITH THE SPECIFICATION
AND SHOW THE SETPOINT OR SETTING USED. INCLUDE THE APPROPRIATE ENGINEERING UNITS
FOR ENTRIES IN THIS COLUMN.
3) RANGE COLUMN: CONFIGURE DEVICES TO USE THE RANGES SHOWN. WHEN A RANGE IS NOT
SHOWN, USE VALUES IN ACCORDANCE WITH THE SPECIFICATION AND SHOW THE RANGE USED.
FOR SENSORS SHOW THE ACTUAL SENSOR RANGE (THIS RANGE MUST AT LEAST ENCOMPASS THE
RANGE SPECIFIED IN SECTION 23 09 23). FOR DAMPER ACTUATORS SHOW THE ACTUAL RANGE
OVER WHICH THE VALVE OR DAMPER IS ACTUATED. INCLUDE THE APPROPRIATE ENGINEERING
UNITS FOR ENTRIES IN THIS COLUMN.
4) NCI/CP NAME COLUMN: ENTRIES IN THIS COLUMN ARE ONLY REQUIRED FOR GENERAL PURPOSE
PROGRAMMABLE CONTROLLERS (GPPC) OR APPROVED APPLICATION SPECIFIC CONTROLLERS
(ASC) LACKING LONWORKS NETWORK SERVICES (LNS) PLUG-INS. SHOW ALL NETWORK
CONFIGURATION INPUTS (NCI) OR CONFIGURATION PROPERTIES (CP) THAT RELATE TO THE POINT.
FOR CPS OF A USER-DEFINED NETWORK CONFIGURATION PARAMETER TYPE (UCPT), PROVIDE
EITHER THE STANDARD NETWORK VARIABLE TYPE (SNVT) THAT RELATES TO THE CP, OR (FOR
UCPTS NOT BASED ON A SNVT) PROVIDE DETAILED DESCRIPTIONS OF THE FIELDS AND UNITS OF
EACH CP. EXPAND ROWS AND USE ADDITIONAL SHEETS AS REQUIRED TO PROVIDE
CONFIGURATION PROPERTY DESCRIPTIONS.
5) I/O TYPE COLUMN: SHOW THE I/O TYPE FOR EACH POINT AS ONE (OR MORE) OF THE FOLLOWING:
* AI FOR ANALOG INPUTS
* AO FOR ANALOG OUTPUTS
* BI FOR BINARY INPUTS
* BO FOR BINARY OUTPUTS
* NVO FOR NETWORK VARIABLE OUTPUTS (BOUND TO ANOTHER PIECE OF DDC HARDWARE)
* NVI FOR NETWORK VARIABLE INPUTS (BOUND FROM ANOTHER PIECE OF DDC HARDWARE)
IF MORE THAN ONE PIECE OF DDC HARDWARE IS USED TO IMPLEMENT A SEQUENCE AND THE VALUE OF A PHYSICAL INPUT TO ONE IS NEEDED BY THE OTHER, SHOW THE POINT AS BOTH A HARDWARE INPUT (AI OR BI) AND A NETWORK VARIABLE OUTPUT (NVO) ON THE FIRST AND AS A NETWORK VARIABLE INPUT (NVI) TO THE OTHER DDC HARDWARE. SIMILARLY FOR OUTPUTS SHOW A NETWORK VARIABLE OUTPUT (NVO) ON ONE CONTROLLER, AND A NETWORK VARIABLE INPUT (NVI) AND HARDWARE OUTPUT (AO OR
BO) ON THE OTHER.
AN ENTRY OF NVO IS ONLY REQUIRED FOR OUTPUTS THAT ARE USED BY ANOTHER PIECE OF DDC HARDWARE; POINTS THAT HAVE SNVT OUTPUTS ONLY FOR DISPLAY OR TRENDING AT AN LDP OR BY THE M&C SOFTWARE ARE ASSUMED TO BE NVOS AND DO NOT NEED AN NVO ENTRY IN THE I/O COLUMN.
FOR EVERY ENTRY OF NVO OR NVI SHOW THE SNVT NAME AND TYPE IN THE SNVT NAME AND SNVT TYPE
COLUMNS UNDER LDP AND M & C DISPLAY. SEE "SNVT TYPE COLUMN"INSTRUCTIONS BELOW.
6) HOA REQ'D COLUMN: FOR EACH OUTPUT WITH AN "X"IN THIS COLUMN PROVIDE A HARDWARE
MANUAL OVERRIDE FOR THAT OUTPUT:
a. THE MANUAL OVERRIDE SWITCH FOR BINARY OUTPUTS SHALL PROVIDE FOR OVERRIDING THE
OUTPUT OPEN OR CLOSED
b. THE MANUAL OVERRIDE SWITCH FOR ANALOG OUTPUTS SHALL EITHER:
i. PROVIDE FOR OVERRIDING THE OUTPUT TO 0% OR 100%
ii. PROVIDE FOR OVERRIDING THROUGH THE RANGE OF 0% TO 100%.
c. THE MANUAL OVERRIDE SHALL BE INTEGRATED WITH THE CONTROLLER HARDWARE OR AN
EXTERNAL OVERRIDE CO-LOCATED WITH (IN THE SAME ENCLOSURE AS) THE
CONTROLLER.
LDP AND M & C DISPLAY COLUMNS:
1) LDP VIEW REQ'D COLUMN: PROVIDE AN LDP AND CONFIGURE THE BUILDING CONTROL NETWORK AND THE LDP TO DISPLAY POINTS MARKED WITH AN "X". SHOW THE SNVT NAME AND SNVT TYPE
FOR EACH POINT SHOWN. (SEE INSTRUCTIONS FOR THE "SNVT TYPE" COLUMN)
2) M & C DISP REQ'D: AN "X" IN THIS COLUMN INDICATES THAT A SNVT FOR THIS POINT MUST BE
AVAILABLE FROM THE DDC HARDWARE PERFORMING THE SEQUENCE FOR THIS SYSTEM. PROVIDE
A SNVT OUTPUT FOR THESE POINTS AND SHOW THE SNVT NAME AND SNVT TYPE. (SEE
INSTRUCTIONS FOR THE "SNVT TYPE" COLUMN)
3) M & C TREND REQ'D COLUMN: FOR ALL POINTS WITH AN X IN THIS COLUMN A SNVT FOR THIS POINT SHALL BE AVAILABLE. PROVIDE A SNVT OUTPUT FOR THESE POINTS AND SHOW THE SNVT NAME
AND SNVT TYPE. (SEE INSTRUCTIONS FOR THE "SNVT TYPE" COLUMN)
4) SNVT TYPE COLUMNS: WHEN A SNVT TYPE IS SHOWN ON THE POINT SCHEDULE CONTRACT
DRAWING, USE THE SHOWN SNVT TYPE FOR THE PROVIDED SNVT. IF NECESSARY, A SNVT TYPE TRANSLATOR MAY BE USED TO CONVERT TO THIS SNVT TYPE. IF THE USE OF A TYPE TRANSLATOR
RESULTS IN THE SHARING OF A SNVT BETWEEN DDC HARDWARE, DOCUMENT IT ON THE POINTS
SCHEDULE AS DESCRIBED IN THE "GENERAL" PORTION OF THESE INSTRUCTIONS. WHERE NO SNVT
TYPE IS SHOWN, SHOW THE SNVT TYPE USED.
OVERRIDES COLUMNS:
1) LDP OVRD REQ'D COLUMN: FOR EACH POINT WITH AN "X" IN THIS COLUMN, PROVIDE A SNVT INPUT FOR THE POINT BY WHICH THE VALUE OF THE POINT CAN BE OVERRIDDEN AND PROVIDE AN LDP (IF
NOT ALREADY PROVIDED) AND CONFIGURE THE BUILDING CONTROL NETWORK AND THE LDP TO
ALLOW AN OPERATOR TO OVERRIDE (WRITE TO) THE POINT FROM THE LDP. SHOW THE OVERRIDE INPUT SNVT NAME AND TYPE FOR EACH POINT REQUIRING AN OVERRIDE. IF THE OVERRIDE IS RELEASED BY A MEANS OTHER THAN WRITING THE "NULL VALUE" FOR THE SNVT TYPE (AS DEFINED IN THE LONWORKS MASTER SNVT LIST), PROVIDE A DESCRIPTION OF HOW THE OVERRIDE IS USED
AND RELEASED.
2) M & C OVRD REQ'D COLUMN: FOR EACH POINT WITH AN "X" IN THIS COLUMN, PROVIDE A SNVT INPUT FOR THE POINT BY WHICH THE VALUE OF THE POINT CAN BE OVERRIDDEN AND SHOW THE SNVT
NAME AND TYPE FOR EACH.
ALARMS COLUMNS:
1) ALARM CONDITION COLUMN: FOR EACH POINT WITH AN ENTRY IN THIS COLUMN PROVIDE A SNVT OUTPUT FOR THE POINT AND SHOW THE SNVT NAME AND SNVT TYPE IN THE SNVT NAME AND SNVT TYPE COLUMNS UNDER LDP AND M & C DISPLAY. SEE "SNVT TYPE COLUMN"INSTRUCTIONS ABOVE.
OTHER:
EMERGENCY STOP BUTTON: IF EMERGENCY STOP BUTTON (EMR-SS) IS PUSHED THE FOLLOWING
HVAC EQUIPMENT MUST BE DISABLED: AHU-1 AND AHU-2. WITH EMERGENCY STOP BUTTON
DEPRESSED ALL EQUIPMENT LISTED MUST BE DISABLED AND OUTSIDE AIR DAMPERS IN THE CLOSED POSITION. THEN WHEN THE EMERGENCY STOP BUTTON IS PULLED OUT TO THE NORMAL POSITION (EMR-RST-BUT) ALL DISABLED HVAC EQUIPMENT SHALL AUTOMATICALLY START-UP SUBJECT TO
EQUIPMENT PROOFS AND SAFETIES.
2) SYSTEM RESET BUTTON (RST-BUT): IF THE "I/O TYPE" COLUMN CONTAINS "BI", THE SYSTEM SHALL BE
CAPABLE OF BEING RESET VIA A LOCAL HARDWARE PUSH-BUTTON.
IF THERE IS AN "X" IN THE LDP OVRD REQ'D OR M & C OVRD REQ'D COLUMN, THE SYSTEM SHALL ALSO BE CAPABLE OF BEING RESET VIA SNVT INPUT (SEE INSTRUCTIONS FOR M & C OVRD REQ'D AND LDP OVRD
REQ'D COLUMNS)
3) SYSTEM OCCUPANCY (SYS-OCC): SHOW OCC, UNOCC, WUCD (WARM-UP/COOL-DOWN) IN THE RANGE COLUMN BASED ON THE SYSTEM-SPECIFIC SEQUENCE OF OPERATIONS AND OCCUPANCY SCHEDULE.
4) MINIMUM OUTSIDE AIR (MINOA) FLOW: FOR SYSTEMS CONTROLLING TO A MINOA SETPOINT, USE THE
MINOA-F-SP SHOWN WHEN CONFIGURING THE DDC HARDWARE PERFORMING THE SEQUENCE OF
OPERATION. FOR OTHER SYSTEMS SET THE MINIMUM OUTSIDE AIR FLOW TO THE MINIMUM OUTSIDE
AIR FLOW SETTING SHOWN AS SPECIFIED.
5) PID LOOP SETTINGS: SHOW ALL PID LOOP SETTINGS IN THE SETTINGS COLUMN, INCLUDING
ENGINEERING UNITS FOR EACH SETTING. ADJUST ROW HEIGHT AS NEEDED TO SHOW ALL PID
SETTINGS.
6) FILTERS: WHEN FILTER PRESSURES ARE SHOWN, INSTALL FILTER PRESSURE SWITCHES. SHOW
LOADED FILTER (HIGH-LIMIT) SETPOINT FOR EACH FILTER.
OTHER POINTS: INSTALL SENSORS FOR MONITORING PURPOSES ONLY.
1)
SHEET
NUMBER
D ra w n by
D es ig ne d by
Su bm itt ed b y:
Sh ee t S iz e
AN
SI
D
D at e:
C on tra ct
N o.
So lic ita tio n N o.
U .S
. A R
M Y
EN
G
IN
EE
R C
O R
PS
O
F
EG
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T
FO
R
T W
O R
TH
, T
EX
AS
C he ck ed b y:
US Army Corps of Engineers ®
A
R ev
M ar k D es cr ip tio n Tr ac ki ng N o.
Ac tio n
D at e
EN
G
IN
EE
R
IN
G
C O
N
ST
R U
C
TI
O N
D
IV
IS
IO
N
EN
G
IN
EE
R
IN
G
B R
AN
C
H
PLOT DATE:
2 3 4 5 6 7 8 9 10
B
C
D
E
F
G
Fort Worth District
FILE PATH:
4/25/2019 8:00:25 AM
FO
R
T H
O O
D , T
X
AD
M
IN
IS
TR
AT
IO
N B
U
IL
D
IN
G B
NO
RT
H
FO
RT
H
O O
D
PN
: N H
P
AP
R
IL
E.
B
R O
O
KS
E.
B
R O
O
KS
G
IL
BE
R
T J.
V
AL
LA
, P
.E
C H
IE
F, M
EC
H
AN
IC
AL
S
EC
TI
O
N
MI002
PO
IN
TS
L
IS
T
IN
ST
RU
CT
IO
NS
K.
W
IL
LI
AM
S
P.
DX
SA-SMK
FLT-P-HL
FAN VFD
SAFETY
CIRCUIT
TO:
DDC-##
FILTER VFD
TsM
TO: DDC TO: DDC TO: DDC
COOLING 78 DEG F OCCUPIED
COOLING 85 DEG F UNOCCUPIED
HEATING 70 DEG F OCCUPIED
HEATING 55 DEG F UNOCCUPIED
SUPPLY AIR
RETURN AIR
MA-T
TO: DDC
PACKAGED AIR HANDLING UNIT
HVAC CONTROLS (AHU-1 & 2)
H L
DDC
DDC
TO: DDC-##
DDC
RST- BUT OA - T
OCCUPANCY SCHEDULE
WARM-UPUNOCCUPIED
OTHERWISE
OCCUPIEDUNOCCUPIED
OTHERWISE
OCCUPIEDSYSTEM
SYSTEM DEFAULT
SCHEDULE
SUPERVISORY MONITORING &
CONTROL SCHEDULE
# OCC
SENSORS TO
PUT AHU IN
OCC MODE
M-F 0800-1800
M-F 0530-1900
M-F 0700-0800
EMR-SS
AHU-1 & 2
TO:
DDC-##
OA-D
RA-D
SYS-OCC
AHU SEQUENCE OF OPERATION:
OCCUPIED, AND UNOCCUPIED MODES OF OPERATION
THE DDC SYSTEM SHALL PROVIDE THE FOLLOWING MODES OF OPERATION: OCCUPIED, AND UNOCCUPIED .
THESE MODE SEQUENCES ARE DESCRIBED IN THE SEQUENCE OF OPERATION BELOW.
UNOCCUPIED MODE - THE RTU (PACKAGED AIR HANDLING UNIT) NOT RUN, OUTSIDE AIR AND EXHAUST AIR DAMPERS SHALL REMAIN CLOSED. MIXED AIR DAMPER SHALL OPEN UNIT AND SHALL PERFORM NIGHT SET
BACK OPERATION DUTY AS SCHEDULED.
OCCUPIED MODE - THE DDC CONTROLLER SHALL OPERATE THE RTU SUPPLY FAN.
DX COOLING COIL
UNIT SHALL MAINTAIN A DISCHARGE DRY BULB POINT TEMPERATURE OF 55 DEG F (ADJUSTABLE) WHEN IN
COOLING MODE.
DX COOLING ALARM CONDITION
AN ALARM SHALL BE GENERATED AT THE DDC PANEL FOR A HIGH SUPPLY AIR TEMPERATURE IN THE COOLING COIL AIR SUPPLY IS 5 DEG F (ADJ) GREATER THAN THE COIL DISCHARGE SET POINT.
ELECTRIC HEATING
COOLING OPERATION SHALL BE OFF. ELECTRIC HEATING SECTION SHALL BE ACTIVATED. THERMOSTAT
SHALL OPERATE THE HEATING UNIT TO MAINTAIN DAY AND NIGHT SETBACK TEMPERATURES.
HEATING ALARM CONDITION
AN ALARM SHALL BE PROVIDED FOR HIGH SUPPLY AIR IF THE UNITS SUPPLY AIR TEMPERATURE IS 5 DEG F
(ADJ) GREATER THAN THE SUPPLY AIR SET POINT.
FILTER DIFFERENTIAL PRESSURE MONITOR
DDC SYSTEM SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS FILTERS. ALARM SIGNAL
SHALL BE GENERATED WHEN PRESSURE EXCEEDS SETPOINT. (ADJ)
SMOKE CONTROL
ALL MODES - SMOKE DETECTORS IN THE SUPPLY-AIR DUCTWORK SHALL STOP THE SUPPLY FAN AND INITIATE A SMOKE ALARM IF SMOKE IS DETECTED. RESTARTING THE SUPPLY FAN SHALL REQUIRE MANUAL
RESET AT THE SMOKE DETECTOR.
EMERGENCY SHUT DOWN
WHEN THE EMERGENCY STOP BUTTON (EMR-SS) IS…