Tab 4 SOW.pdf

PDF 493 KB Posted

Attached to
Purchase of two (2) new Motor Control Centers (MCC) Federal contract opportunity
Solicitation number
80NSSC855977Q
Issued by
National Aeronautics and Space Administration Shared Services Center

About this file

This statement of work outlines the technical requirements for two new motor control centers to be installed at the A-Complex Test Control Center. The objective of this procurement is to acquire two NEMA 1 gasketed MCCs with class 1B wiring at 480V, 3-phase service. MCC1 will have an 800A copper main horizontal bus and MCC2/MCC3 will have a 600A copper main horizontal bus. Both MCCs must meet the detailed specifications and bill of materials provided, including main breakers, branch circuit breakers, starters, auxiliary contacts, overload relays, and additional components. The place of performance is Stennis Space Center, Mississippi and the period of performance is 60 weeks from contract award.

The related federal contract opportunity is solicitation number 80NSSC855977Q for the purchase of two new motor control centers from the National Aeronautics and Space Administration Shared Services Center.

View the file

Other files for this federal contract opportunity

Other files attached to Purchase of two (2) new Motor Control Centers (MCC), newest first.
File Type Posted
Tab 12 EMI 3420-22007.pdf PDF
Tab 12 200GC-GE02 FINAL REV 0 (2) (1).pdf PDF
Tab 12 RFQ 80NSSC855977Q Full and Open.pdf PDF
Tab 4 SOW Revised.pdf PDF
Tab 12 RFQ 80NSSC855977Q.pdf PDF
Tab 12 Brand Name Justification.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATEMENT OF WORK (SOW)

1. Objective/Requirements The objective this procurement is to acquire two new Motor Control Centers (MCC) for the A-Complex Test Control Center (ATCC).

2. Characteristics, Scope, and Specs

The two MCC’s shall be in accordance with the bill of materials indicated by designations MCC 1 and

MCC2/MCC3.

Item No. Qty Product Description 1 Motor Control

Centers 60 Hz, Class 1B wiring, 480V 3-Phase Service, 65,000 Bracing, Short Circuit Rating, Top Incoming, NEMA 1 Gasketed 21" Front Mt Only enclosure, 800A Copper Main Horizontal Bus, ANeutral, Main Breaker. Used X-Space: 24, Blank X-Space: 0, Future X- Space: 0, MCC Lead Time Code: U.

Designation MCC1

Qty List of Materials 1 HFD Main Bkr (225A trip), Lugs: 1-#4-4/0 4 FVNR Starter Size 1 [HMCP] 1 HFD Bkr (150A trip) 4 E125HCompact Bkr (70A trip) 1 E125HCompact Bkr (15A trip) 1 E125HCompact Bkr (60A trip) 1 E125HCompact Bkr (30A trip) 6 N.C. Starter Aux Contacts, Size 1-4 6 N.O. Starter Aux Contacts, Size 1-4 4 Description not available 4 Terminal Block - Latching Pull-Apart, Std.

4 Solid State Overload Relay (Standard C440) 4 Wiremarkers at Each End 4 #16awg, MTW Control Wire 4 C-H Model D7, 300V, 2 Pole Socket Relay 1 Two Circuit Alternator 4 3 Position Selector Switch, E22 (Hand-Off-Auto) 1 12 in. blank relay panel 1 160KA, SPD Standard Features Package, with Circuit Breaker 2 Fire Wall Barriers between each section 2 600A Vertical Bus (Tin-plated cu) 2 600A Copper Full Length Neutral Bus 2 Bottom Vertical Bus Barrier 2 Labyrinth, Isolated/Insulated vertical bus barrier with shutters 2 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 2 65KA Bus Bracing 2 Tin Plated horizontal bus 2 800A Copper Frnt Mtd 21" NEMA 1 Gasketed 1 Install pump alternator in unit 2E

Item No. Qty Product Description 1 Motor Control

Centers 60 Hz, Class 1B wiring, 480V 3-Phase Service, 65,000 Bracing, Short Circuit Rating, Top Incoming, NEMA 1 Gasketed 21" Front Mt Only enclosure, 600A Copper Main Horizontal Bus, No Neutral, Main Breaker. Used X-Space: 65, Blank X-Space: 19, Future X- Space: 0, MCC Lead Time Code: B.

Designation MCC2/MCC3

Qty List of Materials 1 HLD Main Bkr (600A trip), Lugs: 2-#3/0-350Kcmil

10 FVNR Starter Size 1 [HMCP] 12 FVNR Starter Size 2 [HMCP] 3 E125HCompact Bkr (30A trip) 1 E125HCompact Bkr (15A trip) 2 HFD Bkr (60A trip) 3 HFD Bkr (20A trip)

22 100VA Individual CPT, Fused 38 N.O. Starter Aux Contacts, Size 1-4 34 N.C. Starter Aux Contacts, Size 1-4 21 Pilot Light-10250T - LED (Run) 1 Thermal Magnetic Trip

22 Terminal Block - Latching Pull-Apart, Std.

22 Solid State Overload Relay (Standard C440) 22 Wiremarkers at Each End 22 #16awg, MTW Control Wire 9 Pilot Light-10250T - LED (Stopped)

19 3 Pos. Sel. Sw., 10250T (Hand-Off-Auto) 1 160KA, SPD Standard Features Package, with Circuit Breaker 9 12" Door 1 6" Door 7 Fire Wall Barriers between each section 7 600A Vertical Bus (Tin-plated cu) 7 Bottom Vertical Bus Barrier 7 Labyrinth, Isolated/Insulated vertical bus barrier with shutters 7 300A Horiz. Cu Gnd Bus, 1/4" x 1" Bar 7 65KA Bus Bracing 7 Tin Plated horizontal bus 7 600A Copper Frnt Mtd 21" NEMA 1 Gasketed

MCC General Information

MCC General Information Nameplate Size 1" X 2.5" Wiring Diagram Type Eaton Standard Nameplate Color Black / White Letters MCC Quantity Pilot Dev. Model 10250T Standards UL845, NEMA, NEC Ind. Light Type 6v Xfmr Special Codes UL Service Voltage (3 Phase) 480 Structure Schedule Frequency 60 There are 2 structure(s).

System 3PH4W All structures have a 600 A vertical bus.

Witness Testing No Total width of all sections is 40"

Height of all sections is 90" Enclosure Specifications

Total Structures 2 Unit Modifications Type NEMA 1 Gasketed #16awg, MTW Control Wire Depth 21" Front Mt Only Wiremarkers at Each End Height 90" Solid State Overload Relay (Standard C440) Horizontal Wireways 9" High, Top & Bottom Terminal Block - Latching Pull-Apart, Std.

Vertical Wireways 4" Channel Sills No Bottom Plates None 150 Watt Space Heaters No Space Heater Thermostat No Master Terminal Block Location None IBC/CBC Seismic Qualified No ABS Certified No

Bus System Specifications

Main Bus Amps 800 Main Bus Material Copper Main Bus Bar Plating Tin Insulated Horiz. Bus No 1000A/sq in. Cu Bus No Vertical Bus Amps See Structure Schedule Vertical Bus Material Tin Plated Copper Vertical Bus Barrier Labyrinth, Isolated/

Insulated with shutters Bus Bracing 65,000 Ground Bus 300 Ground Bus Location Top Ground Bus Lug Size 1-#6-350Kcmil Ground Bus Lug Type Screw Plug-in 300A Vert. Gnd. Bus No Neutral 600A Neutral Bus Lug Location Incoming Line Neutral Bus Lug Size 1-#6-350Kcmil Neutral Bus Lug Type Screw Horizontal Bus Temperature Rise 65 deg C Bottom Vert. Bus Barrier Yes Vertical Ground Bus No

Incoming Line Termination

Device: HFD Main Bkr (225A trip), Lugs: 1-#4-4/0 Cable Entry Top Splice Kit / Transition None MCC Type Match Up MCC Type Match Up GO# ** None **

MCC Starter Specifications

Wiring Class 1B Control Voltage 120 Control Voltage Src Ind CPT

Notes/Special Instructions

Install pump alternator in unit 2E

.0

5.

Top View

5.41 5.41

17.5 17.5

1F 2F

A

B FVNR S1

C HFD3225

D FVNR S1

E SPD RLY PNL

F

G FVNR S1 70

H 70

J FVNR S1

K 15 HFD3150

L 30 70

M 60 70

20.156 20.078

1.25 1.25

1.25 1 1.25 1

20.156 20.078

Floor View

Unit Nameplate Description Class Starter Size Bkr/Sw Unit

HP/FLA Poles Features Wire Diag. Trip/Clip

1C MCB HFD Main Bkr (225A HFD trip), Lugs: 1-#4-4/ 3P

-#4-4/0 281757.DWF 225

1E 160KA, SPD Standard Features Package, with Circuit Breaker NONE

1G Sanitary Drain Pump FVNR Starter Size 1 F206 1 HMCP 1 N.O. Starter Aux Contacts, Size 1-4

SD-2

[HMCP] 2/3.4 3P 1 N.C. Starter Aux Contacts, Size 1-4 NONE 15 1 Description not available

1 3 Position Selector Switch, E22 (Hand-Off-Auto)

1 C-H Model D7, 300V, 2 Pole Socket Relay

1J Sanitary Drain Pump FVNR Starter Size 1 F206 1 HMCP 1 N.O. Starter Aux Contacts, Size 1-4

SD-1

[HMCP] 2/3.4 3P 1 N.C. Starter Aux Contacts, Size 1-4 NONE 15 1 Description not available

1 3 Position Selector Switch, E22 (Hand-Off-Auto)

1 C-H Model D7, 300V, 2 Pole Socket Relay

1K Spare E125HCompact Bkr E125H (15A trip) 3P

5599A85.DWF 15

1L Hoist E125HCompact Bkr E125H

(30A trip) 3P

5599A85.DWF 30

1M Lift Station #17 E125HCompact Bkr E125H (60A trip) 3P

5599A85.DWF 60

2B Drainage Pump DP-1 FVNR Starter Size 1 F206 1 HMCP 2 N.O. Starter Aux Contacts, Size 1-4

[HMCP] 2/3.4 3P 2 N.C. Starter Aux Contacts, Size 1-4 NONE 15 1 Description not available

1 3 Position Selector Switch, E22 (Hand-Off-Auto)

1 C-H Model D7, 300V, 2 Pole Socket Relay

2D Drainage Pump DP-2 FVNR Starter Size 1 F206 1 HMCP 2 N.O. Starter Aux Contacts, Size 1-4 [HMCP] 2/3.4 3P 2 N.C. Starter Aux Contacts, Size 1-4

NONE 15 1 Description not available 1 3 Position Selector Switch, E22

(Hand-Off-Auto) 1 C-H Model D7, 300V, 2 Pole Socket

Relay 2F Alternator 12 in. blank relay 1 Two Circuit Alternator panel

NONE

2G receptacles North East E125HCompact Bkr E125H (70A trip) 3P

5599A85.DWF 70

2H Receptacles North West E125HCompact Bkr E125H

(70A trip) 3P

5599A85.DWF 70

2K LH2 75KVA Transformer HFD Bkr (150A trip) HFD 3P

5599A85.DWF 150

2L Receptacles Mech Rm E125HCompact Bkr E125H

(70A trip) 3P

Wire Diag. Trip/Clip

5599A85.DWF 70

2M Receptacles South East E125HCompact Bkr E125H

(70A trip) 3P

5599A85.DWF 70

MCC General Information

MCC General Information Ind. Light Type 6v Xfmr Wiring Diagram Type Eaton Standard PL Color (On) Red MCC Quantity PL Color (Off) Green Standards UL845, NEMA, NEC Special Codes UL Structure Schedule Service Voltage (3 Phase) 480 There are 7 structure(s).

Frequency 60 All structures have a 600 A vertical bus.

System 3PH3W Total width of all sections is 140" Witness Testing No Height of all sections is 90"

Enclosure Specifications Unit Modifications

Total Structures 7 #16awg, MTW Control Wire Type NEMA 1 Gasketed Wiremarkers at Each End Depth 21" Front Mt Only Solid State Overload Relay (Standard C440) Height 90" Terminal Block - Latching Pull-Apart, Std.

Horizontal Wireways 9" High, Top & Bottom Vertical Wireways 4" Channel Sills No Bottom Plates None 150 Watt Space Heaters No Space Heater Thermostat No Master Terminal Block Location None IBC/CBC Seismic Qualified No ABS Certified No

Bus System Specifications

Main Bus Amps 600 Main Bus Material Copper Main Bus Bar Plating Tin Insulated Horiz. Bus No 1000A/sq in. Cu Bus No Vertical Bus Amps See Structure Schedule Vertical Bus Material Tin Plated Copper Vertical Bus Barrier Labyrinth, Isolated/

Insulated with shutters Bus Bracing 65,000 Ground Bus 300 Ground Bus Location Top Ground Bus Lug Size 1-#6-350Kcmil Ground Bus Lug Type Screw Plug-in 300A Vert. Gnd. Bus No Neutral None Horizontal Bus Temperature Rise 65 deg C Bottom Vert. Bus Barrier Yes Vertical Ground Bus No

Incoming Line Termination

Device: HLD Main Bkr (600A trip), Lugs: 2-#3/0-350Kcmil Cable Entry Top Splice Kit / Transition None MCC Type Match Up MCC Type Match Up GO# ** None **

MCC Starter Specifications

Wiring Class 1B Control Voltage 120 Control Voltage Src Ind CPT Nameplate Size 1" X 2.5" Nameplate Color Black / White Letters Pilot Dev. Model 10250T

.0

.6

Top View

5.41 5.41 5.41 5.41 5.41 5.41 5.41

17.5 17.5 17.5 17.5 17.5 17.5 17.5

1F 2F 3F 4F 5F 6F 7F

A

B HFD3020 HFD3020 FVNR S2 FVNR S1 FVNR S2

C

D FVNR S2 FVNR S2 FVNR S2

E 15 HLD3600

F FVNR S2 FVNR S2

G FVNR S2 FVNR S1

H 30 HFD3060 FVNR S2 FVNR S2 FVNR S1

J 30 HFD3020

K FVNR S1 30 FVNR S1 FVNR S1 FVNR S2 FVNR S1

L SPD

M HFD3060 FVNR S1 FVNR S1 FVNR S2 FVNR S1

20.156 20.078 20.078 20.078 20.078 20.078 20.078

1.25 1.25 1.25 1.25 1.25 1.25 1.25

1.25 1 1.25 1 1.25 1 1.25 1 1.25 1 1.25 1 1.25 1

20.156 20.078 20.078 20.078 20.078 20.078 20.078

Floor View

Wire Diag. Trip/Clip

1B Spare HFD Bkr (20A trip) HFD 3P

5599A85.DWF 20

1D 12" Door 1F 12" Door 1H 12" Door 1K Spare FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

[HMCP] 10 3P 1 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 30 1 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 1M A1 P1 Pump 1 HFD Bkr (60A trip) HFD

Spare 3P

5599A85.DWF 60

2B Spare HFD Bkr (20A trip) HFD 3P

5599A85.DWF 20

2D Cooling Tower Fan 2 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused

[HMCP] 25 3P 2 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 2E Control Valves E125HCompact Bkr E125H

(15A trip) 3P

5599A85.DWF 15

2G Cooling Tower Fan 1 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused [HMCP] 25 3P 2 N.O. Starter Aux Contacts, Size 1-4

265744.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run)

2H Panel T Transformer E125HCompact Bkr E125H (30A trip) 3P

5599A85.DWF 30

2J Basin Heater E125HCompact Bkr E125H

(30A trip) 3P

5599A85.DWF 30

2K Basin Heater E125HCompact Bkr E125H (30A trip) 3P

5599A85.DWF 30

2M 12" Door 3B Spare FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused

[HMCP] 25 3P 1 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 70 1 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 3D 12" Door 3F 12" Door 3H AHU#1 Fan HFD Bkr (60A trip) HFD

3P

5599A85.DWF 60

3K Spare FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused [HMCP] 10 3P 2 N.O. Starter Aux Contacts, Size 1-4

265744.DWF 30 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto)

Wire Diag. Trip/Clip

1 Pilot Light-10250T - LED (Run) 3M Water Heater circulation FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

[HMCP] 1.5 3P 2 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 15 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 4B Air Compressor FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

[HMCP] 3 3P 2 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 15 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 4D 12" Door 4F Condenser WCP P-1 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused

[HMCP] 25 3P 3 N.O. Starter Aux Contacts, Size 1-4 265738.DWF 70 1 N.C. Starter Aux Contacts, Size 1-4

1 Pilot Light-10250T - LED (Run) 4H Condenser WCP P-2 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused

[HMCP] 25 3P 3 N.O. Starter Aux Contacts, Size 1-4 265738.DWF 70 1 N.C. Starter Aux Contacts, Size 1-4

1 Pilot Light-10250T - LED (Run) 4K AHU2 FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

[HMCP] 10 3P 2 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 30 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 4M AHU3 FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

[HMCP] 5 3P 2 N.O. Starter Aux Contacts, Size 1-4 265744.DWF 15 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 5E Main CB HLD Main Bkr (600A HLD 1 Thermal Magnetic Trip trip), Lugs: 2-#3/0- 3P -#3/0-350Kcmil 5599A89.DWF 600

5G Recycle Fan FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused [HMCP] 1 3P 2 N.O. Starter Aux Contacts, Size 1-4

265744.DWF 15 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run)

5J Spare HFD Bkr (20A trip) HFD 3P

5599A85.DWF 20

5L 160KA, SPD Standard

Features Package, with Circuit Breaker NONE

5M 6" Door 6B 12" Door 6D CHWP1 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused

Pump P1 [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4 265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

6F CHWP2 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused

Wire Diag. Trip/Clip

Pump P2 [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4 265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4

1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

6H CHWP7 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4

265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

6K CHWP6 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4

265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

6M CHWP3 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4

265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

7B CHWP4 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4

265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

7D CHWP5 FVNR Starter Size 2 F206 2 HMCP 1 100VA Individual CPT, Fused [HMCP] 20/14 3P 2 N.O. Starter Aux Contacts, Size 1-4

265745.DWF 70 2 N.C. Starter Aux Contacts, Size 1-4 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

7F 12" Door 7H A1 Hot Water FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

Pump P1 [HMCP] 7.5/14 3P 1 3 Pos. Sel. Sw., 10250T (Hand-Off- Auto)

265745.DWF 30 1 Pilot Light-10250T - LED (Run) 1 Pilot Light-10250T - LED (Stopped)

7K A2 Hot Water FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused Pump P2 [HMCP] 7.5/14 3P 1 3 Pos. Sel. Sw., 10250T (Hand-Off-

Auto) 265745.DWF 30 1 Pilot Light-10250T - LED (Stopped)

1 Pilot Light-10250T - LED (Run) 7M 4110 Hot Water FVNR Starter Size 1 F206 1 HMCP 1 100VA Individual CPT, Fused

Pump P3 [HMCP] 5/14 3P

265737.DWF 15

1. Place of Performance Stennis Space Center, MS

2. Period of Performance 60 weeks from contract award.

File details come from the government source that posted it. Updated .