VA261-17-R-1185-00004016.xlsx

XLSX spreadsheet 16 KB Posted

Attached to
Install Proximity Card Devices Pharmacy, OI&T, Boiler Plant Federal contract opportunity
Solicitation number
VA26117R1185
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 21

About this file

VA261-17-R-1185 00004 C27 - Prox Cards Pharmacy OIT - Door Hardware Requirements Rev1 2017-11-29.xlsx

View the file

Other files for this federal contract opportunity

Other files attached to Install Proximity Card Devices Pharmacy, OI&T, Boiler Plant, newest first.
File Type Posted
36C26118C0025-000.docx DOCX document
VA261-17-R-1185-00005000.docx DOCX document
VA261-17-R-1185-00004013.docx DOCX document
VA261-17-R-1185-00004015.pdf PDF
VA261-17-R-1185-00004017.docx DOCX document
VA261-17-R-1185-00004012.docx DOCX document
VA261-17-R-1185-00004014.docx DOCX document
VA261-17-R-1185-A00002000.docx DOCX document
VA261-17-R-1185-A00001000.docx DOCX document
VA261-17-R-1185-A00001002.pdf PDF
VA261-17-R-1185-A00001001.docx DOCX document
VA261-17-R-1185-010.pdf PDF
VA261-17-R-1185-005.pdf PDF
VA261-17-R-1185-012.pdf PDF
VA261-17-R-1185-004.pptx PPTX presentation
VA261-17-R-1185-001.docx DOCX document
VA261-17-R-1185-009.pdf PDF
VA261-17-R-1185-006.pdf PDF
VA261-17-R-1185-013.pdf PDF
VA261-17-R-1185-003.xlsx XLSX spreadsheet
VA261-17-R-1185-008.pdf PDF
VA261-17-R-1185-007.docx DOCX document
VA261-17-R-1185-011.pdf PDF
VA261-17-R-1185-002.pdf PDF
VA261-17-R-1185-000.docx DOCX document
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Door Schedule

Door IdentifierBldgDoor Type / ConfigurationExisting Access Panel LocationNew Access Panel LocationCard Reader
(RP40-H)Card Reader
(RPK40-H)Card Reader
(RKCLB40)Door Contacts, Embedded
(GE/Sentrol 1078)Door Contacts, Surface-mounted
(GE/Sentrol 2507)Electric Strike
(Von Duprin 6000 Series)Request to Exit Motion Detector
(Bosch DS160)Required Door FunctionalityOther
C13531Single doorC1353-XXXXTo enter: Card reader access + keycode

To exit: Request-to-exit + door handle C2355-A 1 Single door C2355-A - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle C3355 1 Single door C3355 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle C4355 1 Single door C4355 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle C5355 1 Single door C5355 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle

C63591Single doorC5355-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleChanged access panel in Revision 1
K17785Single doorK1778-XXXXTo enter: Card reader access + keycode

To exit: Request-to-exit + door handle K2784-A 5 Single door - K2784A X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle F1479 6 Single door F1479 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle F2476 6 Single door - F2476 X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle

N2107Double doors, manualN215-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemoved from scope in Revision 1
N2217Single doorN215-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemoved from scope in Revision 1
N1018Single doorN215-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemoved from scope in Revision 1
N1058Double doors, manualN215-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemoved from scope in Revision 1
N1068Single doorN215-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemoved from scope in Revision 1
L085710Double doors, manualL0873-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H

L087210Single doorL0873-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H

L087310Single doorL0873-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H L1874 10 Single door L1874 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle L1908 10 Single door L1908 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle

B116912Single doorB1169-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleNote: This room is being reconfigured in December 2017 to combine 2 rooms into 1. It is assumed the room will be reconfigured prior to the proximity card device being installed. Door hardware will be as shown in the photo.
B226312Single doorC2326-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H

B226412Single doorC2326-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H B4196 12 Single door - B4196 X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle B5196 12 Single door - B5196 X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle B6197 12 Single door - B6197 X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle D2456 1A Single door D2456 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle G1585 1D Single door G1585 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle

G16301DSingle doorG1644-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H G1644 1D Double doors, manual G1644 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle G2592 1D Double doors, manual G2605 - X X X X To enter: Card reader access + keycode To exit: Request-to-exit + door handle

G26051DSingle doorG2605-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H

G2630-A1DSingle doorG2605-XXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
G2630-B1DSingle doorG2605-XXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
G26341DSingle doorG2605-XXXTo enter: Card reader access + keycode + biometric
To exit: Request-to-exit + door handle1. Card reader for inner door (metal grate) security door - no change to outer vault door

2. Abandon in place existing scramble pad G2635 1D Single door G2605 - X X X To enter: Card reader access + keycode + biometric To exit: Request-to-exit + door handle

G26561DSingle doorG2605-XXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
G36141DSingle door-G3614XXXXTo enter: Card reader access + keycode

To exit: Request-to-exit + door handle

H16691D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
H1671-A1D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode + biometric
To exit: Request-to-exit + door handle1. Card reader for inner door (metal grate) security door - no change to outer vault door

2. Abandon in place existing scramble pad

H1671-B1D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode + biometric
To exit: Request-to-exit + door handle1. Card reader for metal grate security door

2. Abandon in place existing scramble pad

H1671-C1D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode + biometric
To exit: Request-to-exit + door handle1. Door is 1/2 sized door

2. Abandon in place existing scramble pad

H1683-A1D-
MRI wingDouble doors, manualH1703-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
H1683-B1D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
H1683-C1D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
H16861D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleAbandon in place existing scramble pad
H17031D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode

To exit: Request-to-exit + door handle

H1C011D-
MRI wingSingle doorH1703-XXXXTo enter: Card reader access + keycode

To exit: Request-to-exit + door handle

H26761D-
MRI wingSingle doorH3706-XXXXTo enter: Card reader access
To exit: Request-to-exit + door handleAdded to scope in Revision 1
H27031D-
MRI wingSingle doorH3706-XXXXTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleChanged access panel in Revision 1
H37061D-
MRI wingSingle doorH3706-XTo enter: Card reader access + keycode
To exit: Request-to-exit + door handleRemove and turn over to VA: RP40-H

Install new: RPK40-H VA261-17-R-1185 Amendment 0004 dtd 11/29/2017