REQUEST FOR INFORMATION (RFI) LOG

8 September 2020 W50S8120Q0011

Q01 - Will restrooms be available to contracts or do we need to provide our own?

A01 - Temporary restrooms are the responsibility of the contractor. Government furnished facilities will not be available.

Q02 - There is no ceiling height shown at the accordion Door please provide.

A02 - The suspended ceiling height is 9’-2” at the accordion door.

Q03 - Spec section 2.3.1 aside from the finish needing to be fire rated states that the complete assembly must be fire rated. The finish will be class A rated but the system is not rated.

What is the fire rating requirement for the accordion door.

Please note that usually fully fire rated accordion doors are normally special self-closing system connected to the fire alarm similar to Won Door. (I don’t believe this is what you are looking for?)

A03 - The accordion door does not have to be fire rated.

Q04 - Please confirm if taxes should be carried in proposals?

A04 - This project is tax-exempt.

Q05 - Please confirm if any state, local, and/or Federal permits will be required on this project?

A05 – None required.

Q06 - Please confirm if there are any known hazardous materials?

A06 – None known.

Q07 - Please confirm height of Ceilings?

A07 - The suspended ceiling height is 9’-2” at the accordion door.