Attachment_2_SOW_B-30_Office_Renovation_06142018_REVISED_2_COMPOSITE_w_Appendix.pdf

PDF 3 MB Posted

Attached to
Renovatation of Office Area Federal contract opportunity
Solicitation number
SP330018B0010
Issued by
Defense Logistics Agency Distribution

About this file

Attachment 2 Statement of Work Office Renovation with Appendixes

View the file

Other files for this federal contract opportunity

Other files attached to Renovatation of Office Area, newest first.
File Type Posted
Bid_Abstract_18B0010_signed.pdf PDF
SOW_B-30_Office_Renovation_08302018_REVISED_with_14_Appendixes.pdf PDF
18B00100001.pdf PDF
Site_Visit_Roster_18B0010.pdf PDF
ATTACHMENT_3-__SF25A_Payment_Bond_Form.pdf PDF
Attachment_1_Construction_Wage_Determination_CA180029_Mod_15_Dated_27July2018.pdf PDF
SP330018B0010_as_posted.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Title: Building 30 Renovate Office Area Location: Building 30, Mezzanine Office Area, Tracy Site, Tracy Ca.

Date: 6/14/2018

STATEMENT OF WORK

1.0 GENERAL REQUIREMENTS

Provide construction services to include all labor, management, supervision, tools, materials, equipment, and transportation to renovate Building 30 Office Area.

1.1 General Description

The scope of work includes but is not limited to the following Renovate B-30 Office Area (see Appendix 1 for items a thru j):

a. Remove three (3) cubicles on the south side of the main area to make room for new office walls.

b. Remove the wall and door located in the Division Chief Office located in the southwest corner of the mezzanine office area. Fill in the ceiling tile gap to provide a clean look for the ceiling after the wall is removed.

c. Construct new office walls and doors to create four (4) new private offices.

d. Install new light switches in the four (4) new private offices.

e. Relocate seven (7) existing light fixtures to provide clearance for the new walls.

f. Install a fire-rated window and wall construction into an existing double door opening (75-1/4” wide x 81-1/2” high). The window and wall construction must meet the design requirements for a 90 minute firewall. The window design can be identical to the new window installation in the Division Chief Office.

g. Relocate existing air vent to provide clearance for the new walls (see Appendix 5 for items g thru i).

h. Install new air vent for the new private office.

i. Split the existing air supply duct to provide ventilation to the new private offices.

j. Install a new LAN Jack in the new private office on the south side wall (see

Appendix 11).

k. Site preparation to paint walls in all rooms requires signs and billboards to be removed from the walls (see Appendix 2 for items k thru m).

l. Paint walls in all rooms with an off white ivory tusk color semi-gloss paint (see

Appendix 6).

m. Replace all signs and billboards on the walls.

n. Site preparation to remove carpet requires the system furniture to be elevated above the floor on wood blocks to access all of the floor area with carpet. This will require the electrical power to be disconnected from the system furniture before the equipment is elevated on the wood blocks (see Appendix 3).

o. Remove Carpet tiles and Vinyl Cove Base (see Appendix 3 & 4).

p. Install New Carpet Tile (Color – Charcoal, see Appendix 7).

SP330018B0010

Attachment 2

q. Install new Vinyl Cove Base (Burke Flooring, 0.080” thick, 4” height, Color - Black #701, see Appendix 8).

r. UFC Paint Specification is provided in Appendix 9.

s. UFC Carpet Specification is provided in Appendix 10.

1.2 Submittals

Submittals are required for all material to be utilized and/or installed and shall be in compliance with the Unified Facilities Guide Specifications (UFGS), and the basic contract. All submittals shall be approved prior to commencement of work.

Submittals shall include but not limited to the following:

a. Task specific: Quality Control Plan, Hazard Analysis, and Safety/Health Plan.

b. Construction schedule and Phasing Plan.

c. Manufacturer’s data for suspended ceiling system, carpet floor tiles, cove base, doors and hardware, diffusers, registers, grilles, and cable.

d. As-built drawings.

1.3 Project Schedule and Time Constraints

Schedule and Completion of Work The contractor is required to prosecute the work diligently and complete the entire work, ready for use no later than 180 calendar days after the award/NTP of the task order. The time stated for completion shall include final clean-up of the premises.

Liquidated Damages The liquidated damages for this task order are $ 0.00 per calendar day.

Preconstruction Meeting Prior to the initiation of work, a meeting will be held with the contractor, Depot PM/PE and COR/Inspector to discuss matters of mutual interest concerning the task order. General conditions, work schedule, phasing, and coordination, security, safety, permits, and other matters pertinent to work accomplishments will be discussed in this meeting.

1.4 Point of Contact (POC)

DEPOT: Norm Dalsis Project Engineer (209) 839-4086

Doug Betz COR/Inspector (209) 839-4232

2 WAGE DETERMINATION

Refer to Davis-Bacon and Related Acts. General Decision No. CA180029, see Attachment 1 and referenced decision modifications, are hereby applicable to work performed under this task order. Certified Payrolls are required to be submitted with each pay request.

3 TIME EXTENSIONS FOR UNUSUALLY SEVERE WEATHER

Refer to Default (Fixed-Priced Construction). The monthly anticipated adverse weather delay work days for this task order will be provided.

4 AUTHORITIES

No person other than the DLA Contracting Officer has the authority to make any changes to this contract action that impact cost or schedule. Authority from the DLA Contracting Officer to the contractor to make changes that impact cost or schedule will be in the form of an official, signed modification.

Attachments:

1. Appendix 1: B-30 Office Renovation Work Drawing

2. Appendix 2: B-30 Office Paint Walls Drawing

3. Appendix 3: B-30 Office Carpet Tile Drawing

4. Appendix 4: B-30 Office Vinyl Wall Base Drawing

5. Appendix 5: B-30 Office HVAC System Drawing

6. Appendix 6: Paint Product Sheet

7. Appendix 7: Carpet Product Sheet

8. Appendix 8: Vinyl Wall Base Product Sheet

9. Appendix 9: UFC Paint Specification

10. Appendix 10: UFC Carpet Specification

11. Appendix 11: LAN Specification

END OF RFP DESCRIPTION

TJC0219

Text Box

APPENDIX 1

APPENDIX 2

Typewritten Text

APPENDIX 3

APPENDIX 4

APPENDIX 5

TJC0219

B-30 OFFICE HVAC SYSTEM

APPENDIX 5

TJC0219

B-30 OFFICE HVAC SYSTEM

Benjamin Moore & Co., 101 Paragon Drive, Montvale, NJ 07645 Tel: (201) 573-9600 Fax: (201) 573-9046 www.benjaminmoore.com M72 551 US 111817

REGAL® SELECT

PREMIUM INTERIOR PAINT & PRIMER

SEMI-GLOSS 551

Features General Description Excellent hide Excellent durability Zero VOC, low odor Self-priming on most substrates

Provides a mildew resistant coating

Spatter resistant Premium flow and leveling Easy application

A premium quality, easy to use, durable, washable, and scrubable finish. Beautiful finish for trim and accents. Ideal for surfaces subject to abuse and soil such as corridors, stairwells, cafeterias, locker rooms, laboratories, etc. Easy to apply by brush, roller, or spray gun. Excellent hiding and leveling properties. Self-priming on most substrates

Recommended For Limitations Ideal for interior trim, doors, cabinets, walls, and new or coated acoustic ceilings. For new or previously painted wallboard, plaster, masonry, and primed or previously painted wood and metal

Do not apply when air and surface temperatures are below 50 °F (10 °C)

Product Information Colors — Standard:

White (01), Super White (02), Decorators White (04), White Dove (06), Linen White (70)

Technical Data Pastel Base Vehicle Type Proprietary 100% Acrylic Latex

Pigment Type Titanium Dioxide

Volume Solids 39.9%

Coverage per Gallon at Recommended Film Thickness 400 – 450 Sq. Ft.

Recommended Film Thickness

– Wet 3.8 mils

– Dry 1.5 mils

Depending on surface texture and porosity. Be sure to estimate the right amount of paint for the job. This will ensure color uniformity and minimize the disposal of excess paint.

Dry Time @ 77 °F

(25 °C) @ 50% RH

– To Touch 1 Hour

– To Recoat 3 Hours

Painted surfaces can be washed after two weeks. High humidity and cool temperatures will result in longer dry, recoat and service times.

Dries By Evaporation, Coalescence

Viscosity 99 ± 2 KU

Flash Point None

Gloss / Sheen Semi Gloss (50 – 60 @ 60°)

Surface Temperature at Application

– Min. 50 °F

– Max. 90 °F

Thin With See Chart

Clean Up Thinner Clean Water

Weight Per Gallon 10.9 lbs

Storage Temperature

– Min. 40 °F

– Max. 90 °F

Volatile Organic Compounds (VOC)

0 g/L

Zero VOC post tint (any base and any color)

— Tint Bases:

Benjamin Moore® Gennex® Bases 1X, 2X, 3X, & 4X

— Special Colors:

Contact your Benjamin Moore representative.

Certifications & Qualifications:

VOC compliant in all regulated areas

Zero VOC according to EPA Method 24 Class A (0-25) over non-combustible surfaces when tested in accordance with

ASTM E-84

Master Painter Institute MPI # 54, 54 X-Green™, 141, 141 X-Green™, 147, 147 X-Green™ Anti-microbial - This product contains antimicrobial additives that inhibit the growth of mold and mildew on the surface of the paint film.

YES YES 0 g/L

Benjamin Moore's Green Promise® designation is our company’s assurance that this product meets – and often exceeds – rigorous environmental and performance criteria regarding VOCs, emissions, application, washability, scrubbability and packaging, while also delivering the premium levels of performance you expect from Benjamin Moore.

Qualifies for

LEED v4 Credit

Qualifies for CHPS low emitting credit

(Collaborative for High Performance Schools)

VOC (in any color)

This Benjamin Moore product has been tested by independent third parties and meets or exceeds the published chemical restriction and performance criteria of the Green Seal™ GS-11 2015 standard

YES

CDPH v1

Emission Certified

Technical Assistance:

Available through your local authorized independent Benjamin Moore® retailer.

For the location of the retailer nearest you, call 1-866-708-9180, see www.benjaminmoore.com, or consult your local Yellow Pages.

◊Reported values are for Pastel Base. Contact Benjamin Moore for values of other bases or colors.

http://www.benjaminmoore.com/ http://www.benjaminmoore.com/

TJC0219

Typewritten Text

APPENDIX 6

TJC0219

PAINT PRODUCT SHEET

Regal® Select Premium Interior Paint & Primer, Semi-Gloss (551)

Benjamin Moore & Co., 101 Paragon Drive, Montvale, NJ 07645 Tel: (201) 573-9600 Fax: (201) 573-9046 www.benjaminmoore.com M72 551 US 111817 Benjamin Moore, Fresh Start, Gennex, Green Promise, Regal, Super Spec HP, Ultra Spec and the triangle “M” symbol are registered trademarks licensed to Benjamin Moore & Co. All other marks are the property of their respective owner. This product is not endorsed by or a division of CHPS. This product is provided by Benjamin Moore, not CHPS. © 2014, 2017 Benjamin Moore & Co. All rights reserved

Surface Preparation Surfaces to be painted must be clean, dry, and free of dirt, dust, grease, oil, soap, wax, scaling paint, water soluble materials and mildew. Remove any peeling or scaling paint, and sand these areas to feather edges smooth with adjacent surfaces. Glossy areas should be dulled. Drywall surfaces must be free of sanding dust. Spot prime before and after filling nail holes, cracks, and other surface imperfections.

New plaster or masonry surfaces must be allowed to cure (30 days) before applying base coat. Cured plaster should be hard, have a slight sheen and maximum pH of 10; soft, porous or powdery plaster indicates improper cure.

Never sand a plaster surface; knife off any protrusions and prime plaster before and after applying patching compound. Poured or pre-cast concrete with a very smooth surface should be etched or abraded to promote adhesion, after removing all form release agents and curing compounds.

Remove any powder or loose particles.

Difficult Substrates: Benjamin Moore offers a number of specialty primers for use over difficult substrates such as bleeding woods, grease stains, crayon markings, hard glossy surfaces, galvanized metal, or other substrates where paint adhesion or stain suppression is a particular problem. Your Benjamin Moore® retailer can recommend the right problem-solving primer for your special needs.

WARNING! If you scrape, sand or remove old paint, you may release lead dust.

LEAD IS TOXIC. EXPOSURE TO LEAD DUST CAN CAUSE SERIOUS

ILLNESS, SUCH AS BRAIN DAMAGE, ESPECIALLY IN CHILDREN.

PREGNANT WOMEN SHOULD ALSO AVOID EXPOSURE. Wear a NIOSH-approved respirator to control lead exposure. Carefully clean up with a HEPA vacuum and a wet mop. Before you start, find out how to protect yourself and your family by contacting the National Lead Information Hotline at 1-800-424- LEAD or log on to www.epa.gov/lead.

Primer/Finish Systems Regal Select is self-priming on most surfaces. On bare substrates two coats are required; previously painted surfaces can be finished with 1 or 2 coats. While the high quality of our products sometimes makes one-coat coverage achievable, Benjamin Moore recommends two coats of this product to achieve full color development and to maximize paint film performance. Special Note: Certain deep custom colors may require a Deep Base Primer tinted to a special prescription formula to achieve the desired color. Consult your retailer.

Wood and Engineered Wood Products:

Primer: Fresh Start® Multi-Purpose Latex Primer (N023) or Fresh Start® High-Hiding All Purpose Primer (046) Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi- Gloss (551) Bleeding Type Woods, (Redwood and Cedar):

Primer: Fresh Start® Multi-Purpose Oil Based Primer (024) or 1-2 coats of Fresh Start® High-Hiding All Purpose Primer (046) Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi- Gloss (551) Drywall:

Primer/Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi-Gloss (551) Plaster:

Primer/Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi-Gloss (551) Rough or Pitted Masonry:

Primer: Ultra Spec® Masonry Interior/Exterior Hi-Build Block Filler (571) Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi- Gloss (551) Smooth Poured or Precast Concrete:

Primer/Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi-Gloss (551) Ferrous Metal (Steel and Iron):

Primer: Ultra Spec® HP Acrylic Metal Primer (HP04) or Super Spec HP® Alkyd Metal Primer (P06) Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi- Gloss (551) Non-Ferrous Metal (Galvanized & Aluminum):

All new metal surfaces must be thoroughly cleaned with Oil & Grease Emulsifier Corotech® V600 to remove contaminants. New shiny non-ferrous metal surfaces that will be subject to abrasion should be dulled with very fine sandpaper or a synthetic steel wool pad to promote adhesion.

Primer/Finish: 1 or 2 coats Regal® Select Premium Interior Paint & Primer, Semi-Gloss (551) Repaint, All Substrates: Prime bare areas with the primer recommended for the substrate above.

Application Mixing of Paint: Stir thoroughly before and during use. Apply one or two coats. For best results, use a premium Benjamin Moore® custom-blended nylon/polyester brush, premium Benjamin Moore® roller, or a similar product. Apply paint generously from unpainted area into wet area. This product can also be sprayed.

Thinning/Clean Up

Thinning is unnecessary, but if required to obtain desired application properties, a small amount of clean water may be added. Never add other paints or solvents. Wash painting tools in warm soapy water immediately after use. Spray equipment should be given a final rinse with mineral spirits to prevent rusting or follow state/local guidelines on solvent use.

USE COMPLETELY OR DISPOSE OF PROPERLY. Dry, empty containers may be recycled in a can recycling program. Local disposal requirements vary; consult your sanitation department or state-designated environmental agency on disposal options.

Environmental Health & Safety Information Use only with adequate ventilation. Do not breathe spray mist or sanding dust. Ensure fresh air entry during application and drying.

Avoid contact with eyes and prolonged or repeated contact with skin. Avoid exposure to dust and spray mist by wearing a NIOSH approved respirator during application, sanding and clean up.

Follow respirator manufacturer’s directions for respirator use.

Close container after each use. Wash thoroughly after handling.

WARNING: This product contains a chemical known to the state of California to cause cancer and birth defects, or other reproductive harm.

FIRST AID: In case of eye contact, flush immediately with plenty of water for at least 15 minutes; for skin, wash thoroughly with soap and water. If symptoms persist, seek medical attention. If you experience difficulty breathing, leave the area to obtain fresh air. If continued difficulty is experienced, get medical attention immediately.

IN CASE OF SPILL – Absorb with inert material and dispose of as specified under Thinning/Clean up.

KEEP OUT OF REACH OF CHILDREN

PROTECT FROM FREEZING

Refer to Safety Data Sheet for additional health and safety information.

Conditioning with Benjamin Moore® 518 Extender may be necessary under certain conditions to adjust open time or spray characteristics.

The chart below is for general guidance Mild conditions Severe conditions

Humid (RH> 50%) with no direct sunlight & with little to no wind

Dry (RH<50%), in direct sunlight, or windy conditions Brush:

Nylon / Polyester

No thinning necessary

Add 518 Extender or water:

Max of 8 fl. oz. to a gallon of paint

Never add other paints or solvents.

Roller:

Premium Quality 3/8" roller cover

Spray: Airless Pressure:

1500 -2500 psi Tip: 0. .011 - .015 http://www.benjaminmoore.com/ http://www.epa.gov/lead

RAL 1000 49/15200 RAL 1019 49/13660 • 38/15019 RAL 2008 49/24340 RAL 3014 49/31080 RAL 4008 49/32280 RAL 5014 49/42320

RAL 1001 49/15190 • 38/15001 RAL 1020 49/22500 • 38/20020 RAL 2009 49/24360 RAL 3015 49/33670 RAL 4009 49/34740 RAL 5015 49/42330

RAL 1002 49/22590 • 38/20002 RAL 1021 49/22280 RAL 2010 49/24520 RAL 3016 49/31980 RAL 4010 49/40490 RAL 5017 49/40760 • 38/40017

RAL 1003 49/22580 RAL 1023 49/22490 • 38/20023 RAL 2011 49/24580 RAL 3017 49/31060 RAL 5000 49/42200 RAL 5018 49/41140 • 38/40020

RAL 1005 49/22560 RAL 1027 49/22470 RAL 3000 49/33120 RAL 3020 49/31040 RAL 5002 49/42220 RAL 5020 49/44270 • 38/40018

RAL 1006 49/22550 RAL 1028 49/22460 RAL 3001 49/31120 RAL 3022 49/33700 RAL 5003 49/42230 RAL 5021 49/41190 • 38/40021

RAL 1011 49/15180 RAL 1033 49/22240 RAL 3003 49/31100 RAL 3031 49/34730 RAL 5005 49/43190 RAL 5023 49/44650

RAL 1004 49/22570 RAL 1024 49/22480 • 38/20024 RAL 2012 49/24690 RAL 3018 49/31050 RAL 5001 49/42210 RAL 5019 49/42360 • 38/40019

RAL 1007 49/22540 RAL 1032 49/22450 RAL 3002 49/31110 RAL 3027 49/33660 RAL 5004 49/42240 • 38/40004 RAL 5022 49/42390

RAL 1012 49/22530 RAL 1034 49/23910 RAL 3004 49/33900 RAL 4001 49/43160 RAL 5007 49/42250 • 38/40007 RAL 5024 49/44660

RAL 1013 49/11280 • 38/10013 RAL 1037 49/20096 RAL 3005 49/31900 RAL 4002 49/31030 RAL 5008 49/42260 • 38/40008 RAL 6000 49/53160 • 38/50000

RAL 1014 49/15170 • 38/15014 RAL 2000 49/24570 RAL 3007 49/31910 RAL 4003 49/32270 RAL 5009 49/42270 RAL 6001 49/52900 • 38/50005

RAL 1015 49/15320 • 38/15015 RAL 2001 49/24560 RAL 3009 49/31920 RAL 4004 49/31020 RAL 5010 49/42280 RAL 6002 49/52890

RAL 1016 49/22520 • 38/20016 RAL 2002 49/24550 RAL 3011 49/31090 RAL 4005 49/42780 RAL 5011 49/43180 • 38/40011 RAL 6003 49/52880 • 38/50003

RAL 1017 49/22510 RAL 2003 49/24540 RAL 3012 49/31940 • 38/30012 RAL 4006 49/32090 RAL 5012 49/43170 RAL 6004 49/50980 • 38/50004

RAL 1018 49/21830 RAL 2004 49/24530 RAL 3013 49/31950 RAL 4007 49/32540 RAL 5013 49/42310 • 38/40013 RAL 6005 49/50670 • 38/50002

RAL 6006 49/52870 • 38/50006 RAL 6022 49/52690 • 38/50022 RAL 7006 49/72580 • 38/70006 RAL 7030 49/72890 • 38/70027 RAL 7045 49/77890 • 38/70045 RAL 8019 49/65490 • 38/60019

RAL 6007 49/52860 • 38/50007 RAL 6024 49/52680 RAL 7008 49/72570 RAL 7031 49/72520 • 38/70031 RAL 7046 49/72010 • 38/70002 RAL 8022 49/63080 • 38/60022

RAL 6008 49/53240 • 38/50008 RAL 6025 49/52670 RAL 7009 49/72770 • 38/70009 RAL 7032 49/72910 • 38/70001 RAL 7047 49/72020 • 38/70047 RAL 8023 49/66070 • 38/60023

RAL 6009 49/52840 • 38/50009 RAL 6026 49/52660 • 38/50026 RAL 7010 49/72560 • 38/70014 RAL 7033 49/72510 • 38/70033 RAL 8000 49/66170 RAL 8024 49/66060 • 38/60024

RAL 6011 49/52820 • 38/50011 RAL 6028 49/52650 • 38/50028 RAL 7012 49/71180 • 38/70012 RAL 7035 49/73510 • 38/70035 RAL 8002 49/66150 • 38/60002 RAL 8028 49/66500 • 38/60028

RAL 6012 49/51540 • 38/50012 RAL 6029 49/52640 • 38/50029 RAL 7013 49/72550 • 38/70013 RAL 7036 49/72950 • 38/70036 RAL 8003 49/66140 • 38/60003 RAL 9001 49/10016 • 38/10001

RAL 6014 49/52800 RAL 6033 49/55010 • 38/50033 RAL 7016 49/72830 • 38/70016 RAL 7038 49/72470 • 38/70038 RAL 8007 49/66120 • 38/60007 RAL 9003 49/11400 • 38/10003

RAL 6010 49/52830 • 38/50031 RAL 6027 49/50990 • 38/50027 RAL 7011 49/72790 • 38/70011 RAL 7034 49/72500 RAL 8001 49/66160 • 38/60005 RAL 8025 49/66050 • 38/60025

RAL 6013 49/52810 • 38/50013 RAL 6032 49/52630 • 38/50032 RAL 7015 49/72820 • 38/70015 RAL 7037 49/72480 • 38/70037 RAL 8004 49/66130 • 38/60004 RAL 9002 49/70520 • 38/10002

RAL 6015 49/52790 RAL 6034 49/55020 • 38/50034 RAL 7021 49/72540 • 38/70021 RAL 7039 49/71020 • 38/70039 RAL 8008 49/66110 • 38/60008 RAL 9004 49/81950 • 38/80004

RAL 6016 49/51020 • 38/50016 RAL 7000 49/72700 • 38/70000 RAL 7022 49/72850 • 38/70022 RAL 7040 49/75470 • 38/70046 RAL 8011 49/66100 • 38/60011 RAL 9005 49/82830 • 38/80010

RAL 6017 49/52780 • 38/50017 RAL 7001 49/72710 RAL 7023 49/72530 • 38/70023 RAL 7042 49/73250 • 38/70042 RAL 8012 49/66090 • 38/60012 RAL 9010 49/11500 • 38/10004

RAL 6018 49/52720 • 38/50018 RAL 7002 49/72720 • 38/70007 RAL 7024 49/72870 • 38/70024 RAL 7043 49/72460 • 38/70043 RAL 8014 49/65230 • 38/60010 RAL 9011 49/80540

RAL 6019 49/51000 • 38/50019 RAL 7003 49/72600 RAL 7026 49/72880 • 38/70026 RAL 7044 49/75480 • 38/70044 RAL 8015 49/63040 RAL 9016 49/11340 • 38/10010

RAL 6020 49/52710 • 38/50020 RAL 7004 49/73300 • 38/70004 RAL 8016 49/66080 • 38/60016 RAL 9017 49/80550 • 38/80017

RAL 6021 49/52700 • 38/50021 RAL 7005 49/72590 • 38/70005 RAL 8017 49/65220 • 38/60017 RAL 9018 49/72490 • 38/10018

Final_Tiger_RALChart_BlankOnBack R2:Final 10/28/11 1:03 PM Page 1

CC

T- G

EN

-1

8-

EN

-0

TJC0219

7039 - QUARTZ GRAY 7044 - SILK GRAY

APPENDIX 7

TJC0219

CARPET PRODUCT SHEET

MERCER® VINYL WALL BASE

TYPE TV

Our Mercer® Vinyl Wall Base gives you years of lasting protection.

It’s available in the 81 standard wall base colors, including the Uni-Color® System of 20 colors, providing an economical way to match the entire line of Burke flooring products, including Tile, Stair Treads, Mouldings, and accessory products. Mercer Vinyl Wall Base performs well around curved walls and corners to give your installation a perfect final touch. Mercer Vinyl Wall Base has a matte finish that coordinates nicely with a variety of patterns and textures in both flooring and carpet. When you’re ready to specify vinyl base, remember the quality and vast product selection of Mercer Vinyl Wall Base.

VINYL

• Engineered for heavy traffic and high maintenance areas

• Scuff and abrasion resistant

• Tough matte finish helps hide substrate irregularities

• Available in .080” and .125” gauges

TECHNICAL DATA

WALL BASE CORNERSPre-formed

Inside and outside corners are manufactured to match all wall base sizes.

Positive top return lip for snug wall fit

C O

V E

B

A S

E

T O

E L

E S

S

B A

S E

Matte finish

.125" thickness

Curves without cracking, wraps around columns or curved walls with ease

Flexible down-angle toe covers irregular floors

Ribbed surface keeps adhesive intact

BENEFITS

Composition: Thermoplastic Vinyl

Applicable Standards:

ASTM F-1861, Type TV, Group 1, Styles A & B

ASTM E-648 Class 1

TYPE & THICKNESS HEIGHT LENGTH COLORS CORNERS

.080” Cove Base 2.5”, 4”, 6” 4’, 100’ rolls 77 OS

.080” Toeless Base 2.5”, 4”, 6” 4’, 100’ rolls 77 OS

1/8” Cove Base 2.5”, 4”, 4.5”, 6” 4’, 100’ rolls 77 OS

1/8” Toeless Base 2.5”, 4”, 6” 4’, 100’ rolls 77 OS

AVAILABLE IN ALL UNI-COLORS

See page 59.

RAW MATERIALS

WITHIN 500 MI

OF PLANT

60%

CUSTOM COLORS AVAILABLE

Minimums apply. Please make final selection for all colors from actual product samples. To order samples go to burkeflooring.com or call

800.447.8442 ext. 1031.

* Not available in BurkeBase Rubber Type TS

302 Williamsburg Blue

504 Pecan

259 Seafoam 210 Jade 519 Baha

545 Straw 407 Peachy Rose

378 Rich Blue 295 Envy Green

205 Cream 350 Wheat 305 Camel 200 Basic Brown

820 Daffodil 479 Orange Crate 301 Red Red 495 Royal Purple

211 Mauve 434 Cherrywood 490 Plumberry

664 Mist 556 Blue Denim 335 Hedge Green

383 Lemon Lime 242 Olive

375 Bay Leaf

170 Bright White 168 Bluish White 137 Pearl 150 Nougat

508 Tweed 517 Honey 514 Savannah 564 Smoke 261 Taupe

503 Ginger 860 Dark Bronze 317 Greige 203 Beige 201 Chocolate 104 Fudge

672 Gray Blue 603 Ash 209 Gray Beige 850 Sterling Gray 727 Thunder

103 Espresso

890 Mushroom 674 Carmine Gray

108 Bronze Metallic

123 Copper Metallic

NEUTRALS

COLORS

METALLICS*

244 Off White

117 Platinum Metallic

401 White*

403 Almond

106 Pearl Luster Metallic

253 Dark Teal

BURKE 51

TJC0219

Typewritten Text

APPENDIX 8

TJC0219

VINYL WALL BASE PRODUCT SHEET

THE UNI-COLOR® SYSTEM

A 20-color integrated color coordination system that encompasses the entire Burke Flooring product line.

Please make final selection for all colors from actual product samples. To order samples go to burkeflooring.com or call

800.447.8442 ext. 1031.

001 Malibu Sand 597 Mocha206 Light Beige

502 Brown

527 Clay

523 Black Brown

509 Nutmeg

701 Black 663 Sky Gray

660 Rocky

505 True Blue

208 Light Gray

506 Tahoe

254 Light Teal

204 Gray 323 Bluebonnet

331 Dark Forest

217 Charcoal

875 Navy 607 Cranberry

BURKE 59

UFGS

USACE / NAVFAC / AFCEC / NASA UFGS-09 90 00 (May 2011) Change 1 - 05/13 Preparing Activity: NAVFAC Superseding UFGS-09 90 00 (August 2010)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated January 2015

SECTION TABLE OF CONTENTS

DIVISION 09 - FINISHES

SECTION 09 90 00

PAINTS AND COATINGS

05/11

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 APPLICATOR'S QUALIFICATIONS

1.3.1 Contractor Qualification

1.3.2 SSPC QP 1 Certification

1.4 QUALITY ASSURANCE

1.4.1 Field Samples and Tests

1.4.1.1 Sampling Procedure

1.4.1.2 Testing Procedure

1.4.2 Textured Wall Coating System

1.4.3 Sample Textured Wall Coating System Mock-Up

1.4.4 Sustainable Design Certification

1.5 REGULATORY REQUIREMENTS

1.5.1 Environmental Protection

1.5.2 Lead Content

1.5.3 Chromate Content

1.5.4 Asbestos Content

1.5.5 Mercury Content

1.5.6 Silica

1.5.7 Human Carcinogens

1.6 PACKAGING, LABELING, AND STORAGE

1.7 SAFETY AND HEALTH

1.7.1 Safety Methods Used During Coating Application

1.7.2 Toxic Materials

1.8 ENVIRONMENTAL CONDITIONS

1.8.1 Coatings

1.8.2 Post-Application

1.9 SUSTAINABLE DESIGN REQUIREMENTS

1.9.1 Local/Regional Materials

1.9.2 Environmental Data

1.10 SCHEDULING

1.11 COLOR SELECTION

1.12 LOCATION AND SURFACE TYPE TO BE PAINTED

SECTION 09 90 00 Page 1

TJC0219

Typewritten Text

APPENDIX 9

TJC0219

UFC PAINT SPECIFICATION

1.12.1 Painting Included

1.12.1.1 Exterior Painting

1.12.1.2 Interior Painting

1.12.2 Painting Excluded

1.12.3 Mechanical and Electrical Painting

1.12.3.1 Fire Extinguishing Sprinkler Systems

1.12.4 Exterior Painting of Site Work Items

1.12.5 MISCELLANEOUS PAINTING

1.12.6 Definitions and Abbreviations

1.12.6.1 Qualification Testing

1.12.6.2 Batch Quality Conformance Testing

1.12.6.3 Coating

1.12.6.4 DFT or dft

1.12.6.5 DSD

1.12.6.6 EPP

1.12.6.7 EXT

1.12.6.8 INT

1.12.6.9 micron / microns

1.12.6.10 mil / mils

1.12.6.11 mm

1.12.6.12 MPI Gloss Levels

1.12.6.13 MPI System Number

1.12.6.14 Paint

1.12.6.15 REX

1.12.6.16 RIN

PART 2 PRODUCTS

2.1 MATERIALS

PART 3 EXECUTION

3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED

3.2 REPUTTYING AND REGLAZING

3.3 RESEALING OF EXISTING EXTERIOR JOINTS

3.3.1 Surface Condition

3.3.2 Backstops

3.3.3 Primer and Bond Breaker

3.3.4 Ambient Temperature

3.3.5 Exterior Sealant

3.3.6 Cleaning

3.4 SURFACE PREPARATION

3.4.1 Additional Requirements for Preparation of Surfaces With

Existing Coatings

3.4.2 Existing Coated Surfaces with Minor Defects

3.4.3 Removal of Existing Coatings

3.4.4 Substrate Repair

3.5 PREPARATION OF METAL SURFACES

3.5.1 Existing and New Ferrous Surfaces

3.5.2 Final Ferrous Surface Condition:

3.5.3 Galvanized Surfaces

3.5.4 Non-Ferrous Metallic Surfaces

3.5.5 Terne-Coated Metal Surfaces

3.5.6 Existing Surfaces with a Bituminous or Mastic-Type Coating

3.6 PREPARATION OF CONCRETE AND CEMENTITIOUS SURFACE

3.6.1 Concrete and Masonry

3.6.2 Gypsum Board, Plaster, and Stucco

3.6.3 Existing Asbestos Cement Surfaces

3.7 PREPARATION OF WOOD AND PLYWOOD SURFACES

SECTION 09 90 00 Page 2

3.7.1 New [, Existing Uncoated,] [and] [Existing Coated] Plywood and Wood Surfaces, Except Floors:

3.7.2 Wood Floor Surfaces, Natural Finish

3.7.3 Interior Wood Surfaces, Stain Finish

3.7.4 Water Blasting of Existing Coated Wood Surfaces:

3.8 APPLICATION

3.8.1 Coating Application

3.8.2 Mixing and Thinning of Paints

3.8.3 Two-Component Systems

3.8.4 Coating Systems

3.9 COATING SYSTEMS FOR METAL

3.10 COATING SYSTEMS FOR CONCRETE AND CEMENTITIOUS SUBSTRATES

3.11 COATING SYSTEMS FOR WOOD AND PLYWOOD

3.12 PIPING IDENTIFICATION

3.13 INSPECTION AND ACCEPTANCE

3.14 WASTE MANAGEMENT

3.15 PAINT TABLES

3.15.1 EXTERIOR PAINT TABLES

3.15.2 INTERIOR PAINT TABLES

-- End of Section Table of Contents --

SECTION 09 90 00 Page 3

USACE / NAVFAC / AFCEC / NASA UFGS-09 90 00 (May 2011) Change 1 - 05/13 Preparing Activity: NAVFAC Superseding UFGS-09 90 00 (August 2010)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated January 2015

SECTION 09 90 00

PAINTS AND COATINGS

05/11

NOTE: This guide specification covers the requirements for painting of new and existing, interior and exterior substrates, including masonry, concrete, metal, wood and other miscellaneous materials.

Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.

Remove information and requirements not required in respective project, whether or not brackets are present.

Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).

NOTE: This Guide Specification is used in the preparation of project specifications for Department of Defense facilities:

1. Buildings;

2. Related mechanical, electrical, and miscellaneous items; and

3. Shore-to-ship utility connections.

This guide specification WAS NOT prepared to address the requirements of routine maintenance painting although it could be modified to do so.

SECTION 09 90 00 Page 4

This guide specification DOES NOT address high-performance or specialty coating requirements, or protective coating of industrial structures or facilities, including but not limited to:

1. Towers;

2. Pilings;

3. Pavement markings;

4. Items requiring specialized treatment due to peculiar usage;

5. Petroleum storage facilities;

6. Water storage facilities;

7. Waterfront facilities, except shore-to-ship utility connections; and

8. Hangars

If such items are in the project they should be included in a separate section or this section should be modified accordingly. The following guide specifications are examples of those available for specific service conditions noted, and may be modified to provide for related service conditions:

1. Section 09 97 23 METALLIC TYPE CONDUCTIVE/SPARK RESISTANT CONCRETE FLOOR FINISH. This specification covers the painting of hydraulic structures located in fresh water such as locks and dams.

2. Section 09 97 13.15 LOW VOC POLYSULFIDE INTERIOR

COATING OF WELDED STEEL PETROLEUM FUEL TANKS

3. Section 09 97 13.27 EXTERIOR COATING OF STEEL STRUCTURES. This specification is usable for any steel structure exposed to weather, and is usable for other purposes as well, such as hangar structures, enclosed swimming pool structures, and most situations requiring high-performance protective coating systems.

4. Section 09 97 13.16 INTERIOR COATING OF WELDED

STEEL WATER TANKS

5. Section 09 97 13.15 LOW VOC POLYSULFIDE INTERIOR COATING OF WELDED STEEL PETROLEUM FUEL TANKS. This is a three-coat epoxy system that is adaptable to a wide range of high-performance protective coating requirements where there is no exposure to sunlight.

This guide generally contains only two types of coating systems, solvent based and water based. If different systems are required regionally, or for special needs, modify the guide accordingly.

SECTION 09 90 00 Page 5

PART 1 GENERAL

1.1 REFERENCES

NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.

Use the Reference Wizard's Check Reference feature when you add a RID outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates.

References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)

ACGIH 0100 (2001; Supplements 2002-2008) Documentation of the Threshold Limit Values and Biological Exposure Indices

ASME INTERNATIONAL (ASME)

ASME A13.1 (2007; R 2013) Scheme for the Identification of Piping Systems

ASTM INTERNATIONAL (ASTM)

ASTM C920 (2014a) Standard Specification for Elastomeric Joint Sealants

ASTM D235 (2002; R 2012) Mineral Spirits (Petroleum Spirits) (Hydrocarbon Dry Cleaning Solvent)

ASTM D2824/D2824M (2013) Aluminum-Pigmented Asphalt Roof Coatings, Non-Fibered, Asbestos Fibered, and Fibered without Asbestos

ASTM D4214 (2007) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films

ASTM D4263 (1983; R 2012) Indicating Moisture in

SECTION 09 90 00 Page 6

Concrete by the Plastic Sheet Method

ASTM D4444 (2013) Use and Calibration of Hand-Held Moisture Meters

ASTM D523 (2014) Standard Test Method for Specular Gloss

ASTM D6386 (2010) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting

ASTM E2129 (2010) Standard Practice for Data Collection for Sustainability Assessment of Building Products

ASTM F1869 (2011) Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride

MASTER PAINTERS INSTITUTE (MPI)

MPI 1 (Oct 2009) Aluminum Paint

MPI 10 (Oct 2009) Exterior Latex, Flat, MPI Gloss Level 1

MPI 101 (Oct 2009) Epoxy Anti-Corrosive Metal Primer

MPI 107 (Oct 2009) Rust Inhibitive Primer (Water-Based)

MPI 108 (Oct 2009) High Build Epoxy Coating, Low Gloss

MPI 11 (Oct 2009) Exterior Latex, Semi-Gloss, MPI Gloss Level 5

MPI 113 (Oct 2009) Exterior Pigmented Elastomeric Coating (Water Based)

MPI 116 (Oct 2009) Epoxy Block Filler

MPI 119 (Oct 2009) Exterior Latex, Gloss

MPI 13 (Oct 2009) Exterior Solvent-Based Semi-Transparent Stain

MPI 134 (Oct 2009) Galvanized Primer (Waterbased)

MPI 138 (Oct 2009) Interior High Performance Latex, MPI Gloss Level 2

MPI 139 (Oct 2009) Interior High Performance Latex, MPI Gloss Level 3

MPI 140 (Oct 2009) Interior High Performance

SECTION 09 90 00 Page 7

Latex, MPI Gloss Level 4

MPI 141 (Oct 2009) Interior High Performance Latex MPI Gloss Level 5

MPI 144 (Oct 2009) Institutional Low Odor / VOC Interior Latex, MPI Gloss Level 2

MPI 145 (Oct 2009) Institutional Low Odor / VOC Interior Latex, MPI Gloss Level 3

MPI 146 (Oct 2009) Institutional Low Odor/VOC Interior Latex, MPI Gloss Level 4

MPI 147 (Oct 2009) Institutional Low Odor / VOC Interior Latex, Semi-Gloss, MPI Gloss Level 5

MPI 151 (Oct 2009) Interior W.B. Light Industrial Coating, MPI Gloss Level 3

MPI 153 (Oct 2009) Interior W.B. Light Industrial Coating, Semi-Gloss, MPI Gloss Level 5

MPI 154 (Oct 2009) Interior W.B. Light Industrial Coating, Gloss, MPI Gloss Level 6

MPI 16 (Oct 2009) Exterior Latex-Based Solid Hide Stain

MPI 161 (Oct 2009) Exterior W.B. Light Industrial Coating, MPI Gloss Level 3

MPI 163 (Oct 2009) Exterior W.B. Light Industrial Coating, Semi-Gloss, MPI Gloss Level 5

MPI 164 (Oct 2009) Exterior W.B. Light Industrial Coating, Gloss, MPI Gloss Level 6

MPI 19 (Oct 2009) Inorganic Zinc Rich Primer

MPI 2 (Oct 2009) Aluminum Heat Resistant Enamel (up to 427 C and 800 F

MPI 21 (Oct 2009) Heat Resistant Enamel, Gloss (up to 205 degrees C and 400 degrees F), MPI Gloss Level 6

MPI 22 (Oct 2009) Aluminum Paint, High Heat (up to 590 degrees C and 1100 degrees F.

MPI 23 (Oct 2009) Surface Tolerant Metal Primer

MPI 26 (Oct 2009) Cementitious Galvanized Metal Primer

MPI 27 (Oct 2009) Exterior / Interior Alkyd Floor Enamel, Gloss

SECTION 09 90 00 Page 8

MPI 31 (Oct 2009) Polyurethane, Moisture Cured, Clear Gloss

MPI 39 (Oct 2009) Interior Latex-Based Wood Primer

MPI 4 (Oct 2009) Interior/Exterior Latex Block Filler

MPI 42 (Oct 2009) Latex Stucco and Masonry Textured Coating

MPI 44 (Oct 2009) Interior Latex, MPI Gloss Level

MPI 45 (Oct 2009) Interior Alkyd Primer Sealer

MPI 46 (Oct 2009) Interior Enamel Undercoat

MPI 47 (Oct 2009) Interior Alkyd, Semi-Gloss, MPI Gloss Level 5

MPI 48 (Oct 2009) Interior Alkyd, Gloss, MPI Gloss Level 6

MPI 49 (Oct 2009) Interior Alkyd, Flat, MPI Gloss Level 1

MPI 5 (Oct 2009) Exterior Alkyd Wood Primer

MPI 50 (Oct 2009) Interior Latex Primer Sealer

MPI 51 (Oct 2009) Interior Alkyd, Eggshell, MPI Gloss Level 2

MPI 52 (Oct 2009) Interior Latex, MPI Gloss Level

MPI 54 (Oct 2009) Interior Latex, Semi-Gloss, MPI Gloss Level 5

MPI 56 (Oct 2009) Interior Oil Modified Urethane Clear Gloss

MPI 57 (Oct 2009) Interior Oil Modified Urethane Clear Satin

MPI 59 (Oct 2009) Interior/Exterior Floor Enamel, Low Gloss

MPI 6 (Oct 2009) Exterior Latex Wood Primer

MPI 60 (Oct 2009) Interior/Exterior Latex Floor Paint, Low Gloss

MPI 68 (Oct 2009) Interior/Exterior Latex Floor Enamel, Gloss

MPI 7 (Oct 2009) Exterior Oil Wood Primer

SECTION 09 90 00 Page 9

MPI 71 (Oct 2009) Polyurethane, Moisture Cured, Clear, Flat

MPI 72 (Oct 2009) Polyurethane, Two Component, Pigmented, Gloss

MPI 77 (Oct 2009) Epoxy Gloss

MPI 79 (Oct 2009) Alkyd Anti-Corrosive Metal Primer

MPI 8 (Oct 2009) Exterior Alkyd, Flat, MPI Gloss Level I

MPI 9 (Oct 2009) Exterior Alkyd, Gloss, MPI Gloss Level 6

MPI 90 (Oct 2009) Interior Wood Stain, Semi-Transparent

MPI 94 (Oct 2009) Exterior Alkyd, Semi-Gloss, MPI Gloss Level 5

MPI 95 (Oct 2009) Quick Drying Primer for Aluminum

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS Scientific Certification Systems (SCS)Indoor Advantage

SCS SP-01 (2000) Environmentally Preferable Product Specification for Architectural and Anti-Corrosive Paints

SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC 7/NACE No.4 (2007; E 2004) Brush-Off Blast Cleaning

SSPC Guide 6 (2004) Guide for Containing Surface Preparation Debris Generated During Paint Removal Operations

SSPC Guide 7 (2004; E 2004) Guide to the Disposal of Lead-Contaminated Surface Preparation Debris

SSPC PA 1 (2000; E 2004) Shop, Field, and Maintenance Painting of Steel

SSPC PA Guide 3 (1982; E 1995) A Guide to Safety in Paint Application

SSPC Paint 18 (1982; E 2004) Chlorinated Rubber Intermediate Coat Paint

SSPC QP 1 (2012; E 2012) Standard Procedure for Evaluating Painting Contractors (Field Application to Complex Industrial Structures)

SECTION 09 90 00 Page 10

SSPC SP 1 (1982; E 2004) Solvent Cleaning

SSPC SP 10/NACE No. 2 (2007) Near-White Blast Cleaning

SSPC SP 12/NACE No.5 (2002) Surface Preparation and Cleaning of Metals by Waterjetting Prior to Recoating

SSPC SP 2 (1982; E 2000; E 2004) Hand Tool Cleaning

SSPC SP 3 (1982; E 2004) Power Tool Cleaning

SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning

SSPC VIS 1 (2002; E 2004) Guide and Reference Photographs for Steel Surfaces Prepared by Dry Abrasive Blast Cleaning

SSPC VIS 3 (2004) Guide and Reference Photographs for Steel Surfaces Prepared by Hand and Power Tool Cleaning

SSPC VIS 4/NACE VIS 7 (1998; E 2000; E 2004) Guide and Reference Photographs for Steel Surfaces Prepared by Waterjetting

U.S. ARMY CORPS OF ENGINEERS (USACE)

EM 385-1-1 (2008; Errata 2011) Safety and Health Requirements Manual

U.S. DEPARTMENT OF DEFENSE (DOD)

MIL-PRF-680 (2010; Rev C) Degreasing Solvent

MIL-STD-101 (2014; Rev C) Color Code for Pipelines and for Compressed Gas Cylinders

U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)

EPA Method 24 (2000) Determination of Volatile Matter Content, Water Content, Density, Volume Solids, and Weight Solids of Surface Coatings

U.S. FEDERAL AVIATION ADMINISTRATION (FAA)

FAA AC 70/7460-1 (2007; Rev K) Obstruction Marking and Lighting

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

FED-STD-313 (2014; Rev E) Material Safety Data, Transportation Data and Disposal Data for Hazardous Materials Furnished to Government Activities

FED-STD-595 (Rev C; Notice 1) Colors Used in Government Procurement

SECTION 09 90 00 Page 11

U.S. GREEN BUILDING COUNCIL (USGBC)

LEED NC (2009) Leadership in Energy and Environmental Design(tm) New Construction Rating System

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

29 CFR 1910.1000 Air Contaminants

29 CFR 1910.1001 Asbestos

29 CFR 1910.1025 Lead

29 CFR 1926.62 Lead

UL ENVIRONMENT (ULE)

ULE Greenguard UL Greenguard Certification Program

1.2 SUBMITTALS

NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project.

The Guide Specification technical editors have designated those items that require Government approval, due to their complexity or criticality, with a "G". Generally, other submittal items can be reviewed by the Contractor's Quality Control System. Only add a “G” to an item, if the submittal is sufficiently important or complex in context of the project..

For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the "G" designation to indicate the approving authority.

Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy, Air Force, and NASA projects.

An "S" following a submittal item indicates that the submittal is required for the Sustainability Notebook to fulfill federally mandated sustainable requirements in accordance with Section 01 33 29

SUSTAINABILITY REPORTING.

Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed

SECTION 09 90 00 Page 12 item for Army projects.

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

The current MPI, "Approved Product List" which lists paint by brand, label, product name and product code as of the date of contract award, will be used to determine compliance with the submittal requirements of this specification. The Contractor may choose to use a subsequent MPI "Approved Product List", however, only one list may be used for the entire contract and each coating system is to be from a single manufacturer. All coats on a particular substrate must be from a single manufacturer. No variation from the MPI Approved Products List is acceptable.

Samples of specified materials may be taken and tested for compliance with specification requirements.

In keeping with the intent of Executive Order 13101, "Greening the Government through Waste Prevention, Recycling, and Federal Acquisition", products certified by SCS as meeting SCS SP-01 shall be given preferential consideration over registered products. Products that are registered shall be given preferential consideration over products not carrying any EPP designation.

SD-02 Shop Drawings

Piping identification

Submit color stencil codes

SD-03 Product Data

Certification

[ Local/Regional Materials; (LEED NC)

Submit documentation indicating distance between manufacturing facility and the project site. Indicate distance of raw material origin from the project site. Indicate relative dollar value of local/regional materials to total dollar value of products included in project.]

[ Environmental Data

] Materials; (LEED NC)

Submit documentation indicating percentage of post-industrial and post-consumer recycled content per unit of product. Indicate relative dollar value of recycled content products to total dollar value of products included in project.

Coating; G[, [_____]]

SECTION 09 90 00 Page 13

Manufacturer's Technical Data Sheets; (LEED)

Indicate VOC content.

[Sealant]

SD-04 Samples

Color; G[, [_____]]

Submit manufacturer's samples of paint colors. Cross reference color samples to color scheme as indicated.

Note: The Sample Wall Coating Mock-Up is to be used for texture wall coating systems.

[ Textured Wall Coating System; G[, [_____]]

Sample Textured Wall Coating System Mock-Up; G[, [_____]]

SD-07 Certificates

Applicator's qualifications

Qualification Testing laboratory for coatings; G[, [_____]]

SD-08 Manufacturer's Instructions

Application instructions

Mixing

Detailed mixing instructions, minimum and maximum application temperature and humidity, potlife, and curing and drying times between coats.

Manufacturer's Material Safety Data Sheets

Submit manufacturer's Material Safety Data Sheets for coatings, solvents, and other potentially hazardous materials, as defined in

FED-STD-313.

SD-10 Operation and Maintenance Data

Coatings:; G[, [_____]]

Preprinted cleaning and maintenance instructions for all coating systems shall be provided.

SD-11 Closeout Submittals

[ Local/Regional Materials; (LEED)

LEED documentation relative to local/regional materials credit in accordance with LEED Reference Guide. Include in LEED

SECTION 09 90 00 Page 14

Documentation Notebook.]

[ Materials; (LEED)]

[ LEED documentation relative to recycled content credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook.]

[ LEED documentation relative to low emitting materials credit in accordance with LEED Reference Guide. Include in LEED Documentation Notebook.]

1.3 APPLICATOR'S QUALIFICATIONS

NOTE: When using the contractor qualification clause rather than the SSPC Certification requirements, edit to require appropriate experience.

NOTE: Select only one of the following two bracketed paragraphs.

[1.3.1 Contractor Qualification

Submit the name, address, telephone number, FAX number, and e-mail address of the contractor that will be performing all surface preparation and coating application. Submit evidence that key personnel have successfully performed surface preparation and application of coatings on [_____] on a minimum of three similar projects within the past three years. List information by individual and include the following:

a. Name of individual and proposed position for this work.

b. Information about each previous assignment including:

Position or responsibility

Employer (if other than the Contractor)

Name of facility owner

Mailing address, telephone number, and telex number (if non-US) of facility owner

Name of individual in facility owner's organization who can be contacted as a reference

Location, size and description of structure

Dates work was carried out

Description of work carried out on structure

SECTION 09 90 00 Page 15

NOTE: For projects in continental US, Hawaii, Alaska, and Puerto Rico, require SSPC Certification. Use in other locations where qualified US contractor is desired. If project involves removal of paint containing hazardous materials, add requirement for SSPC QP-2 certification in section of specification where the hazardous paint removal is specified, generally section 02 83 13.00 20 LEAD IN CONSTRUCTION or section 02 82 33.13 20 REMOVAL/CONTROL AND DISPOSAL

OF PAINT WITH LEAD.

NOTE: **WARNING**WARNING**WARNING**WARNING**

Solicitations requiring SSPC Certification should point out the existence and location of the certification requirement, in the Project Information Form. To be enforceable, the requirement must be pointed out in the solicitation documents. SSPC Certification is a special responsibility requirement pursuant to FAR 9.104-2.

This is analogous to requiring bidders to have a specified level of experience or expertise and GAO has sustained these types of special requirements.

NOTE: Use bracket option below concerning SSPC QP 1 only when industrial coatings are required.

Painting qualifications for projects such as BEQ's, training facilities and general administration buildings do not require QP 1 certification.

[1.3.2 SSPC QP 1 Certification

All contractors and subcontractors that perform surface preparation or coating application shall be certified by the Society for Protective Coatings (formerly Steel Structures Painting Council) (SSPC) to the requirements of SSPC QP 1 prior to contract award, and shall remain certified while accomplishing any surface preparation or coating application. The painting contractors and painting subcontractors must remain so certified for the duration of the project. If a contractor's or subcontractor's certification expires, the firm will not be allowed to perform any work until the certification is reissued. Requests for extension of time for any delay to the completion of the project due to an inactive certification will not be considered and liquidated damages will apply. Notify the Contracting Officer of any change in contractor certification status.

]1.4 QUALITY ASSURANCE

1.4.1 Field Samples and Tests

The Contracting Officer may choose up to two coatings that have been delivered to the site to be tested at no cost to the Government. Take

SECTION 09 90 00 Page 16 samples of each chosen product as specified in the paragraph "Sampling Procedures." Test each chosen product as specified in the paragraph "Testing Procedure." Products which do not conform, shall be removed from the job site and replaced with new products that conform to the referenced specification. Testing of replacement products that failed initial testing shall be at no cost to the Government.

NOTE: Only require the testing for large quantities of epoxy/polyurethane coatings or a single…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.